You are on page 1of 1

Amps X 10 TAB TGS (Nom. kV=0.22, Plot Ref. kV=0.

22)
.5 1 3 5 10 30 50 100 300 500 1K 3K 5K 10K
1K 1K
CB4
CABTSG-1 Square-D MICROLOGIC 6.0
500 Cable2 Ampacity Sensor = 1600 500
12-1/C 400 Cable2 LT Pickup = 0.85 (1360 Amps)
Ampacity LT Band = 4
300 300
CB2 ST Pickup = 5 (6800 Amps)
Bus4
Cable4 ST Band = 0.2 (I^x)t = OUT
Ampacity Inst. Pickup = 6 (9600 Amps)
CB Override = 42.9 kA
Cable4 CB2
100 12-1/C 400 100
CB4 Square-D MICROLOGIC 6.0
Sensor = 1600
TAB TGS
50 LT Pickup = 1 (1600 Amps) 50
LT Band = 8
CBTSG-1 ST Pickup = 10 (16000 Amps)
30 30
ST Band = 0.1 (I^x)t = OUT
Inst. Pickup = 15 (24000 Amps)
CABTSG-1 CABA1-3 - P
12-1/C 4/0

10 TAB A1 CBA1 10

CBA1-3 CABTSG-1 - P
5 5
Seconds

Seconds
CABA1-3
3 3-1/C 8 3

ULA-07
10 HP
1 1
ULA-07-am2 Cable2 - P

CBTSG-1
.5 .5
Square-D Micrologic 3.3 (PP)
Sensor = 400
.3 Ir = 400 A (400 Amps) .3
tr = 1.0
Ii = 12 x In (4800 Amps)
CBA1 Cable4 - P
Square-D Micrologic 3.3 (PP)
.1 Sensor = 400 .1
Ir = 350 A (350 Amps)
tr = 0.5
.05 Ii = 5 x In (2000 Amps) .05
CBA1-3
.03 Square-D .03
EDB
Size = 40 Amps
Thermal Trip = Fixed
Magnetic Trip = Fixed
.01 .01
.5 1 3 5 10 30 50 100 300 500 1K 3K 5K 10K

Amps X 10 TAB TGS (Nom. kV=0.22, Plot Ref. kV=0.22) ETAP Star 19.0.1C
.2644 .5 1 3 5 10 30 50 100 300 500 1K 3K 5.289K