CB NAME PLATE

TYPE : HPL245B1 Operating Device Type BLG1002A


NO : 1HSB06040001 NO : 1HSB0604001A1
:Order : Order
VOLTAGE 245 KV SHORT-CIRCUIT Breaking current 50 KA
FREQUANCY 50 HZ DC Component 55%
NORMAL CURRENT 4000 A FIRST POLE TO CLEAR FACTOR 1-5
GAS PRESSURE SF6 TEMP. abs MEAKING CURRENT 125KA
Max working pressure 0.8 MPA SHORT-TIME CURRENT 3sec 50KA
Filling 20C 0.7 MPA MASS TOTAL 2717KG
Alarm 20C 0.62 MPA MAS OF GASS 27KG
Block 20C 0.6 MPA - RULES
Volume per pole 190 l YEAR OF MANEFACTURE 2006
Temperature class -25 c
INSULATION LEVEL at Altitude ≤ 1000 m To Earth A across Open Pole
Lightning Impulse with stand voltage 1050 KV 1050KV
Power Frequency with stand voltage 460 KV 460 KV