5' DROP
8'-8" CEILING
SECTION A-A
12'
CLOSET
- EXTERIOR WALLS ARE 8" CONCRETE BLOCK
LINEN
8' - CORRIDOR WALLS AREA 8" CONCRETE BLOCK (1 HR)
- WALLS BETWEEN ROOMS AREA 6" METAL STUDS WITH 2 LAYERS OF 1/2" DRY WALL
AND INSULATION (1 HR)
3'-6" - INTERIOR ROOM WALLS ARE 3-5/8" METAL STUDS WITH A SINGLE LAYER OF 1/2"
DRYWALL
A A
17'-6"
MECHANICAL
ROOM 8'-4"
SPRINKLER RISER
ROOM 28'-
8"
123'-4" 12'
ELECTRIC
10'
19' 19'
ELEVATOR
MACHINE 7'-8"
ROOM
ELEVATOR
7'
Elevator
109'-4"
5'
127'-8"
8"
7'-6"
9' 4' 8'-6" Living
BATHROOM room 35'-6"
24'-6"
2'-6" 3'
SUITE SUITE
14'-10"
10'-4" FRONT
DESK 28' BATHROOM
OFFICE
LOBBY 8'-8"
9'-8"
LEGEND 8"
10'-9"
20'
ot at o ENTRY
VESTIBULE
8'-8"
BEDROOM
7'-6"
149'
a er alve
DROP
8'-8" CEILING
SECTION A-A
12'
CLOSET
- EXTERIOR WALLS ARE 8" CONCRETE BLOCK
LINEN
8' - CORRIDOR WALLS AREA 8" CONCRETE BLOCK (1 HR)
- WALLS BETWEEN ROOMS AREA 6" METAL STUDS WITH 2 LAYERS OF 1/2" DRY WALL
AND INSULATION (1 HR)
3'-6" - INTERIOR ROOM WALLS ARE 3-5/8" METAL STUDS WITH A SINGLE LAYER OF 1/2"
DRYWALL
A A
17'-6"
8'-4"
MECHANICAL
ROOM
123'-4" 12'
ELECTRIC
10'
19' 19'
ICE 28'-8"
7'-8"
MACHINE
ELEVATOR
7'
Elevator
109'-4"
5'
127'-8"
8"
7'-6"
9' 4' 8'-6" SUITE SUITE
35'-6"
24'-6"
2'-6" 3'
28'
8'-8"
LEGEND 8"
BEDROOM 10'-9"
ot at o 7'-6"
re lar o trol t
a er alve
Tamper Switch 2
Elevator Control 1
Panel
Total Devices 184 < 198, The FACU is sufficient for the number of devices.
HVAC No interface required. NFPA 90A 6.4.2 System operates at less than
2000 cfm
I chose the Honeywell ES-200X because it has the capability to use an appropriate amount of
points for the floor plan. It was not too little, and it was not so capable that it would be a waste of
money to use a more expensive FACU.
I chose the Honeywell SD365 because it interfaces with the ES-200X easily, being manufactured
by the same company. They were made to work well together. Also, the SD365 has a good range
of 30x30ft, enough to cover one bedroom by itself. I am adhering to NFPA72 17.5.3.1 Total
(Complete) Coverage.
I chose the System Sensor L-Series because it is a two-in-one auditory and visual notification
device, and it is very capable at being both. 185ca is bright enough for 1 to cover a 70x70ft space
and 88dBA is very loud. I will place the AV notification appliances in accordance with NFPA 72
18.5.5.7.3.
I chose the Honeywell BG-12LX pull station because it is simple and works well. It is also listed
as being compatible and made to work with the ES-200X FACU. I will install these pull stations
in accordance with NFPA 72 17.15, 5ft from each exit and no more than 200ft in between them.
I chose the System Sensor WFD Series because they are reliable detectors, and because they are
compatible with the Honeywell ES-200X FACU.
Detector Spacing Calculations:
r = 30(0.7) = 21 ft
Lobby: approx 20ft x 34ft
a = 20(0.5) = 10ft
2 2
b = 21 − 10 = 18.5ft
2b = 37ft
21ft x 37ft > 20ft x 34ft ⇒ 1 Detector
East-West Hallway: 5ft x 128 ft
a = 5(0.5) = 2.5 ft
2 2
b = 21 − 2. 5 = 20.85ft
2b = 41.7ft
128
41.7
= 3.1 ⇒ 4 Detectors
North-South Hallway: 5ft x 110ft
a = 5(0.5) = 2.5 ft
2 2
b = 21 − 2. 5 = 20.85ft
2b = 41.7ft
110
41.7
= 2.64 ⇒ 3 Detectors
AV Notification Appliance Spacing:
For combined horn/strobe, use the visible appliance location requirements.
185cd ⇒ 70ft x 70ft (see NFPA 72 Table 18.5.5.7.1(a))
Hallways :
128
70
= 1.8 ⇒ 2 AV Notification Appliances per hallway
Circuits
Component Number Max Current Total Draw
AV Notification 84 0A 262mA
t
ni
U l
tro
n
io
on
ev cat
C
ifi
or
ot
at
U
N
C
AV
FA
SYSTEM INPUTS
El
Smoke Detector ✔ ✔
Elevator Detector ✔ ✔ ✔
Waterflow Alarm ✔
Tamper Switch ✔
Pull Station ✔ ✔
DF-60957:C
ES-200X
Intelligent Addressable FACP
with Communicator
Addressable Fire Alarm Control Panels
General
The ES-200X is the latest intelligent addressable Fire Alarm Control
Panel (FACP) from Fire•Lite Alarms and is a direct replacement for
the MS-9200UDLS. The ES-200X comes with a pre-installed com-
municator and supports up to 198 addressable devices (99 detec-
tors and 99 modules). With an extensive list of powerful features, the
ES-200X programs just like Fire•Lite’s other addressable products,
yet fits into applications previously served only by conventional pan-
els.
The pre-installed IPOTS-COM is a dual technology (POTS and IP)
communicator. The POTS transmits system status (alarms, troubles,
AC loss, etc.) to a Central Station via the public switched telephone
network. The IP communicator’s internet monitoring capability sends
alarm signals over the Internet saving the monthly cost of two dedi-
cated business telephone lines. Although not required, the second-
ary telephone line may be retained providing backup communication
over the public switched telephone line. Optional cellular reporting is
available using the CELL-MOD or CELL-CAB-FL.
Remote and local programming of the control panel is possible using
the FS-Tools Upload/Download utility. Programming databases can
be uploaded/downloaded via the panel’s USB port (and USB cable)
or via an ethernet connection using the IPOTS-COM communicator.
The USB port also allows for the download or upload of the entire
program, history file, walk-test data, current status and system volt-
• Alarm verification selection per detector point
ages by means of a USB flash drive.
• Maintenance alert warns when smoke detector dust accumula-
The power supply and all electronics are contained on a circuit tion is excessive
board supported on a new quick install chassis and housed in a • One-person audible or silent walk test with walk-test log and
metal cabinet. Available accessories include local and remote printout
upload/download software, remote annunciators, and reverse polar- • System alarm verification selection per detector point
ity/city box transmitter (4XTMF). • PAS (Positive Alarm Sequence) and Pre-signal per point (NFPA
Features 72 compliant)
• Up to 16 ANN-BUS annunciators- 8 per each ANN-Bus
• Listed to UL Standard 864, 10th edition • Remote Acknowledge, Alarm Silence, Reset and Drill via
• Pre-installed IPOTS-COM Ethernet IP and POTS (Plain Old Tele- addressable modules or remote annunciator
phone Service) Central Station Communicator over AlarmNet • Upload/Download of program and data via USB with optional FS-
• Optional CELL-MOD or CELL-CAB-FL GSM Central Station Tools Programming Utility
Communicator over AlarmNet®
• Automated activation of the ECC-50/100 Emergency Command SLC COMMUNICATION LOOP
Center • Supports LiteSpeed™ and CLIP protocols
• ECC-FFT Firefighter Telephone option • SLC operates up to 10,000 ft. (3,000 m) in LiteSpeed mode with
• Compatible with SWIFT® wireless devices twisted, unshielded wire
• Auto-programming (learn mode) reduces installation time.
• Single addressable SLC loop which meets NFPA Class B and
Reports two devices set to the same address
Class A requirements
• Four built-in, independently programmable Style Z (Class A) or
Style Y (Class B) NAC circuits • 198 addressable device capacity (99 addressable detectors and
• Selectable strobe synchronization for System Sensor, Wheelock, 99 modules)
and Gentex devices • Compatible with Fire•Lite’s addressable devices (refer to the
• Notification Appliance Circuit End of Line resistor matching SLC Wiring Manual)
• Four programmable function keys for ease of maintenance NOTIFICATION APPLIANCE CIRCUITS (NACS)
• Two programmable relays and one fixed trouble relay
• Built-in Programmer • Four independently programmable output circuits. Circuits can be
• Integral 80-character LCD display with backlighting configured for the following outputs:
• Real-time clock/calendar with automatic daylight savings control – Style Y (Class B)
• History file with 1,000 event capacity – Style Z (Class A)
• Addressable sounder base compatibility • Silence Inhibit and Autosilence timer options
• Multi-criteria detector (smoke, heat, CO) with programmable • Continuous, March Time, Temporal, or California code for main
response circuit board NACs with two-stage capability
• Control module delay timer
• Selectable strobe synchronization per NAC
• Automatic detector sensitivity testing (NFPA 72 compliant)
• Automatic device type-code verification • 2.5 A special application, 250mA regulated, total power for NACs
• Point trouble identification NOTE: Maximum or total 24VDC system power shared between all NAC
• Waterflow selection per module point circuits and the ANN-BUS is 2.7 A
For more information, contact Fire•Lite Alarms. Phone: (800) 627-3473, FAX: (877) 699-4105. Country of Origin: USA
www.firelite.com
SD365 Series
Addressable Photoelectric Smoke Detectors
Addressable Devices
The Fire•Lite® Alarms SD365(A), SD365R(A), and SD365HT(A)
intelligent plug-in smoke detectors are designed for both perfor-
mance and aesthetics, and are direct replacements for the SD355
Series. A new modern, sleek, contemporary design and enhanced
optical sensing chamber is engineered to sense smoke produced by
a wide range of combustion sources in accordance with more strin-
gent code standards.
Exclusively for use with Fire•Lite’s addressable fire alarm control
panels, the SD365(A) Series point ID capability allows each detec-
tor’s address to be set with rotary, decimal address switches, provid-
ing exact detector location for emergency personnel to quickly locate
a fire during its early stages, potentially saving precious rescue time
while also reducing property damage. Two LEDs on each sensor
light to provide a local, visible sensor indication.
The SD365(A) Series also offers 135°F (57°C) fixed temperature
thermal sensing on the SD365T(A) and a remote test capable detec-
tor on the SD365R(A) for use with DNR(A)/DNRW duct smoke
detector housings.
Features • Plugs into separate base for ease of installation and maintenance
SLC LOOP: • Separate base allows interchange of photoelectric, ionization and
thermal sensors
• Two-wire SLC loop connection
• Unit uses base for wiring OPTIONS:
• Compatible with LiteSpeed™ and CLIP protocol systems • Optional relay, isolator, and sounder bases
• Stable communication technique with noise immunity
Installation
ADDRESSING: SD365 Series plug-in intelligent smoke detectors use a detachable
• Addressable by device base to simplify installation, service and maintenance. Installation
• Rotary, decimal addressing instructions are shipped with each detector.
(Refer to the Fire•Lite panel manuals for device capacity.) Mount detector base (all base types) on an electrical backbox which
ARCHITECTURE: is at least 1.5" (3.81 cm) deep. For a chart of compatible junction
boxes, see DF-60059.
• Sleek, low-profile, stylish design
NOTE: Because of the inherent supervision provided by the SLC loop,
• Unique single-source design to respond quickly and dependably end-of-line resistors are not required. Wiring “T-taps” or branches are
to a broad range of fires permitted for Class “B” wiring only.
• Integral communications and built-in device-type identification When using relay or sounder bases, consult the I300(A) installation
• Built-in tamper resistant feature sheet I56-3626 for device limitations between isolator modules and isola-
tor bases.
• Remote test feature from the panel
• Walk test with address display (an address on 121 will blink the Construction
detector LED: 12-[pause]-1(LiteSpeed systems only)
These detectors are constructed of fire-resistant plastic. The SD365
• Built-in functional test switch activated by external magnet Series plug-in intelligent smoke detectors are designed to commer-
• Removable cover and insect-resistant screen for simple field cial standards and offer an attractive appearance.
cleaning
• Expanded color options Operation
Each SD365 Series detector uses one of the panel’s addresses
OPERATION:
(total limit is panel dependent) on the Fire•Lite Signaling Line Circuit
• Designed to meet UL 268 7th Edition (SLC). It responds to regular polls from the control panel and reports
• Factory preset at 1.5% nominal sensitivity for panel alarm thresh- its type and the status. If it receives a test command from the panel
old level (or a local magnet test), it stimulates its electronics and reports an
• LED “blinks” when the unit is polled (communicating with the fire alarm. It blinks its LEDs when polled and turns the LEDs on when
panel) and latches in alarm. commanded by the panel. The SD365 Series offers features and
performance that represent the latest in smoke detector technology.
• Low standby current
MECHANICALS: Detector Sensitivity Test
• Sealed against back pressure Each detector can have its sensitivity tested (required per NFPA 72,
• SEMS screws for wiring of the separate base Chapter 14 on Inspection, Testing and Maintenance) when installed/
connected to an Fire•Lite addressable fire alarm control panel. The
• Designed for direct-surface or electrical-box mounting
results of the sensitivity test can be printed for record keeping.
For more information, contact Fire•Lite Alarms. Phone: (800) 627-3473, FAX:(877) 699-4105. Country of Origin: Mexico
www.firelite.com
Features
• Updated Modern Aesthetics The System Sensor L-Series offers the most versatile and
• Small profile devices for Horns and Horn Strobes easy-to-use line of horns, strobes, and horn strobes in the industry
with lower current draws and modern aesthetics. With white and red
• Plug-in design with minimal intrusion into the back box
plastic housings, standard and compact devices, and plain, FIRE,
• Tamper-resistant construction
and FUEGO-printed devices, System Sensor L-Series can
• A
utomatic selection of 12- or 24-volt operation at 15 and 30 meet virtually any application requirement.
candela
• F
ield-selectable candela settings on wall units: The L-Series line of wall-mount horns, strobes, and horn strobes
15, 30, 75, 95, 110, 135, and 185 include a variety of features that increase their application versatility
• Horn rated at 88+ dBA at 16 volts while simplifying installation. All devices feature plug-in designs
with minimal intrusion into the back box, making installations fast
• Rotary switch for horn tone and two volume selections
and foolproof while virtually eliminating costly and time-consuming
• Mounting plate for all standard and all compact wall units ground faults.
• M
ounting plate shorting spring checks wiring continuity before
device installation To further simplify installation and protect devices from construction
• Electrically compatible with legacy SpectrAlert and SpectrAlert damage, the L-Series utilizes a universal mounting plate for all
Advance devices models with an onboard shorting spring, so installers can test wiring
• Compatible with MDL3 sync module continuity before the device is installed.
Strobe
The strobe shall be a System Sensor L-Series Model _______ listed to UL 1971 and shall be approved for fire protective service. The strobe
shall be wired as a primary-signaling notification appliance and comply with the Americans with Disabilities Act requirements for visible
signaling appliances, flashing at 1 Hz over the strobe’s entire operating voltage range. The strobe light shall consist of a xenon flash tube and
associated lens/reflector system.
Synchronization Module
The module shall be a System Sensor Sync•Circuit model MDL3 listed to UL 464 and shall be approved for fire protective service. The
module shall synchronize Strobes at 1 Hz and horns at temporal three. Also, while operating the strobes, the module shall silence the horns
on horn strobe models over a single pair of wires. The module shall mount to a 411/16 × 411/16 × 21/8-inch back box. The module shall also
control two Style Y (class B) circuits or one Style Z (class A) circuit. The module shall synchronize multiple zones. Daisy chaining two or more
synchronization modules together will synchronize all the zones they control. The module shall not operate on a coded power supply.
Physical/Electrical Specifications
Standard Operating Temperature 32°F to 120°F (0°C to 49°C)
Humidity Range 10 to 93% non-condensing
Strobe Flash Rate 1 flash per second
Nominal Voltage Regulated 12 DC or regulated 24 DC/FWR1
Operating Voltage Range 2
8 to 17.5 V (12 V nominal) or 16 to 33 V (24 V nominal)
Operating Voltage Range MDL3 Sync Module 8.5 to 17.5 V (12 V nominal) or 16.5 to 33 V (24 V nominal)
Input Terminal Wire Gauge 12 to 18 AWG
Wall-Mount Dimensions (including lens) 5.6˝ L × 4.7˝ W × 1.91˝ D (143 mm L × 119 mm W × 49 mm D)
Compact Wall-Mount Dimensions (including lens) 5.26” L x 3.46” W x 1.91” D (133 mm L x 88 mm W x 49 mm D)
Horn Dimensions 5.6˝ L × 4.7˝ W × 1.25˝ D (143 mm L × 119 mm W × 32 mm D)
Compact Horn Dimensions 5.25” L x 3.45” W x 1.25” D (133 mm L x 88 mm W x 32 mm D)
1. Full Wave Rectified (FWR) voltage is a non-regulated, time-varying power source that is used on some power supply and panel outputs.
2. Strobe products will operate at 12 V nominal only for 15 cd and 30 cd.
UL Max. Current Draw (mA RMS), Wall Horn Strobe, Candela Range (15–185 cd)
8–17.5 Volts 16–33 Volts
DC Input 15cd 30cd 15cd 30cd 75cd 95cd 110cd 135cd 185cd
Temporal High 98 158 54 74 121 142 162 196 245
Temporal Low 93 154 44 65 111 133 157 184 235
Non-Temporal High 106 166 73 94 139 160 182 211 262
Non-Temportal Low 93 156 51 71 119 139 162 190 239
3.1K Temporal High 93 156 53 73 119 140 164 190 242
3.1K Temporal Low 91 154 45 66 112 133 160 185 235
3.1K Non-Temporal High 99 162 69 90 135 157 175 208 261
3.1K Non-Temporal Low 93 156 52 72 119 138 162 192 242
16–33 Volts
FWR Input 15cd 30cd 75cd 95cd 110cd 135cd 185cd
Temporal High 83 107 156 177 198 234 287
Temporal Low 68 91 145 165 185 223 271
Non-Temporal High 111 135 185 207 230 264 316
Non-Temportal Low 79 104 157 175 197 235 283
3.1K Temporal High 81 105 155 177 196 234 284
3.1K Temporal Low 68 90 145 166 186 222 276
3.1K Non-Temporal High 104 131 177 204 230 264 326
3.1K Non-Temporal Low 77 102 156 177 199 234 291
1.91" 3.46"
3.46" 48.5 mm 88 mm 1.25" 3.57" 1.55"
88 mm 1.25" 32 mm (9.1 cm) (3.9 cm)
32 mm
5.27" 5.38"
133.9 mm 5.27" (13.7 cm)
133.9 mm
Compact Strobe, Horn Strobe Compact Horn Compact Wall Surface Mount Back Box
SBBGRL, SBBGWL
4.70"
(11.94 cm) 1.91"
4.7" 1.25"
(4.85 cm) 4.82"
119 mm 32 mm 1.85"
(12.24 cm)
1.25" (4.69 cm)
(3.18 mm)
5.78"
5.67" 5.67"
(14.68 cm)
(14.4 cm) 144 mm
A0554-01
A0550-00 A0549-00
Strobe, Horn Strobe Horn Wall Surface Mount Back Box
SBBRL/SBBWL
BG-12LX
Addressable Manual Pull Station
Addressable Devices
General
The Fire·Lite BG-12LX is a state-of-the-art, dual-action (i.e.,
requires two motions to activate the station) pull station that
includes an addressable interface (mounted inside) for
Fire·Lite’s addressable fire alarm control panels (FACPs)
Because the BG-12LX is addressable, the control panel can
display the exact location of the activated manual station. This
leads fire personnel quickly to the location of the alarm.
Features
• Maintenance personnel can open station for inspection and
address setting without causing an alarm condition.
• Built-in bicolor LED, which is visible through the handle of
the station, flashes in normal operation and latches steady
red when in alarm.
• Handle latches in down position and the word “ACTIVATED”
appears to clearly indicate the station has been operated.
• Captive screw terminals wire-ready for easy connection to
SLC loop (accepts up to 12 AWG/3.25 mm² wire).
• Can be surface mounted (with SB-10 or SB-I/O) or semi-
flush mounted. Semi-flush mount to a standard single-
FLPullStation.jpg
gang, double-gang, or 4" (10.16 cm) square electrical box.
• Smooth dual-action design.
• Meets ADAAG controls and operating mechanisms guide-
lines (Section 4.1.3[13]); meets ADA requirement for 5 lb.
maximum activation force.
• Highly visible. usually needed for semi-flush mounting with 4" (10.16 cm) or
double-gang boxes (not with single-gang boxes).
• Attractive shape and textured finish.
• Key reset.
Operation
• Includes Braille text on station handle.
Pushing in, then pulling down on the handle causes it to latch
• Optional trim ring (BG12TR).
in the down/activated position. Once latched, the word “ACTI-
• Meets UL 38, Standard for Manually Actuated Signaling VATED” (in bright yellow) appears at the top of the handle,
Boxes. while a portion of the handle protrudes from the bottom of the
station. To reset the station, simply unlock the station with the
Construction key and pull the door open. This action resets the handle; clos-
ing the door automatically resets the switch.
Shell, door, and handle are molded of durable polycarbonate
material with a textured finish. Each manual station, on command from the control panel,
sends data to the panel representing the state of the manual
Specifications switch. Two rotary decimal switches allow address settings
(1 – 159 with Breakaway Tab removed for MS-9600 Series, 1 –
• Shipping Weight: 9.6 oz. (272.15 g) 99 and MS-9200UDLS, 1 – 50 for MS-9050UD).
• Normal operating voltage: 24 VDC.
• Maximum SLC loop voltage: 28.0 VDC. Architectural/Engineering
• Maximum SLC standby current: 375 μA. Specifications
• Maximum SLC alarm current: 5 mA. Manual Fire Alarm Stations shall be non-coded, with a key-
• Temperature Range: 32°F to 120°F (0°C to 49°C) operated reset lock in order that they may be tested, and so
• Relative Humidity: 10% to 93% (noncondensing) designed that after actual Emergency Operation, they cannot
be restored to normal except by use of a key. An operated sta-
• For use indoors in a dry location tion shall automatically condition itself so as to be visually
detected as activated. Manual stations shall be constructed of
Installation red-colored polycarbonate material with clearly visible operat-
ing instructions provided on the cover. The word FIRE shall
The BG-12LX will mount semi-flush into a single-gang, double-
appear on the front of the stations in white letters, 1.00 inches
gang, or standard 4" (10.16 cm) square electrical outlet box, or
(2.54 cm) or larger. Stations shall be suitable for surface
will surface mount to the model SB-10 or SB-I/O surface back-
mounting on matching backbox SB-10 or SB-I/O; or semi-flush
box. If the BG-12LX is being semi-flush mounted, then the
mounting on a standard single-gang, double-gang, or
optional trim ring (BG12TR) may be used. The BG12TR is
4" (10.16 cm) square electrical box, and shall be installed
• Sealed retard mechanism immune to dust and other contaminants Reliable Performance. UL-listed models are equipped with
tamper-resistant cover screws to prevent unauthorized entry. Inside,
• Visual switch activation
two sets of SPDT (Form C) synchronized switches are enclosed in a
• Field-replaceable retard mechanism and SPDT switches durable terminal block to assure reliable performance.
• Rugged, dual SPDT switches enclosed in a durable terminal block
False Alarm Immunity. The WFD series incorporates a mechanical
• Accommodates up to 12 AWG wire retard feature, which minimizes the risk of false alarm due to
pressure surges or air trapped in the sprinkler system. In addition,
• Designed for both indoor and outdoor use
the mechanical retard’s unique sealed design is immune to dust and
• 100 percent synchronization activates both alarm panel and other contaminants.
local bell
Simplified Operation. The WFD series is designed to simplify
• Tamper-resistant cover screws
installation. Two conduit openings permit easy attachment to the
local alarm system. The retard mechanism and dual SPDT switches
are field-replaceable.
Agency Listings
WFD Field Wiring Diagram Delay Adjustment Dial Overall Dimensions, Installed
NOTE: COMMON AND B-NO DELAY 3.75″
UL-LISTED SSM24-X CONNECTIONS WILL CLOSE ADJUSTMENT
SSV120-X DIAL DIAL IS APP
COMPATIBLE WHEN VANE IS DEFLECTED, I.E., ON R
CONTROL PANEL WHEN WATER IS FLOWING. DUAL R DELAY IN SECO OXI
BE ND MA
M IME
SWITCHES PERMIT
POWER + APPLICATIONS TO BE COMBINED T S
NU
TE
70
+
INITIATING SUGGESTED EOL 125/250 VAC 10 AMPS WFD35 5.7″ WFD80 10.8″
LOOP RESISTOR
–
24 VDC 2.5 AMPS
55
Ordering Information
UL Model ULC Model Pipe Size Hole Size Shipping Weight
WFD20 WFD20A 2˝ 1¼˝ 4.2 lbs.
WFD25 WFD25A 2½˝ 1¼˝ 4.3 lbs.
WFD30-2 WFD30-2A 3˝ 2˝ 4.5 lbs.
WFD35 WFD35A 3½˝ 1¼˝ 4.7 lbs.
WFD40 WFD40A 4˝ 2˝ 5.2 lbs.
WFD50 WFD50A 5˝ 2˝ 6.3 lbs.
WFD60* WFD60A 6˝ 2˝ 6.8 lbs.
WFD80* WFD80A 8˝ 2˝ 7.5 lbs.
Accessories
A3008-00 Retard mechanism
A77-01-02 Terminal block
546-7000 Tamper-proof switch kit
WFDW Tamper-proof wrench for cover
WFDN4 Gasket kit
*Maximum pressure rating 400 psi as approved by Factory Mutual.