(. C H 1. D l d l, i <:,

PRESSURE RELIEF DEVICES


INSPECTION/TESTING

SERIAL NUMBERS

PRESSURE RELIEF
DEVICES
389808-1AE 391071-1AM 390795-1AE

Device Number 1 2 3

Removed Tested X X X
Inspected X X X

Replaced
Reinstalled X X X
Pressure - Discharge Set 42 PSI 38 PSI 42 PSI

Pressure - Open 42 PSI 39 PSI 42 PSI

Pressure - Reseated 39 PSI 35 PSI 40 PSI

lnspector/41,� Date:
�-.J�C)
j ,/--z."J
-------, ---
QC Manager: ___,_�
-=------­ Date: _q._,tJ�J_.._�.._J__
ACT Unit Number: £o()bJ.

Depending on PRV availability and lead time, ACT may procure PRVs at standard pressures that are readily
available. Dependent on the specific requirements of the relevant cryogenic tank design, ACT may adjust the
pressure setting (up or down). In this instance ACT will provide this certification document in addition to the
OEM PRV certification document. ACT assumes the responsibility of complying all necessary regulatory
requirements.