LOGIC DIAGRAM / SCHEME OF SECONDARY AIR DAMPER CONTROL


Title:

Doc./Drg. No.: 51006-66100-1002-01 Rev No.: 02 Total No. of Pages :199


NTPC Doc./Drg. No.: 9578-001-102-PVI-L-005 Rev No.: 02 Unit Designation: 1 & 2
Stamp: Digitally signed QSGM Date Name Sign
by Debabrata Checked 09/01/2017 M. KAKIMI
Digitally signed by Munehiro Kakimi
DN: cn=Munehiro Kakimi, o=QSGM,
ou=MHPS,
email=munehiro_kakimi@mhps.com, c=JP

Kundu
Date: 2017.01.09 17:09:35 +05'30'

Digitally signed by Munehiro


Kakimi

Date: 2017.01.10 Approved 09/01/2017 DN: cn=Munehiro Kakimi,

M. HOKANO o=QSGM, ou=MHPS,


email=munehiro_kakimi@mhps.c
om, c=JP
Date: 2017.01.09 17:09:57 +05'30'

15:42:16 +05'30'

L&T-S&L Date Name


Checked DD.MM.YYYY -
REVISION STATUS
Rev Prepared Reviewed Approved
No. Name Date Name Date Name Date
00 Vibhu K/ Pritha B 26/07/2016 Sunil Sadasivan 26/07/2016 Sumanta Basu 26/07/2016
01 Vibhu K/ Pritha B 06/12/2016 Sunil Sadasivan 06/12/2016 Sumanta Basu 06/12/2016
02 Vibhu K/ Pritha B 09/01/2017 Sunil Sadasivan 09/01/2017 Sumanta Basu 09/01/2017
Sunil Sadasivan sumanta.basu Digitally signed by

2017.01.09 16:07:58 sumanta.basu@lntmhps.com

@lntmhps.com
DN: cn=sumanta.basu@lntmhps.com
+05'30' Date: 2017.01.09 16:18:07 +05'30'
2 × 660 MW KHARGONE SUPER THERMAL
POWER PROJECT
L&T-MHPS BOILERS PRIVATE LIMITED 
(FORMERLY KNOWN AS L&T‐MHI BOILERS PRIVATE LIMITED) 
LOGIC DIAGRAM / SCHEME OF Doc. No.: 66100-1002-01
SECONDARY AIR DAMPER CONTROL Rev. No.: 02
Larsen & Toubro Ltd. Date: 09/01/2017

REVISION SUMMARY SHEET

Rev
Details / Description Date
No.
00 First Submission 26/07/2016

01 CRS Sheet attached. No change in the document 06/12/2016

02 CRS Sheet attached. Comments incorporated in the Document. 09/01/2017


2 × 660 MW KHARGONE SUPER THERMAL
POWER PROJECT
L&T-MHPS BOILERS PRIVATE LIMITED 
(FORMERLY KNOWN AS L&T‐MHI BOILERS PRIVATE LIMITED) 
LOGIC DIAGRAM / SCHEME OF Doc. No.: 66100-1002-01
SECONDARY AIR DAMPER CONTROL Rev. No.: 02
Larsen & Toubro Ltd. Date: 09/01/2017

INDEX

SR. No. CONTENT PAGE NUMBER

1 Input Signal Sheet 6

2 Coal Damper Control 8

3 Oil Damper Control 20

4 Windbox Inlet Damper Control 32

5 Aux-2 Damper Control 38

6 AA Damper Control 50

7 AA Adjustable Drive (Nozzle Tilt) Logic 62

8 Windbox Damper Common Logic 74

9 Appendix-1: Function Block Legend 79

10 Appendix-2: Macro Details 171

11 CRS Sheet 199


2 × 660 MW KHARGONE SUPER THERMAL
POWER PROJECT
L&T-MHPS BOILERS PRIVATE LIMITED 
(FORMERLY KNOWN AS L&T‐MHI BOILERS PRIVATE LIMITED) 
LOGIC DIAGRAM / SCHEME OF Doc. No.: 66100-1002-01
SECONDARY AIR DAMPER CONTROL Rev. No.: 02
Larsen & Toubro Ltd. Date: 09/01/2017

List of Documents for Reference: 
 
S. No.  Document Name  Document number 
Functional Write‐Up For Secondary Air Damper Control 
1  9578‐001‐102‐PVM‐K‐010 
System 
P&ID for Combustion air & Flue gas system along with  9578‐001‐102‐PVM‐L‐002

instrumentation including write‐up/ procedure 
Combustion Air & Flue Gas System along with 
3  9578‐001‐102‐PVM‐L‐003  2
Instrumentation‐Write‐up / procedure 

4  Recommended Unit Control Logics including CMC  9578‐001‐102‐PVI‐L‐019 
A B C D E F G H I

1 1

2 2

3 3

4 4

5 5

OFF D

6 6
REMARKS
A B C D E F G H I

1 1

2 2

3 3

4 4

5 5

OFF D

6 6
REMARKS
A B C D E F G H I

DI
HRDWR MFT1 TO FGSG-09
CED
01CGA05XH001 MFT
1 DI 1
HRDWR MFT2 TO FGSG-09 FGSG09-DI01-D01 <FGSG09-WBC2RYDMP-01>
<FGSG09-WBC-COMMON-01>
01CGA05XH002

2 2

3 3

4 4

5 5

6 6

TITLE Rev.
DIGITAL HARDWIRED SIGNALS (FGSG-09)
REMARKS

2
SHEET NO.

MITSUBISHI FGSG09-DI01
HEAVY INDUSTRIES, LTD
A B C D E F G H I

1 1

2 2

3 3

4 4

5 5

OFF D

6 6
REMARKS
A B C D E F G H I
Loop Plate Alarm/Event CED
X SAB FURNACE PRESS (FRN-WB DP
IN FURNACE PRESS (FRN-WB DP CONTROL) INTERLOCK IN MODE
E N CONTROL) PRESS ABNORMAL
PVA 01HAD01CP-A01-SABN
PVA 01HAD01CP906 OH1 D AH2 D BH2 D <FGSG09-WBCAUX2-01>
X X
OUT FURNACE PRESS (FRN-WB DP CONTROL) INTERLOCK OUT MODE
PVB
PVB E A FURNACE PRESS (FRN-WB DP CONTROL) SIG ABN
SAB S-PB-2
OH2 D AL1 D BL1 D
N X AAB X
1 S-PB-3
DEV
A FURNACE PRESS (FRN-WB DP CONTROL) DEVIATION HIGH
N A FURNACE PRESS (FRN-WB DP CONTROL)-A SIG ABN 1
DEV
OL1 D AL2 D BL2 D
ASE S-PB-5 S-PB-5-Set BAB X
L
PB PBA
N A FURNACE PRESS (FRN-WB DP CONTROL)-B SIG ABN
BSE S-PB-6 S-PB-6-Set
L
PB PBB OL2 D AH1 D
S-PB-9 S-PB-9-Set
IN PB PBI
S-PB-10 S-PB-10-Set
OUT PB PBO BH1 D
FURNACE PRESS (FRN-WB DP CONTROL)
<WIND BOX-2>
<WIND BOX-1>

2 2
FURNACE PRESS (FRN-WB DP CONTROL)
CEA A1
PVS 999.9uu
OS FURNACE PRESSURE (FURNACE
TO WINDBOX DP CONTROL)
PBA ASL ASE 01HAD01CP-A01
PBA A SELECTION
L <FGSG09-WBCDPCNT-01>
BSL BSE <WIND BOX-1>
B SELECTION
L <WIND BOX-2>
PBB H1inA <AIR AND FLUE GAS SYSTEM-2>
PBB SG PVS PROCESS SEL
S=99999.0
FURNACE PRESS (FRN-WB DP CONTROL)-A
PBI IN H2inA
PBI IN INTERLOCK IN SG A1
PVA 999.9uu
S=99999.0
3 3
PBT OUT L1inA AS
PBO OUT INTERLOCK OUT SG PVA PROCESS A
S=-99999.0

SDH L2inA
DEV DEVIATION HIGH SG FURNACE PRESS (FRN-WB DP CONTROL)-B
S=-99999.0 PVB A1
999.9uu

ABN X Y SAB
N
T=0.0 PROCESS VALUE SABN

BS
PVB PROCESS B

4 ASE D1 4
AABN AAB L
A ABNORMAL
N
DRC BABN BAB PVC
B ABNORMAL
A N 3
FURNACE PRESS (FRN-WB DP CONTROL)-A SELECT
<WIND BOX-2>
OH1 <WIND BOX-1>
OH1 PROCESS VALUE H
AI
FURNACE PRESSURE (FURNACE X AIA AS AIA OH2
LAG OH2 PROCESS VALUE HH
TO WINDBOX DP CONTROL)
T=0.0 OL1
01HAD01CP106-XQ01 OL1 PROCESS VALUE L
OL2
OL2 PROCESS VALUE LL
AH1
AH1 PVA H
5 5
AH2
AH2 PVA HH
AL1
AL1 PVA L
BSE D1
AL2 L
AL2 PVA LL
AI
FURNACE PRESSURE (FURNACE X AIB BS AIB BH1
LAG BH1 PVB H
TO WINDBOX DP CONTROL)
FURNACE PRESS (FRN-WB DP CONTROL)-B SELECT
T=0.0 BH2
01HAD01CP115-XQ01 BH2 PVB HH <WIND BOX-2>
BL1 <WIND BOX-1>
BL1 PVB L
BL2
BL2 PVB LL
CED
EXABN OS AIO
FCB/RUNBACK OPERATE
6 6
APC-EMG-10-D001 <APC-EMG-10>

TITLE Rev.
FURNACE PRESS (FRN-WB DP CONTROL)
2
REMARKS

SHEET NO.

MITSUBISHI FGSG09-MSS-
HEAVY INDUSTRIES, LTD FPRS(FWBDP)
A B C D E F G H I
Loop Plate Alarm/Event CED
X SAB WB INL PRESS (FRN-WB DP
IN WB INL PRESS (FRN-WB DP CONTROL) INTERLOCK IN MODE
E N CONTROL) PRESS ABNORMAL
PVA 01HLA05CP-A01-SABN
PVA 01HLA05CP903 OH1 D AH2 D BH2 D <FGSG09-WBCAUX2-01>
X X
OUT WB INL PRESS (FRN-WB DP CONTROL) INTERLOCK OUT MODE
PVB
PVB E A WB INL PRESS (FRN-WB DP CONTROL) SIG ABN
SAB S-PB-2
OH2 D AL1 D BL1 D
N X AAB X
1 S-PB-3
DEV
A WB INL PRESS (FRN-WB DP CONTROL) DEVIATION HIGH
N A WB INL PRESS (FRN-WB DP CONTROL)-A SIG ABN 1
DEV
OL1 D AL2 D BL2 D
ASE S-PB-5 S-PB-5-Set BAB X
L
PB PBA
N A WB INL PRESS (FRN-WB DP CONTROL)-B SIG ABN
BSE S-PB-6 S-PB-6-Set
L
PB PBB OL2 D AH1 D
S-PB-9 S-PB-9-Set
IN PB PBI
S-PB-10 S-PB-10-Set
OUT PB PBO BH1 D

WB INL PRESS (FRN-WB DP CONTROL)

2 2
WB INL PRESS (FRN-WB DP CONTROL)
CEA A1
PVS 999.9uu
OS WB INL PRESSURE (FURNACE TO
WINDBOX DP CONTROL)
PBA ASL ASE 01HLA05CP-A01
PBA A SELECTION
L <FGSG09-WBCDPCNT-01>
BSL BSE
B SELECTION
L
PBB H1inA
PBB SG PVS PROCESS SEL
S=99999.0
WB INL PRESS (FRN-WB DP CONTROL)-A
PBI IN H2inA
PBI IN INTERLOCK IN SG A1
PVA 999.9uu
S=99999.0
3 3
PBT OUT L1inA AS
PBO OUT INTERLOCK OUT SG PVA PROCESS A
S=-99999.0

SDH L2inA
DEV DEVIATION HIGH SG WB INL PRESS (FRN-WB DP CONTROL)-B
S=-99999.0 PVB A1
999.9uu

ABN X Y SAB
N
T=0.0 PROCESS VALUE SABN

BS
PVB PROCESS B

4 ASE D1 4
AABN AAB L
A ABNORMAL
N
DRC BABN BAB PVC
B ABNORMAL
A N 3
WB INL PRESS (FRN-WB DP CONTROL)-A SELECT

2 OH1
OH1 PROCESS VALUE H
AI
WB INL PRESSURE (FURNACE TO X AIA AS AIA OH2
LAG OH2 PROCESS VALUE HH
WINDBOX DP CONTROL)
T=0.0 OL1
01HLA05CP103-XQ01 OL1 PROCESS VALUE L
OL2
OL2 PROCESS VALUE LL
AH1
AH1 PVA H
5 5
AH2
AH2 PVA HH
AL1
AL1 PVA L
BSE D1
AL2 L
AL2 PVA LL
AI
WB INL PRESSURE (FURNACE TO X AIB BS AIB BH1
LAG BH1 PVB H
WINDBOX DP CONTROL)
WB INL PRESS (FRN-WB DP CONTROL)-B SELECT
T=0.0 BH2
01HLA05CP152-XQ01 BH2 PVB HH
BL1
BL1 PVB L
BL2
BL2 PVB LL
CED
EXABN OS AIO
FCB/RUNBACK OPERATE
6 6
APC-EMG-10-D001 <APC-EMG-10>

TITLE Rev.
WB INL PRESS (FRN-WB DP CONTROL)
2
REMARKS

SHEET NO.

MITSUBISHI FGSG09-MSS-
HEAVY INDUSTRIES, LTD WBILPR(FWBDP)
A B C D E F G H I

CEA
COAL A WINDBOX DAMPER
(1,3,5,7) PROGRAM SET
CEA FGSG09-WBCCOAL-A-01-A002
S=0.0
FURNACE-WB DP. CONTROL DEM <FGSG09-DRV-WBCOAL-A1>
1TR SG
FGSG09-WBCDPCNT-01-A002
<FGSG09-WBCDPCNT-01> Ron=200.0
1 Roff=200.0
Ron=10.0 1
Roff=99999.0
MD=0 on off on CEA
off on off COAL A WINDBOX DAMPER
TR TRD TR (1,3,5,7) CONTROL SIGNAL
sw sw sw FGSG09-WBCCOAL-A-01-A001
Ron=100.0 <FGSG09-DRV-WBCOAL-A1>
CEA FX-1 *
Roff=99999.0
LDO HEADER PRESS FX MD=0
1DP FURN-WB DP CNT (1,3,5,7) 1AT
APC-MSS-LDOHDRPRS
<APC-MSS-LDOHDRPRESS> 1ST

FX-2 *
FX CEA
2 COAL A WINDBOX DAMPER
2
(2,4,6,8) PROGRAM SET
S=0.0 FGSG09-WBCCOAL-A-01-A004
FX-3 *
SG <FGSG09-DRV-WBCOAL-A2>
FX 2TR
Ron=200.0 Ron=200.0
Roff=200.0 Ron=10.0
Roff=200.0 Roff=99999.0
CEA FX-4 * MD=0 MD=0 CEA
on on off on off on
off off on off on off COAL A WINDBOX DAMPER
COAL FLOW-A FX TR TR TR TR TRD TR (2,4,6,8) CONTROL SIGNAL
APC-MSS-CF-A-1-A003 Ron=200.0 sw sw Ron=200.0 sw sw sw sw FGSG09-WBCCOAL-A-01-A003
<APC-MSS-CF-A-1>
Roff=200.0 Roff=200.0 Ron=100.0
CED Roff=99999.0 <FGSG09-DRV-WBCOAL-A2>
MD=0 MD=0
MD=0
WORST (COAL-1) SEL
3 APC-CMS-06-D001
A-
ON
2DP FURN-WB DP CNT (2,4,6,8) 2AT 2ST 3
<APC-CMS-06>
CED CED
BEST (COAL-3) SEL WINDBOX BANKING COMMAND
1DP
APC-CMS-06-D003 <APC-CMS-06>
CED APC-ADC-15-D002 <APC-ADC-15>
FURN-WB DP CNT (1,3,5,7)
BID MORE THAN 30%
CED
FGSG09-WBC-COMMON-01-D008 COAL A WINDBOX DAMPER A-
CEA (1,3,5,7) FURN-WB DP CNT ON CED
<FGSG09-WBC-COMMON-01>
COAL A1 WINDBOX DAMPER TR FGSG09-WBCCOAL-A-01-D001
1TR A-CFD SIG ABN (& A-CFD ON)
SIGNAL CED
<FGSG09-DRV-WBCOAL-A1>
FGSG09-DRV-WBCOAL-A1-TR COAL FLOW A SIG.ABN FGSG09-WBCCOAL-A-01-D003
CEA <FGSG09-DRV-WBCOAL-A1> <FGSG09-DRV-WBAUX2-1>
COAL A2 WINDBOX DAMPER TR APC-MSS-CF-A-1-D001 <APC-MSS-CF-A-1> <FGSG09-DRV-WBAUX2-3>
2TR
SIGNAL CED
4 FGSG09-DRV-WBCOAL-A2-TR A COAL BNR ON or AB OIL BNR
<FGSG09-DRV-WBCOAL-A1>
<FGSG09-DRV-WBCOAL-A2>
4
<FGSG09-DRV-WBCOAL-A2> CED ON(1,3,5,7) or FURN-WB DP CNT
ANY AB LDO BURNER ON (1,3,5,7) FGSG09-WBCCOAL-A-01-D002
CED CED CED
<FGSG09-DRV-WBCOAL-A1>
COAL A 1,3,5,7 WINDBOX FGSG09-WBCOIL-AB-02-D005 ANY AB LDO BURNER ON LDO HEADER PRESS ABN (& AB
1ST <FGSG09-WBCOIL-AB-02> 2DP
DAMPER AUTO or STANDBY CED (1,2,3,4,5,6,7,8) LDO ON / A-CF OFF)
FGSG09-DRV-WBCOAL-A1-AST PULV-A & COAL FEEDER-A FURN-WB DP CNT (2,4,6,8) FGSG09-WBCOIL-AB-02-D006 <FGSG09-WBCOIL-AB-02> FGSG09-WBCCOAL-A-01-D006
START / PURGE IN PROGRESS CED CED
<FGSG09-DRV-WBCOAL-A1> <FGSG09-DRV-WBCOAL-A1>
BMS1-11A-9-D03 A- COAL A WINDBOX DAMPER LDO HEADER PRESS SIG
CED ON (2,4,6,8) FURN-WB DP CNT ABNORMAL <FGSG09-DRV-WBCOAL-A2>
COAL A 2,4,6,8 WINDBOX FGSG09-WBCCOAL-A-01-D005 APC-MSS-LDOHDRPRS-SABN
2ST
DAMPER AUTO or STANDBY <FGSG09-DRV-WBCOAL-A2> <APC-MSS-LDOHDRPRESS>
FGSG09-DRV-WBCOAL-A2-AST
<FGSG09-DRV-WBCOAL-A2> FURN-WB DP CNT (1,3,5,7)
1DP
CED CED
5 A COAL BNR ON or AB OIL BNR FURN & WB INL PRESS SIG ABN 5
CED ON(2,4,6,8) or FURN-WB DP CNT CED (& A-COAL DMPR 1,3,5,7 DP CNT)
FGSG09-WBCCOAL-A-01-D004 FURN & WB INL PRESS SIG ABN FGSG09-WBCCOAL-A-01-D009
ANY AB LDO BURNER ON (2,4,6,8)
CED (& BID<30% / A-CF OFF) <FGSG09-DRV-WBCOAL-A1>
<FGSG09-DRV-WBCOAL-A2>
COAL A 1,3,5,7 WINDBOX FGSG09-WBCOIL-AB-03-D005 FGSG09-WBCAUX2-01-D004
1AT <FGSG09-WBCOIL-AB-03>
DAMPER AUTO
<FGSG09-WBCAUX2-01>
FGSG09-DRV-WBCOAL-A1-AT
<FGSG09-DRV-WBCOAL-A1> CED
FURN-WB DP CNT (2,4,6,8)
COAL A 1,3,5,7 WINDBOX
FURN-WB DP CNT (1,3,5,7) 1DP 2DP
DAMPER AUTO (DP CNT) CED
FGSG09-WBCCOAL-A-01-D007 FURN & WB INL PRESS SIG ABN
<FGSG09-WBCDPCNT-02> (& A-COAL DMPR 2,4,6,8 DP CNT)
FGSG09-WBCCOAL-A-01-D010
CED <FGSG09-DRV-WBCOAL-A2>
COAL A 2,4,6,8 WINDBOX
2AT
DAMPER AUTO
6 FGSG09-DRV-WBCOAL-A2-AT 6
<FGSG09-DRV-WBCOAL-A2> CED
COAL A 2,4,6,8 WINDBOX
FURN-WB DP CNT (2,4,6,8) 2DP
DAMPER AUTO (DP CNT)
FGSG09-WBCCOAL-A-01-D008
<FGSG09-WBCDPCNT-02>

FX-1 * FX-2 * FX-3 * FX-4 *


X1=0.0,Y1=50.0 X1=0.0,Y1=70.0 X1=0.0,Y1=70.0 X1=0.0,Y1=70.0
X2=10.0,Y2=50.0 X2=25.0,Y2=70.0 X2=25.0,Y2=70.0 X2=25.0,Y2=70.0 TITLE A-COAL DAMPER CONTROL Rev.
X3=20.0,Y3=50.0 X3=35.0,Y3=70.0 X3=35.0,Y3=70.0 X3=35.0,Y3=70.0
The same logic will be applicable for
REMARKS

X4=30.0,Y4=50.0 X4=45.0,Y4=70.0 X4=45.0,Y4=70.0 X4=45.0,Y4=70.0


2
X5=0.0,Y5=0.0
X6=0.0,Y6=0.0
X5=50.0,Y5=70.0
X6=65.0,Y6=70.0
X5=50.0,Y5=70.0
X6=65.0,Y6=70.0
X5=50.0,Y5=70.0
X6=65.0,Y6=70.0
B~H Coal Damper control. SHEET NO.
X7=0.0,Y7=0.0 X7=75.0,Y7=70.0 X7=75.0,Y7=70.0 X7=75.0,Y7=70.0
X8=0.0,Y8=0.0 X8=100.0,Y8=70.0 X8=100.0,Y8=70.0 X8=100.0,Y8=70.0 MITSUBISHI FGSG09-
* TO BE FINALIZED DURING COMMISSIONING
X9=0.0,Y9=0.0
X10=0.0,Y10=0.0
X9=110.0,Y9=70.0
X10=0.0,Y10=0.0
X9=110.0,Y9=70.0
X10=0.0,Y10=0.0
X9=110.0,Y9=70.0
X10=0.0,Y10=0.0 HEAVY INDUSTRIES, LTD WBCCOAL-A-01
A B C D E F G H I

AI
POS
COAL A1 DAMPER POSITION FB
I A1
VDSI
SV S-PB-3-Set 01HLA51AA712-XQ01 POS Pin C
SV SV 01HLA51AA712 PB RPB 0.0 - 100.0% TRK
I
MV S-PB-8-Set DAB DRAB
PB APB
AI FBI FBO CEA O
COAL A1 WINDBOX DAMPER
V3 S-PB-10-Set COAL A1 DAMPER POSITION RB1I TRKS COAL A1 WINDBOX DAMPER TR RSE RSTC OPND D1
TRK TRACKING SIG PB MPB
1 DEMAND1 RB SIGNAL T
VDSI 1
DAB DRIVE ABN S-PB-2 Tagging FGSG09-DRV-WBCOAL-A1-TR TAG CLSD D3
O
PB TAG 01HLA51AA712-YQ01RB TAG
0.0 - 100.0% <FGSG09-WBCCOAL-A-01>
RSE RESET COND S-PB-3 RBSO MID D2
RB <FGSG09-WBC-COMMON-03>
T
SIG ABN <FGSG09-WBC-COMMON-04>
SAB S-PB-4
COAL A1 WINDBOX DAMPER
N AI
CAU CONTROL AUTO S-PB-8 COAL A1 DAMPER POSITION RB2I FQAB FSA
T DEMAND2 RB B
STB STAND BY MODE S-PB-9 MV-I-PRH
Y MV-D-PRH 01HLA51AA712-YQ02RB CAU D1 <WIND BOX-1>
S-PB-10 MV-Set 0.0 - 100.0% DFDH DFD T <WIND BOX-1>
MAN MANUAL MODE
H STB D2 <WIND BOX-2>
COAL A 1,3,5,7 WINDBOX DAMPER <WIND BOX-1> Y <WIND BOX-2>
CED <WIND BOX-1> D3
MAN
<WIND BOX-2> RQAB RSA
FG INITIALIZING INIT
2 <WIND BOX-2> B
COAL A 1,3,5,7 DAMPER AUTO/MANUAL 2
FG INITIALIZING
CEA
COAL A WINDBOX DAMPER DEM DRDH DRD
SV S=65.0 S=100.0 PVC
(1,3,5,7) PROGRAM SET DPRH IPRH 1 H
FGSG09-WBCCOAL-A-01-A002 ULMT Ain Aout A1 <WIND BOX-1>
SG SG RB 999.9uu
<FGSG09-WBCCOAL-A-01> PVC <WIND BOX-1>
LLMT DRVM FMA Cout A2
<WIND BOX-2>
N
OPMT Ron=200.0 Ron=200.0 COAL A1 WINDBOX DAMPER RB <WIND BOX-2>
Roff=99999.0 Roff=99999.0
CEA S OH OL on on AO
MD=0 MD=0
COAL A WINDBOX DAMPER X Y Ain Aout off off DEM AO COAL A1 WINDBOX DAMPER
(1,3,5,7) CONTROL SIGNAL
S/S TR TR DRIP
POSN DEM1
FGSG09-WBCCOAL-A-01-A001 S=0.0 L sw OPP OPC INIT OPRH sw sw FSA X
<FGSG09-WBCCOAL-A-01> OH=100
01HLA51AA712-YQ01 B A
SG 0.0 - 100.0%
OL=0 MANUAL MODE
MAN COAL A1 WINDBOX DAMPER POS FB SIG ABN
3 S=10.0 on INITIALIZE AO RSA X
3
INIT
off COAL A1 WINDBOX DAMPER B A
SG TR UNF UNFIRING POS CMD POSN DEM2
COAL A1 WINDBOX DAMPER RB SIG ABN
sw P
Ron=200.0 01HLA51AA712-YQ02
STB FOP FORCED OPEN CMD DFD X
STAND BY MODE Roff=200.0
Y N 0.0 - 100.0% H A
MD=0
ALLRST
RPB COAL A1 WINDBOX DAMPER FB DEV HI
CED
DEM_X1in=-10.0 DRD X
WINDBOX BANKING COMMAND
CED DEM_Y1out=110.0 H A
APC-ADC-15-D002 FOP MANU LARP RSE DEM_X2in=110.0
<APC-ADC-15> A-CFD SIG ABN (& A-CFD ON) MAN DEM_Y2out=-10.0 COAL A1 WINDBOX DAMPER RB DEV HI
N T
FGSG09-WBCCOAL-A-01-D003 RB_X1in=-10.0 FMA X
CED CED <FGSG09-WBCCOAL-A-01> RB_Y1out=-10.0 N A
WINDBOX DMPR FORCED OPN FURN & WB INL PRESS SIG ABN SAB SABCND RB_X2in=110.0
RB_Y2out=110.0 COAL A 1,3,5,7 WINDBOX DAMPER FORCED MANUAL
CMD (& A-COAL DMPR 1,3,5,7 DP CNT) N
4 FGSG09-WBC-COMMON-01-D007 UNF FGSG09-WBCCOAL-A-01-D009 SAB RB_CHG=0 4
P <FGSG09-WBCCOAL-A-01> N RB_TRK=0
<FGSG09-WBC-COMMON-01>
DABO DAB FB_TRK=0 X
MAN
CED O DEM_FB=0 E
LDO HEADER PRESS ABN (& AB 12DV=10.0
COAL A 1,3,5,7 DAMPER MANUAL MODE
LDO ON / A-CF OFF) ARDV=10.0
FGSG09-WBCCOAL-A-01-D006 LCN DABCND ONT1=10.0 CAU X
CED <FGSG09-WBCCOAL-A-01> D DFDV=10.0 T E
ACN COAL A WINDBOX DAMPER INIT FDHEX ONT2=60.0
COAL A 1,3,5,7 DAMPER AUTO MODE
CED D (1,3,5,7) FURN-WB DP CNT
A COAL BNR ON or AB OIL BNR FGSG09-WBCCOAL-A-01-D001 STB X
INIT
ON(1,3,5,7) or FURN-WB DP CNT <FGSG09-WBCCOAL-A-01> Y E
FGSG09-WBCCOAL-A-01-D002 COAL A 1,3,5,7 DAMPER STANDBY MODE
<FGSG09-WBCCOAL-A-01> RBK

5 5
CED
CED ATPB CAUTX Y CAU CAU COAL A 1,3,5,7 WINDBOX
APB AUTO PB
COAL A3 WINDBOX DAMPER DRV T T DAMPER AUTO
<FGSG09-WBCCOAL-A-01>
ABN MNPB
MPB MANUAL PB T=0.0 FGSG09-DRV-WBCOAL-A1-AT
FGSG09-DRV-WBCOAL-A3-D001 CED
SAB CED <FGSG09-DRV-WBCOAL-A3> ACN AUT CND ACND CSTB STB DAU COAL A 1,3,5,7 WINDBOX
N COAL A5 WINDBOX DAMPER DRV D Y T DAMPER AUTO or STANDBY <FGSG09-WBCCOAL-A-01>
MCN ABN MCN MANU CND MCND ASM FGSG09-DRV-WBCOAL-A1-AST
D FGSG09-DRV-WBCOAL-A5-D001 D S CED
DAB CED <FGSG09-DRV-WBCOAL-A5> DAUT DAU STB COAL A 1,3,5,7 WINDBOX
O COAL A7 WINDBOX DAMPER DRV LCN T Y DAMPER STANDBY MODE
ABN D FGSG09-DRV-WBCOAL-A1-ST
CED FGSG09-DRV-WBCOAL-A7-D001 CED
<FGSG09-DRV-WBCOAL-A3>
INIT MANU COAL A 1,3,5,7 WINDBOX
FCB/RUNBACK OPERATE RBK <FGSG09-DRV-WBCOAL-A7> INIT INITIALIZE MAN RPB <FGSG09-DRV-WBCOAL-A5>
RSA RB SIG ABN DAMPER RESET PB ON
6 APC-EMG-10-D001 <APC-EMG-10> B FGSG09-DRV-WBCOAL-A1-RST
<FGSG09-DRV-WBCOAL-A7> 6
CEA
DEM COAL A WINDBOX DAMPER
<FGSG09-DRV-WBCOAL-A3>
DRD RB SIG DEV H 1 (1,3,5,7) DEMAND SIGNAL
<FGSG09-DRV-WBCOAL-A5>
H FGSG09-DRV-WBCOAL-A1-A001
<FGSG09-DRV-WBCOAL-A7>
<FGSG09-WBCDPCNT-02>

TITLE COAL A CORNER 1 WINDBOX DAMPER Rev.


REMARKS

2
SHEET NO.
MITSUBISHI FGSG09-DRV-
HEAVY INDUSTRIES, LTD WBCOAL-A1
A B C D E F G H I

AI
POS
COAL A3 DAMPER POSITION FB
I A1
VDSI
01HLA53AA712-XQ01 POS Pin C
0.0 - 100.0% I
DAB DRAB
COAL A3 WINDBOX DAMPER
AI FBI FBO CEA O
COAL A3 DAMPER POSITION RB1I TRKS COAL A3 WINDBOX DAMPER TR RSE RSTC OPND D1
1 DEMAND1 RB SIGNAL T
VDSI 1
FGSG09-DRV-WBCOAL-A3-TR CLSD D3
01HLA53AA712-YQ01RB <FGSG09-WBC-COMMON-03>
0.0 - 100.0% RBSO <FGSG09-WBC-COMMON-04> MID D2
RB

COAL A3 WINDBOX DAMPER


AI
COAL A3 DAMPER POSITION RB2I FQAB FSA
DEMAND2 RB B

01HLA53AA712-YQ02RB PVC
0.0 - 100.0% DFDH DFD Ain Aout A1
RB 999.9uu
H
PVC
Cout A2
COAL A3 WINDBOX DAMPER RB
RQAB RSA
2 B 2
DRDH DRD
H
FSA X
B A
COAL A3 WINDBOX DAMPER FB SIG ABN
RSA X
CEA AO B A
COAL A WINDBOX DAMPER DEM AO COAL A3 WINDBOX DAMPER
DRIP COAL A3 WINDBOX DAMPER RB SIG ABN
(1,3,5,7) DEMAND SIGNAL POSN DEM1
FGSG09-DRV-WBCOAL-A1-A001 DRD X
<FGSG09-DRV-WBCOAL-A1> DEM_X1in=-10.0
01HLA53AA712-YQ01 H A
0.0 - 100.0%
DEM_Y1out=110.0 COAL A3 WINDBOX DAMPER RB DEV HI
3 DEM_X2in=110.0
AO DFD X
3
DEM_Y2out=-10.0
RB_X1in=-10.0
COAL A3 WINDBOX DAMPER H A
POSN DEM2
RB_Y1out=-10.0 COAL A3 WINDBOX DAMPER FB DEV HI
RB_X2in=110.0 01HLA53AA712-YQ02
RB_Y2out=110.0 0.0 - 100.0%
RB_CHG=0
ALLRST
RB_TRK=0 RPB
FB_TRK=0
DEM_FB=0
12DV=10.0 LARP RSE
ARDV=10.0 T
ONT1=10.0
DFDV=10.0 CED
ONT2=60.0 COAL A3 WINDBOX DAMPER DRV
ABN
4 FGSG09-DRV-WBCOAL-A3-D001
4
<FGSG09-DRV-WBCOAL-A1>
DABO DAB
O

LCN DABCND
D
INIT FDHEX

INIT

RBK

5 5
CED
COAL A 1,3,5,7 WINDBOX
RPB
DAMPER RESET PB ON
FGSG09-DRV-WBCOAL-A1-RST
<FGSG09-DRV-WBCOAL-A1>
CED
FG INITIALIZING INIT
FG INITIALIZING RSA RB SIG ABN
B
LCN
CED D
DRD RB SIG DEV H
FCB/RUNBACK OPERATE RBK
H
6 APC-EMG-10-D001 <APC-EMG-10>
6

TITLE COAL A CORNER 3 WINDBOX DAMPER Rev.


REMARKS

2
SHEET NO.
MITSUBISHI FGSG09-DRV-
HEAVY INDUSTRIES, LTD WBCOAL-A3
A B C D E F G H I

AI
POS
COAL A5 DAMPER POSITION FB
I A1
VDSI
01HLA55AA712-XQ01 POS Pin C
0.0 - 100.0% I
DAB DRAB
COAL A5 WINDBOX DAMPER
AI FBI FBO CEA O
COAL A5 DAMPER POSITION RB1I TRKS COAL A5 WINDBOX DAMPER TR RSE RSTC OPND D1
1 DEMAND1 RB SIGNAL T
VDSI 1
FGSG09-DRV-WBCOAL-A5-TR CLSD D3
01HLA55AA712-YQ01RB
0.0 - 100.0% <FGSG09-WBC-COMMON-03>
RBSO MID D2
RB <FGSG09-WBC-COMMON-04>

COAL A5 WINDBOX DAMPER


AI
COAL A5 DAMPER POSITION RB2I FQAB FSA
DEMAND2 RB B

01HLA55AA712-YQ02RB PVC
0.0 - 100.0% DFDH DFD Ain Aout A1
RB 999.9uu
H
PVC
Cout A2
COAL A5 WINDBOX DAMPER RB
RQAB RSA
2 B 2
DRDH DRD
H
FSA X
B A
COAL A5 WINDBOX DAMPER FB SIG ABN
RSA X
CEA AO B A
COAL A WINDBOX DAMPER DEM AO COAL A5 WINDBOX DAMPER
DRIP COAL A5 WINDBOX DAMPER RB SIG ABN
(1,3,5,7) DEMAND SIGNAL POSN DEM1
FGSG09-DRV-WBCOAL-A1-A001 DRD X
<FGSG09-DRV-WBCOAL-A1> DEM_X1in=-10.0
01HLA55AA712-YQ01 H A
0.0 - 100.0%
DEM_Y1out=110.0 COAL A5 WINDBOX DAMPER RB DEV HI
3 DEM_X2in=110.0
AO DFD X
3
DEM_Y2out=-10.0
RB_X1in=-10.0
COAL A5 WINDBOX DAMPER H A
POSN DEM2
RB_Y1out=-10.0 COAL A5 WINDBOX DAMPER FB DEV HI
RB_X2in=110.0 01HLA55AA712-YQ02
RB_Y2out=110.0 0.0 - 100.0%
RB_CHG=0
ALLRST
RB_TRK=0 RPB
FB_TRK=0
DEM_FB=0
12DV=10.0 LARP RSE
ARDV=10.0 T
ONT1=10.0
DFDV=10.0 CED
ONT2=60.0 COAL A5 WINDBOX DAMPER DRV
ABN
4 FGSG09-DRV-WBCOAL-A5-D001
4
<FGSG09-DRV-WBCOAL-A1>
DABO DAB
O

LCN DABCND
D
INIT FDHEX

INIT

RBK

5 5
CED
COAL A 1,3,5,7 WINDBOX
RPB
DAMPER RESET PB ON
FGSG09-DRV-WBCOAL-A1-RST
<FGSG09-DRV-WBCOAL-A1>
CED
FG INITIALIZING INIT
FG INITIALIZING RSA RB SIG ABN
B
LCN
CED D
DRD RB SIG DEV H
FCB/RUNBACK OPERATE RBK
H
6 APC-EMG-10-D001 <APC-EMG-10>
6

TITLE COAL A CORNER 5 WINDBOX DAMPER Rev.


REMARKS

2
SHEET NO.
MITSUBISHI FGSG09-DRV-
HEAVY INDUSTRIES, LTD WBCOAL-A5
A B C D E F G H I

AI
POS
COAL A7 DAMPER POSITION FB
I A1
VDSI
01HLA57AA712-XQ01 POS Pin C
0.0 - 100.0% I
DAB DRAB
COAL A7 WINDBOX DAMPER
AI FBI FBO CEA O
COAL A7 DAMPER POSITION RB1I TRKS COAL A7 WINDBOX DAMPER TR RSE RSTC OPND D1
1 DEMAND1 RB SIGNAL T
VDSI 1
FGSG09-DRV-WBCOAL-A7-TR CLSD D3
01HLA57AA712-YQ01RB
0.0 - 100.0% <FGSG09-WBC-COMMON-03>
RBSO MID D2
RB <FGSG09-WBC-COMMON-04>

COAL A7 WINDBOX DAMPER


AI
COAL A7 DAMPER POSITION RB2I FQAB FSA
DEMAND2 RB B

01HLA57AA712-YQ02RB PVC
0.0 - 100.0% DFDH DFD Ain Aout A1
RB 999.9uu
H
PVC
Cout A2
COAL A7 WINDBOX DAMPER RB
RQAB RSA
2 B 2
DRDH DRD
H
FSA X
B A
COAL A7 WINDBOX DAMPER FB SIG ABN
RSA X
CEA AO B A
COAL A WINDBOX DAMPER DEM AO COAL A7 WINDBOX DAMPER
DRIP COAL A7 WINDBOX DAMPER RB SIG ABN
(1,3,5,7) DEMAND SIGNAL POSN DEM1
FGSG09-DRV-WBCOAL-A1-A001 DRD X
<FGSG09-DRV-WBCOAL-A1> DEM_X1in=-10.0
01HLA57AA712-YQ01 H A
0.0 - 100.0%
DEM_Y1out=110.0 COAL A7 WINDBOX DAMPER RB DEV HI
3 DEM_X2in=110.0
AO DFD X
3
DEM_Y2out=-10.0
RB_X1in=-10.0
COAL A7 WINDBOX DAMPER H A
POSN DEM2
RB_Y1out=-10.0 COAL A7 WINDBOX DAMPER FB DEV HI
RB_X2in=110.0 01HLA57AA712-YQ02
RB_Y2out=110.0 0.0 - 100.0%
RB_CHG=0
ALLRST
RB_TRK=0 RPB
FB_TRK=0
DEM_FB=0
12DV=10.0 LARP RSE
ARDV=10.0 T
ONT1=10.0
DFDV=10.0 CED
ONT2=60.0 COAL A7 WINDBOX DAMPER DRV
ABN
4 FGSG09-DRV-WBCOAL-A7-D001
4
<FGSG09-DRV-WBCOAL-A1>
DABO DAB
O

LCN DABCND
D
INIT FDHEX

INIT

RBK

5 5
CED
COAL A 1,3,5,7 WINDBOX
RPB
DAMPER RESET PB ON
FGSG09-DRV-WBCOAL-A1-RST
<FGSG09-DRV-WBCOAL-A1>
CED
FG INITIALIZING INIT
FG INITIALIZING RSA RB SIG ABN
B
LCN
CED D
DRD RB SIG DEV H
FCB/RUNBACK OPERATE RBK
H
6 APC-EMG-10-D001 <APC-EMG-10>
6

TITLE COAL A CORNER 7 WINDBOX DAMPER Rev.


REMARKS

2
SHEET NO.
MITSUBISHI FGSG09-DRV-
HEAVY INDUSTRIES, LTD WBCOAL-A7
A B C D E F G H I

AI
POS
COAL A2 DAMPER POSITION FB
I A1
VDSI
SV S-PB-3-Set 01HLA52AA712-XQ01 POS Pin C
SV SV 01HLA52AA712 PB RPB 0.0 - 100.0% TRK
I
MV S-PB-8-Set DAB DRAB
PB APB
AI FBI FBO CEA O
COAL A2 WINDBOX DAMPER
V3 S-PB-10-Set COAL A2 DAMPER POSITION RB1I TRKS COAL A2 WINDBOX DAMPER TR RSTC OPND D1
TRK TRACKING SIG PB MPB RST
1 DEMAND1 RB SIGNAL
VDSI 1
DAB DRIVE ABN S-PB-2 Tagging FGSG09-DRV-WBCOAL-A2-TR TAG CLSD D3
O
PB TAG 01HLA52AA712-YQ01RB TAG
0.0 - 100.0% <FGSG09-WBCCOAL-A-01>
S-PB-3 RBSO MID D2
RST RB <FGSG09-WBC-COMMON-03>
<FGSG09-WBC-COMMON-04>
SAB SIG ABN S-PB-4
COAL A2 WINDBOX DAMPER
N AI
CAU CONTROL AUTO S-PB-8 COAL A2 DAMPER POSITION RB2I FQAB FSA
T DEMAND2 RB B
STB STAND BY MODE S-PB-9 MV-I-PRH
Y MV-D-PRH 01HLA52AA712-YQ02RB CAU D1
S-PB-10 MV-Set 0.0 - 100.0% DFDH DFD T <WIND BOX-2>
MAN MANUAL MODE
H STB D2 <WIND BOX-2>
<WIND BOX-2> Y <WIND BOX-1>
COAL A 2,4,6,8 WINDBOX DAMPER
CED <WIND BOX-2> D3 <WIND BOX-1>
MAN
<WIND BOX-1> RQAB RSA
FG INITIALIZING INIT
2 <WIND BOX-1> B
COAL A 2,4,6,8 WINDBOX DAMPER AUTO/MANUAL 2
FG INITIALIZING
CEA
COAL A WINDBOX DAMPER DRDH DRD
SV IPRH S=65.0 S=100.0 PVC
(2,4,6,8) PROGRAM SET DPRH H
DEM
FGSG09-WBCCOAL-A-01-A004 ULMT Ain Aout A1
SG SG RB 999.9uu
<FGSG09-WBCCOAL-A-01> PVC
LLMT DRVM FMA Cout A2
Ron=200.0 Ron=200.0 N
OPMT
Roff=99999.0 Roff=99999.0 COAL A2 WINDBOX DAMPER RB
CEA S OH OL MD=0 on MD=0 on AO <WIND BOX-2>
COAL A WINDBOX DAMPER X Y Ain Aout off off DEM AO COAL A2 WINDBOX DAMPER <WIND BOX-2>
(2,4,6,8) CONTROL SIGNAL
S/S TR TR DRIP
POSN DEM1 <WIND BOX-1>
FGSG09-WBCCOAL-A-01-A003 S=0.0 L sw OPP sw sw <WIND BOX-1>
OPC INIT OPRH 01HLA52AA712-YQ01
<FGSG09-WBCCOAL-A-01>
SG 0.0 - 100.0% RSA X
3 MAN
MANUAL MODE B A 3
S=10.0 on AO
COAL A2 WINDBOX DAMPER RB SIG ABN
off INITIALIZE COAL A2 WINDBOX DAMPER
SG TR INIT
POSN DEM2 FSA X
sw Ron=200.0 UNF UNFIRING POS CMD B A
STB Roff=200.0 P 01HLA52AA712-YQ02
STAND BY MODE 0.0 - 100.0% COAL A2 WINDBOX DAMPER FB SIG ABN
Y MD=0 FOP FORCED OPEN CMD
N ALLRST DRD X
RPB
CED H A
WINDBOX BANKING COMMAND DEM_X1in=-10.0 COAL A2 WINDBOX DAMPER RB DEV HI
CED
FOP MANU DEM_Y1out=110.0 DFD X
APC-ADC-15-D002 A-CFD SIG ABN (& A-CFD ON) MAN
<APC-ADC-15> N DEM_X2in=110.0 H A
DEM_Y2out=-10.0
FGSG09-WBCCOAL-A-01-D003 COAL A2 WINDBOX DAMPER FB DEV HI
CED CED <FGSG09-WBCCOAL-A-01> RB_X1in=-10.0
WINDBOX DMPR FORCED OPN FURN & WB INL PRESS SIG ABN SAB SABCND RB_Y1out=-10.0 FMA X
CMD (& A-COAL DMPR 2,4,6,8 DP CNT) N RB_X2in=110.0 N A
4 FGSG09-WBC-COMMON-01-D007 UNF FGSG09-WBCCOAL-A-01-D010 SAB LARP RB_Y2out=110.0 4
RST RB_CHG=0 COAL A 2,4,6,8 WINDBOX DAMPER FORCED MANUAL
<FGSG09-WBC-COMMON-01> P N
<FGSG09-WBCCOAL-A-01> RB_TRK=0
DABO DAB X
FB_TRK=0 MAN
CED O E
LDO HEADER PRESS ABN (& AB DEM_FB=0
12DV=10.0 COAL A 2,4,6,8 WINDBOX DAMPER MANUAL MODE
LDO ON / A-CF OFF)
FGSG09-WBCCOAL-A-01-D006 LCN DABCND ARDV=10.0 CAU X
D ONT1=10.0 T E
<FGSG09-WBCCOAL-A-01> DFDV=10.0
ACN INIT FDHEX
COAL A 2,4,6,8 WINDBOX DAMPER AUTO MODE
CED D CED ONT2=60.0
A COAL BNR ON or AB OIL BNR COAL A WINDBOX DAMPER STB X
INIT
ON(2,4,6,8) or FURN-WB DP CNT (2,4,6,8) FURN-WB DP CNT Y E
FGSG09-WBCCOAL-A-01-D004 FGSG09-WBCCOAL-A-01-D005 COAL A 2,4,6,8 WINDBOX DAMPER STANDBY MODE
<FGSG09-WBCCOAL-A-01> <FGSG09-WBCCOAL-A-01> RBK

5 5
CED CED
COAL A4 WINDBOX DAMPER DRV ATPB CAUTX Y CAU CAU COAL A 2,4,6,8 WINDBOX
APB AUTO PB <FGSG09-WBCCOAL-A-01>
ABN T T DAMPER AUTO
MNPB
FGSG09-DRV-WBCOAL-A4-D001 MPB MANUAL PB T=0.0 FGSG09-DRV-WBCOAL-A2-AT
CED
<FGSG09-DRV-WBCOAL-A4>
SAB CED ACN AUT CND ACND CSTB STB DAU COAL A 2,4,6,8 WINDBOX
<FGSG09-WBCCOAL-A-01>
N COAL A6 WINDBOX DAMPER DRV D Y T DAMPER AUTO or STANDBY
MCN ABN MCN MANU CND MCND ASM FGSG09-DRV-WBCOAL-A2-AST
D FGSG09-DRV-WBCOAL-A6-D001 D S CED
DAB <FGSG09-DRV-WBCOAL-A6> DAUT DAU STB COAL A 2,4,6,8 WINDBOX
O CED LCN T Y DAMPER STANDBY MODE
COAL A8 WINDBOX DAMPER DRV D FGSG09-DRV-WBCOAL-A2-ST
CED ABN CED
<FGSG09-DRV-WBCOAL-A4>
INIT MANU COAL A 2,4,6,8 WINDBOX
FCB/RUNBACK OPERATE RBK FGSG09-DRV-WBCOAL-A8-D001 INIT INITIALIZE MAN RPB <FGSG09-DRV-WBCOAL-A6>
DAMPER RESET PB ON
6 APC-EMG-10-D001 <APC-EMG-10>
<FGSG09-DRV-WBCOAL-A8>
FGSG09-DRV-WBCOAL-A2-RST
<FGSG09-DRV-WBCOAL-A8> 6
RSA RB SIG ABN CEA
B COAL A WINDBOX DAMPER
DEM <FGSG09-DRV-WBCOAL-A4>
(2,4,6,8) DEMAND SIGNAL
<FGSG09-DRV-WBCOAL-A6>
FGSG09-DRV-WBCOAL-A2-A001
<FGSG09-DRV-WBCOAL-A8>
DRD RB SIG DEV H
<FGSG09-WBCDPCNT-02>
H

TITLE COAL A CORNER 2 WINDBOX DAMPER Rev.


REMARKS

2
SHEET NO.
MITSUBISHI FGSG09-DRV-
HEAVY INDUSTRIES, LTD WBCOAL-A2
A B C D E F G H I

AI
POS
COAL A4 DAMPER POSITION FB
I A1
VDSI
01HLA54AA712-XQ01 POS Pin C
0.0 - 100.0% I
DAB DRAB
COAL A4 WINDBOX DAMPER
AI FBI FBO CEA O
COAL A4 DAMPER POSITION RB1I TRKS COAL A4 WINDBOX DAMPER TR RSE RSTC OPND D1
1 DEMAND1 RB SIGNAL T
VDSI 1
FGSG09-DRV-WBCOAL-A4-TR CLSD D3
01HLA54AA712-YQ01RB
0.0 - 100.0% <FGSG09-WBC-COMMON-03>
RBSO MID D2
RB <FGSG09-WBC-COMMON-04>

COAL A4 WINDBOX DAMPER


AI
COAL A4 DAMPER POSITION RB2I FQAB FSA
DEMAND2 RB B

01HLA54AA712-YQ02RB PVC
0.0 - 100.0% DFDH DFD Ain Aout A1
RB 999.9uu
H
PVC
Cout A2
COAL A4 WINDBOX DAMPER RB
RQAB RSA
2 B 2
DRDH DRD
H
FSA X
B A
COAL A4 WINDBOX DAMPER FB SIG ABN
RSA X
CEA AO B A
COAL A WINDBOX DAMPER DEM AO COAL A4 WINDBOX DAMPER
DRIP COAL A4 WINDBOX DAMPER RB SIG ABN
(2,4,6,8) DEMAND SIGNAL POSN DEM1
FGSG09-DRV-WBCOAL-A2-A001 DFD X
<FGSG09-DRV-WBCOAL-A2> DEM_X1in=-10.0
01HLA54AA712-YQ01 H A
0.0 - 100.0%
DEM_Y1out=110.0 COAL A4 WINDBOX DAMPER FB DEV HI
3 DEM_X2in=110.0
AO DRD X
3
DEM_Y2out=-10.0
RB_X1in=-10.0
COAL A4 WINDBOX DAMPER H A
POSN DEM2
RB_Y1out=-10.0 COAL A4 WINDBOX DAMPER RB DEV HI
RB_X2in=110.0 01HLA54AA712-YQ02
RB_Y2out=110.0 0.0 - 100.0%
RB_CHG=0
ALLRST
RB_TRK=0 RPB
FB_TRK=0
DEM_FB=0
12DV=10.0 LARP RSE
ARDV=10.0 T
ONT1=10.0
DFDV=10.0 CED
ONT2=60.0 COAL A4 WINDBOX DAMPER DRV
ABN
4 FGSG09-DRV-WBCOAL-A4-D001
4
<FGSG09-DRV-WBCOAL-A2>
DABO DAB
O

LCN DABCND
D
INIT FDHEX

INIT

RBK

5 5
CED
COAL A 2,4,6,8 WINDBOX
RPB
DAMPER RESET PB ON
FGSG09-DRV-WBCOAL-A2-RST
<FGSG09-DRV-WBCOAL-A2>
CED
FG INITIALIZING INIT
FG INITIALIZING RSA RB SIG ABN
B
LCN
CED D
DRD RB SIG DEV H
FCB/RUNBACK OPERATE RBK
H
6 APC-EMG-10-D001 <APC-EMG-10>
6

TITLE COAL A CORNER 4 WINDBOX DAMPER Rev.


REMARKS

2
SHEET NO.
MITSUBISHI FGSG09-DRV-
HEAVY INDUSTRIES, LTD WBCOAL-A4
A B C D E F G H I

AI
POS
COAL A6 DAMPER POSITION FB
I A1
VDSI
01HLA56AA712-XQ01 POS Pin C
0.0 - 100.0% I
DAB DRAB
COAL A6 WINDBOX DAMPER
AI FBI FBO CEA O
COAL A6 DAMPER POSITION RB1I TRKS COAL A6 WINDBOX DAMPER TR RSE RSTC OPND D1
1 DEMAND1 RB SIGNAL T
VDSI 1
FGSG09-DRV-WBCOAL-A6-TR CLSD D3
01HLA56AA712-YQ01RB
0.0 - 100.0% <FGSG09-WBC-COMMON-03>
RBSO MID D2
RB <FGSG09-WBC-COMMON-04>

COAL A6 WINDBOX DAMPER


AI
COAL A6 DAMPER POSITION RB2I FQAB FSA
DEMAND2 RB B

01HLA56AA712-YQ02RB PVC
0.0 - 100.0% DFDH DFD Ain Aout A1
RB 999.9uu
H
PVC
Cout A2
COAL A6 WINDBOX DAMPER RB
RQAB RSA
2 B 2
DRDH DRD
H
FSA X
B A
COAL A6 WINDBOX DAMPER FB SIG ABN
RSA X
CEA AO B A
COAL A WINDBOX DAMPER DEM AO COAL A6 WINDBOX DAMPER
DRIP COAL A6 WINDBOX DAMPER RB SIG ABN
(2,4,6,8) DEMAND SIGNAL POSN DEM1
FGSG09-DRV-WBCOAL-A2-A001 DFD X
<FGSG09-DRV-WBCOAL-A2> DEM_X1in=-10.0
01HLA56AA712-YQ01 H A
0.0 - 100.0%
DEM_Y1out=110.0 COAL A6 WINDBOX DAMPER FB DEV HI
3 DEM_X2in=110.0
AO DRD X
3
DEM_Y2out=-10.0
RB_X1in=-10.0
COAL A6 WINDBOX DAMPER H A
POSN DEM2
RB_Y1out=-10.0 COAL A6 WINDBOX DAMPER RB DEV HI
RB_X2in=110.0 01HLA56AA712-YQ02
RB_Y2out=110.0 0.0 - 100.0%
RB_CHG=0
ALLRST
RB_TRK=0 RPB
FB_TRK=0
DEM_FB=0
12DV=10.0 LARP RSE
ARDV=10.0 T
ONT1=10.0
DFDV=10.0 CED
ONT2=60.0 COAL A6 WINDBOX DAMPER DRV
ABN
4 FGSG09-DRV-WBCOAL-A6-D001
4
<FGSG09-DRV-WBCOAL-A2>
DABO DAB
O

LCN DABCND
D
INIT FDHEX

INIT

RBK

5 5
CED
COAL A 2,4,6,8 WINDBOX
RPB
DAMPER RESET PB ON
FGSG09-DRV-WBCOAL-A2-RST
<FGSG09-DRV-WBCOAL-A2>
CED
FG INITIALIZING INIT
FG INITIALIZING RSA RB SIG ABN
B
LCN
CED D
DRD RB SIG DEV H
FCB/RUNBACK OPERATE RBK
H
6 APC-EMG-10-D001 <APC-EMG-10>
6

TITLE COAL A CORNER 6 WINDBOX DAMPER Rev.


REMARKS

2
SHEET NO.
MITSUBISHI FGSG09-DRV-
HEAVY INDUSTRIES, LTD WBCOAL-A6
A B C D E F G H I

AI
POS
COAL A8 DAMPER POSITION FB
I A1
VDSI
01HLA58AA712-XQ01 POS Pin C
0.0 - 100.0% I
DAB DRAB
COAL A8 WINDBOX DAMPER
AI FBI FBO CEA O
COAL A8 DAMPER POSITION RB1I TRKS COAL A8 WINDBOX DAMPER TR RSE RSTC OPND D1
1 DEMAND1 RB SIGNAL T
VDSI 1
FGSG09-DRV-WBCOAL-A8-TR CLSD D3
01HLA58AA712-YQ01RB
0.0 - 100.0% <FGSG09-WBC-COMMON-03>
RBSO MID D2
RB <FGSG09-WBC-COMMON-04>

COAL A8 WINDBOX DAMPER


AI
COAL A8 DAMPER POSITION RB2I FQAB FSA
DEMAND2 RB B

01HLA58AA712-YQ02RB PVC
0.0 - 100.0% DFDH DFD Ain Aout A1
RB 999.9uu
H
PVC
Cout A2
COAL A8 WINDBOX DAMPER RB
RQAB RSA
2 B 2
DRDH DRD
H
FSA X
B A
COAL A8 WINDBOX DAMPER FB SIG ABN
RSA X
CEA AO B A
COAL A WINDBOX DAMPER DEM AO COAL A8 WINDBOX DAMPER
DRIP COAL A8 WINDBOX DAMPER RB SIG ABN
(2,4,6,8) DEMAND SIGNAL POSN DEM1
FGSG09-DRV-WBCOAL-A2-A001 DFD X
<FGSG09-DRV-WBCOAL-A2> DEM_X1in=-10.0
01HLA58AA712-YQ01 H A
0.0 - 100.0%
DEM_Y1out=110.0 COAL A8 WINDBOX DAMPER FB DEV HI
3 DEM_X2in=110.0
AO DRD X
3
DEM_Y2out=-10.0
RB_X1in=-10.0
COAL A8 WINDBOX DAMPER H A
POSN DEM2
RB_Y1out=-10.0 COAL A8 WINDBOX DAMPER RB DEV HI
RB_X2in=110.0 01HLA58AA712-YQ02
RB_Y2out=110.0 0.0 - 100.0%
RB_CHG=0
ALLRST
RB_TRK=0 RPB
FB_TRK=0
DEM_FB=0
12DV=10.0 LARP RSE
ARDV=10.0 T
ONT1=10.0
DFDV=10.0 CED
ONT2=60.0 COAL A8 WINDBOX DAMPER DRV
ABN
4 FGSG09-DRV-WBCOAL-A8-D001
4
<FGSG09-DRV-WBCOAL-A2>
DABO DAB
O

LCN DABCND
D
INIT FDHEX

INIT

RBK

5 5
CED
COAL A 2,4,6,8 WINDBOX
RPB
DAMPER RESET PB ON
FGSG09-DRV-WBCOAL-A2-RST
<FGSG09-DRV-WBCOAL-A2>
CED
FG INITIALIZING INIT
FG INITIALIZING RSA RB SIG ABN
B
LCN
CED D
DRD RB SIG DEV H
FCB/RUNBACK OPERATE RBK
H
6 APC-EMG-10-D001 <APC-EMG-10>
6

TITLE COAL A CORNER 8 WINDBOX DAMPER Rev.


REMARKS

2
SHEET NO.
MITSUBISHI FGSG09-DRV-
HEAVY INDUSTRIES, LTD WBCOAL-A8
A B C D E F G H I

1 1

2 2

3 3

4 4

5 5

OFF D

6 6
REMARKS
A B C D E F G H I

CEA CEA
FUEL OIL-AB WB DAMPER(1,3,5,7)
FURNACE-WB DP. CONTROL DEM
SET POINT
FGSG09-WBCDPCNT-01-A002 FGSG09-WBCOIL-AB-01-A002
<FGSG09-WBCDPCNT-01> S=0.0 <FGSG09-DRV-WBOIL-AB1>

CEA FX-1 * 1TR SG


LDO HEADER PRESS FX Ron=200.0
1 Roff=200.0
Ron=10.0 1
APC-MSS-LDOHDRPRS <APC-MSS-LDOHDRPRESS> Roff=99999.0
MD=0 on off on CEA
off on off FUEL OIL-AB WB DAMPER(1,3,5,7)
TR TRD TR CONT SIGNAL
sw sw sw FGSG09-WBCOIL-AB-01-A001
Ron=100.0 <FGSG09-DRV-WBOIL-AB1>
Roff=99999.0
MD=0
DP 1AT

1ST

FX-2 (FOR AB, EF & GH ELEV)*


2 CEA 2
FX FUEL OIL-AB WB DAMPER(2,4,6,8)
SET POINT
S=0.0 FGSG09-WBCOIL-AB-01-A004
FX-3 (FOR AB, EF & GH ELEV)* <FGSG09-DRV-WBOIL-AB2>
SG
FX 2TR

Ron=200.0 Ron=200.0 Ron=10.0


Roff=200.0 Roff=200.0 Roff=99999.0
CEA FX-4 (FOR AB, EF & GH ELEV)* on on MD=0 off MD=0 on off on CEA
off off on off on off FUEL OIL-AB WB DAMPER(2,4,6,8)
A/B COAL FLOW(AVE or A or B) FX TR TR TR TR TRD TR CONT SIGNAL
FGSG09-WBC-COMMON-01-A001 Ron=200.0 sw sw Ron=200.0 sw sw sw sw FGSG09-WBCOIL-AB-01-A003
<FGSG09-WBC-COMMON-01> Roff=200.0 Roff=200.0 Ron=100.0 <FGSG09-DRV-WBOIL-AB2>
CED MD=0 MD=0 Roff=99999.0
MD=0
WORST (COAL-1) SEL
3 APC-CMS-06-D001
DP 2AT 2ST 3
<APC-CMS-06>
CED CED
WORST (COAL-1) SEL WINDBOX BANKING COMMAND
APC-CMS-06-D001 <APC-CMS-06>
CED APC-ADC-15-D002 <APC-ADC-15>
BID MORE THAN 30%
FGSG09-WBC-COMMON-01-D008 LDO LDO
CED
<FGSG09-WBC-COMMON-01>
CEA LDO HEADER PRESS ABN (& AB
DP FURN-WB DP CNT
FUEL OIL-AB WINDBOX DAMPER CED CED LDO ON)
1TR
(1,3,5,7) CONT DEM ANY AB LDO BURNER ON LDO HEADER PRESS SIG FGSG09-WBCOIL-AB-01-D004
FGSG09-DRV-WBOIL-AB1-A002 (1,2,3,4,5,6,7,8) CED ABNORMAL <FGSG09-DRV-WBOIL-AB1>
<FGSG09-DRV-WBOIL-AB1> FGSG09-WBCOIL-AB-02-D006 AB OIL WINDBOX DAMPER FURN- APC-MSS-LDOHDRPRS-SABN <FGSG09-DRV-WBOIL-AB2>
CEA WB DP CNT <APC-MSS-LDOHDRPRESS>
4 FUEL OIL-AB WINDBOX DAMPER
<FGSG09-WBCOIL-AB-02>
A- FGSG09-WBCOIL-AB-01-D003
4
2TR
(2,4,6,8) CONT DEM CED ON <FGSG09-DRV-WBOIL-AB1>
FGSG09-DRV-WBOIL-AB2-A002 PULV-A & COAL FEEDER-A <FGSG09-DRV-WBOIL-AB2>
<FGSG09-DRV-WBOIL-AB2> START / PURGE IN PROGRESS <FGSG09-DRV-WBOIL-AB3>
BMS1-11A-9-D03 <FGSG09-DRV-WBOIL-AB4> A-
CED CED <FGSG09-DRV-WBOIL-AB5> ON CED
FUEL OIL-AB WINDBOX DAMPER PULV-B & COAL FEEDER-B <FGSG09-DRV-WBOIL-AB6> A/B COAL FLOW SIG ABN (& LDO
1ST
(1,3,5,7) AUTO or STBY START / PURGE IN PROGRESS <FGSG09-DRV-WBOIL-AB7> CED OFF / COAL ON)
FGSG09-DRV-WBOIL-AB1-AST BMS1-11B-9-D03 B- <FGSG09-DRV-WBOIL-AB8> FGSG09-WBCOIL-AB-01-D005
<FGSG09-DRV-WBOIL-AB1> COAL FLOW-A SIG.ABN
ON
<FGSG09-DRV-WBOIL-AB1>
FGSG09-MSS-CF-A-ABN <FGSG09-DRV-WBOIL-AB2>
CED
FUEL OIL-AB WINDBOX DAMPER B-
2ST
(2,4,6,8) AUTO or STBY ON
FGSG09-DRV-WBOIL-AB2-AST
<FGSG09-DRV-WBOIL-AB2> CED
5 5
COAL FLOW-B SIG.ABN
FGSG09-MSS-CF-B-ABN
CED
FUEL OIL-AB WINDBOX DAMPER
1AT FURN-WB DP CNT
(1,3,5,7) AUTO
DP
FGSG09-DRV-WBOIL-AB1-AT CED
<FGSG09-DRV-WBOIL-AB1> CED FURN & WB INL PRESS SIG ABN
FUEL OIL-AB WINDBOX DAMPER CED (& AB-OIL DAMPER DP CNT)
FURN-WB DP CNT DP
(1,3,5,7) AUTO (DP CNT) FURN & WB INL PRESS SIG ABN FGSG09-WBCOIL-AB-01-D006
FGSG09-WBCOIL-AB-01-D001 (& BID<30% / A-CF OFF) <FGSG09-DRV-WBOIL-AB1>
CED <FGSG09-WBCDPCNT-01> FGSG09-WBCAUX2-01-D004 <FGSG09-DRV-WBOIL-AB2>
FUEL OIL-AB WINDBOX DAMPER <FGSG09-WBCAUX2-01>
2AT
(2,4,6,8) AUTO
FGSG09-DRV-WBOIL-AB2-AT
<FGSG09-DRV-WBOIL-AB2> CED
6 FUEL OIL-AB WINDBOX DAMPER 6
(2,4,6,8) AUTO (DP CNT)
FGSG09-WBCOIL-AB-01-D002
<FGSG09-WBCDPCNT-01>

FX-1 * FX-2 (FOR AB, EF & GH ELEV)* FX-3 (FOR AB, EF & GH ELEV)* FX-4 (FOR AB, EF & GH ELEV)* FX-5 (FOR CD ELEV., FX-2,3,4 SHALL BE REPLACED BY FX-5)*
X1=0.0,Y1=60.0 X1=0.0,Y1=49.0 X1=0.0,Y1=49.0 X1=0.0,Y1=49.0 X1=0.0,Y1=49.0
X2=10.0,Y2=60.0 X2=25.0,Y2=49.0 X2=25.0,Y2=49.0 X2=25.0,Y2=49.0 X2=25.0,Y2=49.0 TITLE AB-OIL DAMPER CONTROL Rev.
X3=20.0,Y3=90.0 X3=35.0,Y3=50.0 X3=35.0,Y3=50.0 X3=35.0,Y3=50.0 X3=35.0,Y3=65.0
The same logic will be applicable for
REMARKS

X4=30.0,Y4=90.0 X4=45.0,Y4=50.0 X4=45.0,Y4=50.0 X4=45.0,Y4=50.0 X4=45.0,Y4=65.0 2


X5=0.0,Y5=0.0 X5=50.0,Y5=51.0 X5=50.0,Y5=51.0 X5=50.0,Y5=51.0 X5=50.0,Y5=65.0
X6=0.0,Y6=0.0 X6=65.0,Y6=53.0 X6=65.0,Y6=53.0 X6=65.0,Y6=53.0 X6=65.0,Y6=65.0 CD, EF & GH Oil Damper control. SHEET NO.
X7=0.0,Y7=0.0 X7=75.0,Y7=55.0 X7=75.0,Y7=55.0 X7=75.0,Y7=55.0 X7=75.0,Y7=65.0
X8=0.0,Y8=0.0 X8=100.0,Y8=57.0 X8=100.0,Y8=57.0 X8=100.0,Y8=57.0 X8=100.0,Y8=65.0
MITSUBISHI FGSG09-
X9=0.0,Y9=0.0 X9=110.0,Y9=57.0 X9=110.0,Y9=57.0 X9=110.0,Y9=57.0 X9=110.0,Y9=65.0 * TO BE FINALIZED DURING COMMISSIONING
X10=0.0,Y10=0.0 X10=0.0,Y10=0.0 X10=0.0,Y10=0.0 X10=0.0,Y10=0.0 X10=0.0,Y10=0.0 HEAVY INDUSTRIES, LTD WBCOIL-AB-01
A B C D E F G H I

CED
PULV-A & COAL FEEDER-A
START / PURGE IN PROGRESS
BMS1-11A-9-D03
CED
PULV-B & COAL FEEDER-B
START / PURGE IN PROGRESS
BMS1-11B-9-D03
1 1
CED
X Y A or B COAL BNR ON or AB1-DO
L1
BNR ON
T=1.0 FGSG09-WBCOIL-AB-02-D001<FGSG09-DRV-WBOIL-AB1>

CED
X Y A or B COAL BNR ON or AB3-DO
L3
BNR ON
T=1.0 FGSG09-WBCOIL-AB-02-D002<FGSG09-DRV-WBOIL-AB3>

CED
X Y A or B COAL BNR ON or AB5-DO
L5
2 OIL BNR ON 2
T=1.0 FGSG09-WBCOIL-AB-02-D003<FGSG09-DRV-WBOIL-AB5>

CED
X Y A or B COAL BNR ON or AB7-DO
L7
BNR ON
T=1.0 FGSG09-WBCOIL-AB-02-D004<FGSG09-DRV-WBOIL-AB7>

3 3
CED
ANY AB LDO BURNER ON (1,3,5,7) <FGSG09-WBCCOAL-A-01>
FGSG09-WBCOIL-AB-02-D005
CED CED
ANY AB LDO BURNER ON <FGSG09-WBCCOAL-A-01>
ANY AB LDO BURNER ON (2,4,6,8)
(1,2,3,4,5,6,7,8) <FGSG09-WBCOIL-AB-01>
FGSG09-WBCOIL-AB-03-D005 FGSG09-WBCOIL-AB-02-D006
<FGSG09-WBCOIL-AB-03>

4 4

L1 L5
CED CED
FUEL OIL BURNER AB-1 START- X Y FUEL OIL BURNER AB-5 START- X Y
UP MODE CED UP MODE CED
BMS1-10-9-AB1-D01 <BMS1-12-2-AB1> T=40.0 LDO DAMPER AB1 POSITION BMS1-10-9-AB5-D01 <BMS1-12-2-AB5> T=40.0 LDO DAMPER AB5 POSITION
CED BEFORE LIGHT-OFF CED BEFORE LIGHT-OFF
AB1 LDO BNR ON (BNR VLV OPN FGSG09-WBCOIL-AB-02-D007 AB5 LDO BNR ON (BNR VLV OPN FGSG09-WBCOIL-AB-02-D009
& FLAME ON) & FLAME ON) <FGSG09-DRV-WBOIL-AB5>
<FGSG09-DRV-WBOIL-AB1>
BMS1-10-17-AB1-D04 <BMS1-12-3-AB1> BMS1-10-17-AB5-D04 <BMS1-12-3-AB5>
5 5

L3 L7
CED CED
FUEL OIL BURNER AB-3 START- X Y FUEL OIL BURNER AB-7 START- X Y
UP MODE CED UP MODE CED
6 BMS1-10-9-AB3-D01 <BMS1-12-2-AB3> T=40.0 LDO DAMPER AB3 POSITION BMS1-10-9-AB7-D01 <BMS1-12-2-AB7> T=40.0 LDO DAMPER AB7 POSITION 6
CED BEFORE LIGHT-OFF CED BEFORE LIGHT-OFF
AB3 LDO BNR ON (BNR VLV OPN FGSG09-WBCOIL-AB-02-D008 AB7 LDO BNR ON (BNR VLV OPN FGSG09-WBCOIL-AB-02-D010
& FLAME ON) <FGSG09-DRV-WBOIL-AB3> & FLAME ON) <FGSG09-DRV-WBOIL-AB7>
BMS1-10-17-AB3-D04 <BMS1-12-3-AB3> BMS1-10-17-AB7-D04 <BMS1-12-3-AB7>

TITLE AB-OIL DAMPER PROVIDE CMD (1,5,3,7) Rev.


REMARKS

2
SHEET NO.
MITSUBISHI FGSG09-
HEAVY INDUSTRIES, LTD WBCOIL-AB-02
A B C D E F G H I

CED
PULV-A & COAL FEEDER-A
START / PURGE IN PROGRESS
BMS1-11A-9-D03
CED
PULV-B & COAL FEEDER-B
START / PURGE IN PROGRESS
BMS1-11B-9-D03
1 1
CED
X Y A OR B CFD & PULV ON / AB2-DO
L2
ON
T=1.0 FGSG09-WBCOIL-AB-03-D001
<FGSG09-DRV-WBOIL-AB2>

CED
X Y A OR B CFD & PULV ON / AB4-DO
L4
ON
T=1.0 FGSG09-WBCOIL-AB-03-D002
<FGSG09-DRV-WBOIL-AB4>

CED
X Y A OR B CFD & PULV ON / AB6-DO
L6
2 ON 2
T=1.0 FGSG09-WBCOIL-AB-03-D003
<FGSG09-DRV-WBOIL-AB6>

CED
X Y A OR B CFD & PULV ON / AB8-DO
L8
ON
T=1.0 FGSG09-WBCOIL-AB-03-D004
<FGSG09-DRV-WBOIL-AB8>

3 3
CED
ANY AB LDO BURNER ON (2,4,6,8)
FGSG09-WBCOIL-AB-03-D005
<FGSG09-WBCCOAL-A-01>
<FGSG09-WBCOIL-AB-02>

4 4

L2 L6
CED CED
FUEL OIL BURNER AB-2 START- X Y FUEL OIL BURNER AB-6 START- X Y
UP MODE CED UP MODE CED
BMS1-10-9-AB2-D01 <BMS1-12-2-AB2> T=40.0 LDO DAMPER AB2 POSITION BMS1-10-9-AB6-D01 <BMS1-12-2-AB6> T=40.0 LDO DAMPER AB6 POSITION
CED BEFORE LIGHT-OFF CED BEFORE LIGHT-OFF
AB2 LDO BNR ON (BNR VLV OPN FGSG09-WBCOIL-AB-03-D006 AB6 LDO BNR ON (BNR VLV OPN FGSG09-WBCOIL-AB-03-D008
& FLAME ON) & FLAME ON)
<FGSG09-DRV-WBOIL-AB2> <FGSG09-DRV-WBOIL-AB6>
BMS1-10-17-AB2-D04 <BMS1-12-3-AB2> BMS1-10-17-AB6-D04 <BMS1-12-3-AB6>
5 5

L4 L8
CED CED
FUEL OIL BURNER AB-4 START- X Y FUEL OIL BURNER AB-8 START- X Y
UP MODE CED UP MODE CED
6 BMS1-10-9-AB4-D01 <BMS1-12-2-AB4> T=40.0 LDO DAMPER AB4 POSITION BMS1-10-9-AB8-D01 <BMS1-12-2-AB8> T=40.0 LDO DAMPER AB8 POSITION 6
CED BEFORE LIGHT-OFF CED BEFORE LIGHT-OFF
AB4 LDO BNR ON (BNR VLV OPN FGSG09-WBCOIL-AB-03-D007 AB8 LDO BNR ON (BNR VLV OPN FGSG09-WBCOIL-AB-03-D009
& FLAME ON) & FLAME ON)
<FGSG09-DRV-WBOIL-AB4> <FGSG09-DRV-WBOIL-AB8>
BMS1-10-17-AB4-D04 <BMS1-12-3-AB4> BMS1-10-17-AB8-D04 <BMS1-12-3-AB8>

TITLE Rev.
AB-OIL DAMPER PROVIDE CMD (2,6,4,8)
REMARKS

2
SHEET NO.
FGSG09-
MITSUBISHI WBCOIL-AB-03
HEAVY INDUSTRIES, LTD
A B C D E F G H I

AI
FUEL OIL AB1 CORNER DAMPER POS
POSITION FB I A1

SV S-PB-3-Set 01HLA51AA713-XQ01 POS Pin C


SV SV 01HLA51AA713 PB RPB 0.0 - 100.0% I
MV S-PB-8-Set DAB DRAB
PB APB
AI FBI FBO CEA O
FUEL OIL AB1 WINDBOX DAMPER
DEM V3 S-PB-10-Set FUEL OIL AB1 CORNER DAMPER RB1I TRKS FUEL OIL AB1 WINDBOX DAMPER RSE RSTC OPND D1
PB MPB
1 1 POSITION DEMAND1 RB TR SIGNAL T
VDSI 1
DAB DRIVE ABN S-PB-2 Tagging FGSG09-DRV-WBOIL-AB1-TR TAG CLSD D3
O
PB TAG 01HLA51AA713-YQ01RB TAG
0.0 - 100.0% <FGSG09-WBC-COMMON-02>
RSE RESET COND S-PB-3 RBSO MID D2
RB
T
SAB SIG ABN S-PB-4
FUEL OIL AB1 WINDBOX DAMPER
N AI
CAU CONTROL AUTO S-PB-8 FUEL OIL AB1 CORNER DAMPER RB2I FQAB FSA
T POSITION DEMAND2 RB B
STB STAND BY MODE S-PB-9 MV-I-PRH
Y MV-D-PRH 01HLA51AA713-YQ02RB CAU D1
S-PB-10 MV-Set 0.0 - 100.0% DFDH DFD T <WIND BOX-1>
MAN MANUAL MODE
H STB D2 <WIND BOX-1>
<WIND BOX-1> Y <WIND BOX-2>
FUEL OIL AB WINDBOX DAMPER (1,3,5,7)
CED <WIND BOX-1> D3 <WIND BOX-2>
MAN
<WIND BOX-2> DEM RQAB RSA
FG INITIALIZING INIT
2 <WIND BOX-2> 1 B
FUEL OIL AB WINDBOX DAMPER (1,3,5,7) AUTO/MANUAL 2
FG INITIALIZING
CEA
FUEL OIL AB WB DAMPER(1,3,5,7) DRDH DRD
SV S=10.0 S=25.0 S=100.0
SET POINT DPRH IPRH H
FGSG09-WBCOIL-AB-01-A002 ULMT Ain Aout A1
SG SG SG RB 999.9uu
<FGSG09-WBCOIL-AB-01> PVC
LLMT DRVM FMA Cout A2
N
OPMT FUEL OIL AB1 WINDBOX DAMPER RB
CEA S OH OL on on on AO <WIND BOX-1>
FUEL OIL AB WB DAMPER(1,3,5,7) X Y Ain Aout off off off DEM AO FUEL OIL AB1 WINDBOX DAMPER
CONT SIGNAL
S/S TR TR TR DRIP
POSN DEM1
FGSG09-WBCOIL-AB-01-A001 S=0.0 L sw OPP OPC INIT OPRH sw sw sw
<FGSG09-WBCOIL-AB-01> Ron=99999.0 Ron=100.0 Ron=100.0 01HLA51AA713-YQ01
SG Roff=100.0 Roff=99999.0 Roff=99999.0 0.0 - 100.0% FSA X
3 MAN
MANUAL MODE MD=0 MD=0 MD=0 B A 3
S=10.0 on CLS AO
FUEL OIL AB1 WINDBOX DAMPER FB SIG ABN
off INITIALIZE 1 FUEL OIL AB1 WINDBOX DAMPER
SG TR INIT
POSN DEM2 RSA X
sw
Ron=200.0
UNF UNFIRING POS CMD B A
STB P 01HLA51AA713-YQ02
STAND BY MODE Roff=200.0 0.0 - 100.0% FUEL OIL AB1 WINDBOX DAMPER RB SIG ABN
Y FOP FORCED OPEN CMD
MD=0
N ALLRST DFD X
RPB
CED H A
WINDBOX BANKING COMMAND DEM_X1in=-10.0 FUEL OIL AB1 WINDBOX DAMPER FB DEV HI
DEM_Y1out=110.0
APC-ADC-15-D002 FOP MANU LARP RSE DRD X
<APC-ADC-15> MAN DEM_X2in=110.0
N CED T
DEM_Y2out=-10.0
H A
LDO HEADER PRESS ABN (& AB
RB_X1in=-10.0 FUEL OIL AB1 WINDBOX DAMPER RB DEV HI
CED LDO ON)
RB_Y1out=-10.0
WINDBOX DMPR FORCED OPN FGSG09-WBCOIL-AB-01-D004 <FGSG09-WBCOIL-AB-01> SAB SABCND FMA X
RB_X2in=110.0
CMD CED N N A
4 FGSG09-WBC-COMMON-01-D007 UNF A/B COAL FLOW SIG ABN (& LDO SAB
RB_Y2out=110.0 4
<FGSG09-WBC-COMMON-01> RB_CHG=0 FUEL OIL AB WINDBOX DAMPER (1,3,5,7) FORCED MANUAL
P OFF / COAL ON) N
RB_TRK=0
FGSG09-WBCOIL-AB-01-D005 <FGSG09-WBCOIL-AB-01> DABO DAB X
FB_TRK=0 MAN
CED O E
FURN & WB INL PRESS SIG ABN DEM_FB=0
12DV=10.0 FUEL OIL AB WINDBOX DAMPER (1,3,5,7) MANUAL MODE
(& AB-OIL DAMPER DP CNT)
LCN DABCND ARDV=10.0 CAU X
FGSG09-WBCOIL-AB-01-D006
CED D ONT1=10.0 T E
<FGSG09-WBCOIL-AB-01> DFDV=10.0
AB OIL WINDBOX DAMPER FURN- ACN INIT FDHEX
ONT2=60.0 FUEL OIL AB WINDBOX DAMPER (1,3,5,7) AUTO MODE
WB DP CNT D
FGSG09-WBCOIL-AB-01-D003 STB X
INIT
CED <FGSG09-WBCOIL-AB-01> Y E
A or B COAL BNR ON or AB1-DO
FUEL OIL AB WINDBOX DAMPER (1,3,5,7) STANDBY MODE
BNR ON
RBK
FGSG09-WBCOIL-AB-02-D001
<FGSG09-WBCOIL-AB-02>
5 5
CED
SAB CED ATPB CAUTX Y CAU CAU FUEL OIL AB WINDBOX DAMPER
APB AUTO PB <FGSG09-WBCOIL-AB-01>
N FUEL OIL AB3 WINDBOX DAMPER T T (1,3,5,7) AUTO
MCN DRV ABN MNPB
MPB MANUAL PB T=0.0 FGSG09-DRV-WBOIL-AB1-AT
D FGSG09-DRV-WBOIL-AB3-D001 CED
DAB CED <FGSG09-DRV-WBOIL-AB3> ACN AUT CND ACND CSTB STB DAU FUEL OIL AB WINDBOX DAMPER
O FUEL OIL AB5 WINDBOX DAMPER D Y T (1,3,5,7) AUTO or STBY <FGSG09-WBCOIL-AB-01>
DRV ABN MCN MANU CND MCND ASM FGSG09-DRV-WBOIL-AB1-AST
CED FGSG09-DRV-WBOIL-AB5-D001 D S CED
CED <FGSG09-DRV-WBOIL-AB5> DAUT DAU STB FUEL OIL AB WINDBOX DAMPER
FCB/RUNBACK OPERATE RBK
FUEL OIL AB7 WINDBOX DAMPER LCN T Y (1,3,5,7) STBY MODE
APC-EMG-10-D001 <APC-EMG-10> DRV ABN D FGSG09-DRV-WBOIL-AB1-ST
FGSG09-DRV-WBOIL-AB7-D001 CED
<FGSG09-DRV-WBOIL-AB7> <FGSG09-DRV-WBOIL-AB3>
INIT MANU X Y FUEL OIL AB WINDBOX DAMPER
INIT INITIALIZE MAN RPB <FGSG09-DRV-WBOIL-AB5>
RSA RB SIG ABN (1,3,5,7) RESET PB ON
6 B T=0.5 FGSG09-DRV-WBOIL-AB1-D004
<FGSG09-DRV-WBOIL-AB7> 6
CED DRD RB SIG DEV H CEA
LDO DAMPER AB1 POSITION CLS H DEM FUEL OIL AB WINDBOX DAMPER
<FGSG09-DRV-WBOIL-AB3>
BEFORE LIGHT-OFF 1 1 (1,3,5,7) CONT DEM
<FGSG09-DRV-WBOIL-AB5>
FGSG09-WBCOIL-AB-02-D007 FGSG09-DRV-WBOIL-AB1-A002
<FGSG09-WBCOIL-AB-02> <FGSG09-DRV-WBOIL-AB7>
<FGSG09-WBCDPCNT-01>
<FGSG09-WBCOIL-AB-01>

TITLE AB-FUEL OIL 1CORNER WINDBOX DAMPER Rev.


REMARKS

2
SHEET NO.
MITSUBISHI FGSG09-DRV-
HEAVY INDUSTRIES, LTD WBOIL-AB1
A B C D E F G H I

AI
FUEL OIL AB 5CORNER DAMPER POS
POSITION DEMAND1 RB I A1

01HLA55AA713-XQ01 POS Pin C


0.0 - 100.0% I
DAB DRAB
FUEL OIL AB5 WINDBOX DAMPER
AI FBI FBO CEA O
FUEL OIL AB 5CORNER DAMPER RB1I TRKS FUEL OIL AB5 WINDBOX DAMPER RSTC OPND D1
RST
1 POSITION DEMAND1 RB TR SIGNAL
VDSI 1
FGSG09-DRV-WBOIL-AB5-TR CLSD D3
01HLA55AA713-YQ01RB <FGSG09-WBC-COMMON-02>
0.0 - 100.0% RBSO MID D2
RB

FUEL OIL AB5 WINDBOX DAMPER


AI
FUEL OIL AB 5CORNER DAMPER RB2I FQAB FSA
POSITION DEMAND2 RB B

01HLA55AA713-YQ02RB
0.0 - 100.0% DFDH DFD Ain Aout A1
RB 999.9uu
H
PVC
Cout A2
FUEL OIL AB5 WINDBOX DAMPER RB
RQAB RSA
2 B <WIND BOX-2> 2
DRDH DRD
H
S=10.0 S=10.0 S=100.0
SG SG SG

CEA on on on AO
FUEL OIL AB WINDBOX DAMPER off off off DEM AO FUEL OIL AB5 WINDBOX DAMPER
(1,3,5,7) CONT DEM
TR TR TR DRIP
POSN DEM1
FGSG09-DRV-WBOIL-AB1-A002 sw sw sw
<FGSG09-DRV-WBOIL-AB1> Ron=99999.0 Ron=100.0 Ron=100.0 01HLA55AA713-YQ01
Roff=100.0 Roff=99999.0 Roff=99999.0 0.0 - 100.0% FSA X
3
MD=0 MD=0 MD=0 B A 3
CLS UNF FOP AO
FUEL OIL AB5 WINDBOX DAMPER FB SIG ABN
1 P N FUEL OIL AB5 WINDBOX DAMPER
POSN DEM2 RSA X
B A
01HLA55AA713-YQ02
0.0 - 100.0% FUEL OIL AB5 WINDBOX DAMPER RB SIG ABN
FOP ALLRST DFD X
RPB
N H A
FUEL OIL AB5 WINDBOX DAMPER FB DEV HI
CED DEM_X1in=-10.0
WINDBOX DMPR FORCED OPN DRD X
DEM_Y1out=110.0
CMD
DEM_X2in=110.0
H A
FGSG09-WBC-COMMON-01-D007 DEM_Y2out=-10.0 FUEL OIL AB5 WINDBOX DAMPER RB DEV HI
CED <FGSG09-WBC-COMMON-01>
RB_X1in=-10.0 RST
WINDBOX BANKING COMMAND RB_Y1out=-10.0
4 APC-ADC-15-D002 UNF
RB_X2in=110.0
LARP 4
<APC-ADC-15> RB_Y2out=110.0
CED P CED
RB_CHG=0
AB OIL WINDBOX DAMPER FURN- DABO FUEL OIL AB5 WINDBOX DAMPER
RB_TRK=0
WB DP CNT DRV ABN
FB_TRK=0
FGSG09-WBCOIL-AB-01-D003 FGSG09-DRV-WBOIL-AB5-D001
CED <FGSG09-WBCOIL-AB-01> DEM_FB=0 DAB <FGSG09-DRV-WBOIL-AB1>
A or B COAL BNR ON or AB5-DO 12DV=10.0 LCN DABCND O
OIL BNR ON ARDV=10.0 D
ONT1=10.0 INIT
FGSG09-WBCOIL-AB-02-D003
DFDV=10.0
<FGSG09-WBCOIL-AB-02>
ONT2=60.0
INIT

5 5
RSA RB SIG ABN
B
LCN
D
DRD RB SIG DEV H
H

CED
6 FG INITIALIZING INIT
6
CED
LDO DAMPER AB5 POSITION CLS FG INITIALIZING
BEFORE LIGHT-OFF 1 CED
FGSG09-WBCOIL-AB-02-D009
<FGSG09-WBCOIL-AB-02> FUEL OIL AB WINDBOX DAMPER
RPB
(1,3,5,7) RESET PB ON
FGSG09-DRV-WBOIL-AB1-D004
<FGSG09-DRV-WBOIL-AB1>

TITLE AB-FUEL OIL 5CORNER WINDBOX DAMPER Rev.


REMARKS

2
SHEET NO.
MITSUBISHI FGSG09-DRV-
HEAVY INDUSTRIES, LTD WBOIL-AB5
A B C D E F G H I

AI
FUEL OIL AB3 CORNER DAMPER POS
POSITION FB I A1

01HLA53AA713-XQ01 POS Pin C


0.0 - 100.0% I
DAB DRAB
FUEL OIL AB3 WINDBOX DAMPER
AI FBI FBO CEA O
FUEL OIL AB3 CORNER DAMPER RB1I TRKS FUEL OIL AB3 WINDBOX DAMPER RSTC OPND D1
RST
1 POSITION DEMAND1 RB TR SIGNAL
VDSI 1
FGSG09-DRV-WBOIL-AB3-TR CLSD D3
01HLA53AA713-YQ01RB <FGSG09-WBC-COMMON-02>
0.0 - 100.0% RBSO MID D2
RB

FUEL OIL AB3 WINDBOX DAMPER


AI
FUEL OIL AB3 CORNER DAMPER RB2I FQAB FSA
POSITION DEMAND2 RB B

01HLA53AA713-YQ02RB
0.0 - 100.0% DFDH DFD Ain Aout A1
RB 999.9uu
H
PVC
Cout A2
FUEL OIL AB3 WINDBOX DAMPER RB
RQAB RSA
<WIND BOX-2>
2 B 2
DRDH DRD
H
S=10.0 S=10.0 S=100.0
SG SG SG

CEA on on on AO
FUEL OIL AB WINDBOX DAMPER off off off DEM AO FUEL OIL AB3 WINDBOX DAMPER
(1,3,5,7) CONT DEM
TR TR TR DRIP
POSN DEM1
FGSG09-DRV-WBOIL-AB1-A002 sw sw sw
<FGSG09-DRV-WBOIL-AB1> Ron=99999.0 Ron=100.0 Ron=100.0 01HLA53AA713-YQ01
Roff=100.0 Roff=99999.0 Roff=99999.0 0.0 - 100.0% FSA X
3
MD=0 MD=0 MD=0 B A 3
CLS UNF FOP AO
FUEL OIL AB3 WINDBOX DAMPER FB SIG ABN
1 P N FUEL OIL AB3 WINDBOX DAMPER
POSN DEM2 RSA X
B A
01HLA53AA713-YQ02
0.0 - 100.0% FUEL OIL AB3 WINDBOX DAMPER RB SIG ABN
FOP ALLRST DRD X
RPB
N H A
FUEL OIL AB3 WINDBOX DAMPER RB DEV HI
CED
WINDBOX DMPR FORCED OPN DFD X
CMD H A
FGSG09-WBC-COMMON-01-D007 RST FUEL OIL AB3 WINDBOX DAMPER FB DEV HI
CED DEM_X1in=-10.0
<FGSG09-WBC-COMMON-01>
DEM_Y1out=110.0
WINDBOX BANKING COMMAND DEM_X2in=110.0
4 APC-ADC-15-D002 UNF DEM_Y2out=-10.0 LARP 4
<APC-ADC-15> RB_X1in=-10.0
CED P CED
AB OIL WINDBOX DAMPER FURN- RB_Y1out=-10.0 DABO FUEL OIL AB3 WINDBOX DAMPER
WB DP CNT RB_X2in=110.0 DRV ABN
FGSG09-WBCOIL-AB-01-D003 RB_Y2out=110.0 FGSG09-DRV-WBOIL-AB3-D001
CED <FGSG09-WBCOIL-AB-01> RB_CHG=0 <FGSG09-DRV-WBOIL-AB1>
A or B COAL BNR ON or AB3-DO RB_TRK=0 LCN DABCND DAB
BNR ON FB_TRK=0 D O
FGSG09-WBCOIL-AB-02-D002 DEM_FB=0 INIT
<FGSG09-WBCOIL-AB-02> 12DV=10.0
ARDV=10.0
ONT1=10.0 INIT
DFDV=10.0
ONT2=60.0

5 5
RSA RB SIG ABN
B
LCN
D
DRD RB SIG DEV H
H

CED
FG INITIALIZING INIT
6 FG INITIALIZING 6
CED CED
LDO DAMPER AB3 POSITION CLS FUEL OIL AB WINDBOX DAMPER
RPB
BEFORE LIGHT-OFF 1 (1,3,5,7) RESET PB ON
FGSG09-WBCOIL-AB-02-D008 FGSG09-DRV-WBOIL-AB1-D004
<FGSG09-WBCOIL-AB-02> <FGSG09-DRV-WBOIL-AB1>

TITLE AB-FUEL OIL 3CORNER WINDBOX DAMPER Rev.


REMARKS

2
SHEET NO.
MITSUBISHI FGSG09-DRV-
HEAVY INDUSTRIES, LTD WBOIL-AB3
A B C D E F G H I

AI
FUEL OIL AB7 CORNER DAMPER POS A1
POSITION FB I

01HLA57AA713-XQ01 POS Pin C


0.0 - 100.0% I
FUEL OIL AB7 WINDBOX DAMPER
DAB DRAB
AI FBI FBO CEA O
FUEL OIL AB7 CORNER DAMPER RB1I TRKS FUEL OIL AB7 WINDBOX DAMPER RSTC OPND D1
RST
1 POSITION DEMAND1 RB TR SIGNAL
VDSI 1
FGSG09-DRV-WBOIL-AB7-TR CLSD D3
01HLA57AA713-YQ01RB
0.0 - 100.0% <FGSG09-WBC-COMMON-02>
RBSO MID D2
RB

FUEL OIL AB7 WINDBOX DAMPER


AI
FUEL OIL AB7 CORNER DAMPER RB2I FQAB FSA
POSITION DEMAND2 RB B

01HLA57AA713-YQ02RB
0.0 - 100.0% DFDH DFD
H Ain Aout A1
RB 999.9uu
PVC
Cout A2
RQAB RSA
FUEL OIL AB7 WINDBOX DAMPER RB
2 B
<WIND BOX-1>
2
DRDH DRD
H
S=10.0 S=10.0 S=100.0
SG SG SG

CEA on on on AO
FUEL OIL AB WINDBOX DAMPER off off off DEM AO FUEL OIL AB7 WINDBOX DAMPER
(1,3,5,7) CONT DEM
TR TR TR DRIP
POSN DEM1
FGSG09-DRV-WBOIL-AB1-A002 sw sw sw
<FGSG09-DRV-WBOIL-AB1> Ron=99999.0 Ron=100.0 Ron=100.0 01HLA57AA713-YQ01
Roff=100.0 Roff=99999.0 Roff=99999.0 0.0 - 100.0% FSA X
3
MD=0 MD=0 MD=0 B A 3
CLS UNF FOP AO
FUEL OIL AB7 WINDBOX DAMPER FB SIG ABN
1 P N FUEL OIL AB7 WINDBOX DAMPER
POSN DEM2 RSA X
B A
01HLA57AA713-YQ02
0.0 - 100.0% FUEL OIL AB7 WINDBOX DAMPER RB SIG ABN
FOP ALLRST DRD X
RPB
N H A
FUEL OIL AB7 WINDBOX DAMPER RB DEV HI
CED
WINDBOX DMPR FORCED OPN DFD X
CMD H A
FGSG09-WBC-COMMON-01-D007 FUEL OIL AB7 WINDBOX DAMPER FB DEV HI
CED <FGSG09-WBC-COMMON-01>
DEM_X1in=-10.0 RST
WINDBOX BANKING COMMAND DEM_Y1out=110.0
4 APC-ADC-15-D002 UNF
DEM_X2in=110.0
LARP 4
<APC-ADC-15> DEM_Y2out=-10.0
CED P CED
RB_X1in=-10.0
AB OIL WINDBOX DAMPER FURN- DABO FUEL OIL AB7 WINDBOX DAMPER
RB_Y1out=-10.0
WB DP CNT DRV ABN
RB_X2in=110.0
FGSG09-WBCOIL-AB-01-D003 RB_Y2out=110.0 FGSG09-DRV-WBOIL-AB7-D001
CED <FGSG09-WBCOIL-AB-01> DAB <FGSG09-DRV-WBOIL-AB1>
RB_CHG=0
A or B COAL BNR ON or AB7-DO LCN DABCND O
RB_TRK=0
BNR ON D
FB_TRK=0 INIT
FGSG09-WBCOIL-AB-02-D004
<FGSG09-WBCOIL-AB-02> DEM_FB=0
12DV=10.0
ARDV=10.0 INIT
ONT1=10.0
DFDV=10.0
ONT2=60.0

5 5
RSA RB SIG ABN
B
LCN
D
DRD RB SIG DEV H
H

CED
6 FG INITIALIZING INIT
6
CED
LDO DAMPER AB7 POSITION CLS FG INITIALIZING
BEFORE LIGHT-OFF 1 CED
FGSG09-WBCOIL-AB-02-D010 FUEL OIL AB WINDBOX DAMPER
<FGSG09-WBCOIL-AB-02> RPB
(1,3,5,7) RESET PB ON
FGSG09-DRV-WBOIL-AB1-D004
<FGSG09-DRV-WBOIL-AB1>

TITLE AB-FUEL OIL 7CORNER WINDBOX DAMPER Rev.


REMARKS

2
SHEET NO.
MITSUBISHI FGSG09-DRV-
HEAVY INDUSTRIES, LTD WBOIL-AB7
A B C D E F G H I

AI
FUEL OIL AB2 CORNER DAMPER POS
POSITION FB I A1

SV S-PB-3-Set 01HLA52AA713-XQ01 POS Pin C


SV SV 01HLA52AA713 PB RPB 0.0 - 100.0% I
MV S-PB-8-Set DAB DRAB
PB APB
AI FBI FBO CEA O
FUEL OIL AB2 WINDBOX DAMPER
DEM V3 S-PB-10-Set FUEL OIL AB2 CORNER DAMPER RB1I TRKS FUEL OIL AB2 WINDBOX DAMPER RSTC OPND D1
PB MPB RST
1 1 POSITION DEMAND1 RB TR SIGNAL
VDSI 1
DAB DRIVE ABN S-PB-2 Tagging FGSG09-DRV-WBOIL-AB2-TR TAG CLSD D3
O
PB TAG 01HLA52AA713-YQ01RB TAG
<FGSG09-WBC-COMMON-02>
S-PB-3 0.0 - 100.0% RBSO MID D2
RST RB
SAB SIG ABN S-PB-4
FUEL OIL AB2 WINDBOX DAMPER
N AI
CAU CONTROL AUTO S-PB-8 FUEL OIL AB2 CORNER DAMPER RB2I FQAB FSA
T POSITION DEMAND2 RB B
STB STAND BY MODE S-PB-9 MV-I-PRH CAU D1
Y MV-D-PRH 01HLA52AA713-YQ02RB T <WIND BOX-2>
S-PB-10 MV-Set 0.0 - 100.0% DFDH DFD STB D2 <WIND BOX-2>
MAN MANUAL MODE
H Y <WIND BOX-1>
<WIND BOX-2> D3 <WIND BOX-1>
MAN
CED FUEL OIL AB WINDBOX DAMPER (2,4,6,8)
<WIND BOX-2>
DEM RQAB RSA
FG INITIALIZING INIT <WIND BOX-1> FUEL OIL AB WINDBOX DAMPER (2,4,6,8) AUTO/MANUAL
2 <WIND BOX-1>
1 B 2
FG INITIALIZING
CEA
FUEL OIL AB WB DAMPER(2,4,6,8) DRDH DRD Ain Aout A1
SV S=10.0 S=25.0 S=100.0 RB 999.9uu
SET POINT DPRH IPRH H
PVC
FGSG09-WBCOIL-AB-01-A004
<FGSG09-WBCOIL-AB-01> ULMT Cout A2
SG SG SG
FUEL OIL AB2 WINDBOX DAMPER RB
LLMT DRVM FMA
N <WIND BOX-1>
OPMT
CEA S OH OL on on on AO
FUEL OIL AB WB DAMPER(2,4,6,8) X Y Ain Aout off off off DEM AO FUEL OIL AB2 WINDBOX DAMPER
CONT SIGNAL
S/S TR TR TR DRIP
POSN DEM1
FGSG09-WBCOIL-AB-01-A003 S=0.0 L sw OPP OPC INIT OPRH sw sw sw
<FGSG09-WBCOIL-AB-01> Ron=99999.0 Ron=100.0 Ron=100.0 01HLA52AA713-YQ01
SG Roff=100.0 Roff=99999.0 Roff=99999.0 0.0 - 100.0% FSA X
3 MAN
MANUAL MODE MD=0 MD=0 MD=0 B A 3
S=10.0 on CLS AO
FUEL OIL AB2 WINDBOX DAMPER FB SIG ABN
off INITIALIZE 1 FUEL OIL AB2 WINDBOX DAMPER
SG TR INIT
POSN DEM2 DFD X
sw
Ron=200.0
UNF UNFIRING POS CMD H A
STB P 01HLA52AA713-YQ02
STAND BY MODE Roff=200.0 0.0 - 100.0% FUEL OIL AB2 WINDBOX DAMPER FB DEV HI
Y FOP FORCED OPEN CMD
MD=0
N ALLRST RSA X
RPB
CED B A
WINDBOX BANKING COMMAND DEM_X1in=-10.0 FUEL OIL AB2 WINDBOX DAMPER RB SIG ABN
DEM_Y1out=110.0
APC-ADC-15-D002 <APC-ADC-15> FOP MANU DRD X
MAN DEM_X2in=110.0
N CED
DEM_Y2out=-10.0
H A
LDO HEADER PRESS ABN (& AB
RB_X1in=-10.0 FUEL OIL AB2 WINDBOX DAMPER RB DEV HI
CED LDO ON)
RB_Y1out=-10.0
WINDBOX DMPR FORCED OPN FGSG09-WBCOIL-AB-01-D004 SAB SABCND FMA X
RB_X2in=110.0
CMD CED <FGSG09-WBCOIL-AB-01> N N A
4 FGSG09-WBC-COMMON-01-D007 UNF A/B COAL FLOW SIG ABN (& LDO SAB LARP
RB_Y2out=110.0 4
<FGSG09-WBC-COMMON-01> RST RB_CHG=0 FUEL OIL AB WINDBOX DAMPER (2,4,6,8) FORCED MANUAL
P OFF / COAL ON) N
RB_TRK=0
FGSG09-WBCOIL-AB-01-D005 DABO DAB X
FB_TRK=0 MAN
CED <FGSG09-WBCOIL-AB-01> O E
FURN & WB INL PRESS SIG ABN DEM_FB=0
12DV=10.0 FUEL OIL AB WINDBOX DAMPER (2,4,6,8) MANUAL MODE
(& AB-OIL DAMPER DP CNT)
LCN DABCND ARDV=10.0 CAU X
FGSG09-WBCOIL-AB-01-D006
CED <FGSG09-WBCOIL-AB-01> D ONT1=10.0 T E
AB OIL WINDBOX DAMPER FURN- ACN INIT FDHEX DFDV=10.0
ONT2=60.0 FUEL OIL AB WINDBOX DAMPER (2,4,6,8) AUTO MODE
WB DP CNT D
FGSG09-WBCOIL-AB-01-D003 STB X
<FGSG09-WBCOIL-AB-01> INIT
CED Y E
A OR B CFD & PULV ON / AB2-DO
FUEL OIL AB WINDBOX DAMPER (2,4,6,8) STANDBY MODE
ON
RBK
FGSG09-WBCOIL-AB-03-D001
<FGSG09-WBCOIL-AB-03>
5 5
CED
SAB CED ATPB CAUTX Y CAU CAU FUEL OIL AB WINDBOX DAMPER
APB AUTO PB <FGSG09-WBCOIL-AB-01>
N FUEL OIL AB4 CORNER WINDBOX T T (2,4,6,8) AUTO
MCN DAMPER DRV ABN MNPB
MPB MANUAL PB T=0.0 FGSG09-DRV-WBOIL-AB2-AT
D FGSG09-DRV-WBOIL-AB4-D001 CED
DAB CED <FGSG09-DRV-WBOIL-AB4> ACN AUT CND ACND CSTB STB DAU FUEL OIL AB WINDBOX DAMPER
<FGSG09-WBCOIL-AB-01>
O FUEL OIL AB6 WINDBOX DAMPER D Y T (2,4,6,8) AUTO or STBY
DRV ABN MCN MANU CND MCND ASM FGSG09-DRV-WBOIL-AB2-AST
CED FGSG09-DRV-WBOIL-AB6-D001 D S CED
CED <FGSG09-DRV-WBOIL-AB6> DAUT DAU STB FUEL OIL AB WINDBOX DAMPER
FCB/RUNBACK OPERATE RBK
FUEL OIL AB8 WINDBOX DAMPER LCN T Y (2,4,6,8) STBY MODE
APC-EMG-10-D001 <APC-EMG-10> DRV ABN D FGSG09-DRV-WBOIL-AB2-ST
FGSG09-DRV-WBOIL-AB8-D001 CED
INIT MANU X Y FUEL OIL AB WINDBOX DAMPER <FGSG09-DRV-WBOIL-AB4>
<FGSG09-DRV-WBOIL-AB8> INIT INITIALIZE MAN RPB <FGSG09-DRV-WBOIL-AB6>
RSA RB SIG ABN (2,4,6,8) RESET PB ON
6 B T=0.5 FGSG09-DRV-WBOIL-AB2-D004 <FGSG09-DRV-WBOIL-AB8> 6
CED DRD RB SIG DEV H CEA
LDO DAMPER AB2 POSITION CLS H DEM FUEL OIL AB WINDBOX DAMPER
<FGSG09-DRV-WBOIL-AB4>
BEFORE LIGHT-OFF 1 1 (2,4,6,8) CONT DEM
<FGSG09-DRV-WBOIL-AB6>
FGSG09-WBCOIL-AB-03-D006 FGSG09-DRV-WBOIL-AB2-A002
<FGSG09-DRV-WBOIL-AB8>
<FGSG09-WBCOIL-AB-03> <FGSG09-WBCDPCNT-01>
<FGSG09-WBCOIL-AB-01>

TITLE AB-FUEL OIL 2CORNER WINDBOX DAMPER Rev.


REMARKS

2
SHEET NO.
MITSUBISHI FGSG09-DRV-
HEAVY INDUSTRIES, LTD WBOIL-AB2
A B C D E F G H I

AI
FUEL OIL AB6 CORNER DAMPER POS A1
POSITION FB I

01HLA56AA713-XQ01 POS Pin C


0.0 - 100.0% I
DAB DRAB FUEL OIL AB6 WINDBOX DAMPER
AI FBI FBO CEA O
FUEL OIL AB6 CORNER DAMPER RB1I TRKS FUEL OIL AB6 WINDBOX DAMPER RSTC OPND D1
RST
1 POSITION DEMAND1 RB TR SIGNAL
VDSI 1
FGSG09-DRV-WBOIL-AB6-TR CLSD D3
01HLA56AA713-YQ01RB
0.0 - 100.0% <FGSG09-WBC-COMMON-02>
RBSO MID D2
RB

FUEL OIL AB6 WINDBOX DAMPER


AI
FUEL OIL AB6 CORNER DAMPER RB2I FQAB FSA
POSITION DEMAND2 RB B

01HLA56AA713-YQ02RB Ain Aout A1


0.0 - 100.0% RB 999.9uu
DFDH DFD
PVC
H Cout A2
FUEL OIL AB6 WINDBOX DAMPER RB
RQAB RSA <WIND BOX-2>

2 B 2
DRDH DRD
H
S=10.0 S=10.0 S=100.0
SG SG SG

CEA on on on AO
FUEL OIL AB WINDBOX DAMPER off off off DEM AO FUEL OIL AB6 WINDBOX DAMPER
(2,4,6,8) CONT DEM
TR TR TR DRIP
POSN DEM1
FGSG09-DRV-WBOIL-AB2-A002 sw sw sw
Ron=99999.0 Ron=100.0 Ron=100.0 01HLA56AA713-YQ01
<FGSG09-DRV-WBOIL-AB2> Roff=100.0 Roff=99999.0 Roff=99999.0 0.0 - 100.0% FSA X
3
MD=0 MD=0 MD=0 B A 3
CLS UNF FOP AO
FUEL OIL AB6 WINDBOX DAMPER FB SIG ABN
1 P N FUEL OIL AB6 WINDBOX DAMPER
POSN DEM2 RSA X
B A
01HLA56AA713-YQ02
0.0 - 100.0% FUEL OIL AB6 WINDBOX DAMPER RB SIG ABN
FOP DEM_X1in=-10.0 ALLRST DFD X
RPB
N DEM_Y1out=110.0 H A
DEM_X2in=110.0 FUEL OIL AB6 WINDBOX DAMPER FB DEV HI
CED
DEM_Y2out=-10.0
WINDBOX DMPR FORCED OPN DRD X
RB_X1in=-10.0
CMD
RB_Y1out=-10.0
H A
FGSG09-WBC-COMMON-01-D007 RB_X2in=110.0 FUEL OIL AB6 WINDBOX DAMPER RB DEV HI
CED <FGSG09-WBC-COMMON-01>
RB_Y2out=110.0 RST
WINDBOX BANKING COMMAND RB_CHG=0
4 APC-ADC-15-D002 UNF
RB_TRK=0
LARP 4
<APC-ADC-15> FB_TRK=0
CED P CED
AB OIL WINDBOX DAMPER FURN- DEM_FB=0 DABO FUEL OIL AB6 WINDBOX DAMPER
WB DP CNT 12DV=10.0 DRV ABN
ARDV=10.0
FGSG09-WBCOIL-AB-01-D003 FGSG09-DRV-WBOIL-AB6-D001
CED <FGSG09-WBCOIL-AB-01> ONT1=10.0 DAB <FGSG09-DRV-WBOIL-AB2>
A OR B CFD & PULV ON / AB6-DO DFDV=10.0 LCN DABCND O
ON ONT2=60.0 D
FGSG09-WBCOIL-AB-03-D003 INIT
<FGSG09-WBCOIL-AB-03>
INIT

5 5
RSA RB SIG ABN
B
LCN
D
DRD RB SIG DEV H
H

CED
6 FG INITIALIZING INIT
6
CED
LDO DAMPER AB6 POSITION CLS FG INITIALIZING
BEFORE LIGHT-OFF 1 CED
FGSG09-WBCOIL-AB-03-D008 FUEL OIL AB WINDBOX DAMPER
RPB
<FGSG09-WBCOIL-AB-03> (2,4,6,8) RESET PB ON
FGSG09-DRV-WBOIL-AB2-D004
<FGSG09-DRV-WBOIL-AB2>

TITLE AB-FUEL OIL 6CORNER WINDBOX DAMPER Rev.


REMARKS

2
SHEET NO.
MITSUBISHI FGSG09-DRV-
HEAVY INDUSTRIES, LTD WBOIL-AB6
A B C D E F G H I

AI
FUEL OIL AB4 CORNER DAMPER POS
POSITION FB I A1

01HLA54AA713-XQ01 POS Pin C


0.0 - 100.0% I
DAB DRAB
FUEL OIL AB4 WINDBOX DAMPER
AI FBI FBO CEA O
FUEL OIL AB4 CORNER DAMPER RB1I TRKS FUEL OIL AB4 CORNER WINDBOX RSTC OPND D1
RST
1 POSITION DEMAND1 RB DAMPER TR SIGNAL
VDSI 1
FGSG09-DRV-WBOIL-AB4-TR CLSD D3
01HLA54AA713-YQ01RB
0.0 - 100.0% <FGSG09-WBC-COMMON-02>
RBSO MID D2
RB

AI FUEL OIL AB4 WINDBOX DAMPER


FUEL OIL AB4 CORNER DAMPER RB2I FQAB FSA
POSITION DEMAND2 RB B

01HLA54AA713-YQ02RB Ain Aout A1


0.0 - 100.0% RB 999.9uu
DFDH DFD
PVC
H Cout A2
FUEL OIL AB4 WINDBOX DAMPER RB
RQAB RSA <WIND BOX-2>
2 B 2
DRDH DRD
H
S=10.0 S=10.0 S=100.0
SG SG SG

CEA on on on AO
FUEL OIL AB WINDBOX DAMPER off off off DEM AO FUEL OIL AB4 WINDBOX DAMPER
(2,4,6,8) CONT DEM
TR TR TR DRIP
POSN DEM1
FGSG09-DRV-WBOIL-AB2-A002 sw sw sw
<FGSG09-DRV-WBOIL-AB2> Ron=99999.0 Ron=100.0 Ron=100.0 01HLA54AA713-YQ01
Roff=100.0 Roff=99999.0 Roff=99999.0 0.0 - 100.0% FSA X
3
MD=0 MD=0 MD=0 B A 3
CLS UNF FOP AO
FUEL OIL AB4 WINDBOX DAMPER FB SIG ABN
1 P N FUEL OIL AB4 WINDBOX DAMPER
POSN DEM2 RSA X
B A
01HLA54AA713-YQ02
0.0 - 100.0% FUEL OIL AB4 WINDBOX DAMPER RB SIG ABN
FOP ALLRST DRD X
RPB
N H A
FUEL OIL AB4 WINDBOX DAMPER RB DEV HI
CED
WINDBOX DMPR FORCED OPN DFD X
CMD H A
FGSG09-WBC-COMMON-01-D007 FUEL OIL AB4 WINDBOX DAMPER FB DEV HI
CED <FGSG09-WBC-COMMON-01> DEM_X1in=-10.0 RST
WINDBOX BANKING COMMAND DEM_Y1out=110.0
4 APC-ADC-15-D002 UNF
DEM_X2in=110.0
LARP 4
<APC-ADC-15> DEM_Y2out=-10.0
CED P CED
RB_X1in=-10.0
AB OIL WINDBOX DAMPER FURN- DABO FUEL OIL AB4 CORNER WINDBOX
RB_Y1out=-10.0
WB DP CNT DAMPER DRV ABN
RB_X2in=110.0
FGSG09-WBCOIL-AB-01-D003 RB_Y2out=110.0 FGSG09-DRV-WBOIL-AB4-D001
CED <FGSG09-WBCOIL-AB-01> DAB
RB_CHG=0 <FGSG09-DRV-WBOIL-AB2>
A OR B CFD & PULV ON / AB4-DO LCN DABCND O
RB_TRK=0
ON D
FB_TRK=0 INIT
FGSG09-WBCOIL-AB-03-D002
DEM_FB=0
<FGSG09-WBCOIL-AB-03>
12DV=10.0
ARDV=10.0 INIT
ONT1=10.0
DFDV=10.0
ONT2=60.0

5 5
RSA RB SIG ABN
B
LCN
D
DRD RB SIG DEV H
H

CED
6 FG INITIALIZING INIT
6
CED
LDO DAMPER AB4 POSITION CLS FG INITIALIZING
BEFORE LIGHT-OFF 1 CED
FGSG09-WBCOIL-AB-03-D007 FUEL OIL AB WINDBOX DAMPER
RPB
(2,4,6,8) RESET PB ON
<FGSG09-WBCOIL-AB-03>
FGSG09-DRV-WBOIL-AB2-D004
<FGSG09-DRV-WBOIL-AB2>

TITLE AB-FUEL OIL 4CORNER WINDBOX DAMPER Rev.


REMARKS

2
SHEET NO.
MITSUBISHI FGSG09-DRV-
HEAVY INDUSTRIES, LTD WBOIL-AB4
A B C D E F G H I

AI
FUEL OIL AB8 CORNER DAMPER
TRK
POSITION FB A1

01HLA58AA713-XQ01 Pin C
0.0 - 100.0% TRK
DAB DRAB
FUEL OIL AB8 WINDBOX DAMPER
AI FBI FBO CEA O
FUEL OIL AB8 CORNER DAMPER RB1I TRKS FUEL OIL AB8 WINDBOX DAMPER RSTC OPND D1
RST
1 POSITION DEMAND1 RB TR SIGNAL
VDSI 1
FGSG09-DRV-WBOIL-AB8-TR CLSD D3
01HLA58AA713-YQ01RB
0.0 - 100.0% <FGSG09-WBC-COMMON-02>
RBSO MID D2
RB

FUEL OIL AB8 WINDBOX DAMPER


AI
FUEL OIL AB8 CORNER DAMPER RB2I FQAB FSA
POSITION DEMAND2 RB B

01HLA58AA713-YQ02RB
0.0 - 100.0% DFDH DFD Ain Aout A1
RB 999.9uu
H
PVC
Cout A2
FUEL OIL AB8 WINDBOX DAMPER RB
RQAB RSA
<WIND BOX-1>
2 B 2
DRDH DRD
H
S=10.0 S=10.0 S=100.0
SG SG SG

CEA on on on AO
FUEL OIL AB WINDBOX DAMPER off off off DEM AO FUEL OIL AB8 WINDBOX DAMPER
(2,4,6,8) CONT DEM
TR TR TR DRIP
POSN DEM1
FGSG09-DRV-WBOIL-AB2-A002 sw sw sw
Ron=99999.0 Ron=100.0 Ron=100.0 01HLA58AA713-YQ01
<FGSG09-DRV-WBOIL-AB2> Roff=100.0 Roff=99999.0 Roff=99999.0 0.0 - 100.0% FSA X
3
MD=0 MD=0 MD=0 B A 3
CLS UNF FOP AO FUEL OIL AB8 WINDBOX DAMPER FB SIG ABN
1 P N FUEL OIL AB8 WINDBOX DAMPER
POSN DEM2 RSA X
B A
01HLA58AA713-YQ02 FUEL OIL AB8 WINDBOX DAMPER RB SIG ABN
DEM_X1in=-10.0 0.0 - 100.0%
DEM_Y1out=110.0
FOP ALLRST DRD X
DEM_X2in=110.0 RPB
N
DEM_Y2out=-10.0
H A
RB_X1in=-10.0 FUEL OIL AB8 WINDBOX DAMPER RB DEV HI
CED
RB_Y1out=-10.0
WINDBOX DMPR FORCED OPN DFD X
RB_X2in=110.0
CMD H A
RB_Y2out=110.0
FGSG09-WBC-COMMON-01-D007 FUEL OIL AB8 WINDBOX DAMPER FB DEV HI
CED <FGSG09-WBC-COMMON-01> RB_CHG=0
RB_TRK=0 RST
WINDBOX BANKING COMMAND FB_TRK=0
4 APC-ADC-15-D002 UNF DEM_FB=0 LARP 4
<APC-ADC-15> 12DV=10.0
CED P CED
AB OIL WINDBOX DAMPER FURN- ARDV=10.0 DABO FUEL OIL AB8 WINDBOX DAMPER
WB DP CNT ONT1=10.0 DRV ABN
DFDV=10.0
FGSG09-WBCOIL-AB-01-D003 FGSG09-DRV-WBOIL-AB8-D001
CED <FGSG09-WBCOIL-AB-01> ONT2=60.0 DAB
<FGSG09-DRV-WBOIL-AB2>
A OR B CFD & PULV ON / AB8-DO LCN DABCND O
ON D
FGSG09-WBCOIL-AB-03-D004 INIT
<FGSG09-WBCOIL-AB-03>
INIT

5 5
RSA RB SIG ABN
B
LCN
D
DRD RB SIG DEV H
H

CED
6 FG INITIALIZING INIT
6
CED
LDO DAMPER AB8 POSITION CLS FG INITIALIZING
BEFORE LIGHT-OFF 1 CED
FGSG09-WBCOIL-AB-03-D009 FUEL OIL AB WINDBOX DAMPER
RPB
<FGSG09-WBCOIL-AB-03> (2,4,6,8) RESET PB ON
FGSG09-DRV-WBOIL-AB2-D004
<FGSG09-DRV-WBOIL-AB2>

TITLE AB-FUEL OIL 8CORNER WINDBOX DAMPER Rev.


REMARKS

2
SHEET NO.
MITSUBISHI FGSG09-DRV-
HEAVY INDUSTRIES, LTD WBOIL-AB8
A B C D E F G H I

1 1

2 2

3 3

4 4

5 5

OFF D

6 6
REMARKS
A B C D E F G H I

0%

1 CEA 1
BURNER WINDBOX 2RY AIR CD
(CORNER 1&2) TR SIGNAL
FGSG09-DRV-WB2RYDMP-12-TR
<FGSG09-DRV-WB2RYDMP-12>

CEA FX1 * off on CEA


on off BURNER WINDBOX 2RY AIR CD
BOILER INPUT DEMAND FX TR TR (CORNER 1&2) CTRL DEM
APC-BID-01-A001 <APC-BID-01> sw sw FGSG09-WBC2RYDMP-01-A001
CED Ron=10.0 Ron=100.0 <FGSG09-DRV-WB2RYDMP-12>
BURNER WINDBOX 2RY AIR CD Roff=99999.0 1AS Roff=99999.0
(CORNER 1&2) AUTO MD=0 T MD=0
FGSG09-DRV-WB2RYDMP-12-AT<FGSG09-DRV-WB2RYDMP-12> 1A STAND-BY
CED
BURNER WINDBOX 2RY AIR CD 1AS
2 (CORNER 1&2) AUTO or STANDBY T 2
FGSG09-DRV-WB2RYDMP-12-AST
<FGSG09-DRV-WB2RYDMP-12> CEA
BURNER WINDBOX 2RY AIR CD
CEA (CORNER 1&2) PROGRAM
BURNER WINDBOX 2RY AIR CD FGSG09-WBC2RYDMP-01-A002
(CORNER 7&8) TR SIGNAL <FGSG09-DRV-WB2RYDMP-12>
FGSG09-DRV-WB2RYDMP-78-TR
<FGSG09-DRV-WB2RYDMP-78>

FX2 * off on CEA


on off BURNER WINDBOX 2RY AIR CD
FX TR TR (CORNER 7&8) CTRL DEM
sw sw FGSG09-WBC2RYDMP-01-A003
CED Ron=10.0 Ron=100.0 <FGSG09-DRV-WB2RYDMP-78>
BURNER WINDBOX 2RY AIR CD Roff=99999.0 2AS Roff=99999.0
MD=0
3 (CORNER 7&8) AUTO
FGSG09-DRV-WB2RYDMP-78-AT
T
2A STAND-BY
MD=0 3
CED <FGSG09-DRV-WB2RYDMP-78>
BURNER WINDBOX 2RY AIR CD 2AS
(CORNER 7&8) AUTO or STANDBY T
FGSG09-DRV-WB2RYDMP-78-AST
<FGSG09-DRV-WB2RYDMP-78> CEA
BURNER WINDBOX 2RY AIR CD
CEA (CORNER 7&8) PROGRAM
BURNER WINDBOX 2RY AIR CD FGSG09-WBC2RYDMP-01-A004
(CORNER 3&4) TR SIGNAL <FGSG09-DRV-WB2RYDMP-78>
FGSG09-DRV-WB2RYDMP-34-TR<FGSG09-DRV-WB2RYDMP-34>

FX3 * off on CEA


on off BURNER WINDBOX 2RY AIR CD
FX TR TR (CORNER 3&4) CTRL DEM
4 sw sw FGSG09-WBC2RYDMP-01-A005
4
CED Ron=10.0 Ron=100.0 <FGSG09-DRV-WB2RYDMP-34>
BURNER WINDBOX 2RY AIR CD Roff=99999.0 1BS Roff=99999.0
(CORNER 3&4) AUTO MD=0 T MD=0
FGSG09-DRV-WB2RYDMP-34-AT <FGSG09-DRV-WB2RYDMP-34> 1B STAND-BY
CED
BURNER WINDBOX 2RY AIR CD 2BS
(CORNER 3&4) AUTO or STANDBY T CEA
FGSG09-DRV-WB2RYDMP-34-AST <FGSG09-DRV-WB2RYDMP-34> BURNER WINDBOX 2RY AIR CD
(CORNER 3&4) PROGRAM
FGSG09-WBC2RYDMP-01-A006
CEA <FGSG09-DRV-WB2RYDMP-34>
BURNER WINDBOX 2RY AIR CD
(CORNER 5&6) TR SIGNAL
FGSG09-DRV-WB2RYDMP-56-TR
<FGSG09-DRV-WB2RYDMP-56>
5 5
FX4 * off on CEA
on off BURNER WINDBOX 2RY AIR CD
FX TR TR (CORNER 5&6) CTRL DEM
sw sw FGSG09-WBC2RYDMP-01-A007
CED Ron=10.0 Ron=100.0 <FGSG09-DRV-WB2RYDMP-56>
BURNER WINDBOX 2RY AIR CD Roff=99999.0 2BS Roff=99999.0
(CORNER 5&6) AUTO MD=0 T MD=0
FGSG09-DRV-WB2RYDMP-56-AT <FGSG09-DRV-WB2RYDMP-56> 2B STAND-BY
CED
BURNER WINDBOX 2RY AIR CD 1BS
(CORNER 5&6) AUTO or STANDBY T CEA
FGSG09-DRV-WB2RYDMP-56-AST BURNER WINDBOX 2RY AIR CD
<FGSG09-DRV-WB2RYDMP-56> (CORNER 5&6) PROGRAM
FGSG09-WBC2RYDMP-01-A008
CED <FGSG09-DRV-WB2RYDMP-56>
6 WINDBOX BANKING COMMAND
6
CED
APC-ADC-15-D002 WINDBOX 2RY AIR CD AUTO <FGSG09-DRV-WB2RYDMP-12>
<APC-ADC-15>
CED PERMIT <FGSG09-DRV-WB2RYDMP-34>
FGSG09-WBC2RYDMP-01-D001 <FGSG09-DRV-WB2RYDMP-56>
MFT
<FGSG09-DRV-WB2RYDMP-78>
FGSG09-DI01-D01 <FGSG09-DI01>
FX1 * FX2 * FX3 * FX4 *
X1=0.0,Y1=65.0 X1=0.0,Y1=65.0 X1=0.0,Y1=65.0 X1=0.0,Y1=65.0
X2=198.0,Y2=65.0 X2=198.0,Y2=65.0 X2=198.0,Y2=65.0 X2=198.0,Y2=65.0 TITLE BURNER WINDBOX 2RY AIR CONTROL Rev.
X3=264.0,Y3=65.0 X3=264.0,Y3=65.0 X3=264.0,Y3=65.0 X3=264.0,Y3=65.0
DAMPER CONTROL
REMARKS

X4=330.0,Y4=65.0 X4=330.0,Y4=65.0 X4=330.0,Y4=65.0 X4=330.0,Y4=65.0 2


X5=396.0,Y5=65.0 X5=396.0,Y5=65.0 X5=396.0,Y5=65.0 X5=396.0,Y5=65.0
X6=528.0,Y6=70.0 X6=528.0,Y6=70.0 X6=528.0,Y6=70.0 X6=528.0,Y6=70.0 * TO BE FINALIZED DURING COMMISSIONING SHEET NO.
X7=660.0,Y7=70.0 X7=660.0,Y7=70.0 X7=660.0,Y7=70.0 X7=660.0,Y7=70.0
FGSG09-
X8=693.0,Y8=70.0
X9=700.0,Y9=70.0
X8=693.0,Y8=70.0
X9=700.0,Y9=70.0
X8=693.0,Y8=70.0
X9=700.0,Y9=70.0
X8=693.0,Y8=70.0
X9=700.0,Y9=70.0
MITSUBISHI WBC2RYDMP-01
X10=0.0,Y10=0.0 X10=0.0,Y10=0.0 X10=0.0,Y10=0.0 X10=0.0,Y10=0.0 HEAVY INDUSTRIES, LTD
A B C D E F G H I
BURNER WINDBOX 2RY AIR CD (CORNER 1&2) FB
AI <AIR AND FLUE GAS SYSTEM-2>
BURNER WINDBOX 2RY AIR CD POS <WIND BOX-1>
(CORNER 1&2) POSN FB I VDSI PVC-1
S-PB-3-Set POS Pin Pout Ain Aout A1
SV SV 01HLA05AA701 PB RPB 01HLA05AA701-XQ01 TRK 999.9uu
SV I
0.0 - 100.0% PVC
POS FB SIG MV S-PB-8-Set Cout A2
I V3
PB APB
AI FBI FBO CEA <AIR AND FLUE GAS SYSTEM-2>
S-PB-10-Set BURNER WINDBOX 2RY AIR CD RB1I TRKS BURNER WINDBOX 2RY AIR CD OPND D1 <WIND BOX-1>
TRK TRACKING SIG PB MPB
1 (CORNER 1&2) POSN DEM1 RB (CORNER 1&2) TR SIGNAL
VDSI
D3 1
DAB DRIVE ABN S-PB-2 Tagging FGSG09-DRV-WB2RYDMP-12-TR DAB DRAB CLSD D2
TAG 01HLA05AA701-YQ01RB
O S-PB-3 O
0.0 - 100.0% <FGSG09-WBC2RYDMP-01>
RSE RESET COND S-PB-4 RBSO RSE RSTC MID
RB <FGSG09-WBC-COMMON-02>
T T
SAB SIG ABN TAG C A1
TAG
N AI
BURNER WINDBOX 2RY AIR CD RB2I FQAB FSA
BURNER WINDBOX 2RY AIR CD (CORNER 1&2)
(CORNER 1&2) POSN DEM2 RB B
CAU CONTROL AUTO S-PB-8 MV-I-PRH <AIR AND FLUE GAS SYSTEM-2>
T S-PB-9 MV-D-PRH 01HLA05AA701-YQ02RB CAU <WIND BOX-1> D1
STB STAND BY MODE S-PB-10 MV-Set 0.0 - 100.0% DFDH DFD T
Y H STB D2
Y
MAN MANUAL MODE
D3
BURNER WINDBOX 2RY AIR CD (CORNER 1&2) MAN
RQAB RSA
2 <WIND BOX-1>
<AIR AND FLUE GAS SYSTEM-2>
B
BURNER WINDBOX 2RY AIR CD (CORNER 1&2) AUTO/MANUAL 2
CED <AIR AND FLUE GAS SYSTEM-2>
DRDH DRD <WIND BOX-1>
FG INITIALIZING INIT
DPRH IPRH H
FG INITIALIZING ULMT PVC-2
CEA S=100.0 Ain Aout A1
RB 999.9uu
BURNER WINDBOX 2RY AIR CD LLMT DRVM FMA
(CORNER 1&2) PROGRAM
SV SG N
PVC
Cout A2
OPMT
FGSG09-WBC2RYDMP-01-A002<FGSG09-WBC2RYDMP-01>
CEA S OH OL on AO
BURNER WINDBOX 2RY AIR CD (CORNER 1&2) RB
BURNER WINDBOX 2RY AIR CD X Y Ain Aout off DEM AO BURNER WINDBOX 2RY AIR CD
(CORNER 1&2) CTRL DEM
S/S TR DRIP
(CORNER 1&2) POSN DEM1
OPP Ron=100.0
FGSG09-WBC2RYDMP-01-A001 L sw INIT sw DFD X
OPRH OPC Roff=99999.0
<FGSG09-WBC2RYDMP-01> S=30.0 01HLA05AA701-YQ01 H A
MD=0 0.0 - 100.0%
SG BURNER WINDBOX 2RY AIR CD (CORNER 1&2) FB DEV HI
3 FC FORCE
AO 3
off MANUAL MODE BURNER WINDBOX 2RY AIR CD
MAN
on (CORNER 1&2) POSN DEM2 RSA X
0% TR B A
INITIALIZE
INIT 01HLA05AA701-YQ02
sw
0.0 - 100.0% BURNER WINDBOX 2RY AIR CD (CORNER 1&2) RB SIG ABN
CED
Ron=100.0
ALLRST DRD X
WINDBOX BANKING COMMAND Roff=100.0 RPB
H A
MD=0
APC-ADC-15-D002 <APC-ADC-15> DEM_X1in=-10.0 BURNER WINDBOX 2RY AIR CD (CORNER 1&2) RB DEV HI
DEM_Y1out=-10.0
STB MANU LARP RSE FMA X
MAN DEM_X2in=110.0
Y T
DEM_Y2out=110.0
N A
RB_X1in=-10.0 BURNER WINDBOX 2RY AIR CD (CORNER 1&2) FORCED MANUAL
RB_Y1out=-10.0
SAB SABCND FSA X
FC RB_X2in=110.0
N B A
4 RB_Y2out=110.0 4
RB_CHG=0 BURNER WINDBOX 2RY AIR CD (CORNER 1&2) POS FB SIG ABN
CED
RB_TRK=0
WINDBOX DMPR FORCED OPN DABO DAB X
FB_TRK=0 MAN
CMD O E
ACN DEM_FB=0
FGSG09-WBC-COMMON-01-D007 BURNER WINDBOX 2RY AIR CD (CORNER 1&2) MANUAL MODE
CED D 12DV=10.0
<FGSG09-WBC-COMMON-01>
WINDBOX 2RY AIR CD AUTO LCN DABCND ARDV=10.0 CAU X
PERMIT D ONT1=10.0 T E
INIT FDHEX DFDV=10.0
FGSG09-WBC2RYDMP-01-D001 BURNER WINDBOX 2RY AIR CD (CORNER 1&2) AUTO MODE
ONT2=60.0
<FGSG09-WBC2RYDMP-01>
STB X
INIT
Y E
BURNER WINDBOX 2RY AIR CD (CORNER 1&2) STANDBY MODE
RBK

5 5
CED
ATPB CAUTX Y CAU CAU BURNER WINDBOX 2RY AIR CD
APB AUTO PB
SAB T T (CORNER 1&2) AUTO
N MNPB
MPB MANUAL PB T=0.0 FGSG09-DRV-WB2RYDMP-12-AT
CED <FGSG09-WBC2RYDMP-01>
RSA RB SIG ABN ACN AUT CND ACND CSTB STB
BID SIGNAL ABNORMAL
B D Y CED
APC-BID-01-D004 <APC-BID-01> MCN LCN MCN MANU CND MCND ASM DAU BURNER WINDBOX 2RY AIR CD
D D D S T (CORNER 1&2) AUTO or STANDBY
DAB DRD RB SIG DEV H DAUT DAU FGSG09-DRV-WB2RYDMP-12-AST
O H T <FGSG09-WBC2RYDMP-01>

CED
INIT MANU STB BURNER WINDBOX 2RY AIR CD
INIT INITIALIZE MAN
CED Y (CORNER 1&2) STANDBY MODE
6 FCB/RUNBACK OPERATE RBK FGSG09-DRV-WB2RYDMP-12-ST 6
APC-EMG-10-D001 <APC-EMG-10>

TITLE BURNER WINDBOX 2RY AIR CD (CORNER Rev.


1&2)
REMARKS

2
SHEET NO.
MITSUBISHI FGSG09-DRV-
HEAVY INDUSTRIES, LTD WB2RYDMP-12
A B C D E F G H I
BURNER WINDBOX 2RY AIR CD (CORNER 3&4) FB
AI <AIR AND FLUE GAS SYSTEM-2>
BURNER WINDBOX 2RY AIR CD POS <WIND BOX-1>
(CORNER 3&4) POSN FB I VDSI PVC-1
S-PB-3-Set POS Pin Pout Ain Aout A1
SV SV 01HLA05AA702 PB RPB 01HLA05AA702-XQ01 TRK 999.9uu
SV I
0.0 - 100.0% PVC
POS FB SIG MV S-PB-8-Set Cout A2
I V3
PB APB
AI FBI FBO CEA <AIR AND FLUE GAS SYSTEM-2>
S-PB-10-Set BURNER WINDBOX 2RY AIR CD RB1I TRKS BURNER WINDBOX 2RY AIR CD OPND D1 <WIND BOX-1>
TRK TRACKING SIG PB MPB
1 (CORNER 3&4) POSN DEM1 RB (CORNER 3&4) TR SIGNAL
VDSI
D3 1
DAB DRIVE ABN S-PB-2 Tagging FGSG09-DRV-WB2RYDMP-34-TR DAB DRAB CLSD D2
TAG 01HLA05AA702-YQ01RB
O S-PB-3 O
0.0 - 100.0% <FGSG09-WBC2RYDMP-01>
RSE RESET COND S-PB-4 RBSO RSE RSTC MID
RB <FGSG09-WBC-COMMON-02>
T T
SAB SIG ABN TAG C A1
TAG
N AI
BURNER WINDBOX 2RY AIR CD RB2I FQAB FSA
BURNER WINDBOX 2RY AIR CD (CORNER 3&4)
(CORNER 3&4) POSN DEM2 RB B
CAU CONTROL AUTO S-PB-8 MV-I-PRH <AIR AND FLUE GAS SYSTEM-2>
T S-PB-9 MV-D-PRH 01HLA05AA702-YQ02RB CAU <WIND BOX-1> D1
STB STAND BY MODE S-PB-10 MV-Set 0.0 - 100.0% DFDH DFD T
Y H STB D2
Y
MAN MANUAL MODE
D3
BURNER WINDBOX 2RY AIR CD (CORNER 3&4) MAN
RQAB RSA
<WIND BOX-1>
2 <AIR AND FLUE GAS SYSTEM-2>
B
BURNER WINDBOX 2RY AIR CD (CORNER 3&4) AUTO/MANUAL 2
CED <AIR AND FLUE GAS SYSTEM-2>
DRDH DRD <WIND BOX-1>
FG INITIALIZING INIT
DPRH IPRH H
FG INITIALIZING ULMT PVC-2
CEA S=100.0 Ain Aout A1
RB 999.9uu
BURNER WINDBOX 2RY AIR CD LLMT DRVM FMA
(CORNER 3&4) PROGRAM
SV SG N
PVC
Cout A2
OPMT
FGSG09-WBC2RYDMP-01-A006 <FGSG09-WBC2RYDMP-01>
CEA S OH OL on AO
BURNER WINDBOX 2RY AIR CD (CORNER 3&4) RB
BURNER WINDBOX 2RY AIR CD X Y Ain Aout off DEM AO BURNER WINDBOX 2RY AIR CD
(CORNER 3&4) CTRL DEM
S/S TR DRIP
(CORNER 3&4) POSN DEM1
FGSG09-WBC2RYDMP-01-A005 L sw OPP INIT sw DFD X
OPRH OPC Ron=100.0
<FGSG09-WBC2RYDMP-01> S=30.0 01HLA05AA702-YQ01 H A
Roff=99999.0 0.0 - 100.0%
SG MD=0 BURNER WINDBOX 2RY AIR CD (CORNER 3&4) DEV HI
3 FC FORCE
AO 3
off MANUAL MODE BURNER WINDBOX 2RY AIR CD
MAN
on (CORNER 3&4) POSN DEM2 RSA X
0% TR B A
INITIALIZE
INIT 01HLA05AA702-YQ02
sw
Ron=100.0 0.0 - 100.0% BURNER WINDBOX 2RY AIR CD (CORNER 3&4) RB SIG ABN
CED
Roff=100.0 ALLRST DRD X
WINDBOX BANKING COMMAND RPB
MD=0 H A
APC-ADC-15-D002 <APC-ADC-15> DEM_X1in=-10.0 BURNER WINDBOX 2RY AIR CD (CORNER 3&4) RB DEV HI
DEM_Y1out=-10.0
STB MANU LARP RSE FMA X
MAN DEM_X2in=110.0
Y T
DEM_Y2out=110.0
N A
RB_X1in=-10.0 BURNER WINDBOX 2RY AIR CD (CORNER 3&4) FORCED MANUAL
RB_Y1out=-10.0
SAB SABCND FSA X
FC RB_X2in=110.0
N B A
4 RB_Y2out=110.0 4
RB_CHG=0 BURNER WINDBOX 2RY AIR CD (CORNER 3&4) POS FB SIG ABN
CED
RB_TRK=0
WINDBOX DMPR FORCED OPN DABO DAB X
FB_TRK=0 MAN
CMD O E
ACN DEM_FB=0
FGSG09-WBC-COMMON-01-D007 BURNER WINDBOX 2RY AIR CD (CORNER 3&4) MANUAL MODE
CED <FGSG09-WBC-COMMON-01> D 12DV=10.0
WINDBOX 2RY AIR CD AUTO LCN DABCND ARDV=10.0 CAU X
PERMIT D ONT1=10.0 T E
INIT FDHEX DFDV=10.0
FGSG09-WBC2RYDMP-01-D001 BURNER WINDBOX 2RY AIR CD (CORNER 3&4) AUTO MODE
ONT2=60.0
<FGSG09-WBC2RYDMP-01>
STB X
INIT
Y E
BURNER WINDBOX 2RY AIR CD (CORNER 3&4) STANDBY MODE
RBK

5 5
CED
ATPB CAUTX Y CAU CAU BURNER WINDBOX 2RY AIR CD
APB AUTO PB
SAB T T (CORNER 3&4) AUTO
N MNPB
MPB MANUAL PB T=0.0 FGSG09-DRV-WB2RYDMP-34-AT
CED <FGSG09-WBC2RYDMP-01>
RSA RB SIG ABN ACN AUT CND ACND CSTB STB
BID SIGNAL ABNORMAL
B D Y CED
APC-BID-01-D004 <APC-BID-01> MCN LCN MCN MANU CND MCND ASM DAU BURNER WINDBOX 2RY AIR CD
D D D S T (CORNER 3&4) AUTO or STANDBY
DAB DRD RB SIG DEV H DAUT DAU FGSG09-DRV-WB2RYDMP-34-AST
O H T <FGSG09-WBC2RYDMP-01>

CED
INIT MANU STB BURNER WINDBOX 2RY AIR CD
INIT INITIALIZE MAN
CED Y (CORNER 3&4) STANDBY MODE
6 FCB/RUNBACK OPERATE RBK FGSG09-DRV-WB2RYDMP-34-ST 6
APC-EMG-10-D001 <APC-EMG-10>

TITLE BURNER WINDBOX 2RY AIR CD (CORNER Rev.


3&4)
REMARKS

2
SHEET NO.
MITSUBISHI FGSG09-DRV-
HEAVY INDUSTRIES, LTD WB2RYDMP-34
A B C D E F G H I

BURNER WINDBOX 2RY AIR CD (CORNER 5&6) FB


AI <WIND BOX-2>
BURNER WINDBOX 2RY AIR CD POS
<AIR AND FLUE GAS SYSTEM-2>
(CORNER 5&6) POSN FB I VDSI PVC-1
S-PB-3-Set POS Pin Pout Ain Aout A1
SV SV 01HLA05AA703 PB RPB 01HLA05AA703-XQ01 TRK 999.9uu
SV I
0.0 - 100.0% PVC
POS FB SIG MV S-PB-8-Set Cout A2
I V3
PB APB
AI FBI FBO CEA <WIND BOX-2>
S-PB-10-Set BURNER WINDBOX 2RY AIR CD RB1I TRKS BURNER WINDBOX 2RY AIR CD OPND D1
TRK TRACKING SIG PB MPB <AIR AND FLUE GAS SYSTEM-2>
1 (CORNER 5&6) POSN DEM1 RB (CORNER 5&6) TR SIGNAL
VDSI
D3 1
DAB DRIVE ABN S-PB-2 Tagging FGSG09-DRV-WB2RYDMP-56-TR DAB DRAB CLSD D2
TAG 01HLA05AA703-YQ01RB
O S-PB-3 <FGSG09-WBC2RYDMP-01> O
RSE RESET COND S-PB-4 0.0 - 100.0% RBSO <FGSG09-WBC-COMMON-02> RSE RSTC MID
RB
T T
SAB SIG ABN TAG C A1
TAG
N AI
BURNER WINDBOX 2RY AIR CD RB2I FQAB FSA
BURNER WINDBOX 2RY AIR CD (CORNER 5&6)
(CORNER 5&6) POSN DEM2 RB B
CAU CONTROL AUTO S-PB-8 MV-I-PRH <AIR AND FLUE GAS SYSTEM-2>
T S-PB-9 MV-D-PRH 01HLA05AA703-YQ02RB CAU <WIND BOX-2> D1
STB STAND BY MODE S-PB-10 MV-Set 0.0 - 100.0% DFDH DFD T
Y H STB D2
Y
MAN MANUAL MODE BURNER WINDBOX 2RY AIR CD (CORNER 5&6) D3
<WIND BOX-2> MAN
RQAB RSA
<AIR AND FLUE GAS SYSTEM-2>
2 B
BURNER WINDBOX 2RY AIR CD (CORNER 5&6) 2
CED <WIND BOX-2>
DRDH DRD <AIR AND FLUE GAS SYSTEM-2>
FG INITIALIZING INIT
DPRH IPRH H
FG INITIALIZING ULMT PVC-2
CEA S=100.0 Ain Aout A1
RB 999.9uu
BURNER WINDBOX 2RY AIR CD LLMT DRVM FMA
(CORNER 5&6) PROGRAM
SV SG N
PVC
Cout A2
OPMT
FGSG09-WBC2RYDMP-01-A008
CEA <FGSG09-WBC2RYDMP-01> S OH OL on AO
BURNER WINDBOX 2RY AIR CD (CORNER 5&6) RB
BURNER WINDBOX 2RY AIR CD X Y Ain Aout off DEM AO BURNER WINDBOX 2RY AIR CD
(CORNER 5&6) CTRL DEM
S/S TR DRIP
(CORNER 5&6) POSN DEM1
OPP Ron=100.0
FGSG09-WBC2RYDMP-01-A007 L sw INIT sw DFD X
OPRH OPC Roff=99999.0
<FGSG09-WBC2RYDMP-01> S=30.0 01HLA05AA703-YQ01 H A
MD=0 0.0 - 100.0%
SG BURNER WINDBOX 2RY AIR CD (CORNER 5&6) FB DEV HI
3 FC FORCE
AO 3
off MANUAL MODE BURNER WINDBOX 2RY AIR CD
MAN
on (CORNER 5&6) POSN DEM2 RSA X
0% TR B A
INITIALIZE
INIT 01HLA05AA703-YQ02
sw
0.0 - 100.0% BURNER WINDBOX 2RY AIR CD (CORNER 5&6) RB SIG ABN
CED
Ron=100.0
ALLRST DRD X
WINDBOX BANKING COMMAND Roff=100.0 RPB
H A
MD=0
APC-ADC-15-D002 <APC-ADC-15> DEM_X1in=-10.0 BURNER WINDBOX 2RY AIR CD (CORNER 5&6) RB DEV HI
DEM_Y1out=-10.0
STB MANU LARP RSE FMA X
MAN DEM_X2in=110.0
Y T
DEM_Y2out=110.0
N A
RB_X1in=-10.0 BURNER WINDBOX 2RY AIR CD (CORNER 5&6) FORCED MANUAL
RB_Y1out=-10.0
SAB SABCND FSA X
FC RB_X2in=110.0
N B A
4 RB_Y2out=110.0 4
RB_CHG=0 BURNER WINDBOX 2RY AIR CD (CORNER 5&6) POS SIG ABN
CED
RB_TRK=0
WINDBOX DMPR FORCED OPN DABO DAB X
FB_TRK=0 MAN
CMD O E
ACN DEM_FB=0
FGSG09-WBC-COMMON-01-D007 <FGSG09-WBC-COMMON-01> BURNER WINDBOX 2RY AIR CD (CORNER 5&6) MANUAL MODE
CED D 12DV=10.0
WINDBOX 2RY AIR CD AUTO LCN DABCND ARDV=10.0 CAU X
PERMIT D ONT1=10.0 T E
INIT FDHEX DFDV=10.0
FGSG09-WBC2RYDMP-01-D001 <FGSG09-WBC2RYDMP-01> BURNER WINDBOX 2RY AIR CD (CORNER 5&6) AUTO MODE
ONT2=60.0
STB X
INIT
Y E
BURNER WINDBOX 2RY AIR CD (CORNER 5&6) STANDBY MODE
RBK

5 5
CED
ATPB CAUTX Y CAU CAU BURNER WINDBOX 2RY AIR CD
APB AUTO PB
SAB T T (CORNER 5&6) AUTO
N MNPB
MPB MANUAL PB T=0.0 FGSG09-DRV-WB2RYDMP-56-AT
<FGSG09-WBC2RYDMP-01>
CED
RSA RB SIG ABN ACN AUT CND ACND CSTB STB
BID SIGNAL ABNORMAL
B D Y CED
APC-BID-01-D004 <APC-BID-01> MCN LCN MCN MANU CND MCND ASM DAU BURNER WINDBOX 2RY AIR CD
D D D S T (CORNER 5&6) AUTO or STANDBY
DAB DRD RB SIG DEV H DAUT DAU FGSG09-DRV-WB2RYDMP-56-AST
<FGSG09-WBC2RYDMP-01>
O H T

CED
INIT MANU STB BURNER WINDBOX 2RY AIR CD
INIT INITIALIZE MAN
CED Y (CORNER 5&6) STANDBY MODE
6 FCB/RUNBACK OPERATE RBK FGSG09-DRV-WB2RYDMP-56-ST 6
APC-EMG-10-D001 <APC-EMG-10>

TITLE BURNER WINDBOX 2RY AIR CD (CORNER Rev.


5&6)
REMARKS

2
SHEET NO.
MITSUBISHI FGSG09-DRV-
HEAVY INDUSTRIES, LTD WB2RYDMP-56
A B C D E F G H I

BURNER WINDBOX 2RY AIR CD (CORNER 7&8) FB


AI <WIND BOX-2>
BURNER WINDBOX 2RY AIR CD POS <AIR AND FLUE GAS SYSTEM-2>
(CORNER 7&8) POSN FB I VDSI PVC-1
S-PB-3-Set POS Pin Pout Ain Aout A1
SV SV 01HLA05AA704 PB RPB 01HLA05AA704-XQ01 TRK 999.9uu
SV I
0.0 - 100.0% PVC
POS FB SIG MV S-PB-8-Set Cout A2
I V3
PB APB
AI FBI FBO CEA
S-PB-10-Set BURNER WINDBOX 2RY AIR CD RB1I TRKS BURNER WINDBOX 2RY AIR CD OPND D1 <AIR AND FLUE GAS SYSTEM-2>
TRK TRACKING SIG PB MPB <WIND BOX-2>
1 (CORNER 7&8) POSN DEM1 RB (CORNER 7&8) TR SIGNAL
VDSI
D3 1
DAB DRIVE ABN S-PB-2 Tagging FGSG09-DRV-WB2RYDMP-78-TR DAB DRAB CLSD D2
TAG 01HLA05AA704-YQ01RB
O S-PB-3 O
0.0 - 100.0% <FGSG09-WBC2RYDMP-01>
RSE RESET COND S-PB-4 RBSO RSE RSTC MID
RB <FGSG09-WBC-COMMON-02>
T T
SAB SIG ABN TAG C A1
TAG
N AI
BURNER WINDBOX 2RY AIR CD RB2I FQAB FSA
BURNER WINDBOX 2RY AIR CD (CORNER 7&8)
(CORNER 7&8) POSN DEM2 RB B
CAU CONTROL AUTO S-PB-8 MV-I-PRH <WIND BOX-2>
T S-PB-9 MV-D-PRH 01HLA05AA704-YQ02RB CAU <AIR AND FLUE GAS SYSTEM-2>D1
STB STAND BY MODE S-PB-10 MV-Set 0.0 - 100.0% DFDH DFD T
Y H STB D2
Y
MAN MANUAL MODE
D3
BURNER WINDBOX 2RY AIR CD (CORNER 7&8) MAN
<WIND BOX-2> RQAB RSA
2 <AIR AND FLUE GAS SYSTEM-2> B
BURNER WINDBOX 2RY AIR CD (CORNER 7&8) CD AUTO/MANUAL 2
CED <WIND BOX-2>
DRDH DRD <AIR AND FLUE GAS SYSTEM-2>
FG INITIALIZING INIT PVC-2
DPRH IPRH H
FG INITIALIZING ULMT Ain Aout A1
S=100.0 RB 999.9uu
CEA
PVC
BURNER WINDBOX 2RY AIR CD LLMT DRVM FMA Cout A2
(CORNER 7&8) PROGRAM
SV SG N
OPMT
FGSG09-WBC2RYDMP-01-A004 BURNER WINDBOX 2RY AIR CD (CORNER 7&8) RB
CEA <FGSG09-WBC2RYDMP-01> S OH OL on AO
BURNER WINDBOX 2RY AIR CD X Y Ain Aout off DEM AO BURNER WINDBOX 2RY AIR CD
(CORNER 7&8) CTRL DEM
S/S TR DRIP
(CORNER 7&8) POSN DEM1
OPP Ron=100.0
FGSG09-WBC2RYDMP-01-A003 L sw INIT sw DFD X
OPRH OPC Roff=99999.0
<FGSG09-WBC2RYDMP-01> S=30.0 01HLA05AA704-YQ01 H A
MD=0 0.0 - 100.0%
SG BURNER WINDBOX 2RY AIR CD (CORNER 7&8) CD FB DEV HI
3 FC FORCE
AO 3
off MANUAL MODE BURNER WINDBOX 2RY AIR CD
MAN
on (CORNER 7&8) POSN DEM2 RSA X
0% TR B A
INITIALIZE
INIT 01HLA05AA704-YQ02
sw
0.0 - 100.0% BURNER WINDBOX 2RY AIR CD (CORNER 7&8) RB SIG ABN
CED
Ron=100.0
ALLRST DRD X
WINDBOX BANKING COMMAND Roff=100.0 RPB
H A
MD=0
APC-ADC-15-D002 <APC-ADC-15> DEM_X1in=-10.0 BURNER WINDBOX 2RY AIR CD (CORNER 7&8) RB DEV HI
DEM_Y1out=-10.0
STB MANU LARP RSE FMA X
MAN DEM_X2in=110.0
Y T
DEM_Y2out=110.0
N A
RB_X1in=-10.0 BURNER WINDBOX 2RY AIR CD (CORNER 7&8) CD FORCED MANUAL
RB_Y1out=-10.0
SAB SABCND FSA X
FC RB_X2in=110.0
N B A
4 RB_Y2out=110.0 4
RB_CHG=0 BURNER WINDBOX 2RY AIR CD (CORNER 7&8) POS FB SIG ABN
CED
RB_TRK=0
WINDBOX DMPR FORCED OPN DABO DAB X
FB_TRK=0 MAN
CMD O E
ACN DEM_FB=0
FGSG09-WBC-COMMON-01-D007 <FGSG09-WBC-COMMON-01> BURNER WINDBOX 2RY AIR CD (CORNER 7&8) MANUAL MODE
CED D 12DV=10.0
WINDBOX 2RY AIR CD AUTO LCN DABCND ARDV=10.0 CAU X
PERMIT D ONT1=10.0 T E
INIT FDHEX DFDV=10.0
FGSG09-WBC2RYDMP-01-D001 BURNER WINDBOX 2RY AIR CD (CORNER 7&8) AUTO MODE
<FGSG09-WBC2RYDMP-01> ONT2=60.0
STB X
INIT
Y E
BURNER WINDBOX 2RY AIR CD (CORNER 7&8) STANDBY MODE
RBK

5 5
CED
ATPB CAUTX Y CAU CAU BURNER WINDBOX 2RY AIR CD
APB AUTO PB
SAB T T (CORNER 7&8) AUTO
N MNPB
MPB MANUAL PB T=0.0 FGSG09-DRV-WB2RYDMP-78-AT
CED
<FGSG09-WBC2RYDMP-01>
RSA RB SIG ABN ACN AUT CND ACND CSTB STB
BID SIGNAL ABNORMAL
B D Y CED
APC-BID-01-D004 <APC-BID-01> MCN LCN MCN MANU CND MCND ASM DAU BURNER WINDBOX 2RY AIR CD
D D D S T (CORNER 7&8) AUTO or STANDBY
DAB DRD RB SIG DEV H DAUT DAU FGSG09-DRV-WB2RYDMP-78-AST
O H T
<FGSG09-WBC2RYDMP-01>
CED
INIT MANU STB BURNER WINDBOX 2RY AIR CD
INIT INITIALIZE MAN
CED Y (CORNER 7&8) STANDBY MODE
6 FCB/RUNBACK OPERATE RBK FGSG09-DRV-WB2RYDMP-78-ST 6
APC-EMG-10-D001 <APC-EMG-10>

TITLE BURNER WINDBOX 2RY AIR CD (CORNER Rev.


7&8)
REMARKS

2
SHEET NO.
MITSUBISHI FGSG09-DRV-
HEAVY INDUSTRIES, LTD WB2RYDMP-78
A B C D E F G H I

1 1

2 2

3 3

4 4

5 5

OFF D

6 6
REMARKS
A B C D E F G H I

CEA T=0.0
AUX-2 3CORNER WINDBOX CEA
NUMBER OF COAL WB DAMPER
DAMPER TR SIGNAL
FGSG09-DRV-WBAUX2-3-TR CEA AUTO (DP CNT) + X
LAG NO
<FGSG09-DRV-WBAUX2-3> AUX-2 1CORNER WINDBOX FGSG09-WBCDPCNT-02-A001 OAB X TP
<FGSG09-WBCDPCNT-02> D/A
DAMPER TR SIGNAL 1
CEA FGSG09-DRV-WBAUX2-1-TR <FGSG09-DRV-WBAUX2-1> OAB X S=1.0
D/A
FUEL OIL GH WINDBOX DMPR 2
(1,3,5,7) CONT DEM OCD S=1.0 X D/A
1 FGSG09-DRV-WBOIL-GH2-A002 CEA 1 1
FUEL OIL GH WINDBOX DMPR OCD X S=1.0
D/A
(1,3,5,7) CONT DEM 2
CEA FGSG09-DRV-WBOIL-GH1-A002 OEF S=1.0 X D/A
FUEL OIL EF WINDBOX DMPR 1
(2,4,6,8) CONT DEM OEF X S=1.0
D/A
FGSG09-DRV-WBOIL-EF2-A002 CEA 2
FUEL OIL EF WINDBOX DMPR OGH S=1.0 X D/A
(1,3,5,7) CONT DEM 1
CEA FGSG09-DRV-WBOIL-EF1-A002 OGH X S=1.0
D/A
FUEL OIL CD WINDBOX DMPR 2
(2,4,6,8) CONT DEM
AX1 S=1.0 X D/A
FGSG09-DRV-WBOIL-CD2-A002 CEA
FUEL OIL CD WINDBOX DMPR X S=1.0
AX2 D/A
(1,3,5,7) CONT DEM
CEA FGSG09-DRV-WBOIL-CD1-A002 S=1.0
2 FUEL OIL AB WINDBOX DAMPER
(2,4,6,8) CONT DEM
2
FGSG09-DRV-WBOIL-AB2-A002 CEA
<FGSG09-DRV-WBOIL-AB2> FUEL OIL AB WINDBOX DAMPER
(1,3,5,7) CONT DEM
FGSG09-DRV-WBOIL-AB1-A002 AUT
CEA <FGSG09-DRV-WBOIL-AB1> on on on off on on on on on on
off off off on off off off off off off
COAL WB DAMPER DEM SIGNAL T T T T T T T T T T CED
FGSG09-WBCDPCNT-02-A002 sw sw sw sw sw sw sw sw sw sw ANY COAL WB DAMPER AUTO
<FGSG09-WBCDPCNT-02> (DP CNT)
FGSG09-WBCDPCNT-02-D001
OAB OAB OCD OCD OEF OEF OGH OGH <FGSG09-WBCDPCNT-02>
AX1 AX2
1 2 1 2 1 2 1 2

3 3
CED CED
FUEL OIL-AB WINDBOX DAMPER OAB FUEL OIL-GH WINDBOX DMPR OGH
(1,3,5,7) AUTO (DP CNT) 1 (1,3,5,7) AUTO (DP CNT) 1
FGSG09-WBCOIL-AB-01-D001 <FGSG09-WBCOIL-AB-01> FGSG09-WBCOIL-GH-01-D001
CED CED
FUEL OIL-AB WINDBOX DAMPER OAB FUEL OIL GH WINDBOX DMPR OGH
(2,4,6,8) AUTO (DP CNT) 2 (2,4,6,8) AUTO (DP CNT) 2
FGSG09-WBCOIL-AB-01-D002 <FGSG09-WBCOIL-AB-01> FGSG09-WBCOIL-GH-01-D002
CED CED
FUEL OIL-CD WINDBOX DMPR OCD AUX-2 1,2,7,8CORNER WINDBOX
AX1
(1,3,5,7) AUTO (DP CNT) 1 DAMPER AUTO (DP CNT)
FGSG09-WBCOIL-CD-01-D001 FGSG09-WBCAUX2-01-A003
CED CED <FGSG09-WBCAUX2-01>
FUEL OIL CD WINDBOX DMPR OCD AUX-2 3,4,5,6CORNER WINDBOX
AX2
(2,4,6,8) AUTO (DP CNT) 2 DAMPER AUTO (DP CNT)
4 FGSG09-WBCOIL-CD-01-D002 FGSG09-WBCAUX2-01-A004
4
CED <FGSG09-WBCAUX2-01>
FUEL OIL-EF WINDBOX DMPR OEF
(1,3,5,7) AUTO (DP CNT) 1
FGSG09-WBCOIL-EF-01-D001
CED
FUEL OIL EF WINDBOX DMPR OEF
(2,4,6,8) AUTO (DP CNT) 2
FGSG09-WBCOIL-EF-01-D002

FX-3 *
CEA CEA
AUX-2 WINDBOX DAMPER
BOILER INPUT DEMAND FX UNFIRING POSITION
FGSG05-AI01-A02 <FGSG05-AI01> FX-1 * NO FGSG09-WBCDPCNT-01-A001
<FGSG09-DRV-WBAUX2-1>
5 <FGSG09-DRV-WBAUX2-3> 5
FX
CEA Ron=400.0
Roff=99999.0 FX-2 *
FURNACE PRESSURE (FURNACE
TO WINDBOX DP CONTROL) on MD=0
off sw
FX
01HAD01CP-A01
<FGSG09-MSS-FPRS(FWBDP)> TR

CEA - - X2 Tr CEA
WB INL PRESSURE (FURNACE TO + + X1 X
WINDBOX DP CONTROL)
PI FURNACE-WB DP. CONTROL DEM
01HLA05CP-A01 Ts FGSG09-WBCDPCNT-01-A002
<FGSG09-MSS-WBILPR(FWBDP)> IS=1.0 <FGSG09-WBCAUX2-01>
OS=1.0 <FGSG09-WBCCOAL-A-01>
<FGSG09-WBCOIL-AB-01>
6 LL=0.0 6
HL=100.0
X Y K=0.05
AUT T=30.0
T=1.0

FX-1 * FX-2 * FX-3 *


X1=0.0,Y1=110.0 X1=2.0,Y1=1.0 X1=0.0,Y1=40.0
X2=707.4,Y2=110.0 X2=4.0,Y2=1.0 X2=198.0,Y2=40.0 TITLE FURNACE-WINDBOX DIFF PRESSURE Rev.
X3=0.0,Y3=0.0 X3=6.0,Y3=1.0 X3=264.0,Y3=60.0 CONTROL-1
REMARKS

X4=0.0,Y4=0.0 X4=8.0,Y4=1.0 X4=330.0,Y4=60.0 2


X5=0.0,Y5=0.0 X5=10.0,Y5=1.0 X5=396.0,Y5=60.0
X6=0.0,Y6=0.0 X6=12.0,Y6=1.0 X6=528.0,Y6=60.0 SHEET NO.
X7=0.0,Y7=0.0 X7=14.0,Y7=1.0 X7=660.0,Y7=60.0
* TO BE FINALIZED DURING COMMISSIONING
X8=0.0,Y8=0.0 X8=16.0,Y8=1.0 X8=693.0,Y8=60.0 MITSUBISHI FGSG09-
X9=0.0,Y9=0.0
X10=0.0,Y10=0.0
X9=18.0,Y9=1.0
X10=26.0,Y10=1.0
X9=700.0,Y9=60.0
X10=0.0,Y10=0.0 HEAVY INDUSTRIES, LTD WBCDPCNT-01
A B C D E F G H I
CEA
COAL H WINDBOX DAMPER CEA
(2,4,6,8) DEMAND SIGNAL
FGSG09-DRV-WBCOAL-H2-A001
CA1
X
D/A + NUMBER OF COAL WB
DAMPER AUTO (DP CNT)
CEA CA2 S=1.0 X D/A FGSG09-WBCDPCNT-02-A001
COAL H WINDBOX DAMPER <FGSG09-WBCDPCNT-01>
(1,3,5,7) DEMAND SIGNAL X S=1.0
CB1 D/A
FGSG09-DRV-WBCOAL-H1-A001
CEA CB2 S=1.0 X D/A
COAL G WINDBOX DAMPER
1 (2,4,6,8) DEMAND SIGNAL CC1
X
D/A S=1.0 1
FGSG09-DRV-WBCOAL-G2-A001
CEA CC2 S=1.0 X D/A
COAL G WINDBOX DAMPER
(1,3,5,7) DEMAND SIGNAL X S=1.0
CD1 D/A
FGSG09-DRV-WBCOAL-G1-A001
CEA CD2 S=1.0 X D/A
COAL F WINDBOX DAMPER
(2,4,6,8) DEMAND SIGNAL X S=1.0
CE1 D/A
FGSG09-DRV-WBCOAL-F2-A001
CEA CE2 S=1.0 X D/A
COAL F WINDBOX DAMPER
(1,3,5,7) DEMAND SIGNAL X S=1.0
CF1 D/A
FGSG09-DRV-WBCOAL-F1-A001
CEA CF2 S=1.0 X D/A
COAL E WINDBOX DAMPER
2 (2,4,6,8) DEMAND SIGNAL
CG1
X
D/A
S=1.0 2
FGSG09-DRV-WBCOAL-E2-A001
CEA S=1.0 X
CG2 D/A
COAL E WINDBOX DAMPER
(1,3,5,7) DEMAND SIGNAL X S=1.0
CH1 D/A
FGSG09-DRV-WBCOAL-E1-A001
CEA S=1.0 X
CH2 D/A
COAL D WINDBOX DAMPER
(2,4,6,8) DEMAND SIGNAL S=1.0
CEA FGSG09-DRV-WBCOAL-D2-A001
COAL D WINDBOX DAMPER
(1,3,5,7) DEMAND SIGNAL
FGSG09-DRV-WBCOAL-D1-A001
CEA
COAL C WINDBOX DAMPER
(2,4,6,8) DEMAND SIGNAL
3 FGSG09-DRV-WBCOAL-C2-A001 CED 3
CEA ANY COAL WB DAMPER
COAL C WINDBOX DAMPER AUTO (DP CNT)
(1,3,5,7) DEMAND SIGNAL FGSG09-WBCDPCNT-02-D001
FGSG09-DRV-WBCOAL-C1-A001
CEA <FGSG09-WBCDPCNT-01>
COAL B WINDBOX DAMPER
(2,4,6,8) DEMAND SIGNAL
FGSG09-DRV-WBCOAL-B2-A001
CEA
COAL B WINDBOX DAMPER
(1,3,5,7) DEMAND SIGNAL
FGSG09-DRV-WBCOAL-B1-A001
CEA
COAL A WINDBOX DAMPER
(2,4,6,8) DEMAND SIGNAL
4 CEA
FGSG09-DRV-WBCOAL-A2-A001
<FGSG09-DRV-WBCOAL-A2> on on on on on on on on on on on on on on on CEA 4
COAL A WINDBOX DAMPER off off off off off off off off off off off off off off off
(1,3,5,7) DEMAND SIGNAL T T T T T T T T T T T T T T T COAL WB DAMPER DEM SIGNAL
FGSG09-DRV-WBCOAL-A1-A001 sw sw sw sw sw sw sw sw sw sw sw sw sw sw sw FGSG09-WBCDPCNT-02-A002
<FGSG09-DRV-WBCOAL-A1> <FGSG09-WBCDPCNT-01>
CA2 CB1 CB2 CC1 CC2 CD1 CD2 CE1 CE2 CF1 CF2 CG1 CG2 CH1 CH2

5 5

CED CED CED CED


COAL A 1,3,5,7 WINDBOX COAL A 2,4,6,8 WINDBOX COAL E 1,3,5,7 WINDBOX COAL E 2,4,6,8 WINDBOX
CA1 CA2 CE1 CE2
DAMPER AUTO (DP CNT) DAMPER AUTO (DP CNT) DAMPER AUTO (DP CNT) DAMPER AUTO (DP CNT)
FGSG09-WBCCOAL-A-01-D007 FGSG09-WBCCOAL-A-01-D008 FGSG09-WBCCOAL-E-01-D007 FGSG09-WBCCOAL-E-01-D008
<FGSG09-WBCCOAL-A-01> <FGSG09-WBCCOAL-A-01>
CED CED CED CED
COAL B 1,3,5,7 WINDBOX COAL B 2,4,6,8 WINDBOX COAL F 1,3,5,7 WINDBOX COAL F 2,4,6,8 WINDBOX
CB1 CB2 CF1 CF2
DAMPER AUTO (DP CNT) DAMPER AUTO (DP CNT) DAMPER AUTO (DP CNT) DAMPER AUTO (DP CNT)
FGSG09-WBCCOAL-B-01-D007 FGSG09-WBCCOAL-B-01-D008 FGSG09-WBCCOAL-F-01-D007 FGSG09-WBCCOAL-F-01-D008

CED CED CED CED


COAL C 1,3,5,7 WINDBOX COAL C 2,4,6,8 WINDBOX COAL G 1,3,5,7 WINDBOX COAL G 2,4,6,8 WINDBOX
CC1 CC2 CG1 CG2
DAMPER AUTO (DP CNT) DAMPER AUTO (DP CNT) DAMPER AUTO (DP CNT) DAMPER AUTO (DP CNT)
6 FGSG09-WBCCOAL-C-01-D007 FGSG09-WBCCOAL-C-01-D008 FGSG09-WBCCOAL-G-01-D007 FGSG09-WBCCOAL-G-01-D008 6
CED CED CED CED
COAL D 1,3,5,7 WINDBOX COAL D 2,4,6,8 WINDBOX COAL H 1,3,5,7 WINDBOX COAL H 2,4,6,8 WINDBOX
CD1 CD2 CH1 CH2
DAMPER AUTO (DP CNT) DAMPER AUTO (DP CNT) DAMPER AUTO (DP CNT) DAMPER AUTO (DP CNT)
FGSG09-WBCCOAL-D-01-D007 FGSG09-WBCCOAL-D-01-D008 FGSG09-WBCCOAL-H-01-D007 FGSG09-WBCCOAL-H-01-D008

TITLE FURNACE-WINDBOX DIFF PRESSURE Rev.


CONTROL-2 2
REMARKS

SHEET NO.
MITSUBISHI FGSG09-
HEAVY INDUSTRIES, LTD WBCDPCNT-02
A B C D E F G H I
CEA
FURNACE-WB DP. CONTROL DEM
CEA
FGSG09-WBCDPCNT-01-A002 AUX-2 WINDBOX DAMPER SET
FX-1 * POINT
<FGSG09-WBCDPCNT-01>
FGSG09-WBCAUX2-01-A002
FX S=0.0
<FGSG09-DRV-WBAUX2-1>
FX-2 * 2ON 3ON 4ON 5ON 6ON 7ON 1TR SG <FGSG09-DRV-WBAUX2-3>

FX
1 Ron=200.0 Ron=10.0 1
Roff=200.0 Roff=99999.0
CEA FX-3 * on on sw sw sw sw sw sw off off on CEA
MD=0
off off off off off off off off on on off AUX-2 1,2,7,8CORNER WINDBOX
COAL FLOW-A FX TR TR TR TR TR TR TR TR TR TRD TR DAMPER CONTROL SIGNAL
APC-MSS-CF-A-1-A003 <APC-MSS-CF-A-1> Ron=200.0 sw Ron=200.0 on Ron=200.0 on Ron=200.0 on Ron=200.0 on Ron=200.0 on Ron=200.0 on Ron=200.0 sw sw FGSG09-WBCAUX2-01-A001
C2S sw
CED Roff=200.0 Roff=200.0 Roff=200.0 Roff=200.0 Roff=200.0 Roff=200.0 Roff=200.0 Roff=200.0 Ron=100.0 <FGSG09-DRV-WBAUX2-1>
WORST (COAL-1) SEL MD=0 MD=0 MD=0 MD=0 MD=0 MD=0 MD=0 MD=0 Roff=99999.0
A-
MD=0
APC-CMS-06-D001 <APC-CMS-06> ON
C3S 1AT
CED
BEST (COAL-3) SEL 1ST
FX-4 *
APC-CMS-06-D003 <APC-CMS-06>
FX
FX-5 *
2 2
CED FX
FX-6 * on on
2 COAL BNR ON 2ON S=0.0
off off
FX TR TR SG
FGSG09-WBC-COMMON-01-D001 2TR
CED <FGSG09-WBC-COMMON-01> sw sw
3 COAL BNR ON 3ON Ron=10.0
C2S C3S Roff=99999.0
FX-7 * off on CEA
FGSG09-WBC-COMMON-01-D002
CED <FGSG09-WBC-COMMON-01> on off AUX-2 3,4,5,6CORNER WINDBOX
FX TRD TR DAMPER CONTROL SIGNAL
4 COAL BNR ON 4ON FX-8 * sw sw FGSG09-WBCAUX2-01-A005 <FGSG09-DRV-WBAUX2-3>
FGSG09-WBC-COMMON-01-D003 Ron=100.0
CED <FGSG09-WBC-COMMON-01> FX Roff=99999.0
FX-9 * on on MD=0
5 COAL BNR ON 5ON
3 FGSG09-WBC-COMMON-01-D004
FX
off
TR
off
TR 2AT 2ST 3
CED <FGSG09-WBC-COMMON-01> sw sw
CED
6 COAL BNR ON 6ON
C2S FX-10 * C3S WINDBOX BANKING COMMAND
FGSG09-WBC-COMMON-01-D005
CED <FGSG09-WBC-COMMON-01> APC-ADC-15-D002 <APC-ADC-15>
FX
7 OR 8 COAL BNR ON 7ON FX-11 *
FGSG09-WBC-COMMON-01-D006
<FGSG09-WBC-COMMON-01> FX CED
CED FX-12 * on on AUX-2 1,2,7,8CORNER WINDBOX
1AT
PULV-A & COAL FEEDER-A A- off off DAMPER AUTO
START / PURGE IN PROGRESS ON
FX TR TR
FGSG09-DRV-WBAUX2-1-AT
BMS1-11A-9-D03 sw sw <FGSG09-DRV-WBAUX2-1> CED
AUX-2 1,2,7,8CORNER WINDBOX
DAMPER AUTO (DP CNT)
4 CED C2S FX-13 * C3S
FGSG09-WBCAUX2-01-A003 <FGSG09-WBCDPCNT-01>
4
AUX-2 1,2,7,8CORNER WINDBOX CED
DAMPER AUTO or STANDBY
1ST FX AUX-2 3,4,5,6CORNER WINDBOX
FX-14 * 2AT
FGSG09-DRV-WBAUX2-1-AST <FGSG09-DRV-WBAUX2-1> DAMPER AUTO
CED FGSG09-DRV-WBAUX2-3-AT
AUX-2 3,4,5,6CORNER WINDBOX
FX CED
2ST <FGSG09-DRV-WBAUX2-3>
DAMPER AUTO or STANDBY FX-15 * on on AUX-2 3,4,5,6CORNER WINDBOX
FGSG09-DRV-WBAUX2-3-AST<FGSG09-DRV-WBAUX2-3> off off DAMPER AUTO (DP CNT)
FX TR TR
FGSG09-WBCAUX2-01-A004 <FGSG09-WBCDPCNT-01>
CEA sw sw A-
AUX-2 1,2,7,8CORNER WINDBOX ON
1TR
DAMPER CONTROL DEMAND
C2S C3S
FGSG09-DRV-WBAUX2-1-A002 CED CED
<FGSG09-DRV-WBAUX2-1> FX-16 * FURN & WB INL PRESS SIG ABN
BID MORE THAN 30%
CEA (& BID<30% / A-CF OFF)
AUX-2 3,4,5,6CORNER WINDBOX
FX
FGSG09-WBC-COMMON-01-D008 FGSG09-WBCAUX2-01-D004
5 DAMPER CONTROL DEMAND
2TR FX-17 * CED <FGSG09-WBC-COMMON-01> 5
<FGSG09-DRV-WBAUX2-1>
FGSG09-DRV-WBAUX2-3-A002 FURNACE PRESS (FRN-WB DP
FX CONTROL) PRESS ABNORMAL
<FGSG09-DRV-WBAUX2-3>
<FGSG09-DRV-WBAUX2-3> FX-18 * <FGSG09-WBCCOAL-A-01>
on on 01HAD01CP-A01-SABN
CED <FGSG09-MSS-FPRS(FWBDP)> <FGSG09-WBCOIL-AB-01>
off off
FX TR TR WB INL PRESS (FRN-WB DP
sw sw CONTROL) PRESS ABNORMAL
01HLA05CP-A01-SABN
C2S C3S <FGSG09-MSS-WBILPR(FWBDP)>
FX-19 *

FX-15 * FX-16 * FX-17 * FX-18 * FX FX-19 * FX-20 * FX-21 *


X1=0.0,Y1=60.0 X1=0.0,Y1=60.0 X1=0.0,Y1=60.0 X1=0.0,Y1=60.0 FX-20 * X1=0.0,Y1=60.0 X1=0.0,Y1=60.0 X1=0.0,Y1=60.0
X2=25.0,Y2=60.0 X2=25.0,Y2=60.0 X2=25.0,Y2=60.0 X2=25.0,Y2=60.0 X2=25.0,Y2=60.0 X2=25.0,Y2=60.0 X2=25.0,Y2=60.0
X3=35.0,Y3=60.0 X3=35.0,Y3=60.0 X3=35.0,Y3=60.0 X3=35.0,Y3=60.0 FX X3=35.0,Y3=60.0 X3=35.0,Y3=60.0 X3=35.0,Y3=60.0
6 X4=45.0,Y4=60.0 X4=45.0,Y4=60.0 X4=45.0,Y4=60.0 X4=45.0,Y4=60.0 FX-21 * on on X4=45.0,Y4=60.0 X4=45.0,Y4=60.0 X4=45.0,Y4=60.0 6
X5=50.0,Y5=100.0 X5=50.0,Y5=100.0 X5=50.0,Y5=100.0 X5=50.0,Y5=100.0 off off X5=50.0,Y5=100.0 X5=50.0,Y5=100.0 X5=50.0,Y5=100.0
X6=65.0,Y6=100.0 X6=65.0,Y6=100.0 X6=65.0,Y6=100.0 X6=65.0,Y6=100.0 FX TR TR X6=65.0,Y6=100.0 X6=65.0,Y6=100.0 X6=65.0,Y6=100.0
X7=75.0,Y7=100.0 X7=75.0,Y7=100.0 X7=75.0,Y7=100.0 X7=75.0,Y7=100.0 sw sw X7=75.0,Y7=100.0 X7=75.0,Y7=100.0 X7=75.0,Y7=100.0
X8=100.0,Y8=100.0 X8=100.0,Y8=100.0 X8=100.0,Y8=100.0 X8=100.0,Y8=100.0 X8=100.0,Y8=100.0 X8=100.0,Y8=100.0 X8=100.0,Y8=100.0
X9=110.0,Y9=100.0 X9=110.0,Y9=100.0 X9=110.0,Y9=100.0 X9=110.0,Y9=100.0 X9=110.0,Y9=100.0 X9=110.0,Y9=100.0 X9=110.0,Y9=100.0
X10=0.0,Y10=0.0 X10=0.0,Y10=0.0 X10=0.0,Y10=0.0 X10=0.0,Y10=0.0 C2S C3S X10=0.0,Y10=0.0 X10=0.0,Y10=0.0 X10=0.0,Y10=0.0 * TO BE FINALIZED DURING COMMISSIONING

FX-1 * FX-2 * FX-3 * FX-4 * FX-5 * FX-6 * FX-7 * FX-8 * FX-9 * FX-10 * FX-11 * FX-12 * FX-13 * FX-14 *
X1=0.0,Y1=60.0 X1=0.0,Y1=60.0 X1=0.0,Y1=60.0 X1=0.0,Y1=60.0 X1=0.0,Y1=60.0 X1=0.0,Y1=60.0 X1=0.0,Y1=60.0 X1=0.0,Y1=60.0 X1=0.0,Y1=60.0 X1=0.0,Y1=60.0 X1=0.0,Y1=60.0 X1=0.0,Y1=60.0 X1=0.0,Y1=60.0 X1=0.0,Y1=60.0
X2=25.0,Y2=60.0 X2=25.0,Y2=60.0 X2=25.0,Y2=60.0 X2=25.0,Y2=60.0 X2=25.0,Y2=60.0 X2=25.0,Y2=60.0 X2=25.0,Y2=60.0 X2=25.0,Y2=60.0 X2=25.0,Y2=60.0 X2=25.0,Y2=60.0 X2=25.0,Y2=60.0 X2=25.0,Y2=60.0 X2=25.0,Y2=60.0 X2=25.0,Y2=60.0 TITLE Rev.
X3=35.0,Y3=60.0 X3=35.0,Y3=60.0 X3=35.0,Y3=60.0 X3=35.0,Y3=60.0 X3=35.0,Y3=60.0 X3=35.0,Y3=60.0 X3=35.0,Y3=60.0 X3=35.0,Y3=60.0 X3=35.0,Y3=60.0 X3=35.0,Y3=60.0 X3=35.0,Y3=60.0 X3=35.0,Y3=60.0 X3=35.0,Y3=60.0 X3=35.0,Y3=60.0 AUX-2 DAMPER CONTROL
REMARKS

X4=45.0,Y4=60.0 X4=45.0,Y4=60.0 X4=45.0,Y4=60.0 X4=45.0,Y4=60.0 X4=45.0,Y4=60.0 X4=45.0,Y4=60.0 X4=45.0,Y4=60.0 X4=45.0,Y4=60.0 X4=45.0,Y4=60.0 X4=45.0,Y4=60.0 X4=45.0,Y4=60.0 X4=45.0,Y4=60.0 X4=45.0,Y4=60.0 X4=45.0,Y4=60.0
2
X5=50.0,Y5=100.0 X5=50.0,Y5=100.0 X5=50.0,Y5=100.0 X5=50.0,Y5=100.0 X5=50.0,Y5=100.0 X5=50.0,Y5=100.0 X5=50.0,Y5=100.0 X5=50.0,Y5=100.0 X5=50.0,Y5=100.0 X5=50.0,Y5=100.0 X5=50.0,Y5=100.0 X5=50.0,Y5=100.0 X5=50.0,Y5=100.0 X5=50.0,Y5=100.0
X6=65.0,Y6=100.0 X6=65.0,Y6=100.0 X6=65.0,Y6=100.0 X6=65.0,Y6=100.0 X6=65.0,Y6=100.0 X6=65.0,Y6=100.0 X6=65.0,Y6=100.0 X6=65.0,Y6=100.0 X6=65.0,Y6=100.0 X6=65.0,Y6=100.0 X6=65.0,Y6=100.0 X6=65.0,Y6=100.0 X6=65.0,Y6=100.0 X6=65.0,Y6=100.0
SHEET NO.
X7=75.0,Y7=100.0 X7=75.0,Y7=100.0 X7=75.0,Y7=100.0 X7=75.0,Y7=100.0 X7=75.0,Y7=100.0 X7=75.0,Y7=100.0 X7=75.0,Y7=100.0 X7=75.0,Y7=100.0 X7=75.0,Y7=100.0 X7=75.0,Y7=100.0 X7=75.0,Y7=100.0 X7=75.0,Y7=100.0 X7=75.0,Y7=100.0 X7=75.0,Y7=100.0
X8=100.0,Y8=100.0 X8=100.0,Y8=100.0 X8=100.0,Y8=100.0 X8=100.0,Y8=100.0 X8=100.0,Y8=100.0 X8=100.0,Y8=100.0 X8=100.0,Y8=100.0 X8=100.0,Y8=100.0 X8=100.0,Y8=100.0 X8=100.0,Y8=100.0 X8=100.0,Y8=100.0 X8=100.0,Y8=100.0 X8=100.0,Y8=100.0 X8=100.0,Y8=100.0 MITSUBISHI FGSG09-
X9=110.0,Y9=100.0
X10=0.0,Y10=0.0
X9=110.0,Y9=100.0
X10=0.0,Y10=0.0
X9=110.0,Y9=100.0
X10=0.0,Y10=0.0
X9=110.0,Y9=100.0
X10=0.0,Y10=0.0
X9=110.0,Y9=100.0
X10=0.0,Y10=0.0
X9=110.0,Y9=100.0
X10=0.0,Y10=0.0
X9=110.0,Y9=100.0
X10=0.0,Y10=0.0
X9=110.0,Y9=100.0
X10=0.0,Y10=0.0
X9=110.0,Y9=100.0
X10=0.0,Y10=0.0
X9=110.0,Y9=100.0
X10=0.0,Y10=0.0
X9=110.0,Y9=100.0
X10=0.0,Y10=0.0
X9=110.0,Y9=100.0
X10=0.0,Y10=0.0
X9=110.0,Y9=100.0
X10=0.0,Y10=0.0
X9=110.0,Y9=100.0
X10=0.0,Y10=0.0 HEAVY INDUSTRIES, LTD WBCAUX2-01
A B C D E F G H I

AI
AUX-2 1CORNER WINDBOX POS
DAMPER POSITION FB I A1

SV S-PB-3-Set 01HLA51AA711-XQ01 POS Pin C


SV SV 01HLA51AA711 PB RPB 0.0 - 100.0% TRK
I
MV S-PB-8-Set DAB DRAB
PB APB
AI FBI FBO CEA O
AUX-2 1CORNER WINDBOX DAMPER
V3 S-PB-10-Set AUX-2 1CORNER WINDBOX RB1I TRKS AUX-2 1CORNER WINDBOX RSE RSTC OPND D1
TRK TRACKING SIG PB MPB
1 DAMPER POSITION DEMAND1 RB DAMPER TR SIGNAL T
VDSI 1
DAB DRIVE ABN S-PB-2 Tagging FGSG09-DRV-WBAUX2-1-TR TAG CLSD D3
O
PB TAG 01HLA51AA711-YQ01RB TAG
<FGSG09-WBC-COMMON-02>
RSE RESET COND S-PB-3 0.0 - 100.0% RBSO <FGSG09-WBCDPCNT-01> MID D2
RB
T
SAB SIG ABN S-PB-4
AUX-2 1CORNER WINDBOX DAMPER
N AI
CAU CONTROL AUTO S-PB-8 AUX-2 1CORNER WINDBOX RB2I FQAB FSA
T DAMPER POSITION DEMAND2 RB B
STB STAND BY MODE S-PB-9 MV-I-PRH
Y MV-D-PRH 01HLA51AA711-YQ02RB CAU D1
S-PB-10 MV-Set 0.0 - 100.0% DFDH DFD T <WIND BOX-1>
MAN MANUAL MODE
H STB D2 <WIND BOX-1>
<WIND BOX-1> Y <WIND BOX-1>
AUX-2 (LHS) WINDBOX DAMPER
CED <WIND BOX-1> D3 <WIND BOX-1>
MAN
<WIND BOX-1> RQAB RSA
FG INITIALIZING INIT
2 <WIND BOX-1> B
AUX-2 1,2,7,8CORNER WINDBOX DAMPER AUTO/MANUAL 2
FG INITIALIZING
CEA
AUX-2 WINDBOX DAMPER SET UNFIRING POS DRDH DRD
SV S=100.0 PVC-1
POINT DPRH IPRH H
FGSG09-WBCAUX2-01-A002<FGSG09-WBCAUX2-01> ULMT Ain Aout A1
CEA UNFI SG RB 999.9uu
PVC
AUX-2 WINDBOX DAMPER LLMT DRVM FMA Cout A2
UNFI DEM
UNFIRING POSITION N
OPMT Ron=200.0 Ron=200.0 AUX-2 1CORNER WINDBOX DAMPER RB
FGSG09-WBCDPCNT-01-A001
<FGSG09-WBCDPCNT-01> Roff=99999.0 Roff=99999.0
CEA S OH OL on on AO <WIND BOX-1>
MD=0 MD=0
AUX-2 1,2,7,8CORNER WINDBOX X Y Ain Aout off off DEM AO AUX-2 1CORNER WINDBOX <WIND BOX-1>
DAMPER CONTROL SIGNAL
S/S TR TR DRIP
DAMPER POSN DEM1 <WIND BOX-1>
FGSG09-WBCAUX2-01-A001<FGSG09-WBCAUX2-01> S=0.0 L sw OPP OPC INIT OPRH sw sw <WIND BOX-1>
01HLA51AA711-YQ01 FSA X
SG 0.0 - 100.0% B A
3 S=5.0 on AO AUX-2 1CORNER WINDBOX DAMPER FB SIG ABN 3
off MANUAL MODE AUX-2 1CORNER WINDBOX RSA X
SG TR MAN
DAMPER POSN DEM2 B A
sw INITIALIZE
Ron=200.0 INIT 01HLA51AA711-YQ02 AUX-2 1CORNER WINDBOX DAMPER RB SIG ABN
STB
STAND BY MODE Roff=200.0 0.0 - 100.0%
Y UNF UNFIRING POS CMD DFD X
MD=0 A
P ALLRST H
RPB
CED FOP FORCED OPEN CMD AUX-2 1CORNER WINDBOX DAMPER FB DEV HI
N
WINDBOX BANKING COMMAND
DRIP DRD X
APC-ADC-15-D002 FOP
MAN
MANU LARP RSE
DEM_X1in=-10.0 H A
<APC-ADC-15> N CED T
DEM_Y1out=110.0 AUX-2 1CORNER WINDBOX DAMPER RB DEV HI
A-CFD SIG ABN (& A-CFD ON) DEM_X2in=110.0
CED FMA X
DEM_Y2out=-10.0
WINDBOX DMPR FORCED OPN FGSG09-WBCCOAL-A-01-D003<FGSG09-WBCCOAL-A-01> SAB SABCND
RB_X1in=-10.0
N A
CMD CED N
4 FGSG09-WBC-COMMON-01-D007 UNF BID SIGNAL ABN(&BID MORE THAN SAB
RB_Y1out=-10.0 AUX-2 1,2,7,8CORNER WINDBOX DAMPER FORCED MANUAL 4
RB_X2in=110.0
<FGSG09-WBC-COMMON-01> P 30%) N
RB_Y2out=110.0
FGSG09-WBC-COMMON-01-D010 DABO DAB X
RB_CHG=0 MAN
CED <FGSG09-WBC-COMMON-01> O E
RB_TRK=0
FURN & WB INL PRESS SIG ABN (&
FB_TRK=0 AUX-2 1,2,7,8CORNER WINDBOX DAMPER MANUAL MODE
BID<30% / A-CF OFF)
LCN DABCND DEM_FB=0 CAU X
FGSG09-WBCAUX2-01-D004
CED <FGSG09-WBCAUX2-01> D 12DV=10.0 T E
PULV-A & COAL FEEDER-A ACN INIT FDHEX ARDV=10.0
ONT1=10.0 AUX-2 1,2,7,8CORNER WINDBOX DAMPER AUTO MODE
START / PURGE IN PROGRESS D
DFDV=10.0 STB X
BMS1-11A-9-D03 INIT
CED ONT2=60.0 Y E
BID MORE THAN 30% AUX-2 1,2,7,8CORNER WINDBOX DAMPER STANDBY MODE
RBK
FGSG09-WBC-COMMON-01-D008
<FGSG09-WBC-COMMON-01>
5 CED 5
CED CAU AUX-2 1,2,7,8CORNER WINDBOX
<FGSG09-WBCAUX2-01>
AUX-2 2CORNER WINDBOX DAMPER ATPB CAUTX Y CAU T DAMPER AUTO
APB AUTO PB
DRV ABN T FGSG09-DRV-WBAUX2-1-AT
MNPB
FGSG09-DRV-WBAUX2-2-D001 MPB MANUAL PB T=0.0
CED <FGSG09-DRV-WBAUX2-2> CED
AUX-2 7CORNER WINDBOX DAMPER ACN AUT CND ACND CSTB STB DAU AUX-2 1,2,7,8CORNER WINDBOX <FGSG09-WBCAUX2-01>
DRV ABN D Y T DAMPER AUTO or STANDBY
SAB FGSG09-DRV-WBAUX2-7-D001 MCN MANU CND MCND ASM FGSG09-DRV-WBAUX2-1-AST
N CED <FGSG09-DRV-WBAUX2-7> D S
MCN AUX-2 8CORNER WINDBOX DAMPER LCN DAUT DAU CED
D DRV ABN D T STB AUX-2 1,2,7,8CORNER WINDBOX
DAB FGSG09-DRV-WBAUX2-8-D001 Y DAMPER STANDBY MODE
O <FGSG09-DRV-WBAUX2-8> FGSG09-DRV-WBAUX2-1-ST
RSA RB SIG ABN INIT MANU
INIT INITIALIZE MAN
CED B CEA <FGSG09-DRV-WBAUX2-2>
6 FCB/RUNBACK OPERATE RBK DEM
AUX-2 1,2,7,8CORNER WINDBOX <FGSG09-DRV-WBAUX2-7> 6
DAMPER CONTROL DEMAND <FGSG09-DRV-WBAUX2-8>
APC-EMG-10-D001 <APC-EMG-10> DRD RB SIG DEV H FGSG09-DRV-WBAUX2-1-A002 <FGSG09-WBCAUX2-01>
H
CED
<FGSG09-DRV-WBAUX2-2>
AUX-2 1,2,7,8CORNER WINDBOX
RPB <FGSG09-DRV-WBAUX2-7>
DAMPER RESET PB ON
<FGSG09-DRV-WBAUX2-8>
FGSG09-DRV-WBAUX2-1-D001

TITLE AUX-2 1CORNER WINDBOX DAMPER Rev.


REMARKS

2
SHEET NO.
MITSUBISHI FGSG09-DRV-
HEAVY INDUSTRIES, LTD WBAUX2-1
A B C D E F G H I

AI
AUX-2 2CORNER WINDBOX POS
DAMPER POSITION DEMAND1 RB I A1

01HLA52AA711-XQ01 POS Pin C


0.0 - 100.0% I
DAB DRAB
AUX-2 2CORNER WINDBOX DAMPER
AI FBI FBO CEA O
AUX-2 2CORNER WINDBOX RB1I TRKS AUX-2 2CORNER WINDBOX RSE RSTC OPND D1
1 DAMPER POSITION DEMAND1 RB DAMPER TR SIGNAL T
VDSI 1
FGSG09-DRV-WBAUX2-2-TR <FGSG09-WBC-COMMON-02> CLSD D3
01HLA52AA711-YQ01RB
0.0 - 100.0% RBSO MID D2
RB

AUX-2 2CORNER WINDBOX DAMPER


AI
AUX-2 2CORNER WINDBOX RB2I FQAB FSA
DAMPER POSITION DEMAND2 RB B

01HLA52AA711-YQ02RB PVC-1
0.0 - 100.0% DFDH DFD Ain Aout A1
RB 999.9uu
H
PVC
Cout A2
AUX-2 2CORNER WINDBOX DAMPER RB
RQAB RSA
2 B 2
DRDH DRD
H FSA X
B A
AUX-2 2CORNER WINDBOX DAMPER FB SIG ABN
RSA X
B A
CEA AO
AUX-2 2CORNER WINDBOX DAMPER RB SIG ABN
AUX-2 1,2,7,8CORNER WINDBOX DEM AO AUX-2 2CORNER WINDBOX
DRIP
DAMPER CONTROL DEMAND DAMPER POSN DEM1 DFD X
FGSG09-DRV-WBAUX2-1-A002<FGSG09-DRV-WBAUX2-1> H A
01HLA52AA711-YQ01 AUX-2 2CORNER WINDBOX DAMPER FB DEV HI
0.0 - 100.0%
DRIP
3 DEM_X1in=-10.0
AO
DRD
H
X
A 3
DEM_Y1out=110.0
AUX-2 2CORNER WINDBOX AUX-2 2CORNER WINDBOX DAMPER RB DEV HI
DEM_X2in=110.0
DAMPER POSN DEM2
DEM_Y2out=-10.0
RB_X1in=-10.0 01HLA52AA711-YQ02
RB_Y1out=-10.0 0.0 - 100.0%
RB_X2in=110.0
ALLRST
RB_Y2out=110.0 RPB
RB_CHG=0
RB_TRK=0
FB_TRK=0 LARP RSE
DEM_FB=0 T
12DV=10.0
ARDV=10.0 CED
ONT1=10.0 AUX-2 2CORNER WINDBOX
DFDV=10.0 DAMPER DRV ABN
4 ONT2=60.0
FGSG09-DRV-WBAUX2-2-D001
4
<FGSG09-DRV-WBAUX2-1>
DABO DAB
O

LCN DABCND
D
INIT FDHEX

INIT

RBK

5 5

CED
RSA RB SIG ABN
FG INITIALIZING INIT
B
FG INITIALIZING LCN
D
DRD RB SIG DEV H
CED H
FCB/RUNBACK OPERATE RBK
APC-EMG-10-D001 <APC-EMG-10>

6 CED 6
AUX-2 1,2,7,8CORNER WINDBOX
RPB
DAMPER RESET PB ON
FGSG09-DRV-WBAUX2-1-D001
<FGSG09-DRV-WBAUX2-1>

TITLE AUX-2 2CORNER WINDBOX DAMPER Rev.


REMARKS

2
SHEET NO.
MITSUBISHI FGSG09-DRV-
HEAVY INDUSTRIES, LTD WBAUX2-2
A B C D E F G H I

AI
AUX-2 7CORNER WINDBOX POS
DAMPER POSITION DEMAND1 RB I A1

01HLA57AA711-XQ01 POS Pin C


0.0 - 100.0% I
DAB DRAB
AUX-2 7CORNER WINDBOX DAMPER
AI FBI FBO CEA O
AUX-2 7CORNER WINDBOX RB1I TRKS AUX-2 7CORNER WINDBOX RSE RSTC OPND D1
1 DAMPER POSITION DEMAND1 RB DAMPER TR SIGNAL T
VDSI 1
FGSG09-DRV-WBAUX2-7-TR <FGSG09-WBC-COMMON-02> CLSD D3
01HLA57AA711-YQ01RB
0.0 - 100.0% RBSO MID D2
RB

AUX-2 7CORNER WINDBOX DAMPER


AI
AUX-2 7CORNER WINDBOX RB2I FQAB FSA
DAMPER POSITION DEMAND2 RB B

01HLA57AA711-YQ02RB
0.0 - 100.0% DFDH DFD
H PVC-1
Ain Aout A1
RB 999.9uu
PVC
RQAB RSA Cout A2
2 B
AUX-2 7CORNER WINDBOX DAMPER RB 2
DRDH DRD
H

FSA X
B A
AUX-2 7CORNER WINDBOX DAMPER FB SIG ABN
CEA AO RSA X
AUX-2 1,2,7,8CORNER WINDBOX DEM
DRIP
AO AUX-2 7CORNER WINDBOX B A
DAMPER CONTROL DEMAND DAMPER POSN DEM1
AUX-2 7CORNER WINDBOX DAMPER RB SIG ABN
FGSG09-DRV-WBAUX2-1-A002
01HLA57AA711-YQ01 DFD X
<FGSG09-DRV-WBAUX2-1> DRIP
DEM_X1in=-10.0
0.0 - 100.0% H A
3 DEM_Y1out=110.0
AO
AUX-2 7CORNER WINDBOX DAMPER FB DEV HI 3
DEM_X2in=110.0
AUX-2 7CORNER WINDBOX DRD X
DEM_Y2out=-10.0
RB_X1in=-10.0
DAMPER POSN DEM2 H A
RB_Y1out=-10.0 AUX-2 7CORNER WINDBOX DAMPER RB DEV HI
01HLA57AA711-YQ02
RB_X2in=110.0 0.0 - 100.0%
RB_Y2out=110.0
ALLRST
RB_CHG=0 RPB
RB_TRK=0
FB_TRK=0
DEM_FB=0 LARP RSE
12DV=10.0 T
ARDV=10.0
ONT1=10.0 CED
DFDV=10.0 AUX-2 7CORNER WINDBOX
ONT2=60.0 DAMPER DRV ABN
4 FGSG09-DRV-WBAUX2-7-D001
4
<FGSG09-DRV-WBAUX2-1>
DABO DAB
O

LCN DABCND
D
INIT FDHEX

INIT

RBK

5 5

CED
RSA RB SIG ABN
FG INITIALIZING INIT
B
FG INITIALIZING LCN
D
DRD RB SIG DEV H
CED H
FCB/RUNBACK OPERATE RBK
APC-EMG-10-D001 <APC-EMG-10>

6 CED 6
AUX-2 1,2,7,8CORNER WINDBOX
RPB
DAMPER RESET PB ON
FGSG09-DRV-WBAUX2-1-D001
<FGSG09-DRV-WBAUX2-1>

TITLE AUX-2 7CORNER WINDBOX DAMPER Rev.


REMARKS

2
SHEET NO.
MITSUBISHI FGSG09-DRV-
HEAVY INDUSTRIES, LTD WBAUX2-7
A B C D E F G H I

AI
AUX-2 8CORNER WINDBOX POS
DAMPER POSITION DEMAND1 RB I A1

01HLA58AA711-XQ01 POS Pin C


0.0 - 100.0% I
DAB DRAB
AUX-2 8CORNER WINDBOX DAMPER
AI FBI FBO CEA O
AUX-2 8CORNER WINDBOX RB1I TRKS AUX-2 8CORNER WINDBOX RSE RSTC OPND D1
1 DAMPER POSITION DEMAND1 RB DAMPER TR SIGNAL T
VDSI 1
FGSG09-DRV-WBAUX2-8-TR <FGSG09-WBC-COMMON-02> CLSD D3
01HLA58AA711-YQ01RB
0.0 - 100.0% RBSO MID D2
RB

AUX-2 8CORNER WINDBOX DAMPER


AI
AUX-2 8CORNER WINDBOX RB2I FQAB FSA
DAMPER POSITION DEMAND2 RB B

01HLA58AA711-YQ02RB
0.0 - 100.0% DFDH DFD
H PVC-1
Ain Aout A1
RB 999.9uu
PVC
RQAB RSA Cout A2
2 B
AUX-2 8CORNER WINDBOX DAMPER RB 2
DRDH DRD
H

FSA X
B A
AUX-2 8CORNER WINDBOX DAMPER FB SIG ABN
CEA AO RSA X
AUX-2 1,2,7,8CORNER WINDBOX DEM
DRIP
AO AUX-2 8CORNER WINDBOX B A
DAMPER CONTROL DEMAND DAMPER POSN DEM1
AUX-2 8CORNER WINDBOX DAMPER RB SIG ABN
FGSG09-DRV-WBAUX2-1-A002
01HLA58AA711-YQ01 DFD X
<FGSG09-DRV-WBAUX2-1> DRIP
DEM_X1in=-10.0
0.0 - 100.0% H A
3 DEM_Y1out=110.0
AO
AUX-2 8CORNER WINDBOX DAMPER FB DEV HI 3
DEM_X2in=110.0
AUX-2 8CORNER WINDBOX DRD X
DEM_Y2out=-10.0
RB_X1in=-10.0
DAMPER POSN DEM2 H A
RB_Y1out=-10.0 AUX-2 8CORNER WINDBOX DAMPER RB DEV HI
01HLA58AA711-YQ02
RB_X2in=110.0 0.0 - 100.0%
RB_Y2out=110.0
ALLRST
RB_CHG=0 RPB
RB_TRK=0
FB_TRK=0
DEM_FB=0 LARP RSE
12DV=10.0 T
ARDV=10.0
ONT1=10.0 CED
DFDV=10.0 AUX-2 8CORNER WINDBOX
ONT2=60.0 DAMPER DRV ABN
4 FGSG09-DRV-WBAUX2-8-D001
4
<FGSG09-DRV-WBAUX2-1>
DABO DAB
O

LCN DABCND
D
INIT FDHEX

INIT

RBK

5 5

CED
RSA RB SIG ABN
FG INITIALIZING INIT
B
FG INITIALIZING LCN
D
DRD RB SIG DEV H
CED H
FCB/RUNBACK OPERATE RBK
APC-EMG-10-D001 <APC-EMG-10>

6 CED 6
AUX-2 1,2,7,8CORNER WINDBOX
RPB
DAMPER RESET PB ON
FGSG09-DRV-WBAUX2-1-D001
<FGSG09-DRV-WBAUX2-1>

TITLE AUX-2 8CORNER WINDBOX DAMPER Rev.


REMARKS

2
SHEET NO.
MITSUBISHI FGSG09-DRV-
HEAVY INDUSTRIES, LTD WBAUX2-8
A B C D E F G H I

AI
AUX-2 3CORNER WINDBOX POS
DAMPER POSITION FB I A1

SV S-PB-3-Set 01HLA53AA711-XQ01 POS Pin C


SV SV 01HLA53AA711 PB RPB 0.0 - 100.0% TRK
I
MV S-PB-8-Set DAB DRAB
PB APB
AI FBI FBO CEA O
AUX-2 3CORNER WINDBOX DAMPER
V3 S-PB-10-Set AUX-2 3CORNER WINDBOX RB1I TRKS AUX-2 3CORNER WINDBOX RSE RSTC OPND D1
TRK TRACKING SIG PB MPB
1 DAMPER POSITION DEMAND1 RB DAMPER TR SIGNAL T
VDSI 1
DAB DRIVE ABN S-PB-2 Tagging FGSG09-DRV-WBAUX2-3-TR TAG CLSD D3
O
PB TAG 01HLA53AA711-YQ01RB TAG
0.0 - 100.0% <FGSG09-WBC-COMMON-02>
RSE RESET COND S-PB-3 RBSO <FGSG09-WBCDPCNT-01> MID D2
RB
T
SAB SIG ABN S-PB-4
AUX-2 3CORNER WINDBOX DAMPER
N AI
CAU CONTROL AUTO S-PB-8 AUX-2 3CORNER WINDBOX RB2I FQAB FSA
T DAMPER POSITION DEMAND2 RB B
STB STAND BY MODE S-PB-9 MV-I-PRH
Y MV-D-PRH 01HLA53AA711-YQ02RB CAU D1
S-PB-10 MV-Set 0.0 - 100.0% DFDH DFD T <WIND BOX-2>
MAN MANUAL MODE
H STB D2 <WIND BOX-2>
<WIND BOX-2> Y <WIND BOX-2>
AUX-2 (RHS) WINDBOX DAMPER
CED <WIND BOX-2> D3 <WIND BOX-2>
MAN
<WIND BOX-2> RQAB RSA
FG INITIALIZING INIT
2 <WIND BOX-2> B
AUX-2 3,4,5,6CORNER WINDBOX DAMPER AUTO/MANUAL 2
FG INITIALIZING
CEA
UNFIRING POS PVC-1
AUX-2 WINDBOX DAMPER SET DRDH DRD
SV S=100.0
POINT DPRH IPRH H Ain Aout A1
RB 999.9uu
FGSG09-WBCAUX2-01-A002 ULMT
CEA <FGSG09-WBCAUX2-01> UNFI SG PVC
Cout A2
AUX-2 WINDBOX DAMPER LLMT DRVM FMA
UNFI DEM AUX-2 3CORNER WINDBOX DAMPER RB
UNFIRING POSITION N
OPMT Ron=200.0 Ron=200.0
FGSG09-WBCDPCNT-01-A001 <WIND BOX-2>
<FGSG09-WBCDPCNT-01> Roff=99999.0 Roff=99999.0
CEA S OH OL on on AO <WIND BOX-2>
MD=0 MD=0
AUX-2 3,4,5,6CORNER WINDBOX X Y Ain Aout off off DEM AO AUX-2 3CORNER WINDBOX <WIND BOX-2>
DAMPER CONTROL SIGNAL
S/S TR TR DRIP
DAMPER POSN DEM1 <WIND BOX-2>
FGSG09-WBCAUX2-01-A005 S=0.0 L sw OPP OPC INIT OPRH sw sw
<FGSG09-WBCAUX2-01> 01HLA53AA711-YQ01 FSA X
SG 0.0 - 100.0% B A
3 S=5.0 on AO AUX-2 3CORNER WINDBOX DAMPER FB SIG ABN 3
off MANUAL MODE AUX-2 3CORNER WINDBOX DFD X
MAN
SG TR DAMPER POSN DEM2 H A
sw INITIALIZE
Ron=200.0 INIT AUX-2 3CORNER WINDBOX DAMPER FB DEV HI
STB 01HLA53AA711-YQ02
STAND BY MODE Roff=200.0 UNF UNFIRING POS CMD 0.0 - 100.0%
Y RSA X
MD=0 P A
ALLRST B
CED FOP FORCED OPEN CMD RPB
N AUX-2 3CORNER WINDBOX DAMPER RB SIG ABN
WINDBOX BANKING COMMAND
DRIP DRD X
APC-ADC-15-D002 FOP
MAN
MANU LARP RSE
DEM_X1in=-10.0 H A
<APC-ADC-15>
N CED T
DEM_Y1out=110.0 AUX-2 3CORNER WINDBOX DAMPER RB DEV HI
A-CFD SIG ABN (& A-CFD ON) DEM_X2in=110.0
CED FMA X
DEM_Y2out=-10.0
WINDBOX DMPR FORCED OPN FGSG09-WBCCOAL-A-01-D003 SAB SABCND
RB_X1in=-10.0
N A
CMD CED <FGSG09-WBCCOAL-A-01> N
4 FGSG09-WBC-COMMON-01-D007 UNF BID SIGNAL ABN(&BID MORE SAB
RB_Y1out=-10.0 AUX-2 3,4,5,6CORNER WINDBOX DAMPER FORCED MANUAL 4
<FGSG09-WBC-COMMON-01> RB_X2in=110.0
P THAN 30%) N
RB_Y2out=110.0
FGSG09-WBC-COMMON-01-D010 DABO DAB X
RB_CHG=0 MAN
CED <FGSG09-WBC-COMMON-01> O E
RB_TRK=0
FURN & WB INL PRESS SIG ABN
FB_TRK=0 AUX-2 3,4,5,6CORNER WINDBOX DAMPER MANUAL MODE
(& BID<30% / A-CF OFF)
LCN DABCND DEM_FB=0 CAU X
FGSG09-WBCAUX2-01-D004
CED <FGSG09-WBCAUX2-01> D 12DV=10.0 T E
PULV-A & COAL FEEDER-A ACN INIT FDHEX ARDV=10.0
ONT1=10.0 AUX-2 3,4,5,6CORNER WINDBOX DAMPER AUTO MODE
START / PURGE IN PROGRESS D
DFDV=10.0 STB X
BMS1-11A-9-D03 INIT
CED ONT2=60.0 Y E
BID MORE THAN 30% AUX-2 3,4,5,6CORNER WINDBOX DAMPER STANDBY MODE
RBK
FGSG09-WBC-COMMON-01-D008
<FGSG09-WBC-COMMON-01>
5 CED 5
CED CAU AUX-2 3,4,5,6CORNER WINDBOX <FGSG09-WBCAUX2-01>
AUX-2 4CORNER WINDBOX ATPB CAUTX Y CAU T DAMPER AUTO
APB AUTO PB
DAMPER DRV ABN T FGSG09-DRV-WBAUX2-3-AT
MNPB
FGSG09-DRV-WBAUX2-4-D001
<FGSG09-DRV-WBAUX2-4> MPB MANUAL PB T=0.0
CED CED
<FGSG09-WBCAUX2-01>
AUX-2 5CORNER WINDBOX ACN AUT CND ACND CSTB STB DAU AUX-2 3,4,5,6CORNER WINDBOX
DAMPER DRV ABN D Y T DAMPER AUTO or STANDBY
SAB FGSG09-DRV-WBAUX2-5-D001 MCN MANU CND MCND ASM FGSG09-DRV-WBAUX2-3-AST
N CED <FGSG09-DRV-WBAUX2-5> D S
MCN AUX-2 6CORNER WINDBOX LCN DAUT DAU CED
D DAMPER DRV ABN D T STB AUX-2 3,4,5,6CORNER WINDBOX
DAB FGSG09-DRV-WBAUX2-6-D001 Y DAMPER STANDBY MODE
O <FGSG09-DRV-WBAUX2-6> FGSG09-DRV-WBAUX2-3-ST
RSA RB SIG ABN INIT MANU
INIT INITIALIZE MAN
CED B CEA <FGSG09-DRV-WBAUX2-4>
6 FCB/RUNBACK OPERATE RBK DEM
AUX-2 3,4,5,6CORNER WINDBOX <FGSG09-DRV-WBAUX2-5> 6
DAMPER CONTROL DEMAND <FGSG09-DRV-WBAUX2-6>
APC-EMG-10-D001 <APC-EMG-10> DRD RB SIG DEV H FGSG09-DRV-WBAUX2-3-A002 <FGSG09-WBCAUX2-01>
H
CED
AUX-2 3,4,5,6CORNER WINDBOX <FGSG09-DRV-WBAUX2-4>
RPB <FGSG09-DRV-WBAUX2-5>
DAMPER RESET PB ON
FGSG09-DRV-WBAUX2-3-D001 <FGSG09-DRV-WBAUX2-6>

TITLE AUX-2 3CORNER WINDBOX DAMPER Rev.


REMARKS

2
SHEET NO.
MITSUBISHI FGSG09-DRV-
HEAVY INDUSTRIES, LTD WBAUX2-3
A B C D E F G H I

AI
AUX-2 4CORNER WINDBOX POS
DAMPER POSITION DEMAND1 RB I A1

01HLA54AA711-XQ01 POS Pin C


0.0 - 100.0% I
DAB DRAB
AUX-2 4CORNER WINDBOX DAMPER
AI FBI FBO CEA O
AUX-2 4CORNER WINDBOX RB1I TRKS AUX-2 4CORNER WINDBOX RSE RSTC OPND D1
1 DAMPER POSITION DEMAND1 RB DAMPER TR SIGNAL T
VDSI 1
FGSG09-DRV-WBAUX2-4-TR <FGSG09-WBC-COMMON-02> CLSD D3
01HLA54AA711-YQ01RB
0.0 - 100.0% RBSO MID D2
RB

AUX-2 4CORNER WINDBOX DAMPER


AI
AUX-2 4CORNER WINDBOX RB2I FQAB FSA
DAMPER POSITION DEMAND2 RB B

01HLA54AA711-YQ02RB
0.0 - 100.0% DFDH DFD
H PVC-1
Ain Aout A1
RB 999.9uu
PVC
RQAB RSA Cout A2
2 B
AUX-2 4CORNER WINDBOX DAMPER RB 2
DRDH DRD
H

FSA X
B A
AUX-2 4CORNER WINDBOX DAMPER FB SIG ABN
CEA AO RSA X
AUX-2 3,4,5,6CORNER WINDBOX DEM
DRIP
AO AUX-2 4CORNER WINDBOX B A
DAMPER CONTROL DEMAND DAMPER POSN DEM1
AUX-2 4CORNER WINDBOX DAMPER RB SIG ABN
FGSG09-DRV-WBAUX2-3-A002
01HLA54AA711-YQ01 DFD X
<FGSG09-DRV-WBAUX2-3> DRIP
DEM_X1in=-10.0
0.0 - 100.0% H A
3 DEM_Y1out=110.0
AO
AUX-2 4CORNER WINDBOX DAMPER FB DEV HI 3
DEM_X2in=110.0
AUX-2 4CORNER WINDBOX DRD X
DEM_Y2out=-10.0
RB_X1in=-10.0
DAMPER POSN DEM2 H A
RB_Y1out=-10.0 AUX-2 4CORNER WINDBOX DAMPER RB DEV HI
01HLA54AA711-YQ02
RB_X2in=110.0 0.0 - 100.0%
RB_Y2out=110.0
ALLRST
RB_CHG=0 RPB
RB_TRK=0
FB_TRK=0
DEM_FB=0 LARP RSE
12DV=10.0 T
ARDV=10.0
ONT1=10.0 CED
DFDV=10.0 AUX-2 4CORNER WINDBOX
ONT2=60.0 DAMPER DRV ABN
4 FGSG09-DRV-WBAUX2-4-D001
4
<FGSG09-DRV-WBAUX2-3>
DABO DAB
O

LCN DABCND
D
INIT FDHEX

INIT

RBK

5 5

CED
RSA RB SIG ABN
FG INITIALIZING INIT
B
FG INITIALIZING LCN
D
DRD RB SIG DEV H
CED H
FCB/RUNBACK OPERATE RBK
APC-EMG-10-D001 <APC-EMG-10>

6 CED 6
AUX-2 3,4,5,6CORNER WINDBOX
RPB
DAMPER RESET PB ON
FGSG09-DRV-WBAUX2-3-D001
<FGSG09-DRV-WBAUX2-3>

TITLE AUX-2 4CORNER WINDBOX DAMPER Rev.


REMARKS

2
SHEET NO.
MITSUBISHI FGSG09-DRV-
HEAVY INDUSTRIES, LTD WBAUX2-4
A B C D E F G H I

AI
AUX-2 5CORNER WINDBOX POS
DAMPER POSITION DEMAND1 RB I A1

01HLA55AA711-XQ01 POS Pin C


0.0 - 100.0% I
DAB DRAB
AUX-2 5CORNER WINDBOX DAMPER
AI FBI FBO CEA O
AUX-2 5CORNER WINDBOX RB1I TRKS AUX-2 5CORNER WINDBOX RSE RSTC OPND D1
1 DAMPER POSITION DEMAND1 RB DAMPER TR SIGNAL T
VDSI 1
FGSG09-DRV-WBAUX2-5-TR <FGSG09-WBC-COMMON-02> CLSD D3
01HLA55AA711-YQ01RB
0.0 - 100.0% RBSO MID D2
RB

AUX-2 5CORNER WINDBOX DAMPER


AI
AUX-2 5CORNER WINDBOX RB2I FQAB FSA
DAMPER POSITION DEMAND2 RB B

01HLA55AA711-YQ02RB
0.0 - 100.0% DFDH DFD
H PVC-1
Ain Aout A1
RB 999.9uu
PVC
RQAB RSA Cout A2
2 B
AUX-2 5CORNER WINDBOX DAMPER RB 2
DRDH DRD
H

FSA X
B A
AUX-2 5CORNER WINDBOX DAMPER FB SIG ABN
CEA AO RSA X
AUX-2 3,4,5,6CORNER WINDBOX DEM
DRIP
AO AUX-2 5CORNER WINDBOX B A
DAMPER CONTROL DEMAND DAMPER POSN DEM1
AUX-2 5CORNER WINDBOX DAMPER RB SIG ABN
FGSG09-DRV-WBAUX2-3-A002
01HLA55AA711-YQ01 DFD X
<FGSG09-DRV-WBAUX2-3> DRIP
DEM_X1in=-10.0
0.0 - 100.0% H A
3 DEM_Y1out=110.0
AO
AUX-2 5CORNER WINDBOX DAMPER FB DEV HI 3
DEM_X2in=110.0
AUX-2 5CORNER WINDBOX DRD X
DEM_Y2out=-10.0
RB_X1in=-10.0
DAMPER POSN DEM2 H A
RB_Y1out=-10.0 AUX-2 5CORNER WINDBOX DAMPER RB DEV HI
01HLA55AA711-YQ02
RB_X2in=110.0 0.0 - 100.0%
RB_Y2out=110.0
ALLRST
RB_CHG=0 RPB
RB_TRK=0
FB_TRK=0
DEM_FB=0 LARP RSE
12DV=10.0 T
ARDV=10.0
ONT1=10.0 CED
DFDV=10.0 AUX-2 5CORNER WINDBOX
ONT2=60.0 DAMPER DRV ABN
4 FGSG09-DRV-WBAUX2-5-D001
4
<FGSG09-DRV-WBAUX2-3>
DABO DAB
O

LCN DABCND
D
INIT FDHEX

INIT

RBK

5 5

CED
RSA RB SIG ABN
FG INITIALIZING INIT
B
FG INITIALIZING LCN
D
DRD RB SIG DEV H
CED H
FCB/RUNBACK OPERATE RBK
APC-EMG-10-D001 <APC-EMG-10>

6 CED 6
AUX-2 3,4,5,6CORNER WINDBOX
RPB
DAMPER RESET PB ON
FGSG09-DRV-WBAUX2-3-D001
<FGSG09-DRV-WBAUX2-3>

TITLE AUX-2 5CORNER WINDBOX DAMPER Rev.


REMARKS

2
SHEET NO.
MITSUBISHI FGSG09-DRV-
HEAVY INDUSTRIES, LTD WBAUX2-5
A B C D E F G H I

AI
AUX-2 6CORNER WINDBOX POS
DAMPER POSITION DEMAND1 RB I A1

01HLA56AA711-XQ01 POS Pin C


0.0 - 100.0% I
DAB DRAB
AUX-2 6CORNER WINDBOX DAMPER
AI FBI FBO CEA O
AUX-2 6CORNER WINDBOX RB1I TRKS AUX-2 6CORNER WINDBOX RSE RSTC OPND D1
1 DAMPER POSITION DEMAND1 RB DAMPER TR SIGNAL T
VDSI 1
FGSG09-DRV-WBAUX2-6-TR CLSD D3
01HLA56AA711-YQ01RB
0.0 - 100.0% <FGSG09-WBC-COMMON-02>
RBSO MID D2
RB

AUX-2 6CORNER WINDBOX DAMPER


AI
AUX-2 6CORNER WINDBOX RB2I FQAB FSA
DAMPER POSITION DEMAND2 RB B

01HLA56AA711-YQ02RB
0.0 - 100.0% DFDH DFD
H PVC-1
Ain Aout A1
RB 999.9uu
PVC
RQAB RSA Cout A2
2 B
AUX-2 6CORNER WINDBOX DAMPER RB 2
DRDH DRD
H

FSA X
B A
AUX-2 6CORNER WINDBOX DAMPER FB SIG ABN
CEA AO RSA X
AUX-2 3,4,5,6CORNER WINDBOX DEM
DRIP
AO AUX-2 6CORNER WINDBOX B A
DAMPER CONTROL DEMAND DAMPER POSN DEM1
AUX-2 6CORNER WINDBOX DAMPER RB SIG ABN
FGSG09-DRV-WBAUX2-3-A002
01HLA56AA711-YQ01 DFD X
<FGSG09-DRV-WBAUX2-3> DRIP
DEM_X1in=-10.0
0.0 - 100.0% H A
3 DEM_Y1out=110.0
AO
AUX-2 6CORNER WINDBOX DAMPER FB DEV HI 3
DEM_X2in=110.0
AUX-2 6CORNER WINDBOX DRD X
DEM_Y2out=-10.0
RB_X1in=-10.0
DAMPER POSN DEM2 H A
RB_Y1out=-10.0 AUX-2 6CORNER WINDBOX DAMPER RB DEV HI
01HLA56AA711-YQ02
RB_X2in=110.0 0.0 - 100.0%
RB_Y2out=110.0
ALLRST
RB_CHG=0 RPB
RB_TRK=0
FB_TRK=0
DEM_FB=0 LARP RSE
12DV=10.0 T
ARDV=10.0
ONT1=10.0 CED
DFDV=10.0 AUX-2 6CORNER WINDBOX
ONT2=60.0 DAMPER DRV ABN
4 FGSG09-DRV-WBAUX2-6-D001
4
<FGSG09-DRV-WBAUX2-3>
DABO DAB
O

LCN DABCND
D
INIT FDHEX

INIT

RBK

5 5

CED
RSA RB SIG ABN
FG INITIALIZING INIT
B
FG INITIALIZING LCN
D
DRD RB SIG DEV H
CED H
FCB/RUNBACK OPERATE RBK
APC-EMG-10-D001 <APC-EMG-10>

CED
6 AUX-2 3,4,5,6CORNER WINDBOX 6
RPB
DAMPER RESET PB ON
FGSG09-DRV-WBAUX2-3-D001
<FGSG09-DRV-WBAUX2-3>

TITLE AUX-2 6CORNER WINDBOX DAMPER Rev.


REMARKS

2
SHEET NO.
MITSUBISHI FGSG09-DRV-
HEAVY INDUSTRIES, LTD WBAUX2-6
A B C D E F G H I

1 1

2 2

3 3

4 4

5 5

OFF D

6 6
REMARKS
A B C D E F G H I
CEA
AA DAMPER BIAS (LH+/RH-)
FGSG09-WBCAA-BIAS-A001<FGSG09-WBCAA-BIAS>

CEA
AA BIR SIGNAL

1 APC-BIR-AAUP-A001 <APC-BIR-AAUP> 1

CEA
AA DAMPER 1/2/7/8CORNER
CEA FX-1 * PROGRAM DEMAND
FGSG09-WBCAA-LHS-A005 <FGSG09-DRV-WBAA-1>
LOAD INDEX FX
<FGSG09-DRV-WBAA-2>
APC-BID-04-A001 <APC-BID-04> <FGSG09-DRV-WBAA-7>
<FGSG09-DRV-WBAA-8>
<FGSG09-WBCAA-BIAS>
FX-2 *
FX
2 2

FX-3 * 0% CEA
AA 1CORNER WINDBOX DAMPER
FX TR SIGNAL
RI=3.0 FGSG09-DRV-WBAA-1-TR
RD=3.0 <FGSG09-DRV-WBAA-1>
FX-4 * on on on on off CEA
off off off off X
FX TR TR TR TR V + + on
TR
AA DAMPER 1CORNER CONTROL
DEMAND
swRon=10.0 swRon=10.0 sw swRon=10.0 TP sw FGSG09-WBCAA-LHS-A001 <FGSG09-DRV-WBAA-1>
Roff=10.0 Roff=10.0 Ron=200.0 Roff=10.0 Ron=5.0
MD=0 MD=0 Roff=99999.0 MD=0 Roff=99999.0
1AT
CED MD=0
3 MD=0 3
WORST (COAL-1) SEL
APC-CMS-06-D001 <APC-CMS-06>
CEA
AA 2CORNER WINDBOX DAMPER
CED TR SIGNAL
BEST (COAL-3) SEL FGSG09-DRV-WBAA-2-TR
<FGSG09-DRV-WBAA-2>
APC-CMS-06-D003 <APC-CMS-06>
off CEA
on AA DAMPER 2CORNER CONTROL
CED TR DEMAND
ALL FUEL OIL BURNER VALVES sw FGSG09-WBCAA-LHS-A002 <FGSG09-DRV-WBAA-2>
CLOSED Ron=5.0
FGSG05-6-6-D01 <BMS1-5-6> 2AT Roff=99999.0
4 MD=0
4
CED
WINDBOX BANKING COMMAND
CEA
APC-ADC-15-D002 <APC-ADC-15> AA 7CORNER WINDBOX DAMPER
CED TR SIGNAL
AA 1CORNER WINDBOX DAMPER FGSG09-DRV-WBAA-7-TR
STANDBY MODE
<FGSG09-DRV-WBAA-7>
FGSG09-DRV-WBAA-1-ST <FGSG09-DRV-WBAA-1>
CED off CEA
AA 2CORNER WINDBOX DAMPER on AA DAMPER 7CORNER CONTROL
STANDBY MODE
TR DEMAND
FGSG09-DRV-WBAA-2-ST <FGSG09-DRV-WBAA-2> sw FGSG09-WBCAA-LHS-A003 <FGSG09-DRV-WBAA-7>
CED Ron=5.0
AA 7CORNER WINDBOX DAMPER Roff=99999.0
7AT
STANDBY MODE MD=0
5 FGSG09-DRV-WBAA-7-ST <FGSG09-DRV-WBAA-7> 5
CED
AA 8CORNER WINDBOX DAMPER
STANDBY MODE CEA
FGSG09-DRV-WBAA-8-ST <FGSG09-DRV-WBAA-8> AA 8CORNER WINDBOX DAMPER
TR SIGNAL
1AT
CED FGSG09-DRV-WBAA-8-TR
AA 1CORNER WINDBOX DAMPER
<FGSG09-DRV-WBAA-8>
AUTO or STANDBY
FGSG09-DRV-WBAA-1-AST <FGSG09-DRV-WBAA-1> off CEA
2AT
CED on AA DAMPER 8CORNER CONTROL
AA 2CORNER WINDBOX DAMPER
TR DEMAND
AUTO or STANDBY CED sw FGSG09-WBCAA-LHS-A004 <FGSG09-DRV-WBAA-8>
FGSG09-DRV-WBAA-2-AST <FGSG09-DRV-WBAA-2> AA 1,2,7,8 ANY CORNER Ron=5.0
7AT
CED WINDBOX DAMPER AUTO Roff=99999.0
8AT
AA 7CORNER WINDBOX DAMPER FGSG09-WBCAA-LHS-D001 <FGSG09-WBCAA-BIAS> MD=0
6 AUTO or STANDBY 6
FGSG09-DRV-WBAA-7-AST <FGSG09-DRV-WBAA-7> 8AT
CED
AA 8CORNER WINDBOX DAMPER
AUTO or STANDBY
FGSG09-DRV-WBAA-8-AST <FGSG09-DRV-WBAA-8>

FX-1 * FX-2 * FX-3 * FX-4 *


X1=0.0,Y1=20.0 X1=0.0,Y1=20.0 X1=0.0,Y1=20.0 X1=0.0,Y1=20.0
X2=198.0,Y2=45.0 X2=198.0,Y2=45.0 X2=198.0,Y2=45.0 X2=198.0,Y2=45.0 TITLE AA DAMPER 1,2,7,8CORNER CONTROL Rev.
X3=264.0,Y3=55.0 X3=264.0,Y3=55.0 X3=264.0,Y3=55.0 X3=264.0,Y3=55.0
REMARKS

X4=330.0,Y4=70.0 X4=330.0,Y4=70.0 X4=330.0,Y4=70.0 X4=330.0,Y4=70.0 2


X5=396.0,Y5=70.0 X5=396.0,Y5=70.0 X5=396.0,Y5=70.0 X5=396.0,Y5=70.0
X6=528.0,Y6=70.0 X6=528.0,Y6=70.0 X6=528.0,Y6=70.0 X6=528.0,Y6=70.0 SHEET NO.
X7=660.0,Y7=70.0 X7=660.0,Y7=70.0 X7=660.0,Y7=70.0 X7=660.0,Y7=70.0
* TO BE FINALIZED DURING COMMISSIONING FGSG09-WBCAA-
X8=693.0,Y8=70.0
X9=700.0,Y9=70.0
X8=693.0,Y8=70.0
X9=700.0,Y9=70.0
X8=693.0,Y8=70.0
X9=700.0,Y9=70.0
X8=693.0,Y8=70.0
X9=700.0,Y9=70.0
MITSUBISHI LHS
X10=0.0,Y10=0.0 X10=0.0,Y10=0.0 X10=0.0,Y10=0.0 X10=0.0,Y10=0.0 HEAVY INDUSTRIES, LTD
A B C D E F G H I
CEA
AA DAMPER BIAS (LH+/RH-)
FGSG09-WBCAA-BIAS-A001<FGSG09-WBCAA-BIAS>

CEA
AA BIR SIGNAL

1 APC-BIR-AAUP-A001 <APC-BIR-AAUP> 1

CEA
AA DAMPER 3/4/5/6CORNER
CEA FX-1 * PROGRAM DEMAND
FGSG09-WBCAA-RHS-A005 <FGSG09-DRV-WBAA-3>
LOAD INDEX FX
<FGSG09-DRV-WBAA-4>
APC-BID-04-A001 <APC-BID-04> <FGSG09-DRV-WBAA-5>
<FGSG09-DRV-WBAA-6>
<FGSG09-WBCAA-BIAS>
FX-2 *
FX
2 2

FX-3 * 0% CEA
AA 3CORNER WINDBOX DAMPER
FX TR SIGNAL
RI=3.0 FGSG09-DRV-WBAA-3-TR
RD=3.0 <FGSG09-DRV-WBAA-3>
FX-4 * on on on on - off CEA
off off off off X
FX TR TR TR TR V + + on
TR
AA DAMPER 3CORNER CONTROL
DEMAND
swRon=10.0 swRon=10.0 sw swRon=10.0 TP sw FGSG09-WBCAA-RHS-A001 <FGSG09-DRV-WBAA-3>
Roff=10.0 Roff=10.0 Ron=200.0 Roff=10.0 Ron=5.0
MD=0 MD=0 Roff=99999.0 MD=0 Roff=99999.0
3AT
CED MD=0
3 MD=0 3
WORST (COAL-1) SEL
APC-CMS-06-D001 <APC-CMS-06>
CEA
AA 4CORNER WINDBOX DAMPER
CED TR SIGNAL
BEST (COAL-3) SEL FGSG09-DRV-WBAA-4-TR
<FGSG09-DRV-WBAA-4>
APC-CMS-06-D003 <APC-CMS-06>
off CEA
on AA DAMPER 4CORNER CONTROL
CED TR DEMAND
ALL FUEL OIL BURNER VALVES sw FGSG09-WBCAA-RHS-A002 <FGSG09-DRV-WBAA-4>
CLOSED Ron=5.0
FGSG05-6-6-D01 <BMS1-5-6> 4AT Roff=99999.0
4 MD=0
4
CED
WINDBOX BANKING COMMAND
CEA
APC-ADC-15-D002 <APC-ADC-15> AA 5CORNER WINDBOX DAMPER
CED TR SIGNAL
AA 3CORNER WINDBOX DAMPER FGSG09-DRV-WBAA-5-TR
STANDBY MODE
<FGSG09-DRV-WBAA-5>
FGSG09-DRV-WBAA-3-ST <FGSG09-DRV-WBAA-3>
CED off CEA
AA 4CORNER WINDBOX DAMPER on AA DAMPER 5CORNER CONTROL
STANDBY MODE
TR DEMAND
FGSG09-DRV-WBAA-4-ST <FGSG09-DRV-WBAA-4> sw FGSG09-WBCAA-RHS-A003 <FGSG09-DRV-WBAA-5>
CED Ron=5.0
AA 5CORNER WINDBOX DAMPER Roff=99999.0
5AT
STANDBY MODE MD=0
5 FGSG09-DRV-WBAA-5-ST <FGSG09-DRV-WBAA-5> 5
CED
AA 6CORNER WINDBOX DAMPER
STANDBY MODE CEA
FGSG09-DRV-WBAA-6-ST <FGSG09-DRV-WBAA-6> AA 6CORNER WINDBOX DAMPER
TR SIGNAL
3AT
CED FGSG09-DRV-WBAA-6-TR
AA 3CORNER WINDBOX DAMPER
<FGSG09-DRV-WBAA-6>
AUTO or STANDBY
FGSG09-DRV-WBAA-3-AST <FGSG09-DRV-WBAA-3> off CEA
4AT
CED on AA DAMPER 6CORNER CONTROL
AA 4CORNER WINDBOX DAMPER
TR DEMAND
AUTO or STANDBY CED sw FGSG09-WBCAA-RHS-A004 <FGSG09-DRV-WBAA-6>
FGSG09-DRV-WBAA-4-AST <FGSG09-DRV-WBAA-4> AA 3,4,5,6 ANY CORNER Ron=5.0
5AT
CED WINDBOX DAMPER AUTO Roff=99999.0
6AT
AA 5CORNER WINDBOX DAMPER FGSG09-WBCAA-RHS-D001 <FGSG09-WBCAA-BIAS> MD=0
6 AUTO or STANDBY 6
FGSG09-DRV-WBAA-5-AST <FGSG09-DRV-WBAA-5> 6AT
CED
AA 6CORNER WINDBOX DAMPER
AUTO or STANDBY
FGSG09-DRV-WBAA-6-AST <FGSG09-DRV-WBAA-6>

FX-1 * FX-2 * FX-3 * FX-4 *


X1=0.0,Y1=20.0 X1=0.0,Y1=20.0 X1=0.0,Y1=20.0 X1=0.0,Y1=20.0
X2=198.0,Y2=45.0 X2=198.0,Y2=45.0 X2=198.0,Y2=45.0 X2=198.0,Y2=45.0 TITLE AA DAMPER 3,4,5,6CORNER CONTROL Rev.
X3=264.0,Y3=55.0 X3=264.0,Y3=55.0 X3=264.0,Y3=55.0 X3=264.0,Y3=55.0
REMARKS

X4=330.0,Y4=70.0 X4=330.0,Y4=70.0 X4=330.0,Y4=70.0 X4=330.0,Y4=70.0 2


X5=396.0,Y5=70.0 X5=396.0,Y5=70.0 X5=396.0,Y5=70.0 X5=396.0,Y5=70.0
X6=528.0,Y6=70.0 X6=528.0,Y6=70.0 X6=528.0,Y6=70.0 X6=528.0,Y6=70.0 SHEET NO.
X7=660.0,Y7=70.0 X7=660.0,Y7=70.0 X7=660.0,Y7=70.0 X7=660.0,Y7=70.0
* TO BE FINALIZED DURING COMMISSIONING FGSG09-WBCAA-
X8=693.0,Y8=70.0
X9=700.0,Y9=70.0
X8=693.0,Y8=70.0
X9=700.0,Y9=70.0
X8=693.0,Y8=70.0
X9=700.0,Y9=70.0
X8=693.0,Y8=70.0
X9=700.0,Y9=70.0
MITSUBISHI RHS
X10=0.0,Y10=0.0 X10=0.0,Y10=0.0 X10=0.0,Y10=0.0 X10=0.0,Y10=0.0 HEAVY INDUSTRIES, LTD
A B C D E F G H I

WBCAA-1-BS01

SV
PV

S-PB-9-Set
PB APB
1 1
SV-I-PRH
SIP1
SDP SV-D-PRH
1 S-PB-10-Set
AUT S-PB-8
PB MPB
O A1
999.9uu
STB S-PB-9
Y SV-Set AA DMPR (RIGHT) BIAS
S-PB-10
MAN <WIND BOX-2>
INIT IPRH A1
AA DAMPER BIAS (LH+/RH-) INIT SIP1 999.9uu
on
<WIND BOX-1> TLT sw off ULMT DPRH SDP AA DAMPER (LEFT) BIAS
<WIND BOX-2> A T 0% MUL SIP
1
PV <WIND BOX-1>
LLMT
MLL SDP OPMT
2 RI=10.0 RI=100.0 2
RD=10.0 S OH OL RD=100.0
CEA off CEA
- X X
ECO OUTLET GAS O2 -LHS
L
D/A + + X
V
on
T
X
S/S
Y Ain Aout X
V AA DAMPER BIAS (LH+/RH-)
APC-MSS-ECOOUTO2-LHS-A001 + L=-99999.0 S=0.0 TP sw sw OPP OPC TP FGSG09-WBCAA-BIAS-A001 <FGSG09-WBCAA-LHS>
OH=50
<APC-MSS-ECOOUTO2-B> DB=0.0 OL=-50 <FGSG09-WBCAA-RHS>
CEA X X
D/A
ECO OUTLET GAS O2 -RHS
L
L=-99999.0 S=0.0 MAN
APC-MSS-ECOOUTO2-RHS-A001 DB=0.0 AUT X Y
<APC-MSS-ECOOUTO2-A> O
MAN
X X T=1.0
D/A
L
L=-99999.0 S=0.0
3 DB=0.0 3
X X
D/A
L
L=-99999.0 S=0.0
DB=0.0

X X
H
D/A +
H=99999.0 S=0.0
DB=0.0

X X
D/A
H
H=99999.0 S=0.0
DB=0.0
4 X X 4
D/A
H
H=99999.0 S=0.0
DB=0.0
TLT
X X CED A
D/A
H AA 1,2,7,8 ANY CORNER
H=99999.0 S=0.0 WINDBOX DAMPER AUTO
DB=0.0 FGSG09-WBCAA-LHS-D001 <FGSG09-WBCAA-LHS> ACND CAUT AUT
CED O
AA 3,4,5,6 ANY CORNER
MUL
WINDBOX DAMPER AUTO
FGSG09-WBCAA-RHS-D001<FGSG09-WBCAA-RHS>
CEA
AA DAMPER 1/2/7/8CORNER X
PROGRAM DEMAND H SIP
5 FGSG09-WBCAA-LHS-A005 H=99.9 ATPB CSTB STB 5
APB
CEA <FGSG09-WBCAA-LHS> ASM Y
AA DAMPER 3/4/5/6CORNER X S
PROGRAM DEMAND L CED
FGSG09-WBCAA-RHS-A005 L=10.1 ECO OUTLET O2 ANALYZER -LHS MNPB
MPB
<FGSG09-WBCAA-RHS> ABN
MLL APC-MSS-ECOOUTO2-LHS-D001
CED <APC-MSS-ECOOUTO2-B>
ECO OUTLET O2 ANALYZER -RHS MCND MANU
MAN
ABN
X APC-MSS-ECOOUTO2-RHS-D001
H SDP
CED <APC-MSS-ECOOUTO2-A>
H=99.9 FG INITIALIZING
X FG INITIALIZING
L
6 L=10.1 INIT
6

TITLE Rev.
AA DAMPER BIAS LOGIC
2
REMARKS

SHEET NO.

MITSUBISHI FGSG09-
HEAVY INDUSTRIES, LTD WBCAA-BIAS
A B C D E F G H I

AI
AA 1CORNER DAMPER POSITION POS
FB I

SV S-PB-3-Set 01HLA51AA791-XQ01 POS Pin


SV SV 01HLA51AA791 PB RPB 0.0 - 100.0% TRK
I
MV S-PB-8-Set
PB APB
AI FBI FBO CEA
V3 S-PB-10-Set AA 1CORNER DAMPER POSITION RB1I TRKS AA 1CORNER WINDBOX DAMPER OPND D1
TRK TRACKING SIG PB MPB
1 DEMAND1 RB TR SIGNAL
VDSI 1
DAB DRIVE ABN S-PB-2 FGSG09-DRV-WBAA-1-TR <FGSG09-WBCAA-LHS> CLSD D3
O 01HLA51AA791-YQ01RB
RSE RESET COND S-PB-3 0.0 - 100.0% RBSO MID D2
RB
T
SAB SIG ABN S-PB-4
AA 1CORNER WINDBOX DAMPER
N AI
CAU CONTROL AUTO S-PB-8 AA 1CORNER DAMPER POSITION RB2I FQAB FSA
T DEMAND2 RB B
STB STAND BY MODE S-PB-9 MV-I-PRH
Y MV-D-PRH 01HLA51AA791-YQ02RB CAU D1
S-PB-10 MV-Set 0.0 - 100.0% DFDH DFD T
MAN MANUAL MODE
H STB D2
Y
AA 1CORNER WINDBOX DAMPER D3
<WIND BOX-1> MAN
RQAB RSA
2 B
AA(L) 1CORNER WINDBOX DAMPER AUTO/MANUAL 2
<WIND BOX-1>
CED DRDH DRD
DPRH IPRH H
FG INITIALIZING INIT
ULMT Ain Aout A1
RB 999.9uu
FG INITIALIZING PVC
LLMT DRVM FMA Cout A2
N
OPMT
AA 1CORNER WINDBOX DAMPER RB
CEA S OH OL AO
AA DAMPER 1CORNER CONTROL X Y Ain Aout DEM AO AA 1CORNER DAMPER POSITION <WIND BOX-1>
S/S DRIP
DEMAND DEMAND1
FGSG09-WBCAA-LHS-A001 <FGSG09-WBCAA-LHS> L sw OPP
OPC INIT 01HLA51AA791-YQ01
0.0 - 100.0% FSA X
3 B A 3
CEA AO
AA 1CORNER WINDBOX DAMPER FB SIG ABN
AA DAMPER 1/2/7/8CORNER MANUAL MODE AA 1CORNER DAMPER POSITION
SV MAN
PROGRAM DEMAND DEMAND2 DFD X
FGSG09-WBCAA-LHS-A005 <FGSG09-WBCAA-LHS> INIT
INITIALIZE H A
01HLA51AA791-YQ02
0.0 - 100.0% AA 1CORNER WINDBOX DAMPER FB DEV HI
ALLRST RSA X
RPB
B A
STB sw on
Y
TR SG AA 1CORNER WINDBOX DAMPER RB SIG ABN
DEM_X1in=-10.0
off S=0.0 MANU LARP RSE DRD X
MAN DEM_Y1out=-10.0
T
DEM_X2in=110.0
H A
SG DEM_Y2out=110.0 AA 1CORNER WINDBOX DAMPER RB DEV HI
S=10.0 RB_X1in=-10.0
SAB SABCND FMA X
RB_Y1out=-10.0
CED N N A
4 ACN
RB_X2in=110.0 4
WINDBOX BANKING COMMAND RB_Y2out=110.0 AA 1CORNER WINDBOX DAMPER FORCED MANUAL
D
RB_CHG=0
APC-ADC-15-D002 <APC-ADC-15> DABO DAB X
RB_TRK=0 MAN
O E
FB_TRK=0
DEM_FB=0 AA 1CORNER WINDBOX DAMPER MANUAL MODE
LCN DABCND 12DV=10.0 CAU X
D ARDV=10.0 T E
INIT FDHEX ONT1=10.0
DFDV=10.0 AA 1CORNER WINDBOX DAMPER AUTO MODE
ONT2=60.0 STB X
INIT
Y E
AA 1CORNER WINDBOX DAMPER STANDBY MODE
RBK

5 5
CED
ATPB CAUTX Y CAU CAU AA 1CORNER WINDBOX DAMPER
APB AUTO PB
SAB T T AUTO MODE
N MNPB
MPB MANUAL PB T=0.0 FGSG09-DRV-WBAA-1-AT
CED
ACN AUT CND ACND CSTB STB CED
BID SIGNAL ABNORMAL
RSA RB SIG ABN D Y DAU AA 1CORNER WINDBOX DAMPER
APC-BID-01-D004 <APC-BID-01> MCN B MCN MANU CND MCND ASM T AUTO or STANDBY
D LCN D S FGSG09-DRV-WBAA-1-AST <FGSG09-WBCAA-LHS>
DAB D DAUT DAU
O DRD RB SIG DEV H T CED
H STB AA 1CORNER WINDBOX DAMPER
CED Y STANDBY MODE
INIT MANU
FCB/RUNBACK OPERATE RBK INIT INITIALIZE MAN FGSG09-DRV-WBAA-1-ST <FGSG09-WBCAA-LHS>
6 APC-EMG-10-D001 <APC-EMG-10>
6

TITLE AA 1CORNER WINDBOX DAMPER Rev.


REMARKS

2
SHEET NO.
MITSUBISHI FGSG09-DRV-
HEAVY INDUSTRIES, LTD WBAA-1
A B C D E F G H I

AI
AA 2CORNER DAMPER POSITION POS
FB I

SV S-PB-3-Set 01HLA52AA791-XQ01 POS Pin


SV SV 01HLA52AA791 PB RPB 0.0 - 100.0% TRK
I
MV S-PB-8-Set
PB APB
AI FBI FBO CEA
V3 S-PB-10-Set AA 2CORNER DAMPER POSITION RB1I TRKS AA 2CORNER WINDBOX DAMPER OPND D1
TRK TRACKING SIG PB MPB
1 DEMAND1 RB TR SIGNAL
VDSI 1
DAB DRIVE ABN S-PB-2 FGSG09-DRV-WBAA-2-TR <FGSG09-WBCAA-LHS> CLSD D3
O 01HLA52AA791-YQ01RB
RSE RESET COND S-PB-3 0.0 - 100.0% RBSO MID D2
RB
T
SAB SIG ABN S-PB-4
AA 2CORNER WINDBOX DAMPER
N AI
CAU CONTROL AUTO S-PB-8 AA 2CORNER DAMPER POSITION RB2I FQAB FSA
T DEMAND2 RB B
STB STAND BY MODE S-PB-9 MV-I-PRH
Y MV-D-PRH 01HLA52AA791-YQ02RB CAU D1
S-PB-10 MV-Set 0.0 - 100.0% DFDH DFD T
MAN MANUAL MODE
H STB D2
Y
AA 2CORNER WINDBOX DAMPER D3
<WIND BOX-1> MAN
RQAB RSA
2 B
AA(L) 2CORNER WINDBOX DAMPER AUTO/MANUAL 2
<WIND BOX-1>
CED DRDH DRD
DPRH IPRH H
FG INITIALIZING INIT
ULMT Ain Aout A1
RB 999.9uu
FG INITIALIZING PVC
LLMT DRVM FMA Cout A2
N
OPMT
AA 2CORNER WINDBOX DAMPER RB
CEA S OH OL AO
AA DAMPER 2CORNER CONTROL X Y Ain Aout DEM AO AA 2CORNER DAMPER POSITION <WIND BOX-1>
S/S DRIP
DEMAND DEMAND1
FGSG09-WBCAA-LHS-A002 <FGSG09-WBCAA-LHS> L sw OPP
OPC INIT 01HLA52AA791-YQ01
0.0 - 100.0% FSA X
3 B A 3
CEA AO
AA 2CORNER WINDBOX DAMPER FB SIG ABN
AA DAMPER 1/2/7/8CORNER MANUAL MODE AA 2CORNER DAMPER POSITION
SV MAN
PROGRAM DEMAND DEMAND2 DFD X
FGSG09-WBCAA-LHS-A005 <FGSG09-WBCAA-LHS> INIT
INITIALIZE H A
01HLA52AA791-YQ02
0.0 - 100.0% AA 2CORNER WINDBOX DAMPER FB DEV HI
ALLRST RSA X
RPB
B A
STB sw on DEM_X1in=-10.0
Y
TR SG AA 2CORNER WINDBOX DAMPER RB SIG ABN
DEM_Y1out=-10.0
off S=0.0 MANU LARP RSE DRD X
MAN DEM_X2in=110.0
T
DEM_Y2out=110.0
H A
SG RB_X1in=-10.0 AA 2CORNER WINDBOX DAMPER RB DEV HI
RB_Y1out=-10.0
S=10.0 SAB SABCND FMA X
RB_X2in=110.0
CED N N A
4 ACN
RB_Y2out=110.0 4
WINDBOX BANKING COMMAND RB_CHG=0 AA 2CORNER WINDBOX DAMPER FORCED MANUAL
D
RB_TRK=0
APC-ADC-15-D002 <APC-ADC-15> DABO DAB X
FB_TRK=0 MAN
O E
DEM_FB=0
12DV=10.0 AA 2CORNER WINDBOX DAMPER MANUAL MODE
LCN DABCND ARDV=10.0 CAU X
D ONT1=10.0 T E
INIT FDHEX DFDV=10.0
ONT2=60.0 AA 2CORNER WINDBOX DAMPER AUTO MODE
STB X
INIT
Y E
AA 2CORNER WINDBOX DAMPER STANDBY MODE
RBK

5 5
CED
ATPB CAUTX Y CAU CAU AA 2CORNER WINDBOX DAMPER
APB AUTO PB
SAB T T AUTO
N MNPB
MPB MANUAL PB T=0.0 FGSG09-DRV-WBAA-2-AT
CED
ACN AUT CND ACND CSTB STB CED
BID SIGNAL ABNORMAL
RSA RB SIG ABN D Y DAU AA 2CORNER WINDBOX DAMPER
APC-BID-01-D004 <APC-BID-01> MCN B MCN MANU CND MCND ASM T AUTO or STANDBY
D LCN D S FGSG09-DRV-WBAA-2-AST <FGSG09-WBCAA-LHS>
DAB D DAUT DAU
O DRD RB SIG DEV H T CED
H STB AA 2CORNER WINDBOX DAMPER
CED Y STANDBY MODE
INIT MANU
FCB/RUNBACK OPERATE RBK INIT INITIALIZE MAN FGSG09-DRV-WBAA-2-ST <FGSG09-WBCAA-LHS>
6 APC-EMG-10-D001 <APC-EMG-10>
6

TITLE AA 2CORNER WINDBOX DAMPER Rev.


REMARKS

2
SHEET NO.
MITSUBISHI FGSG09-DRV-
HEAVY INDUSTRIES, LTD WBAA-2
A B C D E F G H I

AI
AA 7CORNER DAMPER POSITION POS
FB I

SV S-PB-3-Set 01HLA57AA791-XQ01 POS Pin


SV SV 01HLA57AA791 PB RPB 0.0 - 100.0% TRK
I
MV S-PB-8-Set
PB APB
AI FBI FBO CEA
V3 S-PB-10-Set AA 7CORNER DAMPER POSITION RB1I TRKS AA 7CORNER WINDBOX DAMPER OPND D1
TRK TRACKING SIG PB MPB
1 DEMAND1 RB TR SIGNAL
VDSI 1
DAB DRIVE ABN S-PB-2 FGSG09-DRV-WBAA-7-TR <FGSG09-WBCAA-LHS> CLSD D3
O 01HLA57AA791-YQ01RB
RSE RESET COND S-PB-3 0.0 - 100.0% RBSO MID D2
RB
T
SAB SIG ABN S-PB-4
AA 7CORNER WINDBOX DAMPER
N AI
CAU CONTROL AUTO S-PB-8 AA 7CORNER DAMPER POSITION RB2I FQAB FSA
T DEMAND2 RB B
STB STAND BY MODE S-PB-9 MV-I-PRH
Y MV-D-PRH 01HLA57AA791-YQ02RB CAU D1
S-PB-10 MV-Set 0.0 - 100.0% DFDH DFD T
MAN MANUAL MODE
H STB D2
Y
AA 7CORNER WINDBOX DAMPER D3
<WIND BOX-1> MAN
RQAB RSA
2 B
AA(L) 7CORNER WINDBOX DAMPER AUTO/MANUAL 2
<WIND BOX-1>
CED DRDH DRD
DPRH IPRH H
FG INITIALIZING INIT
ULMT Ain Aout A1
RB 999.9uu
FG INITIALIZING PVC
LLMT DRVM FMA Cout A2
N
OPMT
AA 7CORNER WINDBOX DAMPER RB
CEA S OH OL AO
AA DAMPER 7CORNER CONTROL X Y Ain Aout DEM AO AA 7CORNER DAMPER POSITION <WIND BOX-1>
S/S DRIP
DEMAND DEMAND1
FGSG09-WBCAA-LHS-A003 <FGSG09-WBCAA-LHS> L sw OPP
OPC INIT 01HLA57AA791-YQ01
0.0 - 100.0% FSA X
3 B A 3
CEA AO
AA 7CORNER WINDBOX DAMPER FB SIG ABN
AA DAMPER 1/2/7/8CORNER MANUAL MODE AA 7CORNER DAMPER POSITION
SV MAN
PROGRAM DEMAND DEMAND2 DFD X
FGSG09-WBCAA-LHS-A005 <FGSG09-WBCAA-LHS> INIT
INITIALIZE H A
01HLA57AA791-YQ02
0.0 - 100.0% AA 7CORNER WINDBOX DAMPER FB DEV HI
ALLRST RSA X
RPB
B A
DEM_X1in=-10.0 AA 7CORNER WINDBOX DAMPER RB SIG ABN
DEM_Y1out=-10.0
STB sw on MANU LARP RSE DRD X
Y
TR SG MAN
T
DEM_X2in=110.0
H A
DEM_Y2out=110.0
off S=0.0 RB_X1in=-10.0 AA 7CORNER WINDBOX DAMPER RB DEV HI
RB_Y1out=-10.0
SG SAB SABCND FMA X
RB_X2in=110.0
N N A
4 S=10.0 RB_Y2out=110.0 4
RB_CHG=0 AA 7CORNER WINDBOX DAMPER FORCED MANUAL
CED
RB_TRK=0
ACN DABO DAB X
WINDBOX BANKING COMMAND FB_TRK=0 MAN
D O E
DEM_FB=0
APC-ADC-15-D002 <APC-ADC-15> AA 7CORNER WINDBOX DAMPER MANUAL MODE
12DV=10.0
LCN DABCND ARDV=10.0 CAU X
D ONT1=10.0 T E
INIT FDHEX DFDV=10.0
ONT2=60.0 AA 7CORNER WINDBOX DAMPER AUTO MODE
STB X
INIT
Y E
AA 7CORNER WINDBOX DAMPER STANDBY MODE
RBK

5 5
CED
ATPB CAUTX Y CAU CAU AA 7CORNER WINDBOX DAMPER
APB AUTO PB
SAB T T AUTO
N MNPB
MPB MANUAL PB T=0.0 FGSG09-DRV-WBAA-7-AT
CED
ACN AUT CND ACND CSTB STB CED
BID SIGNAL ABNORMAL
RSA RB SIG ABN D Y DAU AA 7CORNER WINDBOX DAMPER
APC-BID-01-D004 <APC-BID-01> MCN B MCN MANU CND MCND ASM T AUTO or STANDBY
D LCN D S FGSG09-DRV-WBAA-7-AST <FGSG09-WBCAA-LHS>
DAB D DAUT DAU
O DRD RB SIG DEV H T CED
H STB AA 7CORNER WINDBOX DAMPER
CED Y STANDBY MODE
INIT MANU
FCB/RUNBACK OPERATE RBK INIT INITIALIZE MAN FGSG09-DRV-WBAA-7-ST <FGSG09-WBCAA-LHS>
6 APC-EMG-10-D001 <APC-EMG-10>
6

TITLE AA 7CORNER WINDBOX DAMPER Rev.


REMARKS

2
SHEET NO.
MITSUBISHI FGSG09-DRV-
HEAVY INDUSTRIES, LTD WBAA-7
A B C D E F G H I

AI
AA 8CORNER DAMPER POSITION POS
FB I

SV S-PB-3-Set 01HLA58AA791-XQ01 POS Pin


SV SV 01HLA58AA791 PB RPB 0.0 - 100.0% TRK
I
MV S-PB-8-Set
PB APB
AI FBI FBO CEA
V3 S-PB-10-Set AA 8CORNER DAMPER POSITION RB1I TRKS AA 8CORNER WINDBOX DAMPER OPND D1
TRK TRACKING SIG PB MPB
1 DEMAND1 RB TR SIGNAL
VDSI 1
DAB DRIVE ABN S-PB-2 FGSG09-DRV-WBAA-8-TR <FGSG09-WBCAA-LHS> CLSD D3
O 01HLA58AA791-YQ01RB
RSE RESET COND S-PB-3 0.0 - 100.0% RBSO MID D2
RB
T
SAB SIG ABN S-PB-4
AA 8CORNER WINDBOX DAMPER
N AI
CAU CONTROL AUTO S-PB-8 AA 8CORNER DAMPER POSITION RB2I FQAB FSA
T DEMAND2 RB B
STB STAND BY MODE S-PB-9 MV-I-PRH
Y MV-D-PRH 01HLA58AA791-YQ02RB CAU D1
S-PB-10 MV-Set 0.0 - 100.0% DFDH DFD T
MAN MANUAL MODE
H STB D2
Y
AA 8CORNER WINDBOX DAMPER D3
<WIND BOX-1> MAN
RQAB RSA
2 B
AA(L) 8CORNER WINDBOX DAMPER AUTO/MANUAL 2
<WIND BOX-1>
CED DRDH DRD
DPRH IPRH H
FG INITIALIZING INIT
ULMT Ain Aout A1
RB 999.9uu
FG INITIALIZING PVC
LLMT DRVM FMA Cout A2
N
OPMT
AA 8CORNER WINDBOX DAMPER RB
CEA S OH OL AO
AA DAMPER 8CORNER CONTROL X Y Ain Aout DEM AO AA 8CORNER DAMPER POSITION <WIND BOX-1>
S/S DRIP
DEMAND DEMAND1
FGSG09-WBCAA-LHS-A004 <FGSG09-WBCAA-LHS> L sw OPP FSA X
OPC INIT 01HLA58AA791-YQ01 B A
0.0 - 100.0%
AA 8CORNER WINDBOX DAMPER FB SIG ABN
3 CEA AO DFD X
3
AA DAMPER 1/2/7/8CORNER
SV MAN
MANUAL MODE AA 8CORNER DAMPER POSITION H A
PROGRAM DEMAND DEMAND2
AA 8CORNER WINDBOX DAMPER FB DEV HI
FGSG09-WBCAA-LHS-A005 <FGSG09-WBCAA-LHS> INITIALIZE
INIT 01HLA58AA791-YQ02 RSA X
0.0 - 100.0% B A
ALLRST
RPB AA 8CORNER WINDBOX DAMPER RB SIG ABN

DEM_X1in=-10.0 DRD X
DEM_Y1out=-10.0 H A
STB sw on MANU LARP RSE
Y
TR SG MAN
T
DEM_X2in=110.0 AA 8CORNER WINDBOX DAMPER RB DEV HI
DEM_Y2out=110.0
off S=0.0 FMA X
RB_X1in=-10.0
RB_Y1out=-10.0
N A
SAB SABCND
SG N
RB_X2in=110.0 AA 8CORNER WINDBOX DAMPER FORCED MANUAL
4 S=10.0
RB_Y2out=110.0
X 4
RB_CHG=0 MAN
CED E
RB_TRK=0
ACN DABO DAB
WINDBOX BANKING COMMAND FB_TRK=0 AA 8CORNER WINDBOX DAMPER MANUAL MODE
D O
DEM_FB=0 CAU X
APC-ADC-15-D002 <APC-ADC-15> 12DV=10.0 T E
LCN DABCND ARDV=10.0
ONT1=10.0 AA 8CORNER WINDBOX DAMPER AUTO MODE
D
INIT FDHEX DFDV=10.0 STB X
ONT2=60.0 Y E
INIT AA 8CORNER WINDBOX DAMPER STANDBY MODE

RBK

5 5
CED
ATPB CAUTX Y CAU CAU AA 8CORNER WINDBOX DAMPER
APB AUTO PB
SAB T T AUTO
N MNPB
MPB MANUAL PB T=0.0 FGSG09-DRV-WBAA-8-AT
CED
ACN AUT CND ACND CSTB STB CED
BID SIGNAL ABNORMAL
RSA RB SIG ABN D Y DAU AA 8CORNER WINDBOX DAMPER
APC-BID-01-D004 <APC-BID-01> MCN B MCN MANU CND MCND ASM T AUTO or STANDBY
D LCN D S FGSG09-DRV-WBAA-8-AST <FGSG09-WBCAA-LHS>
DAB D DAUT DAU
O DRD RB SIG DEV H T CED
H STB AA 8CORNER WINDBOX DAMPER
CED Y STANDBY MODE
INIT MANU
FCB/RUNBACK OPERATE RBK INIT INITIALIZE MAN FGSG09-DRV-WBAA-8-ST <FGSG09-WBCAA-LHS>
6 APC-EMG-10-D001 <APC-EMG-10>
6

TITLE AA 8CORNER WINDBOX DAMPER Rev.


REMARKS

2
SHEET NO.
MITSUBISHI FGSG09-DRV-
HEAVY INDUSTRIES, LTD WBAA-8
A B C D E F G H I

AI
AA 3CORNER DAMPER POSITION POS
FB I

SV S-PB-3-Set 01HLA53AA791-XQ01 POS Pin


SV SV 01HLA53AA791 PB RPB 0.0 - 100.0% TRK
I
MV S-PB-8-Set
PB APB
AI FBI FBO CEA
V3 S-PB-10-Set AA 3CORNER DAMPER POSITION RB1I TRKS AA 3CORNER WINDBOX DAMPER OPND D1
TRK TRACKING SIG PB MPB
1 DEMAND1 RB TR SIGNAL
VDSI 1
DAB DRIVE ABN S-PB-2 FGSG09-DRV-WBAA-3-TR <FGSG09-WBCAA-RHS> CLSD D3
O 01HLA53AA791-YQ01RB
RSE RESET COND S-PB-3 0.0 - 100.0% RBSO MID D2
RB
T
SAB SIG ABN S-PB-4
AA CORNER WINDBOX DAMPER
N AI
CAU CONTROL AUTO S-PB-8 AA 3CORNER DAMPER POSITION RB2I FQAB FSA
T DEMAND2 RB B
STB STAND BY MODE S-PB-9 MV-I-PRH
Y MV-D-PRH 01HLA53AA791-YQ02RB CAU D1
S-PB-10 MV-Set 0.0 - 100.0% DFDH DFD T
MAN MANUAL MODE
H STB D2
Y
AA 3CORNER WINDBOX DAMPER D3
<WIND BOX-2> MAN
RQAB RSA
2 B
AA(L) 3CORNER WINDBOX DAMPER AUTO/MANUAL 2
<WIND BOX-2>
CED DRDH DRD
DPRH IPRH H
FG INITIALIZING INIT
ULMT Ain Aout A1
RB 999.9uu
FG INITIALIZING PVC
LLMT DRVM FMA Cout A2
N
OPMT
AA 3CORNER WINDBOX DAMPER RB
CEA S OH OL AO
AA DAMPER 3CORNER CONTROL X Y Ain Aout DEM AO AA 3CORNER DAMPER POSITION <WIND BOX-2>
S/S DRIP
DEMAND DEMAND1
FGSG09-WBCAA-RHS-A001 <FGSG09-WBCAA-RHS> L sw OPP FSA X
OPC INIT 01HLA53AA791-YQ01 B A
0.0 - 100.0%
AA 3CORNER WINDBOX DAMPER FB SIG ABN
CEA
3 AA DAMPER 3/4/5/6CORNER AO DFD X
3
SV
PROGRAM DEMAND
MAN
MANUAL MODE AA 3CORNER DAMPER POSITION H A
FGSG09-WBCAA-RHS-A005 <FGSG09-WBCAA-RHS> DEMAND2
AA 3CORNER WINDBOX DAMPER FB DEV HI
INITIALIZE
INIT 01HLA53AA791-YQ02 RSA X
0.0 - 100.0% B A
ALLRST
RPB AA 3CORNER WINDBOX DAMPER RB SIG ABN
STB sw on DEM_X1in=-10.0 DRD X
Y
TR SG H A
DEM_Y1out=-10.0
off S=0.0 MANU LARP RSE
MAN DEM_X2in=110.0 AA 3CORNER WINDBOX DAMPER RB DEV HI
T
DEM_Y2out=110.0
FMA X
SG RB_X1in=-10.0
N A
RB_Y1out=-10.0
S=10.0 SAB SABCND
RB_X2in=110.0 AA 3CORNER WINDBOX DAMPER FORCED MANUAL
CED N
4 ACN
RB_Y2out=110.0
X 4
WINDBOX BANKING COMMAND RB_CHG=0 MAN
D E
RB_TRK=0
APC-ADC-15-D002 <APC-ADC-15> DABO DAB
FB_TRK=0 AA CORNER WINDBOX DAMPER MANUAL MODE
O
DEM_FB=0 CAU X
12DV=10.0 T E
LCN DABCND ARDV=10.0
ONT1=10.0 AA CORNER WINDBOX DAMPER AUTO MODE
D
INIT FDHEX DFDV=10.0 STB X
ONT2=60.0 Y E
INIT AA CORNER WINDBOX DAMPER STANDBY MODE

RBK

5 5
CED
ATPB CAUTX Y CAU CAU AA 3CORNER WINDBOX DAMPER
APB AUTO PB
SAB T T AUTO
N MNPB
MPB MANUAL PB T=0.0 FGSG09-DRV-WBAA-3-AT
CED
ACN AUT CND ACND CSTB STB CED
BID SIGNAL ABNORMAL
RSA RB SIG ABN D Y DAU AA 3CORNER WINDBOX DAMPER
APC-BID-01-D004 <APC-BID-01> MCN B MCN MANU CND MCND ASM T AUTO or STANDBY
D LCN D S FGSG09-DRV-WBAA-3-AST <FGSG09-WBCAA-RHS>
DAB D DAUT DAU
O DRD RB SIG DEV H T CED
H STB AA 3CORNER WINDBOX DAMPER
CED Y STANDBY MODE
INIT MANU
FCB/RUNBACK OPERATE RBK INIT INITIALIZE MAN FGSG09-DRV-WBAA-3-ST <FGSG09-WBCAA-RHS>
6 APC-EMG-10-D001 <APC-EMG-10>
6

TITLE AA 3CORNER WINDBOX DAMPER Rev.


REMARKS

2
SHEET NO.
MITSUBISHI FGSG09-DRV-
HEAVY INDUSTRIES, LTD WBAA-3
A B C D E F G H I

AI
AA 4CORNER DAMPER POSITION POS
FB I

SV S-PB-3-Set 01HLA54AA791-XQ01 POS Pin


SV SV 01HLA54AA791 PB RPB 0.0 - 100.0% TRK
I
MV S-PB-8-Set
PB APB
AI FBI FBO CEA
V3 S-PB-10-Set AA 4CORNER DAMPER POSITION RB1I TRKS AA 4CORNER WINDBOX DAMPER OPND D1
TRK TRACKING SIG PB MPB
1 DEMAND1 RB TR SIGNAL
VDSI 1
DAB DRIVE ABN S-PB-2 FGSG09-DRV-WBAA-4-TR <FGSG09-WBCAA-RHS> CLSD D3
O 01HLA54AA791-YQ01RB
RSE RESET COND S-PB-3 0.0 - 100.0% RBSO MID D2
RB
T
SAB SIG ABN S-PB-4
AA 4CORNER WINDBOX DAMPER
N AI
CAU CONTROL AUTO S-PB-8 AA 4CORNER DAMPER POSITION RB2I FQAB FSA
T DEMAND2 RB B
STB STAND BY MODE S-PB-9 MV-I-PRH
Y MV-D-PRH 01HLA54AA791-YQ02RB CAU D1
S-PB-10 MV-Set 0.0 - 100.0% DFDH DFD T
MAN MANUAL MODE
H STB D2
Y
AA 4CORNER WINDBOX DAMPER D3
<WIND BOX-2> MAN
RQAB RSA
2 B
AA(L) 4CORNER WINDBOX DAMPER AUTO/MANUAL 2
<WIND BOX-2>
CED DRDH DRD
DPRH IPRH H
FG INITIALIZING INIT
ULMT Ain Aout A1
RB 999.9uu
FG INITIALIZING PVC
LLMT DRVM FMA Cout A2
N
OPMT
AA 4CORNER WINDBOX DAMPER RB
CEA S OH OL AO
AA DAMPER 4CORNER CONTROL X Y Ain Aout DEM AO AA 4CORNER DAMPER POSITION <WIND BOX-2>
S/S DRIP
DEMAND DEMAND1
FGSG09-WBCAA-RHS-A002 <FGSG09-WBCAA-RHS> L sw OPP FSA X
OPC INIT 01HLA54AA791-YQ01 B A
0.0 - 100.0%
AA 4CORNER WINDBOX DAMPER FB SIG ABN
CEA
3 AA DAMPER 3/4/5/6CORNER AO DFD X
3
SV
PROGRAM DEMAND
MAN
MANUAL MODE AA 4CORNER DAMPER POSITION H A
FGSG09-WBCAA-RHS-A005 <FGSG09-WBCAA-RHS> DEMAND2
AA 4CORNER WINDBOX DAMPER FB DEV HI
INITIALIZE
INIT 01HLA54AA791-YQ02 RSA X
0.0 - 100.0% B A
ALLRST
RPB AA 4CORNER WINDBOX DAMPER RB SIG ABN

DEM_X1in=-10.0 DRD X
DEM_Y1out=-10.0 H A
STB sw on MANU LARP RSE
Y
TR SG MAN
T
DEM_X2in=110.0 AA 4CORNER WINDBOX DAMPER RB DEV HI
DEM_Y2out=110.0
off S=0.0 FMA X
RB_X1in=-10.0
RB_Y1out=-10.0
N A
SG SAB SABCND
RB_X2in=110.0 AA 4CORNER WINDBOX DAMPER FORCED MANUAL
N
4 S=10.0 RB_Y2out=110.0
X 4
RB_CHG=0 MAN
CED E
RB_TRK=0
ACN DABO DAB
WINDBOX BANKING COMMAND FB_TRK=0 AA 4CORNER WINDBOX DAMPER MANUAL MODE
D O
DEM_FB=0 CAU X
APC-ADC-15-D002 <APC-ADC-15> 12DV=10.0 T E
LCN DABCND ARDV=10.0
ONT1=10.0 AA 4CORNER WINDBOX DAMPER AUTO MODE
D
INIT FDHEX DFDV=10.0 STB X
ONT2=60.0 Y E
INIT AA 4CORNER WINDBOX DAMPER STANDBY MODE

RBK

5 5
CED
ATPB CAUTX Y CAU CAU AA 4CORNER WINDBOX DAMPER
APB AUTO PB
SAB T T AUTO
N MNPB
MPB MANUAL PB T=0.0 FGSG09-DRV-WBAA-4-AT
CED
ACN AUT CND ACND CSTB STB CED
BID SIGNAL ABNORMAL
RSA RB SIG ABN D Y DAU AA 4CORNER WINDBOX DAMPER
APC-BID-01-D004 <APC-BID-01> MCN B MCN MANU CND MCND ASM T AUTO or STANDBY
D LCN D S FGSG09-DRV-WBAA-4-AST <FGSG09-WBCAA-RHS>
DAB D DAUT DAU
O DRD RB SIG DEV H T CED
H STB AA 4CORNER WINDBOX DAMPER
CED Y STANDBY MODE
INIT MANU
FCB/RUNBACK OPERATE RBK INIT INITIALIZE MAN FGSG09-DRV-WBAA-4-ST <FGSG09-WBCAA-RHS>
6 APC-EMG-10-D001 <APC-EMG-10>
6

TITLE AA 4CORNER WINDBOX DAMPER Rev.


REMARKS

2
SHEET NO.
MITSUBISHI FGSG09-DRV-
HEAVY INDUSTRIES, LTD WBAA-4
A B C D E F G H I

AI
AA 5CORNER DAMPER POSITION POS
FB I

SV S-PB-3-Set 01HLA55AA791-XQ01 POS Pin


SV SV 01HLA55AA791 PB RPB 0.0 - 100.0% TRK
I
MV S-PB-8-Set
PB APB
AI FBI FBO CEA
V3 S-PB-10-Set AA 5CORNER DAMPER POSITION RB1I TRKS AA 5CORNER WINDBOX DAMPER OPND D1
TRK TRACKING SIG PB MPB
1 DEMAND1 RB TR SIGNAL
VDSI 1
DAB DRIVE ABN S-PB-2 FGSG09-DRV-WBAA-5-TR <FGSG09-WBCAA-RHS> CLSD D3
O 01HLA55AA791-YQ01RB
RSE RESET COND S-PB-3 0.0 - 100.0% RBSO MID D2
RB
T
SAB SIG ABN S-PB-4
AA 5CORNER WINDBOX DAMPER
N AI
CAU CONTROL AUTO S-PB-8 AA 5CORNER DAMPER POSITION RB2I FQAB FSA
T DEMAND2 RB B
STB STAND BY MODE S-PB-9 MV-I-PRH
Y MV-D-PRH 01HLA55AA791-YQ02RB CAU D1
S-PB-10 MV-Set 0.0 - 100.0% DFDH DFD T
MAN MANUAL MODE
H STB D2
Y
AA 5CORNER WINDBOX DAMPER D3
<WIND BOX-2> MAN
RQAB RSA
2 B
AA(L) 5CORNER WINDBOX DAMPER AUTO/MANUAL 2
<WIND BOX-2>
CED DRDH DRD
DPRH IPRH H
FG INITIALIZING INIT
ULMT Ain Aout A1
RB 999.9uu
FG INITIALIZING PVC
LLMT DRVM FMA Cout A2
N
OPMT
AA 5CORNER WINDBOX DAMPER RB
CEA S OH OL AO
AA DAMPER 5CORNER CONTROL X Y Ain Aout DEM AO AA 5CORNER DAMPER POSITION <WIND BOX-2>
S/S DRIP
DEMAND DEMAND1
FGSG09-WBCAA-RHS-A003 <FGSG09-WBCAA-RHS> L sw OPP FSA X
OPC INIT 01HLA55AA791-YQ01 B A
0.0 - 100.0%
AA 5CORNER WINDBOX DAMPER FB SIG ABN
CEA
3 AA DAMPER 3/4/5/6CORNER AO DFD X
3
SV
PROGRAM DEMAND
MAN
MANUAL MODE AA 5CORNER DAMPER POSITION H A
FGSG09-WBCAA-RHS-A005 <FGSG09-WBCAA-RHS> DEMAND2
AA 5CORNER WINDBOX DAMPER FB DEV HI
INITIALIZE
INIT 01HLA55AA791-YQ02 RSA X
0.0 - 100.0% B A
ALLRST
RPB AA 5CORNER WINDBOX DAMPER RB SIG ABN

DEM_X1in=-10.0 DRD X
DEM_Y1out=-10.0 H A
STB sw on MANU LARP RSE
Y
TR SG MAN
T
DEM_X2in=110.0 AA 5CORNER WINDBOX DAMPER RB DEV HI
DEM_Y2out=110.0
off S=0.0 FMA X
RB_X1in=-10.0
RB_Y1out=-10.0
N A
SG SAB SABCND
RB_X2in=110.0 AA 5CORNER WINDBOX DAMPER FORCED MANUAL
N
4 S=10.0 RB_Y2out=110.0
X 4
RB_CHG=0 MAN
E
CED RB_TRK=0
DABO DAB
FB_TRK=0 AA 5CORNER WINDBOX DAMPER MANUAL MODE
ACN O
WINDBOX BANKING COMMAND DEM_FB=0
D CAU X
12DV=10.0
APC-ADC-15-D002 <APC-ADC-15> T E
LCN DABCND ARDV=10.0
ONT1=10.0 AA 5CORNER WINDBOX DAMPER AUTO MODE
D
INIT FDHEX DFDV=10.0 STB X
ONT2=60.0 Y E
INIT AA 5CORNER WINDBOX DAMPER STANDBY MODE

RBK

5 5
CED
ATPB CAUTX Y CAU CAU AA 5CORNER WINDBOX DAMPER
APB AUTO PB
SAB T T AUTO
N MNPB
MPB MANUAL PB T=0.0 FGSG09-DRV-WBAA-5-AT
CED
ACN AUT CND ACND CSTB STB CED
BID SIGNAL ABNORMAL
RSA RB SIG ABN D Y DAU AA 5CORNER WINDBOX DAMPER
APC-BID-01-D004 <APC-BID-01> MCN B MCN MANU CND MCND ASM T AUTO or STANDBY
D LCN D S FGSG09-DRV-WBAA-5-AST <FGSG09-WBCAA-RHS>
DAB D DAUT DAU
O DRD RB SIG DEV H T CED
H STB AA 5CORNER WINDBOX DAMPER
CED Y STANDBY MODE
INIT MANU
FCB/RUNBACK OPERATE RBK INIT INITIALIZE MAN FGSG09-DRV-WBAA-5-ST <FGSG09-WBCAA-RHS>
6 APC-EMG-10-D001 <APC-EMG-10>
6

TITLE AA 5CORNER WINDBOX DAMPER Rev.


REMARKS

2
SHEET NO.
MITSUBISHI FGSG09-DRV-
HEAVY INDUSTRIES, LTD WBAA-5
A B C D E F G H I

AI
AA 6CORNER DAMPER POSITION POS
FB I

SV S-PB-3-Set 01HLA56AA791-XQ01 POS Pin


SV SV 01HLA56AA791 PB RPB 0.0 - 100.0% TRK
I
MV S-PB-8-Set
PB APB
AI FBI FBO CEA
V3 S-PB-10-Set AA 6CORNER DAMPER POSITION RB1I TRKS AA 6CORNER WINDBOX DAMPER OPND D1
TRK TRACKING SIG PB MPB
1 DEMAND1 RB TR SIGNAL
VDSI 1
DAB DRIVE ABN S-PB-2 FGSG09-DRV-WBAA-6-TR <FGSG09-WBCAA-RHS> CLSD D3
O 01HLA56AA791-YQ01RB
RSE RESET COND S-PB-3 0.0 - 100.0% RBSO MID D2
RB
T
SAB SIG ABN S-PB-4
AA 6CORNER WINDBOX DAMPER
N AI
CAU CONTROL AUTO S-PB-8 AA 6CORNER DAMPER POSITION RB2I FQAB FSA
T DEMAND2 RB B
STB STAND BY MODE S-PB-9 MV-I-PRH
Y MV-D-PRH 01HLA56AA791-YQ02RB CAU D1
S-PB-10 MV-Set 0.0 - 100.0% DFDH DFD T
MAN MANUAL MODE
H STB D2
Y
AA 6CORNER WINDBOX DAMPER D3
<WIND BOX-2> MAN
RQAB RSA
2 B
AA(L) 6CORNER WINDBOX DAMPER AUTO/MANUAL 2
<WIND BOX-2>
CED DRDH DRD
DPRH IPRH H
FG INITIALIZING INIT
ULMT Ain Aout A1
RB 999.9uu
FG INITIALIZING PVC
LLMT DRVM FMA Cout A2
N
OPMT
AA 6CORNER WINDBOX DAMPER RB
CEA S OH OL AO
AA DAMPER 6CORNER CONTROL X Y Ain Aout DEM AO AA 6CORNER DAMPER POSITION <WIND BOX-2>
S/S DRIP
DEMAND DEMAND1
FGSG09-WBCAA-RHS-A004 <FGSG09-WBCAA-RHS> L sw OPP FSA X
OPC INIT 01HLA56AA791-YQ01 B A
0.0 - 100.0%
AA 6CORNER WINDBOX DAMPER FB SIG ABN
CEA
3 AA DAMPER 3/4/5/6CORNER AO DFD X
3
SV
PROGRAM DEMAND
MAN
MANUAL MODE AA 6CORNER DAMPER POSITION H A
FGSG09-WBCAA-RHS-A005 <FGSG09-WBCAA-RHS> DEMAND2
AA 6CORNER WINDBOX DAMPER FB DEV HI
INITIALIZE
INIT 01HLA56AA791-YQ02 RSA X
0.0 - 100.0% B A
ALLRST
RPB AA 6CORNER WINDBOX DAMPER RB SIG ABN

DEM_X1in=-10.0 DRD X
DEM_Y1out=-10.0 H A
STB sw on MANU LARP RSE
Y
TR SG MAN
T
DEM_X2in=110.0 AA 6CORNER WINDBOX DAMPER RB DEV HI
DEM_Y2out=110.0
off S=0.0 FMA X
RB_X1in=-10.0
RB_Y1out=-10.0
N A
SAB SABCND
SG RB_X2in=110.0 AA 6CORNER WINDBOX DAMPER FORCED MANUAL
N
4 S=10.0
RB_Y2out=110.0
X 4
RB_CHG=0 MAN
CED E
RB_TRK=0
ACN DABO DAB
WINDBOX BANKING COMMAND FB_TRK=0 AA 6CORNER WINDBOX DAMPER MANUAL MODE
D O
DEM_FB=0 CAU X
APC-ADC-15-D002 <APC-ADC-15> 12DV=10.0 T E
LCN DABCND ARDV=10.0
ONT1=10.0 AA 6CORNER WINDBOX DAMPER AUTO MODE
D
INIT FDHEX DFDV=10.0 STB X
ONT2=60.0 Y E
INIT AA 6CORNER WINDBOX DAMPER STANDBY MODE

RBK

5 5
CED
ATPB CAUTX Y CAU CAU AA 6CORNER WINDBOX DAMPER
APB AUTO PB
SAB T T AUTO
N MNPB
MPB MANUAL PB T=0.0 FGSG09-DRV-WBAA-6-AT
CED
ACN AUT CND ACND CSTB STB CED
BID SIGNAL ABNORMAL
RSA RB SIG ABN D Y DAU AA 6CORNER WINDBOX DAMPER
APC-BID-01-D004 <APC-BID-01> MCN B MCN MANU CND MCND ASM T AUTO or STANDBY
D LCN D S FGSG09-DRV-WBAA-6-AST <FGSG09-WBCAA-RHS>
DAB D DAUT DAU
O DRD RB SIG DEV H T CED
H STB AA 6CORNER WINDBOX DAMPER
CED Y STANDBY MODE
INIT MANU
FCB/RUNBACK OPERATE RBK INIT INITIALIZE MAN FGSG09-DRV-WBAA-6-ST <FGSG09-WBCAA-RHS>
6 APC-EMG-10-D001 <APC-EMG-10>
6

TITLE AA 6CORNER WINDBOX DAMPER Rev.


REMARKS

2
SHEET NO.
MITSUBISHI FGSG09-DRV-
HEAVY INDUSTRIES, LTD WBAA-6
A B C D E F G H I

1 1

2 2

3 3

4 4

5 5

OFF D

6 6
REMARKS
A B C D E F G H I

1 1
CEA
AA ADJUSTABLE CD AUTO BIAS
(LH+/RH-)
FGSG09-WBCAAADJ-BIAS-A001
CEA
<FGSG09-WBCAAADJ-BIAS>
AA ADJUSTABLE 1/2/7/8 CORNER
CEA FX-1 * CD PROGRAM DEMAND
FGSG09-WBCAAADJ-LHS-A005 <FGSG09-DRV-AAADJST-1>
LOAD INDEX FX
<FGSG09-DRV-AAADJST-2>
FGSG05-AI01-A01 <FGSG05-AI01> <FGSG09-DRV-AAADJST-7>
<FGSG09-DRV-AAADJST-8>
<FGSG09-WBCAAADJ-BIAS>
FX-2 *
FX
2 2

FX-3 * CEA
AA ADJUSTABLE 1CORNER
FX CONTROL DRIVE TR SIGNAL
RI=3.0 FGSG09-DRV-AAADJST-1-TR
RD=3.0 <FGSG09-DRV-AAADJST-1>
FX-4 * on on on off CEA
off off off X
FX TR TR TR V + on
TR
AA ADJUSTABLE 1CORNER CD
CONTROL SIGNAL
swRon=10.0 swRon=10.0 sw TP sw FGSG09-WBCAAADJ-LHS-A001
Roff=10.0 Roff=10.0 Ron=200.0 Ron=5.0
Roff=99999.0 <FGSG09-DRV-AAADJST-1>
MD=0 MD=0 1AT Roff=99999.0
CED MD=0
3 MD=0 3
WORST COAL SELECT
FGSG05-DI01-D01 <FGSG05-DI01>
CEA
AA ADJUSTABLE 2CORNER
CED CONTROL DRIVE TR SIGNAL
BEST COAL SELECT FGSG09-DRV-AAADJST-2-TR
<FGSG09-DRV-AAADJST-2>
FGSG05-DI01-D02 <FGSG05-DI01>
off CEA
on AA ADJUSTABLE 2CORNER CD
CED TR CONTROL SIGNAL
ALL FUEL OIL BURNER VALVES sw FGSG09-WBCAAADJ-LHS-A002
CLOSED Ron=5.0 <FGSG09-DRV-AAADJST-2>
FGSG05-6-6-D01 <BMS1-5-6> 2AT Roff=99999.0
4 MD=0
4
1AT
CED
AA NOZZLE ADJUSTABLE
1CORNER DRV AUTO CEA
FGSG09-DRV-AAADJST-1-AT AA ADJUSTABLE 7CORNER
<FGSG09-DRV-AAADJST-1> 2AT
CED CONTROL DRIVE TR SIGNAL
AA NOZZLE ADJUSTABLE FGSG09-DRV-AAADJST-7-TR
2CORNER DRV AUTO
<FGSG09-DRV-AAADJST-7>
FGSG09-DRV-AAADJST-2-AT 7AT
CED <FGSG09-DRV-AAADJST-2> off CEA
AA NOZZLE ADJUSTABLE on AA ADJUSTABLE 7CORNER CD
7CORNER DRV AUTO
TR CONTROL SIGNAL
FGSG09-DRV-AAADJST-7-AT sw FGSG09-WBCAAADJ-LHS-A003
8AT
CED <FGSG09-DRV-AAADJST-7> Ron=5.0 <FGSG09-DRV-AAADJST-7>
AA NOZZLE ADJUSTABLE Roff=99999.0
7AT
8CORNER DRV AUTO MD=0
5 FGSG09-DRV-AAADJST-8-AT 5
<FGSG09-DRV-AAADJST-8>

CEA
AA ADJUSTABLE 8CORNER CD
TR SIGNAL
FGSG09-DRV-AAADJST-8-TR
<FGSG09-DRV-AAADJST-8>
off CEA
on AA ADJUSTABLE 8CORNER CD
TR CONTROL SIGNAL
sw FGSG09-WBCAAADJ-LHS-A004
Ron=5.0 <FGSG09-DRV-AAADJST-8>
8AT Roff=99999.0
MD=0
6 6

FX-1 * FX-2 * FX-3 * FX-4 *


X1=0.0,Y1=0.0 X1=0.0,Y1=0.0 X1=0.0,Y1=0.0 X1=0.0,Y1=0.0
X2=198.0,Y2=0.0 X2=198.0,Y2=0.0 X2=198.0,Y2=0.0 X2=198.0,Y2=0.0 TITLE AA ADJUSTABLE DRIVE 1,2,7,8CORNER Rev.
X3=264.0,Y3=0.0 X3=264.0,Y3=0.0 X3=264.0,Y3=0.0 X3=264.0,Y3=0.0 CONTROL
REMARKS

X4=330.0,Y4=0.0 X4=330.0,Y4=0.0 X4=330.0,Y4=0.0 X4=330.0,Y4=0.0 2


X5=396.0,Y5=0.0 X5=396.0,Y5=0.0 X5=396.0,Y5=0.0 X5=396.0,Y5=0.0
X6=528.0,Y6=0.0 X6=528.0,Y6=0.0 X6=528.0,Y6=0.0 X6=528.0,Y6=0.0 SHEET NO.
X7=660.0,Y7=0.0 X7=660.0,Y7=0.0 X7=660.0,Y7=0.0 X7=660.0,Y7=0.0
* TO BE FINALIZED DURING COMMISSIONING FGSG09-
X8=693.0,Y8=0.0
X9=700.0,Y9=0.0
X8=693.0,Y8=0.0
X9=700.0,Y9=0.0
X8=693.0,Y8=0.0
X9=700.0,Y9=0.0
X8=693.0,Y8=0.0
X9=700.0,Y9=0.0
MITSUBISHI WBCAAADJ-LHS
X10=0.0,Y10=0.0 X10=0.0,Y10=0.0 X10=0.0,Y10=0.0 X10=0.0,Y10=0.0 HEAVY INDUSTRIES, LTD
A B C D E F G H I

1 1
CEA
AA ADJUSTABLE CD AUTO BIAS
(LH+/RH-)
FGSG09-WBCAAADJ-BIAS-A001
<FGSG09-WBCAAADJ-BIAS> CEA
AA ADJUSTABLE 3/4/5/6CORNER
CEA FX-1 * CD PROGRAM DEMAND
FGSG09-WBCAAADJ-RHS-A005
LOAD INDEX FX
<FGSG09-DRV-AAADJST-3>
FGSG05-AI01-A01 <FGSG05-AI01> <FGSG09-DRV-AAADJST-4>
<FGSG09-DRV-AAADJST-5>
FX-2 * <FGSG09-DRV-AAADJST-6>
<FGSG09-WBCAAADJ-BIAS>
FX
2 2

FX-3 * CEA
AA ADJUSTABLE 3CORNER
FX CONTROL DRIVE TR SIGNAL
FGSG09-DRV-AAADJST-3-TR
RI=3.0 <FGSG09-DRV-AAADJST-3>
RD=3.0
FX-4 * on on on - off CEA
off off off X + on AA ADJUSTABLE 3CORNER CD
FX TR TR TR V TR CONTROL SIGNAL
swRon=10.0 swRon=10.0 sw TP sw FGSG09-WBCAAADJ-RHS-A001
Roff=10.0 Roff=10.0 Ron=200.0 Ron=5.0
Roff=99999.0 <FGSG09-DRV-AAADJST-3>
MD=0 MD=0 3AT Roff=99999.0
CED MD=0
3 MD=0 3
WORST COAL SELECT
FGSG05-DI01-D01 <FGSG05-DI01>
CEA
AA ADJUSTABLE 4CORNER
CED CONTROL DRIVE TR SIGNAL
BEST COAL SELECT FGSG09-DRV-AAADJST-4-TR
<FGSG09-DRV-AAADJST-4>
FGSG05-DI01-D02 <FGSG05-DI01>
off CEA
on AA ADJUSTABLE 4CORNER CD
CED TR CONTROL SIGNAL
ALL FUEL OIL BURNER VALVES sw FGSG09-WBCAAADJ-RHS-A002
CLOSED Ron=5.0 <FGSG09-DRV-AAADJST-4>
FGSG05-6-6-D01 <BMS1-5-6> 4AT Roff=99999.0
4 MD=0
4
3AT
CED
AA NOZZLE ADJUSTABLE
3CORNER DRV AUTO CEA
FGSG09-DRV-AAADJST-3-AT AA ADJUSTABLE 5CORNER
<FGSG09-DRV-AAADJST-3> 4AT
CED CONTROL DRIVE TR SIGNAL
AA NOZZLE ADJUSTABLE FGSG09-DRV-AAADJST-5-TR
4CORNER DRV AUTO
<FGSG09-DRV-AAADJST-5>
FGSG09-DRV-AAADJST-4-AT
<FGSG09-DRV-AAADJST-4> 5AT
CED off CEA
AA NOZZLE ADJUSTABLE on AA ADJUSTABLE 5CORNER CD
5CORNER DRV AUTO
TR CONTROL SIGNAL
FGSG09-DRV-AAADJST-5-AT sw FGSG09-WBCAAADJ-RHS-A003
<FGSG09-DRV-AAADJST-5> 6AT
CED Ron=5.0 <FGSG09-DRV-AAADJST-5>
AA NOZZLE ADJUSTABLE Roff=99999.0
5AT
6CORNER DRV AUTO MD=0
5 FGSG09-DRV-AAADJST-6-AT 5
<FGSG09-DRV-AAADJST-6>

CEA
AA ADJUSTABLE 6CORNER
CONTROL DRIVE TR SIGNAL
FGSG09-DRV-AAADJST-6-TR
<FGSG09-DRV-AAADJST-6>
off CEA
on AA ADJUSTABLE 6CORNER CD
TR CONTROL SIGNAL
sw FGSG09-WBCAAADJ-RHS-A004
Ron=5.0 <FGSG09-DRV-AAADJST-6>
6AT Roff=99999.0
MD=0
6 6

FX-1 * FX-2 * FX-3 * FX-4 *


X1=0.0,Y1=0.0 X1=0.0,Y1=0.0 X1=0.0,Y1=0.0 X1=0.0,Y1=0.0
X2=198.0,Y2=0.0 X2=198.0,Y2=0.0 X2=198.0,Y2=0.0 X2=198.0,Y2=0.0 TITLE AA ADJUSTABLE DRIVE 3,4,5,6CORNER Rev.
X3=264.0,Y3=0.0 X3=264.0,Y3=0.0 X3=264.0,Y3=0.0 X3=264.0,Y3=0.0 CONTROL
REMARKS

X4=330.0,Y4=0.0 X4=330.0,Y4=0.0 X4=330.0,Y4=0.0 X4=330.0,Y4=0.0 2


X5=396.0,Y5=0.0 X5=396.0,Y5=0.0 X5=396.0,Y5=0.0 X5=396.0,Y5=0.0
X6=528.0,Y6=0.0 X6=528.0,Y6=0.0 X6=528.0,Y6=0.0 X6=528.0,Y6=0.0 SHEET NO.
X7=660.0,Y7=0.0 X7=660.0,Y7=0.0 X7=660.0,Y7=0.0 X7=660.0,Y7=0.0
* TO BE FINALIZED DURING COMMISSIONING FGSG09-
X8=693.0,Y8=0.0
X9=700.0,Y9=0.0
X8=693.0,Y8=0.0
X9=700.0,Y9=0.0
X8=693.0,Y8=0.0
X9=700.0,Y9=0.0
X8=693.0,Y8=0.0
X9=700.0,Y9=0.0
MITSUBISHI WBCAAADJ-RHS
X10=0.0,Y10=0.0 X10=0.0,Y10=0.0 X10=0.0,Y10=0.0 X10=0.0,Y10=0.0 HEAVY INDUSTRIES, LTD
A B C D E F G H I

AADRVBS(LH+/RH-)

1 1
SV-I-PRH
SIP1
SDP SV-D-PRH
1

A1
999.9uu

SV-Set AA ADJUSTABLE DRIVE BIAS (RIGHT)


<WIND BOX-2>
INIT IPRH
AA ADJUSTABLE DRIVE BIAS (LH+/RH-) INIT SIP1
<WIND BOX-1> ULMT DPRH SDP A1
<WIND BOX-2> MUL SIP 999.9uu
1
LLMT AA ADJUSTABLE DRIVE BIAS (LEFT)
MLL SDP OPMT
2 RI=1.0 <WIND BOX-1> 2
S RD=1.0
off OH OL CEA
on X Y Ain Aout X AA ADJUSTABLE CD AUTO BIAS
0% T S/S V (LH+/RH-)
sw OH=15 sw OPP FGSG09-WBCAAADJ-BIAS-A001
OL=-15 <FGSG09-WBCAAADJ-LHS>
CED <FGSG09-WBCAAADJ-RHS>

FG INITIALIZING INIT
FG INITIALIZING

3 3

MUL

CEA
AA ADJUSTABLE 1/2/7/8 CORNER X
CD PROGRAM DEMAND H SIP
FGSG09-WBCAAADJ-LHS-A005 H=29.9
CEA <FGSG09-WBCAAADJ-LHS>
AA ADJUSTABLE 3/4/5/6CORNER X
CD PROGRAM DEMAND L
4 FGSG09-WBCAAADJ-RHS-A005 L=0.1
4
<FGSG09-WBCAAADJ-RHS>

MLL

X
H SDP
H=29.9

X
L
L=0.1

5 5

6 6

TITLE AA ADJUSTABLE CONTROL DRIVE BIAS Rev.


LOGIC
REMARKS

2
SHEET NO.
MITSUBISHI FGSG09-
HEAVY INDUSTRIES, LTD WBCAAADJ-BIAS
A B C D E F G H I

AI
AA ADJUSTABLE 1CORNER POS
CONTROL DRIVE POSN FB I

SV S-PB-3-Set 01HLA51AA714-XQ01
SV SV 01HLA51AA714 PB RPB 0.0 - 100.0% TRK
POS MV S-PB-8-Set
I
PB APB
AI FBI FBO CEA
<FGSG09-WBCAAADJ-LHS>
V3 S-PB-10-Set AA ADJUSTABLE 1CORNER RB1I TRKS AA ADJUSTABLE 1CORNER
TRK TRACKING SIG PB MPB
1 CONTROL DRIVE POSN DEM1 RB CONTROL DRIVE TR SIGNAL 1
DAB DRIVE ABN S-PB-2 FGSG09-DRV-AAADJST-1-TR
O 01HLA51AA714-YQ01RB
RSE RESET COND S-PB-3 0.0 - 100.0% RBSO
T
A
SAB SIG ABN S-PB-4
N AI
CAU CONTROL AUTO S-PB-8 AA ADJUSTABLE 1CORNER RB2I FQAB FSA
T CONTROL DRIVE POSN DEM2 RB B
STB STAND BY MODE S-PB-9 MV-I-PRH
Y MV-D-PRH 01HLA51AA714-YQ02RB CAU D1
S-PB-10 MV-Set 0.0 - 100.0% DFDH DFD T
MAN MANUAL MODE
H STB D2
Y
AA NOZZLE ADJUSTABLE 1CORNER DRV D3
MAN
<WIND BOX-1> RQAB RSA
2 B
AA NOZZLE ADJUSTABLE 1CORNER DRV AUTO/MANUAL 2
<WIND BOX-1>
CED DRDH DRD
DPRH IPRH H
FG INITIALIZING INIT
ULMT Ain Aout A1
TRK 999.9uu
FG INITIALIZING PVC
LLMT DRVM FMA Cout A2
N
OPMT
AA NOZZLE ADJUSTABLE 1CORNER DRV RB(deg)
CEA S OH OL AO
AA ADJUSTABLE 1CORNER CD X Y Ain Aout DEM AO AA NOZZLE ADJUSTABLE <WIND BOX-1>
S/S DRIP
CONTROL SIGNAL 1CORNER DRV POSN DEM1
FGSG09-WBCAAADJ-LHS-A001 sw OPP
OH=30 OPC INIT 01HLA51AA714-YQ01
<FGSG09-WBCAAADJ-LHS> FSA X
OL=-30 0.0 - 100.0% B A
CEA
3 AA ADJUSTABLE 1/2/7/8 CORNER AO AA NOZZLE ADJUSTABLE 1CORNER DRV FB SIG ABN 3
SV
CD PROGRAM DEMAND MANUAL MODE AA NOZZLE ADJUSTABLE DFD X
MAN
FGSG09-WBCAAADJ-LHS-A005 1CORNER DRV POSN DEM2 H A
<FGSG09-WBCAAADJ-LHS> INITIALIZE
INIT 01HLA51AA714-YQ02 AA NOZZLE ADJUSTABLE 1CORNER DRV FB DEV HI
0.0 - 100.0% RSA X
OFF
ACN
RPB
ALLRST B A
D
AA NOZZLE ADJUSTABLE 1CORNER DRV RB SIG ABN
DEM_X1in=-30.0
DRD X
DEM_Y1out=0.0
MAN
MANU LARP RSE
DEM_X2in=30.0
H A
T
DEM_Y2out=100.0 AA NOZZLE ADJUSTABLE 1CORNER DRV RB DEV HI
RB_X1in=0.0
FMA X
RB_Y1out=-30.0
SAB SABCND
RB_X2in=100.0
N A
N
4 RB_Y2out=30.0 AA NOZZLE ADJUSTABLE 1CORNER DRV FORCED MANUAL 4
RB_CHG=0
RB_TRK=0
DABO DAB X
FB_TRK=0 MAN
O E
DEM_FB=0
AA NOZZLE ADJUSTABLE 1CORNER DRV MANUAL MODE
12DV=10.0
LCN DABCND ARDV=10.0 CAU X
D ONT1=10.0 T E
INIT FDHEX DFDV=10.0
AA NOZZLE ADJUSTABLE 1CORNER DRV AUTO MODE
ONT2=60.0
STB X
INIT
Y E
AA NOZZLE ADJUSTABLE 1CORNER DRV STANDBY MODE
RBK

5 5
CED
ATPB CAUTX Y CAU CAU AA NOZZLE ADJUSTABLE
APB AUTO PB
SAB T T 1CORNER DRV AUTO
N MNPB
MPB MANUAL PB T=0.0 FGSG09-DRV-AAADJST-1-AT
<FGSG09-WBCAAADJ-LHS>
CED
ACN AUT CND ACND CSTB STB CED
BID SIGNAL ABNORMAL
RSA RB SIG ABN D Y DAU AA NOZZLE ADJUSTABLE
APC-BID-01-D004 <APC-BID-01> MCN B MCN MANU CND MCND ASM T 1CORNER DRV AUTO or STANDBY
D LCN D S FGSG09-DRV-AAADJST-1-AST
DAB D DAUT DAU
O DRD RB SIG DEV H T CED
H STB AA NOZZLE ADJUSTABLE
CED Y 1CORNER DRV STANDBY MODE
INIT MANU
FCB/RUNBACK OPERATE RBK INIT INITIALIZE MAN FGSG09-DRV-AAADJST-1-ST

6 APC-EMG-10-D001 <APC-EMG-10>
6

TITLE AA ADJUSTABLE 1CORNER CONTROL DRIVE Rev.


REMARKS

2
SHEET NO.
MITSUBISHI FGSG09-DRV-
HEAVY INDUSTRIES, LTD AAADJST-1
A B C D E F G H I

AI
AA ADJUSTABLE 2CORNER POS
CONTROL DRIVE POSN FB I

SV S-PB-3-Set 01HLA52AA714-XQ01
SV SV 01HLA52AA714 PB RPB 0.0 - 100.0% TRK TRACKING SIG
POS MV S-PB-8-Set
I
PB APB
AI FBI FBO CEA
V3 S-PB-10-Set AA ADJUSTABLE 2CORNER RB1I TRKS AA ADJUSTABLE 2CORNER CAU D1
TRK TRACKING SIG PB MPB
1 CONTROL DRIVE POSN DEM1 RB CONTROL DRIVE TR SIGNAL T 1
DAB DRIVE ABN S-PB-2 FGSG09-DRV-AAADJST-2-TR<FGSG09-WBCAAADJ-LHS> STB D2
O 01HLA52AA714-YQ01RB Y
RSE RESET COND S-PB-3 0.0 - 100.0% RBSO D3
T
A MAN
SAB SIG ABN S-PB-4
AA NOZZLE ADJUSTABLE 2CORNER DRV AUTO/MANUAL
N AI
CAU CONTROL AUTO S-PB-8 AA ADJUSTABLE 2CORNER RB2I FQAB FSA <WIND BOX-1>
T CONTROL DRIVE POSN DEM2 RB B
STB STAND BY MODE S-PB-9 MV-I-PRH
Y MV-D-PRH 01HLA52AA714-YQ02RB Ain Aout A1
0.0 - 100.0% TRK 999.9uu
S-PB-10 MV-Set DFDH DFD
MAN MANUAL MODE PVC
H Cout A2

AA NOZZLE ADJUSTABLE 2CORNER DRV AA NOZZLE ADJUSTABLE 2CORNER DRV RB(deg)


<WIND BOX-1> RQAB RSA
2 B <WIND BOX-1> 2
CED DRDH DRD
DPRH IPRH H
FG INITIALIZING INIT
ULMT
FG INITIALIZING
LLMT DRVM FMA
N
OPMT
CEA S OH OL AO
AA ADJUSTABLE 2CORNER CD X Y Ain Aout DEM AO AA NOZZLE ADJUSTABLE
S/S DRIP
CONTROL SIGNAL 2CORNER DRV POSN DEM1
FGSG09-WBCAAADJ-LHS-A002 sw OPP
OH=30 OPC INIT 01HLA52AA714-YQ01
<FGSG09-WBCAAADJ-LHS> OL=-30 FSA X
0.0 - 100.0% B A
CEA
3 AA ADJUSTABLE 1/2/7/8 CORNER AO AA NOZZLE ADJUSTABLE 2CORNER DRV FB SIG ABN 3
SV
CD PROGRAM DEMAND MANUAL MODE AA NOZZLE ADJUSTABLE DFD X
MAN
FGSG09-WBCAAADJ-LHS-A005 2CORNER DRV POSN DEM2 H A
<FGSG09-WBCAAADJ-LHS> INITIALIZE
INIT 01HLA52AA714-YQ02 AA NOZZLE ADJUSTABLE 2CORNER DRV FB DEV HI
0.0 - 100.0% RSA X
OFF
ACN
RPB
ALLRST B A
D
AA NOZZLE ADJUSTABLE 2CORNER DRV RB SIG ABN
DEM_X1in=-30.0
DRD X
DEM_Y1out=0.0
MAN
MANU LARP RSE
DEM_X2in=30.0
H A
T
DEM_Y2out=100.0 AA NOZZLE ADJUSTABLE 2CORNER DRV RB DEV HI
RB_X1in=0.0
FMA X
RB_Y1out=-30.0
SAB SABCND
RB_X2in=100.0
N A
N
4 RB_Y2out=30.0 AA NOZZLE ADJUSTABLE 2CORNER DRV FORCED MANUAL 4
RB_CHG=0
RB_TRK=0
DABO DAB X
FB_TRK=0 MAN
O E
DEM_FB=0
12DV=10.0 AA NOZZLE ADJUSTABLE 2CORNER DRV MANUAL MODE
LCN DABCND ARDV=10.0 CAU X
D ONT1=10.0 T E
INIT FDHEX DFDV=10.0
ONT2=60.0 AA NOZZLE ADJUSTABLE 2CORNER DRV AUTO MODE
STB X
INIT
Y E
AA NOZZLE ADJUSTABLE 2CORNER DRV STANDBY MODE
RBK

5 5
CED
ATPB CAUTX Y CAU CAU AA NOZZLE ADJUSTABLE
APB AUTO PB
SAB T T 2CORNER DRV AUTO
N MNPB
MPB MANUAL PB T=0.0 FGSG09-DRV-AAADJST-2-AT
<FGSG09-WBCAAADJ-LHS>
CED
ACN AUT CND ACND CSTB STB CED
BID SIGNAL ABNORMAL
RSA RB SIG ABN D Y DAU AA NOZZLE ADJUSTABLE
APC-BID-01-D004 <APC-BID-01> MCN B MCN MANU CND MCND ASM T 2CORNER DRV AUTO or STANDBY
D LCN D S FGSG09-DRV-AAADJST-2-AST
DAB D DAUT DAU
O DRD RB SIG DEV H T CED
H STB AA NOZZLE ADJUSTABLE
CED Y 2CORNER DRV STANDBY MODE
INIT MANU
FCB/RUNBACK OPERATE RBK INIT INITIALIZE MAN FGSG09-DRV-AAADJST-2-ST

6 APC-EMG-10-D001 <APC-EMG-10>
6

TITLE AA ADJUSTABLE 2CORNER CONTROL DRIVE Rev.


REMARKS

2
SHEET NO.
MITSUBISHI FGSG09-DRV-
HEAVY INDUSTRIES, LTD AAADJST-2
A B C D E F G H I

AI
AA ADJUSTABLE 7CORNER POS
CONTROL DRIVE POSN FB I

SV S-PB-3-Set 01HLA57AA714-XQ01
SV SV 01HLA57AA714 PB RPB 0.0 - 100.0% TRK TRACKING SIG
POS MV S-PB-8-Set
I
PB APB
AI FBI FBO CEA
V3 S-PB-10-Set AA ADJUSTABLE 7CORNER RB1I TRKS AA ADJUSTABLE 7CORNER CAU D1
TRK TRACKING SIG PB MPB
1 CONTROL DRIVE POSN DEM1 RB CONTROL DRIVE TR SIGNAL T 1
DAB DRIVE ABN S-PB-2 FGSG09-DRV-AAADJST-7-TR<FGSG09-WBCAAADJ-LHS> STB D2
O 01HLA57AA714-YQ01RB Y
RSE RESET COND S-PB-3 0.0 - 100.0% RBSO D3
T
A MAN
SAB SIG ABN S-PB-4
AA NOZZLE ADJUSTABLE 7CORNER DRV AUTO/MANUAL
N AI
CAU CONTROL AUTO S-PB-8 AA ADJUSTABLE 7CORNER RB2I FQAB FSA <WIND BOX-1>
T CONTROL DRIVE POSN DEM2 RB B
STB STAND BY MODE S-PB-9 MV-I-PRH
Y MV-D-PRH 01HLA57AA714-YQ02RB
S-PB-10 MV-Set 0.0 - 100.0% DFDH DFD Ain Aout A1
MAN MANUAL MODE TRK 999.9uu
H
PVC
Cout A2
AA NOZZLE ADJUSTABLE 7CORNER DRV AA NOZZLE ADJUSTABLE 7CORNER DRV RB(deg)
<WIND BOX-1> RQAB RSA
<WIND BOX-1>
2 B 2
CED DRDH DRD
DPRH IPRH H
FG INITIALIZING INIT
ULMT
FG INITIALIZING
LLMT DRVM FMA
N
OPMT
CEA S OH OL AO
AA ADJUSTABLE 7CORNER CD X Y Ain Aout DEM AO AA NOZZLE ADJUSTABLE
S/S DRIP
CONTROL SIGNAL 7CORNER DRV POSN DEM2
FGSG09-WBCAAADJ-LHS-A003 sw OPP
OH=30 OPC INIT 01HLA57AA714-YQ01
<FGSG09-WBCAAADJ-LHS>
OL=-30 0.0 - 100.0% FSA X
3 CEA B A 3
AA ADJUSTABLE 1/2/7/8 CORNER AO
SV AA NOZZLE ADJUSTABLE 7CORNER DRV FB SIG ABN
CD PROGRAM DEMAND MANUAL MODE AA NOZZLE ADJUSTABLE
MAN
FGSG09-WBCAAADJ-LHS-A005 7CORNER DRV POSN DEM1 DFD X
<FGSG09-WBCAAADJ-LHS> INIT
INITIALIZE H A
01HLA57AA714-YQ02
0.0 - 100.0% AA NOZZLE ADJUSTABLE 7CORNER DRV FB DEV HI
ACN ALLRST RSA X
OFF RPB
D B A
DEM_X1in=-30.0 AA NOZZLE ADJUSTABLE 7CORNER DRV RB SIG ABN
DEM_Y1out=0.0
MANU LARP RSE DRD X
MAN DEM_X2in=30.0
T
DEM_Y2out=100.0
H A
RB_X1in=0.0 AA NOZZLE ADJUSTABLE 7CORNER DRV RB DEV HI
RB_Y1out=-30.0
SAB SABCND FMA X
RB_X2in=100.0
N N A
4 RB_Y2out=30.0 4
RB_CHG=0 AA NOZZLE ADJUSTABLE 7CORNER DRV FORCED MANUAL
RB_TRK=0
DABO DAB X
FB_TRK=0 MAN
O E
DEM_FB=0
12DV=10.0 AA NOZZLE ADJUSTABLE 7CORNER DRV MANUAL MODE
LCN DABCND ARDV=10.0 CAU X
D ONT1=10.0 T E
INIT FDHEX DFDV=10.0
ONT2=60.0 AA NOZZLE ADJUSTABLE 7CORNER DRV AUTO MODE
STB X
INIT
Y E
AA NOZZLE ADJUSTABLE 7CORNER DRV STANDBY MODE
RBK

5 5
CED
ATPB CAUTX Y CAU CAU AA NOZZLE ADJUSTABLE
APB AUTO PB
SAB T T 7CORNER DRV AUTO
N MNPB
MPB MANUAL PB T=0.0 FGSG09-DRV-AAADJST-7-AT
<FGSG09-WBCAAADJ-LHS>
CED
ACN AUT CND ACND CSTB STB CED
BID SIGNAL ABNORMAL
RSA RB SIG ABN D Y DAU AA NOZZLE ADJUSTABLE
APC-BID-01-D004 <APC-BID-01> MCN B MCN MANU CND MCND ASM T 7CORNER DRV AUTO or STANDBY
D LCN D S FGSG09-DRV-AAADJST-7-AST
DAB D DAUT DAU
O DRD RB SIG DEV H T CED
H STB AA NOZZLE ADJUSTABLE
CED Y 7CORNER DRV STANDBY MODE
INIT MANU
FCB/RUNBACK OPERATE RBK INIT INITIALIZE MAN FGSG09-DRV-AAADJST-7-ST

6 APC-EMG-10-D001 <APC-EMG-10>
6

TITLE AA ADJUSTABLE 7CORNER CONTROL DRIVE Rev.


REMARKS

2
SHEET NO.
MITSUBISHI FGSG09-DRV-
HEAVY INDUSTRIES, LTD AAADJST-7
A B C D E F G H I

AI
AA ADJUSTABLE 8CORNER CD POS
POSN FB I

SV S-PB-3-Set 01HLA58AA714-XQ01
SV SV 01HLA58AA714 PB RPB 0.0 - 100.0% TRK TRACKING SIG
POS MV S-PB-8-Set
I
PB APB
AI FBI FBO CEA
V3 S-PB-10-Set AA ADJUSTABLE 8CORNER CD RB1I TRKS AA ADJUSTABLE 8CORNER CD CAU D1
TRK TRACKING SIG PB MPB
1 POSN DEM1 RB TR SIGNAL T 1
DAB DRIVE ABN S-PB-2 FGSG09-DRV-AAADJST-8-TR<FGSG09-WBCAAADJ-LHS> STB D2
O 01HLA58AA714-YQ01RB Y
RSE RESET COND S-PB-3 0.0 - 100.0% RBSO D3
T
A MAN
SAB SIG ABN S-PB-4
N AI AA NOZZLE ADJUSTABLE 8CORNER DRV AUTO/MANUAL
CAU CONTROL AUTO S-PB-8 AA ADJUSTABLE 8CORNER CD RB2I FQAB FSA <WIND BOX-1>
T POSN DEM2 RB B
STB STAND BY MODE S-PB-9 MV-I-PRH
Y MV-D-PRH 01HLA58AA714-YQ02RB Ain Aout A1
0.0 - 100.0% TRK 999.9uu
S-PB-10 MV-Set DFDH DFD
MAN MANUAL MODE PVC
H Cout A2
AA NOZZLE ADJUSTABLE 8CORNER DRV RB(deg)
AA NOZZLE ADJUSTABLE 8CORNER DRV
<WIND BOX-1> RQAB RSA <WIND BOX-1>
2 B 2
CED DRDH DRD
DPRH IPRH H
FG INITIALIZING INIT
ULMT
FG INITIALIZING
LLMT DRVM FMA
N
OPMT
CEA S OH OL AO
AA ADJUSTABLE 8CORNER CD X Y Ain Aout DEM AO AA NOZZLE ADJUSTABLE
S/S DRIP
CONTROL SIGNAL 8CORNER DRV POSN DEM1
FGSG09-WBCAAADJ-LHS-A004 OH=30 sw OPP
OPC INIT 01HLA58AA714-YQ01
<FGSG09-WBCAAADJ-LHS> OL=-30 FSA X
0.0 - 100.0% B A
CEA
3 AA ADJUSTABLE 1/2/7/8 CORNER AO AA NOZZLE ADJUSTABLE 8CORNER DRV FB SIG ABN 3
SV
CD PROGRAM DEMAND MANUAL MODE AA NOZZLE ADJUSTABLE DFD X
MAN
FGSG09-WBCAAADJ-LHS-A005 8CORNER DRV POSN DEM2 H A
INITIALIZE
<FGSG09-WBCAAADJ-LHS> INIT 01HLA58AA714-YQ02 AA NOZZLE ADJUSTABLE 8CORNER DRV FB DEV HI
0.0 - 100.0% RSA X
OFF
ACN
RPB
ALLRST B A
D
AA NOZZLE ADJUSTABLE 8CORNER DRV RB SIG ABN
DEM_X1in=-30.0
DRD X
DEM_Y1out=0.0
MAN
MANU LARP RSE
DEM_X2in=30.0
H A
T
DEM_Y2out=100.0 AA NOZZLE ADJUSTABLE 8CORNER DRV RB DEV HI
RB_X1in=0.0
FMA X
RB_Y1out=-30.0
SAB SABCND
RB_X2in=100.0
N A
N
4 RB_Y2out=30.0 AA NOZZLE ADJUSTABLE 8CORNER DRV FORCED MANUAL 4
RB_CHG=0
RB_TRK=0
DABO DAB X
FB_TRK=0 MAN
O E
DEM_FB=0
12DV=10.0 AA NOZZLE ADJUSTABLE 8CORNER DRV MANUAL MODE
LCN DABCND ARDV=10.0 CAU X
D ONT1=10.0 T E
INIT FDHEX DFDV=10.0
ONT2=60.0 AA NOZZLE ADJUSTABLE 8CORNER DRV AUTO MODE
STB X
INIT
Y E
AA NOZZLE ADJUSTABLE 8CORNER DRV STANDBY MODE
RBK

5 5
CED
ATPB CAUTX Y CAU CAU AA NOZZLE ADJUSTABLE
APB AUTO PB
SAB T T 8CORNER DRV AUTO
N MNPB
MPB MANUAL PB T=0.0 FGSG09-DRV-AAADJST-8-AT<FGSG09-WBCAAADJ-LHS>
CED
ACN AUT CND ACND CSTB STB CED
BID SIGNAL ABNORMAL
RSA RB SIG ABN D Y DAU AA NOZZLE ADJUSTABLE
APC-BID-01-D004 <APC-BID-01> MCN B MCN MANU CND MCND ASM T 8CORNER DRV AUTO or STANDBY
D LCN D S FGSG09-DRV-AAADJST-8-AST
DAB D DAUT DAU
O DRD RB SIG DEV H T CED
H STB AA NOZZLE ADJUSTABLE
CED Y 8CORNER DRV STANDBY MODE
INIT MANU
FCB/RUNBACK OPERATE RBK INIT INITIALIZE MAN FGSG09-DRV-AAADJST-8-ST

6 APC-EMG-10-D001 <APC-EMG-10>
6

TITLE AA ADJUSTABLE 8CORNER CONTROL DRIVE Rev.


REMARKS

2
SHEET NO.
MITSUBISHI FGSG09-DRV-
HEAVY INDUSTRIES, LTD AAADJST-8
A B C D E F G H I

AI
AA ADJUSTABLE 3CORNER POS
CONTROL DRIVE POSN FB I

SV S-PB-3-Set 01HLA53AA714-XQ01
SV SV 01HLA53AA714 PB RPB 0.0 - 100.0% TRK
POS MV S-PB-8-Set
I
PB APB
AI FBI FBO CEA
V3 S-PB-10-Set AA ADJUSTABLE 3CORNER RB1I TRKS AA ADJUSTABLE 3CORNER CAU D1
TRK TRACKING SIG PB MPB
1 CONTROL DRIVE POSN DEM1 RB CONTROL DRIVE TR SIGNAL T 1
DAB DRIVE ABN S-PB-2 FGSG09-DRV-AAADJST-3-TR STB D2
O 01HLA53AA714-YQ01RB <FGSG09-WBCAAADJ-RHS> Y
RSE RESET COND S-PB-3 0.0 - 100.0% RBSO D3
T
A MAN
SAB SIG ABN S-PB-4
AA NOZZLE ADJUSTABLE 3CORNER DRV AUTO/MANUAL
N AI
CAU CONTROL AUTO S-PB-8 AA ADJUSTABLE 3CORNER RB2I FQAB FSA <WIND BOX-2>
T CONTROL DRIVE POSN DEM2 RB B
STB STAND BY MODE S-PB-9 MV-I-PRH Ain Aout A1
01HLA53AA714-YQ02RB TRK 999.9uu
Y MV-D-PRH
0.0 - 100.0% PVC
S-PB-10 MV-Set DFDH DFD Cout A2
MAN MANUAL MODE
H
AA NOZZLE ADJUSTABLE 3CORNER DRV RB(deg)
AA NOZZLE ADJUSTABLE 3CORNER DRV
<WIND BOX-2> RQAB RSA <WIND BOX-2>
2 B 2
CED DRDH DRD
DPRH IPRH H
FG INITIALIZING INIT
ULMT
FG INITIALIZING
LLMT DRVM FMA
N
OPMT
CEA S OH OL AO
AA ADJUSTABLE 3CORNER CD X Y Ain Aout DEM AO AA NOZZLE ADJUSTABLE
S/S DRIP
CONTROL SIGNAL 3CORNER DRV POSN DEM1
FGSG09-WBCAAADJ-RHS-A001 OH=30 sw OPP
OPC INIT 01HLA53AA714-YQ01
<FGSG09-WBCAAADJ-RHS> OL=-30
0.0 - 100.0% FSA X
3 CEA B A 3
AA ADJUSTABLE 3/4/5/6CORNER AO
SV AA NOZZLE ADJUSTABLE 3CORNER DRV FB SIG ABN
CD PROGRAM DEMAND MANUAL MODE AA NOZZLE ADJUSTABLE
MAN
FGSG09-WBCAAADJ-RHS-A005 3CORNER DRV POSN DEM2 DFD X
<FGSG09-WBCAAADJ-RHS>
INIT
INITIALIZE H A
01HLA53AA714-YQ02
0.0 - 100.0% AA NOZZLE ADJUSTABLE 3CORNER DRV FB DEV HI
ACN ALLRST RSA X
OFF RPB
D B A
DEM_X1in=-30.0 AA NOZZLE ADJUSTABLE 3CORNER DRV RB SIG ABN
DEM_Y1out=0.0
MANU LARP RSE DRD X
MAN DEM_X2in=30.0
T
DEM_Y2out=100.0
H A
RB_X1in=0.0 AA NOZZLE ADJUSTABLE 3CORNER DRV RB DEV HI
RB_Y1out=-30.0
SAB SABCND FMA X
RB_X2in=100.0
N N A
4 RB_Y2out=30.0 4
RB_CHG=0 AA NOZZLE ADJUSTABLE 3CORNER DRV FORCED MANUAL
RB_TRK=0
DABO DAB X
FB_TRK=0 MAN
O E
DEM_FB=0
12DV=10.0 AA NOZZLE ADJUSTABLE CORNER DRV MANUAL MODE
LCN DABCND ARDV=10.0 CAU X
D ONT1=10.0 T E
INIT FDHEX DFDV=10.0
ONT2=60.0 AA NOZZLE ADJUSTABLE CORNER DRV AUTO MODE
STB X
INIT
Y E
AA NOZZLE ADJUSTABLE CORNER DRV STANDBY MODE
RBK

5 5
CED
ATPB CAUTX Y CAU CAU AA NOZZLE ADJUSTABLE
APB AUTO PB
SAB T T 3CORNER DRV AUTO
N MNPB
MPB MANUAL PB T=0.0 FGSG09-DRV-AAADJST-3-AT
<FGSG09-WBCAAADJ-RHS>
CED
ACN AUT CND ACND CSTB STB CED
BID SIG ABNORMAL
RSA RB SIG ABN D Y DAU AA NOZZLE ADJUSTABLE
FGSG06-DI01-D04 <FGSG06-DI01> MCN B MCN MANU CND MCND ASM T 3CORNER DRV AUTO or STANDBY
D LCN D S FGSG09-DRV-AAADJST-3-AST
DAB D DAUT DAU
O DRD RB SIG DEV H T CED
H STB AA NOZZLE ADJUSTABLE
CED Y 3CORNER DRV STANDBY MODE
INIT MANU
RUNBACK / FCB OPERATE RBK INIT INITIALIZE MAN FGSG09-DRV-AAADJST-3-ST

6 FGSG05-DI01-D05 <FGSG05-DI01>
6

TITLE AA ADJUSTABLE 3CORNER CONTROL DRIVE Rev.


REMARKS

2
SHEET NO.
MITSUBISHI FGSG09-DRV-
HEAVY INDUSTRIES, LTD AAADJST-3
A B C D E F G H I

AI POS
AA ADJUSTABLE 4CORNER I
CONTROL DRIVE POSN FB

01HLA54AA714-XQ01 TRK TRACKING SIG


SV S-PB-3-Set
SV SV 01HLA54AA714 PB RPB 0.0 - 100.0%
POS MV S-PB-8-Set
I
PB APB
AI FBI FBO CEA
V3 S-PB-10-Set AA ADJUSTABLE 4CORNER RB1I TRKS AA ADJUSTABLE 4CORNER CAU D1
TRK TRACKING SIG PB MPB
1 CONTROL DRIVE POSN DEM1 RB CONTROL DRIVE TR SIGNAL T 1
DAB DRIVE ABN S-PB-2 FGSG09-DRV-AAADJST-4-TR STB D2
O 01HLA54AA714-YQ01RB <FGSG09-WBCAAADJ-RHS> Y
RSE RESET COND S-PB-3 0.0 - 100.0% RBSO D3
T
A MAN
SAB SIG ABN S-PB-4
AA NOZZLE ADJUSTABLE 4CORNER DRV AUTO/MANUAL
N AI
CAU CONTROL AUTO S-PB-8 AA ADJUSTABLE 4CORNER RB2I FQAB FSA <WIND BOX-2>
T CONTROL DRIVE POSN DEM2 RB B
STB STAND BY MODE S-PB-9 MV-I-PRH
Y MV-D-PRH 01HLA54AA714-YQ02RB Ain Aout A1
0.0 - 100.0% TRK 999.9uu
S-PB-10 MV-Set DFDH DFD
MAN MANUAL MODE PVC
H Cout A2

AA NOZZLE ADJUSTABLE 4CORNER DRV AA NOZZLE ADJUSTABLE 4CORNER DRV RB(deg)


<WIND BOX-2> RQAB RSA
2 B <WIND BOX-2> 2
CED DRDH DRD
DPRH IPRH H
FG INITIALIZING INIT
ULMT
FG INITIALIZING
LLMT DRVM FMA
N
OPMT
CEA S OH OL AO
AA ADJUSTABLE 4CORNER CD X Y Ain Aout DEM AO AA NOZZLE ADJUSTABLE FSA X
S/S DRIP
CONTROL SIGNAL 4CORNER DRV POSN DEM1 B A
FGSG09-WBCAAADJ-RHS-A002 sw OPP
OH=30 OPC INIT 01HLA54AA714-YQ01 AA NOZZLE ADJUSTABLE 4CORNER DRV FB SIG ABN
<FGSG09-WBCAAADJ-RHS> OL=-30 0.0 - 100.0% DFD X
3 CEA H A 3
AA ADJUSTABLE 3/4/5/6CORNER AO
SV AA NOZZLE ADJUSTABLE 4CORNER DRV FB DEV HI
CD PROGRAM DEMAND MANUAL MODE AA NOZZLE ADJUSTABLE
MAN
FGSG09-WBCAAADJ-RHS-A005 4CORNER DRV POSN DEM2 RSA X
<FGSG09-WBCAAADJ-RHS>
INIT
INITIALIZE B A
01HLA54AA714-YQ02
0.0 - 100.0% AA NOZZLE ADJUSTABLE 4CORNER DRV RB SIG ABN
ACN ALLRST DRD X
OFF RPB
D H A
DEM_X1in=-30.0 AA NOZZLE ADJUSTABLE 4CORNER DRV RB DEV HI
DEM_Y1out=0.0
MANU LARP RSE FMA X
MAN DEM_X2in=30.0
T
DEM_Y2out=100.0
N A
RB_X1in=0.0 AA NOZZLE ADJUSTABLE 4CORNER DRV FORCED MANUAL
RB_Y1out=-30.0
SAB SABCND
RB_X2in=100.0
N
4 RB_Y2out=30.0
X 4
RB_CHG=0 MAN
E
RB_TRK=0
DABO DAB
FB_TRK=0 AA NOZZLE ADJUSTABLE 4CORNER DRV MANUAL MODE
O
DEM_FB=0 CAU X
12DV=10.0 T E
LCN DABCND ARDV=10.0
ONT1=10.0 AA NOZZLE ADJUSTABLE 4CORNER DRV AUTO MODE
D
INIT FDHEX DFDV=10.0 STB X
ONT2=60.0 Y E
INIT AA NOZZLE ADJUSTABLE 4CORNER DRV STANDBY MODE

RBK

5 5
CED
ATPB CAUTX Y CAU CAU AA NOZZLE ADJUSTABLE
APB AUTO PB
SAB T T 4CORNER DRV AUTO
N MNPB
MPB MANUAL PB T=0.0 FGSG09-DRV-AAADJST-4-AT
<FGSG09-WBCAAADJ-RHS>
CED
ACN AUT CND ACND CSTB STB CED
BID SIGNAL ABNORMAL
RSA RB SIG ABN D Y DAU AA NOZZLE ADJUSTABLE
APC-BID-01-D004 <APC-BID-01> MCN B MCN MANU CND MCND ASM T 4CORNER DRV AUTO or STANDBY
D LCN D S FGSG09-DRV-AAADJST-4-AST
DAB D DAUT DAU
O DRD RB SIG DEV H T CED
H STB AA NOZZLE ADJUSTABLE
CED Y 4CORNER DRV STANDBY MODE
INIT MANU
FCB/RUNBACK OPERATE RBK INIT INITIALIZE MAN FGSG09-DRV-AAADJST-4-ST

6 APC-EMG-10-D001 <APC-EMG-10>
6

TITLE AA ADJUSTABLE 4CORNER CONTROL DRIVE Rev.


REMARKS

2
SHEET NO.
MITSUBISHI FGSG09-DRV-
HEAVY INDUSTRIES, LTD AAADJST-4
A B C D E F G H I

AI
AA ADJUSTABLE 5CORNER POS
CONTROL DRIVE POSN FB I

SV S-PB-3-Set 01HLA55AA714-XQ01
SV SV 01HLA55AA714 PB RPB 0.0 - 100.0% TRK TRACKING SIG
POS MV S-PB-8-Set
I
PB APB
AI FBI FBO CEA
V3 S-PB-10-Set AA ADJUSTABLE 5CORNER RB1I TRKS AA ADJUSTABLE 5CORNER CAU D1
TRK TRACKING SIG PB MPB
1 CONTROL DRIVE POSN DEM1 RB CONTROL DRIVE TR SIGNAL T 1
DAB DRIVE ABN S-PB-2 FGSG09-DRV-AAADJST-5-TR STB D2
O 01HLA55AA714-YQ01RB <FGSG09-WBCAAADJ-RHS> Y
RSE RESET COND S-PB-3 0.0 - 100.0% RBSO D3
T
A MAN
SAB SIG ABN S-PB-4
AA NOZZLE ADJUSTABLE 5CORNER DRV AUTO/MANUAL
N AI
CAU CONTROL AUTO S-PB-8 AA ADJUSTABLE 5CORNER RB2I FQAB FSA <WIND BOX-2>
T CONTROL DRIVE POSN DEM2 RB B
STB STAND BY MODE S-PB-9 MV-I-PRH Ain Aout A1
01HLA55AA714-YQ02RB TRK 999.9uu
Y MV-D-PRH
0.0 - 100.0% PVC
S-PB-10 MV-Set DFDH DFD Cout A2
MAN MANUAL MODE
H
AA NOZZLE ADJUSTABLE 5CORNER DRV RB(deg)
AA NOZZLE ADJUSTABLE 5CORNER DRV
<WIND BOX-2> RQAB RSA <WIND BOX-2>
2 B 2
CED DRDH DRD
DPRH IPRH H
FG INITIALIZING INIT
ULMT
FG INITIALIZING
LLMT DRVM FMA
N
OPMT
CEA S OH OL AO
AA ADJUSTABLE 5CORNER CD X Y Ain Aout DEM AO AA NOZZLE ADJUSTABLE
S/S DRIP
CONTROL SIGNAL 5CORNER DRV POSN DEM1
FGSG09-WBCAAADJ-RHS-A003 sw OPP
OH=30 OPC INIT 01HLA55AA714-YQ01
<FGSG09-WBCAAADJ-RHS> FSA X
OL=-30 0.0 - 100.0% B A
CEA
3 AA ADJUSTABLE 3/4/5/6CORNER AO AA NOZZLE ADJUSTABLE 5CORNER DRV FB SIG ABN 3
SV
CD PROGRAM DEMAND MANUAL MODE AA NOZZLE ADJUSTABLE DFD X
MAN
FGSG09-WBCAAADJ-RHS-A005 5CORNER DRV POSN DEM2 H A
<FGSG09-WBCAAADJ-RHS> INITIALIZE
INIT 01HLA55AA714-YQ02 AA NOZZLE ADJUSTABLE 5CORNER DRV FB DEV HI
0.0 - 100.0% RSA X
OFF
ACN
RPB
ALLRST B A
D
AA NOZZLE ADJUSTABLE 5CORNER DRV RB SIG ABN
DEM_X1in=-30.0
DRD X
DEM_Y1out=0.0
MAN
MANU LARP RSE
DEM_X2in=30.0
H A
T
DEM_Y2out=100.0 AA NOZZLE ADJUSTABLE 5CORNER DRV RB DEV HI
RB_X1in=0.0
FMA X
RB_Y1out=-30.0
SAB SABCND
RB_X2in=100.0
N A
N
4 RB_Y2out=30.0 AA NOZZLE ADJUSTABLE 5CORNER DRV FORCED MANUAL 4
RB_CHG=0
RB_TRK=0
DABO DAB X
FB_TRK=0 MAN
O E
DEM_FB=0
12DV=10.0 AA NOZZLE ADJUSTABLE 5CORNER DRV MANUAL MODE
LCN DABCND ARDV=10.0 CAU X
D ONT1=10.0 T E
INIT FDHEX DFDV=10.0
ONT2=60.0 AA NOZZLE ADJUSTABLE 5CORNER DRV AUTO MODE
STB X
INIT
Y E
AA NOZZLE ADJUSTABLE 5CORNER DRV STANDBY MODE
RBK

5 5
CED
ATPB CAUTX Y CAU CAU AA NOZZLE ADJUSTABLE
APB AUTO PB
SAB T T 5CORNER DRV AUTO
N MNPB
MPB MANUAL PB T=0.0 FGSG09-DRV-AAADJST-5-AT
<FGSG09-WBCAAADJ-RHS>
CED
ACN AUT CND ACND CSTB STB CED
BID SIGNAL ABNORMAL
RSA RB SIG ABN D Y DAU AA NOZZLE ADJUSTABLE
APC-BID-01-D004 <APC-BID-01> MCN B MCN MANU CND MCND ASM T 5CORNER DRV AUTO or STANDBY
D LCN D S FGSG09-DRV-AAADJST-5-AST
DAB D DAUT DAU
O DRD RB SIG DEV H T CED
H STB AA NOZZLE ADJUSTABLE
CED Y 5CORNER DRV STANDBY MODE
INIT MANU
FCB/RUNBACK OPERATE RBK INIT INITIALIZE MAN FGSG09-DRV-AAADJST-5-ST

6 APC-EMG-10-D001 <APC-EMG-10>
6

TITLE AA ADJUSTABLE 5CORNER CONTROL DRIVE Rev.


REMARKS

2
SHEET NO.
MITSUBISHI FGSG09-DRV-
HEAVY INDUSTRIES, LTD AAADJST-5
A B C D E F G H I

AI
AA ADJUSTABLE 6CORNER CD POS
POSN FB I

SV S-PB-3-Set 01HLA56AA714-XQ01
SV SV 01HLA56AA714 PB RPB 0.0 - 100.0% TRK TRACKING SIG
POS MV S-PB-8-Set
I
PB APB
AI FBI FBO CEA
V3 S-PB-10-Set AA ADJUSTABLE 6CORNER CD RB1I TRKS AA ADJUSTABLE 6CORNER CAU D1
TRK TRACKING SIG PB MPB
1 POSN DEM1 RB CONTROL DRIVE TR SIGNAL T 1
DAB DRIVE ABN S-PB-2 FGSG09-DRV-AAADJST-6-TR<FGSG09-WBCAAADJ-RHS> STB D2
O 01HLA56AA714-YQ01RB Y
RSE RESET COND S-PB-3 0.0 - 100.0% RBSO D3
T
A MAN
SAB SIG ABN S-PB-4
AA NOZZLE ADJUSTABLE 6CORNER DRV AUTO/MANUAL
N AI
CAU CONTROL AUTO S-PB-8 AA ADJUSTABLE 6CORNER CD RB2I FQAB FSA <WIND BOX-2>
T POSN DEM2 RB B
STB STAND BY MODE S-PB-9 MV-I-PRH
Y MV-D-PRH 01HLA56AA714-YQ02RB Ain Aout A1
0.0 - 100.0% TRK 999.9uu
S-PB-10 MV-Set DFDH DFD
MAN MANUAL MODE PVC
H Cout A2

AA NOZZLE ADJUSTABLE 6CORNER DRV AA NOZZLE ADJUSTABLE 6CORNER DRV RB(deg)


<WIND BOX-2> RQAB RSA
2 B <WIND BOX-2> 2
CED DRDH DRD
DPRH IPRH H
FG INITIALIZING INIT
ULMT
FG INITIALIZING
LLMT DRVM FMA
N
OPMT
CEA S OH OL AO
AA ADJUSTABLE 6CORNER CD X Y Ain Aout DEM AO AA NOZZLE ADJUSTABLE
S/S DRIP
CONTROL SIGNAL 6CORNER DRV POSN DEM1
FGSG09-WBCAAADJ-RHS-A004 sw OPP
OH=30 OPC INIT 01HLA56AA714-YQ01
<FGSG09-WBCAAADJ-RHS> FSA X
OL=-30 0.0 - 100.0% B A
CEA
3 AA ADJUSTABLE 3/4/5/6CORNER AO AA NOZZLE ADJUSTABLE 6CORNER DRV FB SIG ABN 3
SV
CD PROGRAM DEMAND MANUAL MODE AA NOZZLE ADJUSTABLE DFD X
MAN
FGSG09-WBCAAADJ-RHS-A005 6CORNER DRV POSN DEM2 H A
<FGSG09-WBCAAADJ-RHS> INITIALIZE
INIT 01HLA56AA714-YQ02 AA NOZZLE ADJUSTABLE 6CORNER DRV FB DEV HI
0.0 - 100.0% RSA X
OFF
ACN
RPB
ALLRST B A
D
AA NOZZLE ADJUSTABLE 6CORNER DRV RB SIG ABN
DEM_X1in=-30.0
DRD X
DEM_Y1out=0.0
MAN
MANU LARP RSE
DEM_X2in=30.0
H A
T
DEM_Y2out=100.0 AA NOZZLE ADJUSTABLE 6CORNER DRV RB DEV HI
RB_X1in=0.0
FMA X
RB_Y1out=-30.0
SAB SABCND
RB_X2in=100.0
N A
N
4 RB_Y2out=30.0 AA NOZZLE ADJUSTABLE 6CORNER DRV FORCED MANUAL 4
RB_CHG=0
RB_TRK=0
DABO DAB X
FB_TRK=0 MAN
O E
DEM_FB=0
12DV=10.0 AA NOZZLE ADJUSTABLE 6CORNER DRV MANUAL MODE
LCN DABCND ARDV=10.0 CAU X
D ONT1=10.0 T E
INIT FDHEX DFDV=10.0
ONT2=60.0 AA NOZZLE ADJUSTABLE 6CORNER DRV AUTO MODE
STB X
INIT
Y E
AA NOZZLE ADJUSTABLE 6CORNER DRV STANDBY MODE
RBK

5 5
CED
ATPB CAUTX Y CAU CAU AA NOZZLE ADJUSTABLE
APB AUTO PB
SAB T T 6CORNER DRV AUTO
N MNPB
MPB MANUAL PB T=0.0 FGSG09-DRV-AAADJST-6-AT
<FGSG09-WBCAAADJ-RHS>
CED
ACN AUT CND ACND CSTB STB CED
BID SIGNAL ABNORMAL
RSA RB SIG ABN D Y DAU AA NOZZLE ADJUSTABLE
APC-BID-01-D004 <APC-BID-01> MCN B MCN MANU CND MCND ASM T 6CORNER DRV AUTO or STANDBY
D LCN D S FGSG09-DRV-AAADJST-6-AST
DAB D DAUT DAU
O DRD RB SIG DEV H T CED
H STB AA NOZZLE ADJUSTABLE
CED Y 6CORNER DRV STANDBY MODE
INIT MANU
FCB/RUNBACK OPERATE RBK INIT INITIALIZE MAN FGSG09-DRV-AAADJST-6-ST

6 APC-EMG-10-D001 <APC-EMG-10>
6

TITLE AA ADJUSTABLE 6CORNER CONTROL DRIVE Rev.


REMARKS

2
SHEET NO.
MITSUBISHI FGSG09-DRV-
HEAVY INDUSTRIES, LTD AAADJST-6
A B C D E F G H I

1 1

2 2

3 3

4 4

5 5

OFF D

6 6
REMARKS
A B C D E F G H I

CEA CED CED


NUMBER OF COAL BURNER X
FIRING
H/L 2 COAL BNR ON <FGSG09-WBCAUX2-01> MFT
CED
FGSG05-6-12-A01 L=1.9 FGSG09-WBC-COMMON-01-D001 FGSG09-DI01-D01 <FGSG09-DI01> WINDBOX DMPR FORCED OPN
<BMS2-5-4> H=2.1 CED CMD
WINDBOX BANKING COMMAND FGSG09-WBC-COMMON-01-D007
CED <FGSG09-DRV-WB2RYDMP-12> <FGSG09-DRV-WB2RYDMP-34>
X APC-ADC-15-D002 <APC-ADC-15> <FGSG09-DRV-WB2RYDMP-56> <FGSG09-DRV-WB2RYDMP-78>
H/L 3 COAL BNR ON <FGSG09-WBCAUX2-01>
1 <FGSG09-DRV-WBAUX2-1> <FGSG09-DRV-WBAUX2-3> 1
L=2.9 FGSG09-WBC-COMMON-01-D002 <FGSG09-DRV-WBCOAL-A1> <FGSG09-DRV-WBCOAL-A2>
H=3.1 <FGSG09-DRV-WBOIL-AB1> <FGSG09-DRV-WBOIL-AB2>
<FGSG09-DRV-WBOIL-AB3> <FGSG09-DRV-WBOIL-AB4>
CED <FGSG09-DRV-WBOIL-AB5> <FGSG09-DRV-WBOIL-AB6>
X <FGSG09-DRV-WBOIL-AB7> <FGSG09-DRV-WBOIL-AB8>
H/L 4 COAL BNR ON <FGSG09-WBCAUX2-01>
L=3.9 FGSG09-WBC-COMMON-01-D003
H=4.1

CED
X
H/L 5 COAL BNR ON <FGSG09-WBCAUX2-01>
L=4.9 FGSG09-WBC-COMMON-01-D004
H=5.1

2 CED 2
X
H/L 6 COAL BNR ON <FGSG09-WBCAUX2-01>
L=5.9 FGSG09-WBC-COMMON-01-D005
H=6.1
CEA CED
CED X
BOILER INPUT DEMAND BID MORE THAN 30% <FGSG09-DRV-WBAUX2-1> <FGSG09-DRV-WBAUX2-3>
X H
H/L 7 OR 8 COAL BNR ON <FGSG09-WBCAUX2-01> <FGSG09-WBCAUX2-01> <FGSG09-WBCCOAL-A-01>
FGSG05-AI01-A02 <FGSG05-AI01> H=198.0 FGSG09-WBC-COMMON-01-D008
L=6.9 FGSG09-WBC-COMMON-01-D006 DB=0.0 <FGSG09-WBCOIL-AB-01>
H=8.1
CED
BID MORE THAN 30%(&SIG
NORM)
CEA FGSG09-WBC-COMMON-01-D009
COAL FLOW A
3 3
APC-MSS-CF-A-1-A003 <APC-MSS-CF-A-1> X1
K1=0.5
CEA K2=0.5 CED
X2 off on CEA BID SIGNAL ABN(&BID MORE
COAL FLOW B
on off CED THAN 30%)
APC-MSS-CF-B-1-A003
T T A/B COAL FLOW(AVE or A or B)
FGSG09-WBC-COMMON-01-D010
<APC-MSS-CF-B-1> BID SIG ABNORMAL
sw sw FGSG09-WBC-COMMON-01-A001 <FGSG09-DRV-WBAUX2-1> <FGSG09-DRV-WBAUX2-3>
CED <FGSG09-WBCOIL-AB-01> FGSG06-DI01-D04 <FGSG06-DI01>
PULV-B & COAL FEEDER-B
START / PURGE IN PROGRESS
BMS1-11B-9-D03
CED
PULV-A & COAL FEEDER-A
START / PURGE IN PROGRESS
BMS1-11A-9-D03
4 4
CEA
COAL FLOW C
APC-MSS-CF-C-1-A003 <APC-MSS-CF-C-1> X1
K1=0.5
K2=0.5
CEA X2 off on CEA
on off
COAL FLOW D T T C/D COAL FLOW(AVE or C or D)
APC-MSS-CF-D-1-A003 <APC-MSS-CF-D-1> sw sw FGSG09-WBC-COMMON-01-A002
CED
PULV-D & COAL FEEDER-D
START / PURGE IN PROGRESS
BMS2-11D-9-D03
CED
5 PULV-C & COAL FEEDER-C 5
START / PURGE IN PROGRESS
BMS2-11C-9-D03 CEA
COAL FLOW G
CEA APC-MSS-CF-G-1-AA003 X1
K1=0.5
COAL FLOW E K2=0.5
APC-MSS-CF-E-1-A003 <APC-MSS-CF-E-1> X1
CEA X2 off on CEA
K1=0.5 on off
K2=0.5 COAL FLOW H T T G/H COAL FLOW(AVE or G or H)
CEA X2 off on CEA APC-MSS-CF-H-1-A003 sw sw FGSG09-WBC-COMMON-01-A004
on off CED
COAL FLOW F T T E/F COAL FLOW(AVE or E or F)
PULV-H & COAL FEEDER-H
APC-MSS-CF-F-1-A003 <APC-MSS-CF-F-1> sw sw FGSG09-WBC-COMMON-01-A003 START / PURGE IN PROGRESS
CED BMS4-11H-9-D03
6 PULV-F & COAL FEEDER-F CED 6
START / PURGE IN PROGRESS PULV-G & COAL FEEDER-G
BMS3-11F-9-D03 START / PURGE IN PROGRESS
CED BMS4-11G-9-D03
PULV-E & COAL FEEDER-E
START / PURGE IN PROGRESS
BMS3-11E-9-D03

TITLE Rev.
WIND BOX DAMPER COMMON LOGIC
REMARKS

2
SHEET NO.
FGSG09-WBC-
MITSUBISHI COMMON-01
HEAVY INDUSTRIES, LTD
A B C D E F G H I

CEA CEA CEA


BURNER WINDBOX 2RY AIR CD X FUEL OIL CD1 WINDBOX DAMPER X FUEL OIL GH1 WINDBOX DAMPER X
(CORNER 1&2) TR SIGNAL H TR SIGNAL H TR SIGNAL H
FGSG09-DRV-WB2RYDMP-12-TR H=10.0 FGSG09-DRV-WBOIL-CD1-TR H=10.0 FGSG09-DRV-WBOIL-GH1-TR H=10.0
CEA <FGSG09-DRV-WB2RYDMP-12> DB=0.0 CEA DB=0.0 CEA DB=0.0
BURNER WINDBOX 2RY AIR CD X FUEL OIL CD3 WINDBOX DAMPER X FUEL OIL GH3 WINDBOX DAMPER X
(CORNER 3&4) TR SIGNAL H TR SIGNAL H TR SIGNAL H
FGSG09-DRV-WB2RYDMP-34-TR H=10.0 01 FGSG09-DRV-WBOIL-CD3-TR H=10.0 FGSG09-DRV-WBOIL-GH3-TR H=10.0
CEA <FGSG09-DRV-WB2RYDMP-34> DB=0.0 CEA DB=0.0 CEA DB=0.0
1 BURNER WINDBOX 2RY AIR CD X FUEL OIL CD5 WINDBOX DAMPER X FUEL OIL GH5 WINDBOX DAMPER X 1
(CORNER 7&8) TR SIGNAL H TR SIGNAL H TR SIGNAL H
FGSG09-DRV-WB2RYDMP-78-TR H=10.0 FGSG09-DRV-WBOIL-CD5-TR H=10.0 FGSG09-DRV-WBOIL-GH5-TR H=10.0
CEA <FGSG09-DRV-WB2RYDMP-78> DB=0.0 CEA DB=0.0 CEA DB=0.0
BURNER WINDBOX 2RY AIR CD X FUEL OIL CD7 WINDBOX DAMPER X FUEL OIL GH7 WINDBOX DAMPER X
(CORNER 5&6) TR SIGNAL H TR SIGNAL H TR SIGNAL H
FGSG09-DRV-WB2RYDMP-56-TR H=10.0 FGSG09-DRV-WBOIL-CD7-TR H=10.0 04 FGSG09-DRV-WBOIL-GH7-TR H=10.0 06
<FGSG09-DRV-WB2RYDMP-56> DB=0.0 CEA DB=0.0 CEA DB=0.0
FUEL OIL CD2 WINDBOX DAMPER X FUEL OIL GH2 WINDBOX DAMPER X
TR SIGNAL H TR SIGNAL H
FGSG09-DRV-WBOIL-CD2-TR H=10.0 FGSG09-DRV-WBOIL-GH2-TR H=10.0
CEA DB=0.0 CEA DB=0.0
CEA FUEL OIL CD4 CORNER WINDBOX X FUEL OIL GH4 CORNER WINDBOX X
AUX-2 1CORNER WINDBOX X DAMPER TR SIGNAL H DAMPER TR SIGNAL H
DAMPER TR SIGNAL H FGSG09-DRV-WBOIL-CD4-TR H=10.0 FGSG09-DRV-WBOIL-GH4-TR H=10.0
FGSG09-DRV-WBAUX2-1-TR H=5.0 CEA DB=0.0 CEA DB=0.0
2 CEA <FGSG09-DRV-WBAUX2-1> DB=0.0 FUEL OIL CD6 WINDBOX DAMPER X FUEL OIL GH6 WINDBOX DAMPER X 2
AUX-2 2CORNER WINDBOX X TR SIGNAL H TR SIGNAL H
DAMPER TR SIGNAL H FGSG09-DRV-WBOIL-CD6-TR H=10.0 FGSG09-DRV-WBOIL-GH6-TR H=10.0
FGSG09-DRV-WBAUX2-2-TR H=5.0 CEA DB=0.0 CEA DB=0.0
CEA <FGSG09-DRV-WBAUX2-2> DB=0.0 FUEL OIL CD8 WINDBOX DAMPER X FUEL OIL GH8 WINDBOX DAMPER X
AUX-2 3CORNER WINDBOX X TR SIGNAL H TR SIGNAL H
DAMPER TR SIGNAL H FGSG09-DRV-WBOIL-CD8-TR H=10.0 FGSG09-DRV-WBOIL-GH8-TR H=10.0
FGSG09-DRV-WBAUX2-3-TR H=5.0 DB=0.0 DB=0.0
CEA <FGSG09-DRV-WBAUX2-3> DB=0.0
AUX-2 4CORNER WINDBOX X CEA
DAMPER TR SIGNAL H FUEL OIL EF1 WINDBOX DAMPER X
FGSG09-DRV-WBAUX2-4-TR H=5.0 02
TR SIGNAL H
CEA <FGSG09-DRV-WBAUX2-4> DB=0.0 FGSG09-DRV-WBOIL-EF1-TR H=10.0
AUX-2 5CORNER WINDBOX X CEA DB=0.0
DAMPER TR SIGNAL H FUEL OIL EF3 WINDBOX DAMPER X
FGSG09-DRV-WBAUX2-5-TR H=5.0 TR SIGNAL H
CEA <FGSG09-DRV-WBAUX2-5>
3 AUX-2 6CORNER WINDBOX X
DB=0.0 FGSG09-DRV-WBOIL-EF3-TR
CEA
H=10.0
DB=0.0
3
DAMPER TR SIGNAL H FUEL OIL EF5 WINDBOX DAMPER X
FGSG09-DRV-WBAUX2-6-TR H=5.0 TR SIGNAL H
CEA <FGSG09-DRV-WBAUX2-6> DB=0.0 FGSG09-DRV-WBOIL-EF5-TR H=10.0
AUX-2 7CORNER WINDBOX X CEA DB=0.0
DAMPER TR SIGNAL H FUEL OIL EF7 WINDBOX DAMPER X
FGSG09-DRV-WBAUX2-7-TR H=5.0 TR SIGNAL H
CEA <FGSG09-DRV-WBAUX2-7> DB=0.0 FGSG09-DRV-WBOIL-EF7-TR H=10.0 05
AUX-2 8CORNER WINDBOX X CEA DB=0.0
DAMPER TR SIGNAL H FUEL OIL EF2 WINDBOX DAMPER X
FGSG09-DRV-WBAUX2-8-TR H=5.0 TR SIGNAL H
<FGSG09-DRV-WBAUX2-8> DB=0.0 FGSG09-DRV-WBOIL-EF2-TR H=10.0
CEA DB=0.0
FUEL OIL EF4 CORNER WINDBOX X
DAMPER TR SIGNAL H
4 FGSG09-DRV-WBOIL-EF4-TR
CEA
H=10.0
DB=0.0
4
FUEL OIL EF6 WINDBOX DAMPER X
CEA TR SIGNAL H
FUEL OIL AB1 WINDBOX DAMPER X FGSG09-DRV-WBOIL-EF6-TR H=10.0
TR SIGNAL H CEA DB=0.0
FGSG09-DRV-WBOIL-AB1-TR H=10.0 FUEL OIL EF8 WINDBOX DAMPER X
CEA <FGSG09-DRV-WBOIL-AB1> DB=0.0 TR SIGNAL H
FUEL OIL AB3 WINDBOX DAMPER X FGSG09-DRV-WBOIL-EF8-TR H=10.0 CED
TR SIGNAL H DB=0.0 ALL COAL WIND BOX DAMPER
FGSG09-DRV-WBOIL-AB3-TR H=10.0 NORMAL
CEA <FGSG09-DRV-WBOIL-AB3> DB=0.0 FGSG09-WBC-COMMON-03-D001
FUEL OIL AB5 WINDBOX DAMPER X <FGSG09-WBC-COMMON-03>
TR SIGNAL H 01
FGSG09-DRV-WBOIL-AB5-TR H=10.0
CEA <FGSG09-DRV-WBOIL-AB5> DB=0.0
FUEL OIL AB7 WINDBOX DAMPER X
5 TR SIGNAL H 5
02
FGSG09-DRV-WBOIL-AB7-TR H=10.0 03
CEA <FGSG09-DRV-WBOIL-AB7> DB=0.0
FUEL OIL AB2 WINDBOX DAMPER X CED
TR SIGNAL H 03 ALL WIND BOX DAMPER NORMAL
FGSG09-DRV-WBOIL-AB2-TR H=10.0
CEA <FGSG09-DRV-WBOIL-AB2> DB=0.0 FGSG09-WBC-COMMON-02-D001
FUEL OIL AB4 CORNER WINDBOX X
DAMPER TR SIGNAL H 04
FGSG09-DRV-WBOIL-AB4-TR H=10.0
CEA <FGSG09-DRV-WBOIL-AB4> DB=0.0
FUEL OIL AB6 WINDBOX DAMPER X
TR SIGNAL H 05
FGSG09-DRV-WBOIL-AB6-TR H=10.0
CEA <FGSG09-DRV-WBOIL-AB6> DB=0.0
FUEL OIL AB8 WINDBOX DAMPER X
6 TR SIGNAL H 06
6
FGSG09-DRV-WBOIL-AB8-TR H=10.0
<FGSG09-DRV-WBOIL-AB8> DB=0.0

TITLE WIND BOX DAMPER FURNACE PURGE Rev.


CONDITION-1
REMARKS

2
SHEET NO.
FGSG09-WBC-
MITSUBISHI COMMON-02
HEAVY INDUSTRIES, LTD
A B C D E F G H I
CEA CEA CEA
COAL A1 WINDBOX DAMPER TR X COAL D1 WINDBOX DAMPER TR X COAL G1 WINDBOX DAMPER TR X
SIGNAL H SIGNAL H SIGNAL H
FGSG09-DRV-WBCOAL-A1-TR H=10.0 FGSG09-DRV-WBCOAL-D1-TR H=10.0 FGSG09-DRV-WBCOAL-G1-TR H=10.0
CEA <FGSG09-DRV-WBCOAL-A1> DB=1.0 CEA DB=1.0 CEA DB=1.0
COAL A2 WINDBOX DAMPER TR X COAL D2 WINDBOX DAMPER TR X COAL G2 WINDBOX DAMPER TR X
SIGNAL H SIGNAL H SIGNAL H
FGSG09-DRV-WBCOAL-A2-TR H=10.0 FGSG09-DRV-WBCOAL-D2-TR H=10.0 FGSG09-DRV-WBCOAL-G2-TR H=10.0
CEA <FGSG09-DRV-WBCOAL-A2> DB=1.0 CEA DB=1.0 CEA DB=1.0
COAL A3 WINDBOX DAMPER TR X COAL D3 WINDBOX DAMPER TR X COAL G3 WINDBOX DAMPER TR X
1 SIGNAL H SIGNAL H SIGNAL H 1
FGSG09-DRV-WBCOAL-A3-TR H=10.0 01 FGSG09-DRV-WBCOAL-D3-TR H=10.0 04 FGSG09-DRV-WBCOAL-G3-TR H=10.0 07
CEA <FGSG09-DRV-WBCOAL-A3> DB=1.0 CEA DB=1.0 CEA DB=1.0
COAL A4 WINDBOX DAMPER TR X COAL D4 WINDBOX DAMPER TR X COAL G4 WINDBOX DAMPER TR X
SIGNAL H CED SIGNAL H CED SIGNAL H CED
FGSG09-DRV-WBCOAL-A4-TR H=10.0 COAL BURNER A ALL FGSG09-DRV-WBCOAL-D4-TR H=10.0 COAL BURNER D ALL FGSG09-DRV-WBCOAL-G4-TR H=10.0 COAL BURNER G ALL
CEA <FGSG09-DRV-WBCOAL-A4> DB=1.0 WINDBOX DAMPER NORMAL CEA DB=1.0 WINDBOX DAMPER NORMAL CEA DB=1.0 WINDBOX DAMPER NORMAL
COAL A5 WINDBOX DAMPER TR X FGSG09-WBC-COMMON-03-D002 COAL D5 WINDBOX DAMPER TR X FGSG09-WBC-COMMON-03-D005 COAL G5 WINDBOX DAMPER TR X FGSG09-WBC-COMMON-03-D008
SIGNAL H SIGNAL H SIGNAL H
FGSG09-DRV-WBCOAL-A5-TR H=10.0 FGSG09-DRV-WBCOAL-D5-TR H=10.0 FGSG09-DRV-WBCOAL-G5-TR H=10.0
CEA <FGSG09-DRV-WBCOAL-A5> DB=1.0 CEA DB=1.0 CEA DB=1.0
COAL A6 WINDBOX DAMPER TR X COAL D6 WINDBOX DAMPER TR X COAL G6 WINDBOX DAMPER TR X
SIGNAL H SIGNAL H SIGNAL H
FGSG09-DRV-WBCOAL-A6-TR H=10.0 FGSG09-DRV-WBCOAL-D6-TR H=10.0 FGSG09-DRV-WBCOAL-G6-TR H=10.0
CEA <FGSG09-DRV-WBCOAL-A6> DB=1.0 CEA DB=1.0 CEA DB=1.0
COAL A7 WINDBOX DAMPER TR X COAL D7 WINDBOX DAMPER TR X COAL G7 WINDBOX DAMPER TR X
2 SIGNAL H SIGNAL H SIGNAL H 2
FGSG09-DRV-WBCOAL-A7-TR H=10.0 FGSG09-DRV-WBCOAL-D7-TR H=10.0 FGSG09-DRV-WBCOAL-G7-TR H=10.0
CEA <FGSG09-DRV-WBCOAL-A7> DB=1.0 CEA DB=1.0 CEA DB=1.0
COAL A8 WINDBOX DAMPER TR X COAL D8 WINDBOX DAMPER TR X COAL G8 WINDBOX DAMPER TR X
SIGNAL H SIGNAL H SIGNAL H
FGSG09-DRV-WBCOAL-A8-TR H=10.0 FGSG09-DRV-WBCOAL-D8-TR H=10.0 FGSG09-DRV-WBCOAL-G8-TR H=10.0
<FGSG09-DRV-WBCOAL-A8> DB=1.0 DB=1.0 DB=1.0
CEA CEA CEA
COAL B1 WINDBOX DAMPER TR X COAL E1 WINDBOX DAMPER TR X COAL H1 WINDBOX DAMPER TR X
SIGNAL H SIGNAL H SIGNAL H
FGSG09-DRV-WBCOAL-B1-TR H=10.0 FGSG09-DRV-WBCOAL-E1-TR H=10.0 FGSG09-DRV-WBCOAL-H1-TR H=10.0
CEA DB=1.0 CEA DB=1.0 CEA DB=1.0
COAL B2 WINDBOX DAMPER TR X COAL E2 WINDBOX DAMPER TR X COAL H2 WINDBOX DAMPER TR X
SIGNAL H SIGNAL H SIGNAL H
FGSG09-DRV-WBCOAL-B2-TR H=10.0 FGSG09-DRV-WBCOAL-E2-TR H=10.0 FGSG09-DRV-WBCOAL-H2-TR H=10.0
CEA DB=1.0 CEA DB=1.0 CEA DB=1.0
3 COAL B3 WINDBOX DAMPER TR
SIGNAL
X
H
COAL E3 WINDBOX DAMPER TR
SIGNAL
X
H
COAL H3 WINDBOX DAMPER TR
SIGNAL
X
H
3
08
FGSG09-DRV-WBCOAL-B3-TR H=10.0 02 FGSG09-DRV-WBCOAL-E3-TR H=10.0 05 FGSG09-DRV-WBCOAL-H3-TR H=10.0
CEA DB=1.0 CEA DB=1.0 CEA DB=1.0
COAL B4 WINDBOX DAMPER TR X COAL E4 WINDBOX DAMPER TR X COAL H4 WINDBOX DAMPER TR X
SIGNAL H CED SIGNAL H CED SIGNAL H CED
FGSG09-DRV-WBCOAL-B4-TR H=10.0 COAL BURNER B ALL FGSG09-DRV-WBCOAL-E4-TR H=10.0 COAL BURNER E ALL FGSG09-DRV-WBCOAL-H4-TR H=10.0 COAL BURNER H ALL
CEA DB=1.0 WINDBOX DAMPER NORMAL CEA DB=1.0 WINDBOX DAMPER NORMAL CEA DB=1.0 WINDBOX DAMPER NORMAL
COAL B5 WINDBOX DAMPER TR X FGSG09-WBC-COMMON-03-D003 COAL E5 WINDBOX DAMPER TR X FGSG09-WBC-COMMON-03-D006 COAL H5 WINDBOX DAMPER TR X FGSG09-WBC-COMMON-03-D009
SIGNAL H SIGNAL H SIGNAL H
FGSG09-DRV-WBCOAL-B5-TR H=10.0 FGSG09-DRV-WBCOAL-E5-TR H=10.0 FGSG09-DRV-WBCOAL-H5-TR H=10.0
CEA DB=1.0 CEA DB=1.0 CEA DB=1.0
COAL B6 WINDBOX DAMPER TR X COAL E6 WINDBOX DAMPER TR X COAL H6 WINDBOX DAMPER TR X
SIGNAL H SIGNAL H SIGNAL H
FGSG09-DRV-WBCOAL-B6-TR H=10.0 FGSG09-DRV-WBCOAL-E6-TR H=10.0 FGSG09-DRV-WBCOAL-H6-TR H=10.0
CEA DB=1.0 CEA DB=1.0 CEA DB=1.0
COAL B7 WINDBOX DAMPER TR X COAL E7 WINDBOX DAMPER TR X COAL H7 WINDBOX DAMPER TR X
4 SIGNAL H SIGNAL H SIGNAL H 4
FGSG09-DRV-WBCOAL-B7-TR H=10.0 FGSG09-DRV-WBCOAL-E7-TR H=10.0 FGSG09-DRV-WBCOAL-H7-TR H=10.0
CEA DB=1.0 CEA DB=1.0 CEA DB=1.0
COAL B8 WINDBOX DAMPER TR X COAL E8 WINDBOX DAMPER TR X COAL H8 WINDBOX DAMPER TR X
SIGNAL H SIGNAL H SIGNAL H
FGSG09-DRV-WBCOAL-B8-TR H=10.0 FGSG09-DRV-WBCOAL-E8-TR H=10.0 FGSG09-DRV-WBCOAL-H8-TR H=10.0
DB=1.0 DB=1.0 DB=1.0
CEA CEA
COAL C1 WINDBOX DAMPER TR X COAL F1 WINDBOX DAMPER TR X
SIGNAL H SIGNAL H 01
FGSG09-DRV-WBCOAL-C1-TR H=10.0 FGSG09-DRV-WBCOAL-F1-TR H=10.0
CEA DB=1.0 CEA DB=1.0
COAL C2 WINDBOX DAMPER TR X COAL F2 WINDBOX DAMPER TR X
SIGNAL H SIGNAL H 02
FGSG09-DRV-WBCOAL-C2-TR H=10.0 FGSG09-DRV-WBCOAL-F2-TR H=10.0
CEA DB=1.0 CEA DB=1.0
5 COAL C3 WINDBOX DAMPER TR X COAL F3 WINDBOX DAMPER TR X 5
SIGNAL H SIGNAL H 03
FGSG09-DRV-WBCOAL-C3-TR H=10.0 03 FGSG09-DRV-WBCOAL-F3-TR H=10.0 06
CEA DB=1.0 CEA DB=1.0
COAL C4 WINDBOX DAMPER TR X COAL F4 WINDBOX DAMPER TR X
SIGNAL H CED SIGNAL H CED
04
FGSG09-DRV-WBCOAL-C4-TR H=10.0 COAL BURNER C ALL FGSG09-DRV-WBCOAL-F4-TR H=10.0 COAL BURNER F ALL CED
CEA DB=1.0 WINDBOX DAMPER NORMAL CEA DB=1.0 WINDBOX DAMPER NORMAL ALL COAL WIND BOX DAMPER
COAL C5 WINDBOX DAMPER TR X FGSG09-WBC-COMMON-03-D004 COAL F5 WINDBOX DAMPER TR X FGSG09-WBC-COMMON-03-D007 NORMAL
SIGNAL H SIGNAL H 05 FGSG09-WBC-COMMON-03-D001
FGSG09-DRV-WBCOAL-C5-TR H=10.0 FGSG09-DRV-WBCOAL-F5-TR H=10.0 <FGSG09-WBC-COMMON-02>
CEA DB=1.0 CEA DB=1.0
COAL C6 WINDBOX DAMPER TR X COAL F6 WINDBOX DAMPER TR X
SIGNAL H SIGNAL H 06
FGSG09-DRV-WBCOAL-C6-TR H=10.0 FGSG09-DRV-WBCOAL-F6-TR H=10.0
CEA DB=1.0 CEA DB=1.0
6 COAL C7 WINDBOX DAMPER TR X COAL F7 WINDBOX DAMPER TR X 6
SIGNAL H SIGNAL H 07
FGSG09-DRV-WBCOAL-C7-TR H=10.0 FGSG09-DRV-WBCOAL-F7-TR H=10.0
CEA DB=1.0 CEA DB=1.0
COAL C8 WINDBOX DAMPER TR X COAL F8 WINDBOX DAMPER TR X
SIGNAL H SIGNAL H 08
FGSG09-DRV-WBCOAL-C8-TR H=10.0 FGSG09-DRV-WBCOAL-F8-TR H=10.0
DB=1.0 DB=1.0

TITLE WIND BOX DAMPER FURNACE PURGE Rev.


CONDITION-2
REMARKS

2
SHEET NO.
FGSG09-WBC-
MITSUBISHI COMMON-03
HEAVY INDUSTRIES, LTD
A B C D E F G H I
CEA CEA CEA
COAL A1 WINDBOX DAMPER TR X COAL D1 WINDBOX DAMPER TR X COAL G1 WINDBOX DAMPER TR X
SIGNAL H SIGNAL H SIGNAL H
FGSG09-DRV-WBCOAL-A1-TR H=5.0 FGSG09-DRV-WBCOAL-D1-TR H=5.0 FGSG09-DRV-WBCOAL-G1-TR H=5.0
CEA <FGSG09-DRV-WBCOAL-A1> DB=1.0 CEA DB=1.0 CEA DB=1.0
COAL A2 WINDBOX DAMPER TR X COAL D2 WINDBOX DAMPER TR X COAL G2 WINDBOX DAMPER TR X
SIGNAL H SIGNAL H SIGNAL H
FGSG09-DRV-WBCOAL-A2-TR H=5.0 FGSG09-DRV-WBCOAL-D2-TR H=5.0 FGSG09-DRV-WBCOAL-G2-TR H=5.0
CEA <FGSG09-DRV-WBCOAL-A2> DB=1.0 CEA DB=1.0 CEA DB=1.0
COAL A3 WINDBOX DAMPER TR X COAL D3 WINDBOX DAMPER TR X COAL G3 WINDBOX DAMPER TR X
1 SIGNAL H SIGNAL H 4
SIGNAL H 7 1
FGSG09-DRV-WBCOAL-A3-TR H=5.0 1 FGSG09-DRV-WBCOAL-D3-TR H=5.0 FGSG09-DRV-WBCOAL-G3-TR H=5.0
CEA <FGSG09-DRV-WBCOAL-A3> DB=1.0 CEA DB=1.0 CEA DB=1.0
COAL A4 WINDBOX DAMPER TR X COAL D4 WINDBOX DAMPER TR X COAL G4 WINDBOX DAMPER TR X
SIGNAL H CED SIGNAL H CED SIGNAL H CED
FGSG09-DRV-WBCOAL-A4-TR H=5.0 COAL BURNER A ALL FGSG09-DRV-WBCOAL-D4-TR H=5.0 COAL BURNER D ALL FGSG09-DRV-WBCOAL-G4-TR H=5.0 COAL BURNER G ALL
CEA <FGSG09-DRV-WBCOAL-A4> DB=1.0 WINDBOX DAMPER CLOSE CEA DB=1.0 WINDBOX DAMPER CLOSE CEA DB=1.0 WINDBOX DAMPER CLOSE
COAL A5 WINDBOX DAMPER TR X FGSG09-WBC-COMMON-04-D001 COAL D5 WINDBOX DAMPER TR X FGSG09-WBC-COMMON-04-D004 COAL G5 WINDBOX DAMPER TR X FGSG09-WBC-COMMON-04-D007
SIGNAL H SIGNAL H SIGNAL H
FGSG09-DRV-WBCOAL-A5-TR H=5.0 FGSG09-DRV-WBCOAL-D5-TR H=5.0 FGSG09-DRV-WBCOAL-G5-TR H=5.0
CEA <FGSG09-DRV-WBCOAL-A5> DB=1.0 CEA DB=1.0 CEA DB=0.0
COAL A6 WINDBOX DAMPER TR X COAL D6 WINDBOX DAMPER TR X COAL G6 WINDBOX DAMPER TR X
SIGNAL H SIGNAL H SIGNAL H
FGSG09-DRV-WBCOAL-A6-TR H=5.0 FGSG09-DRV-WBCOAL-D6-TR H=5.0 FGSG09-DRV-WBCOAL-G6-TR H=5.0
CEA <FGSG09-DRV-WBCOAL-A6> DB=1.0 CEA DB=1.0 CEA DB=1.0
COAL A7 WINDBOX DAMPER TR X COAL D7 WINDBOX DAMPER TR X COAL G7 WINDBOX DAMPER TR X
2 SIGNAL H SIGNAL H SIGNAL H 2
FGSG09-DRV-WBCOAL-A7-TR H=5.0 FGSG09-DRV-WBCOAL-D7-TR H=5.0 FGSG09-DRV-WBCOAL-G7-TR H=5.0
CEA <FGSG09-DRV-WBCOAL-A7> DB=1.0 CEA DB=1.0 CEA DB=1.0
COAL A8 WINDBOX DAMPER TR X COAL D8 WINDBOX DAMPER TR X COAL G8 WINDBOX DAMPER TR X
SIGNAL H SIGNAL H SIGNAL H
FGSG09-DRV-WBCOAL-A8-TR H=5.0 FGSG09-DRV-WBCOAL-D8-TR H=5.0 FGSG09-DRV-WBCOAL-G8-TR H=5.0
<FGSG09-DRV-WBCOAL-A8> DB=1.0 DB=1.0 DB=1.0
CEA CEA CEA
COAL B1 WINDBOX DAMPER TR X COAL E1 WINDBOX DAMPER TR X COAL H1 WINDBOX DAMPER TR X
SIGNAL H SIGNAL H SIGNAL H
FGSG09-DRV-WBCOAL-B1-TR H=5.0 FGSG09-DRV-WBCOAL-E1-TR H=5.0 FGSG09-DRV-WBCOAL-H1-TR H=5.0
CEA DB=1.0 CEA DB=1.0 CEA DB=1.0
COAL B2 WINDBOX DAMPER TR X COAL E2 WINDBOX DAMPER TR X COAL H2 WINDBOX DAMPER TR X
SIGNAL H SIGNAL H SIGNAL H
FGSG09-DRV-WBCOAL-B2-TR H=5.0 FGSG09-DRV-WBCOAL-E2-TR H=5.0 FGSG09-DRV-WBCOAL-H2-TR H=5.0
CEA DB=1.0 CEA DB=1.0 CEA DB=1.0
3 COAL B3 WINDBOX DAMPER TR
SIGNAL
X
H
COAL E3 WINDBOX DAMPER TR
SIGNAL
X
H
COAL H3 WINDBOX DAMPER TR
SIGNAL
X
H
8 3
2 5
FGSG09-DRV-WBCOAL-B3-TR H=5.0 FGSG09-DRV-WBCOAL-E3-TR H=5.0 FGSG09-DRV-WBCOAL-H3-TR H=5.0
CEA DB=1.0 CEA DB=1.0 CEA DB=1.0
COAL B4 WINDBOX DAMPER TR X COAL E4 WINDBOX DAMPER TR X COAL H4 WINDBOX DAMPER TR X
SIGNAL H CED SIGNAL H CED SIGNAL H CED
FGSG09-DRV-WBCOAL-B4-TR H=5.0 COAL BURNER B ALL FGSG09-DRV-WBCOAL-E4-TR H=5.0 COAL BURNER E ALL FGSG09-DRV-WBCOAL-H4-TR H=5.0 COAL BURNER H ALL
CEA DB=1.0 WINDBOX DAMPER CLOSE CEA DB=0.0 WINDBOX DAMPER CLOSE CEA DB=1.0 WINDBOX DAMPER CLOSE
COAL B5 WINDBOX DAMPER TR X FGSG09-WBC-COMMON-04-D002 COAL E5 WINDBOX DAMPER TR X FGSG09-WBC-COMMON-04-D005 COAL H5 WINDBOX DAMPER TR X FGSG09-WBC-COMMON-04-D008
SIGNAL H SIGNAL H SIGNAL H
FGSG09-DRV-WBCOAL-B5-TR H=5.0 FGSG09-DRV-WBCOAL-E5-TR H=5.0 FGSG09-DRV-WBCOAL-H5-TR H=5.0
CEA DB=1.0 CEA DB=1.0 CEA DB=1.0
COAL B6 WINDBOX DAMPER TR X COAL E6 WINDBOX DAMPER TR X COAL H6 WINDBOX DAMPER TR X
SIGNAL H SIGNAL H SIGNAL H
FGSG09-DRV-WBCOAL-B6-TR H=5.0 FGSG09-DRV-WBCOAL-E6-TR H=5.0 FGSG09-DRV-WBCOAL-H6-TR H=5.0
CEA DB=1.0 CEA DB=1.0 CEA DB=1.0
COAL B7 WINDBOX DAMPER TR X COAL E7 WINDBOX DAMPER TR X COAL H7 WINDBOX DAMPER TR X
4 SIGNAL H SIGNAL H SIGNAL H 4
FGSG09-DRV-WBCOAL-B7-TR H=5.0 FGSG09-DRV-WBCOAL-E7-TR H=5.0 FGSG09-DRV-WBCOAL-H7-TR H=5.0
CEA DB=1.0 CEA DB=1.0 CEA DB=1.0
COAL B8 WINDBOX DAMPER TR X COAL E8 WINDBOX DAMPER TR X COAL H8 WINDBOX DAMPER TR X
SIGNAL H SIGNAL H SIGNAL H
FGSG09-DRV-WBCOAL-B8-TR H=5.0 FGSG09-DRV-WBCOAL-E8-TR H=5.0 FGSG09-DRV-WBCOAL-H8-TR H=5.0
DB=1.0 DB=1.0 DB=1.0
CEA CEA
COAL C1 WINDBOX DAMPER TR X COAL F1 WINDBOX DAMPER TR X
SIGNAL H SIGNAL H
FGSG09-DRV-WBCOAL-C1-TR H=5.0 FGSG09-DRV-WBCOAL-F1-TR H=5.0
CEA DB=1.0 CEA DB=1.0
COAL C2 WINDBOX DAMPER TR X COAL F2 WINDBOX DAMPER TR X
SIGNAL H SIGNAL H 1
FGSG09-DRV-WBCOAL-C2-TR H=5.0 FGSG09-DRV-WBCOAL-F2-TR H=5.0
CEA DB=1.0 CEA DB=1.0
5 COAL C3 WINDBOX DAMPER TR X COAL F3 WINDBOX DAMPER TR X 5
2
SIGNAL H 3
SIGNAL H 6
FGSG09-DRV-WBCOAL-C3-TR H=5.0 FGSG09-DRV-WBCOAL-F3-TR H=5.0
CEA DB=1.0 CEA DB=1.0 3
COAL C4 WINDBOX DAMPER TR X COAL F4 WINDBOX DAMPER TR X
SIGNAL H CED SIGNAL H CED
FGSG09-DRV-WBCOAL-C4-TR H=5.0 COAL BURNER C ALL FGSG09-DRV-WBCOAL-F4-TR H=5.0 COAL BURNER F ALL
4
CEA DB=1.0 WINDBOX DAMPER CLOSE CEA DB=1.0 WINDBOX DAMPER CLOSE CED
COAL C5 WINDBOX DAMPER TR X FGSG09-WBC-COMMON-04-D003 COAL F5 WINDBOX DAMPER TR X FGSG09-WBC-COMMON-04-D006 ALL WINDBOX DAMPER
SIGNAL H SIGNAL H CLOSED
FGSG09-DRV-WBCOAL-C5-TR H=5.0 FGSG09-DRV-WBCOAL-F5-TR H=5.0 5 FGSG09-WBC-COMMON-04-D009
CEA DB=1.0 CEA DB=1.0
COAL C6 WINDBOX DAMPER TR X COAL F6 WINDBOX DAMPER TR X
SIGNAL H SIGNAL H 6
FGSG09-DRV-WBCOAL-C6-TR H=5.0 FGSG09-DRV-WBCOAL-F6-TR H=5.0
CEA DB=1.0 CEA DB=1.0
6 COAL C7 WINDBOX DAMPER TR X COAL F7 WINDBOX DAMPER TR X
7
6
SIGNAL H SIGNAL H
FGSG09-DRV-WBCOAL-C7-TR H=5.0 FGSG09-DRV-WBCOAL-F7-TR H=5.0
CEA DB=1.0 CEA DB=1.0 8
COAL C8 WINDBOX DAMPER TR X COAL F8 WINDBOX DAMPER TR X
SIGNAL H SIGNAL H
FGSG09-DRV-WBCOAL-C8-TR H=5.0 FGSG09-DRV-WBCOAL-F8-TR H=5.0
DB=1.0 DB=1.0

TITLE COAL WIND BOX DAMPER CLOSE Rev.


STATUS
REMARKS

2
SHEET NO.
FGSG09-WBC-
MITSUBISHI COMMON-04
HEAVY INDUSTRIES, LTD
APPENDIX-1 : FUNCTION BLOCK DESCRIPTION

1 AND Logic Conjuction 11 TON Trigger ON 27 ADD Simple Addition 41 MED Medium Value Select 51 PI Proportion Integral (CSR)
CSR=Conventional Saturation Recovery type
60 DT Arithmetic Cycle 126 NLD Null Digital
X 01 Ts The element which nothing
X 01 ON outputs when all input Output of the value that is X1 Output of the value added
conditions are all ON.
X Y Outputs ON only for one
+ added with multiple input
Output of the intermediate with the proportional and
The arithmetic cycle is fetched
does.
Temporarily, it uses when a
X 02 Y signals (X1-n). X2 Y X Y Y for the logic sheet.. X
Y
X 02
20 input conditions at the
arithmetic cycle when the MED value among three analog input PI integral calculation of the t D signal line is output or when
input signal is turned ON. X3 signals. input signal. the condition of the signal line
Xn Xn Input conditions are 20 at the Tr Outputs(sec)
maximum. ☆The movement of the is watched.
maximum.
partition emphasis of the (Digital)
operation end is done.
2 OR Logic Sum 12 TOF Trigger OFF 28 SUM Addition 42 LMT Restriction of
Upper/Lower Limit 102 T Simple Analog Switch 127 NLA Null Analog
(ⅰ)Ts=0
The element which nothing
ON outputs even when one Output of the value that is add Output of the input signal 1 K:Proportional gain Output of switching two analog
X 01 X1 Y  KX   Xdt sw does.
ON input condition is two input signals multiple by multiplied by upper/lower-limit T T:Integral time constant(sec) input according to the
X Y Outputs ON only for one Y X Temporarily, it uses when a
Y provided. each gain to the signals. X Y restriction. HL:Output upper-limit value
X 02
arithmetic cycle when the X2 Σ (ⅱ)Ts=1 LL:Output lower-limit value
off
T Y switching conditions.
A signal line is output or when
input signal is turned OFF. sw:Condition input the condition of the signal line
20 input conditions at the K1:Gain of input signal X1 H:Upper-limit signal
Xn Y  Tr off:Selection signal when the input is OFF is watched.
maximum. K2:Gain of input signal X2 L :Lower-limit signal on on:Selection signal when the input is ON
(Analog)
on
Tracking Ts
3 NOT Logic Negation 17 HLM High-Low Monitor 29 DLT Subtraction 43 LIN Linearizer
sw X
off
X
103 TR Analog Switch with Rate 129 THD Through Digital
Output by liner interpolation of O
Outputs ON when the analog Controler sw Output of switching two analog input according
+ two-point polyline for input input to the switching conditions
OFF (Y=0) outputs for ON input signal exceeds the Y Output is changed by the set rate at switching Output of input for digital input
X Y signal. Y
(X=1) input condition. X Y upper/lower-limit setting Y The value that a minus signal time. signals without any action.
X Y
H/L value. - was subtracted from the plus LIN Controler
output Tr(tracking)
off
TR Y sw:Condition input
off:Selection signal when the condition input is
X Y
It is installed in a line to need a
Used for the range change of L value
ON (Y=1) outputs for OFF signal is output. OFF manual set, and adjusted from
AI singnals on:Selection signal when the condition input is
(X=0) input condition. H:Upper limit value on ON this element. (Digital)
X1/Y1:Lower limit
L:Lower limit value Ron:off on Roff: on off
X2/Y2:Upper limit
Analog Switch
4 XOR Exclusive OR 18 HMH High Monitor with Hysteresis 30 MUL Multiplication 44 LAG Primary Delay 52 PIQ Proportion Integral (QSR)
QSR=Quick Saturation Recovery type
104 TRD with Defferential Rate 130 THA Through analog
Outputs ON when the analog Ts Output of switching two analog input according
ON outputs for two input signal exceeds the X Output of the value that is sw to the switching conditions
Output of input for Analog
X1 Output of the value added with Output is changed by the set rate at switching
different input conditions. upper-limit setting value. performed with primary-delay time. input signals without any
X1 X Y Y X Y the proportional and integral X Y
Y off Y Should be reduced according to the rate set

X2 XOR Y
The setting value has the
X2 × Output of the multiplication LAG calculation for the input signal. PIQ calculation of the input signal. TRD with deviation of target input at the time of
action.
OFF outputs when two H hysteresis. value of two input signals.
TP ☆It uses as a general
switch. It is installed in a line to need a
input conditions are the T:Primary-delay time(sec) Tr manual set, and adjusted from
controller. on sw:Condition input
same. H:High setting value TP:Through pass(TP=1) Ron:off on Change rate(/min) this element. (Analog)
Roff:on off Change rate(/min)
DB:Hysteresis width on
5 SSR Set / Reset 19 LMH Low Monitor with Hysteresis 31 DIV Division 46 RLT Variation Rate Limiter Switch sw off 205 QGD Quality Fetch Digital
Outputs ON when the analog (ⅰ)Ts=0 K:Proportional gain on
input signal exceeds the X Output is acquired with the T:Integral time constant(sec) The quality information of the
N/ 1 Input 2
T
S(X1) S(Y1) Set signals are prioritized lower-limit setting value.
Output of the division value of
input signal multipled by Y  KX  Xdt HL:Output upper-limit value input signal is output.
Y Y AE
S
R(Y2)
X Y The setting value has the /D ÷ two input signals.
TP
V 2
designated change rate. LL:Output lower-limit value
Input 1
off X
QGD CN ON output is abnormal, OFF output is normal
AE:Data access incapability
R(X2) Y1=1, Y2=0 when two inputs L hysteresis.
N/:Numerator
(ⅱ)Ts=1 DS CN:Scan exclusion
R are ON. RI:Increasing-direction change rate(/min)
UK DS:Data set
L:Low setting value
/D:Denominator RD:Decreasing-direction change rate(/min) Y  Tr Output Y
UK:Unfixed my element output
TP:Through pass(TP=1) CE CE:Block arithmetic error
DB:Hysteresis width Ron Roff

6 SRR Set / Reset 21 DHL Deviation Monitor 33 ROT Square Root Extraction 47 MAV Moving Average
Tracking Ts
on 105 OLD Previous Digital Value 206 QGA Quality Fetch Analog
Outputs ON when the off
Output of move average value sw X RO The quality information of the input signal is
difference of two input signals X output.
of the input signal for the Controller O RU ON output is abnormal, OFF output is normal
S(X1) S(Y1) + exceeds the upper/lower
X Y X Y designate period. input Y AE
S Reset signals are prioritized Y
Y setting values. √ Output of square-root of input MAV Used for filtering of AI signals etc.
T:Time width(It is set up in the sampling
X
OLD Y Output of digital input signals X
QGA CN RO:Range-over upper limit
RU:Range-over lower limit
R(X2) R(Y2) - H/L +:Addition side input(X1) signals. number of times 64)
Controller by lagging one arithmetic cycle. DS AE:Data access incapability
R Y1=0, Y2=1 when two inputs output Tr(tracking)
CN:Scan exclusion
-:Subtraction side input(X2) DT:Sampling period(Initial value 0.1sec) L value UK
are ON. DS:Data set
H:Upper limit value 1 t CE
L :Lower limit value
Y 
T tT Xdt UK:Unfixed my element output
CE:Block arithmetic error

7 OND On Delay Timer 22 RHL Change-Rate Monitor 38 SG Signal Generator 48 DLY Dead Time 53 D Differential 106 OLA Previous Analog Value 403 PB PB Operation
The input signal is output TP The value that the primary
Outputs ON after a Outputs ON when the absolute X delay of the input differential
Output of the analog signal delayed for the designated value was calculated is output.
X designated period of time value of the analog input
Y X R Y Y designated in the parameter. Y time. When there is no change in the PB operation signals are
when an input turned ON. signal's change rate exceeds SG TP e-LS X
D
Y
input, output is made 0 by the
X
OLA
Y Output of analog input signals X
PB
Y
output from OPS as One-
H/L the setting value. primary delay. by lagging one arithmetic cycle.
W TP:Through pass(TP=1) Shot.
T:Timer setting(sec) Time constants(sec.)
S:Setting value T:Delay(sec)
W:Past time(sec) R:Change rate value(sec) K:Gain
DT:Sampling time(sec) TP:Reset SW

8 OFD Off Delay Timer 23 MN M out of N 39 HSL High-value Selection 49 P Proportion Control Reset
sw
TP on
off 118 MCD Macro I/F Digital 404 S/S
Outputs ON when more than M (ⅰ)Tp=0
X 01 X 01 Increasing/decreasing
Outputs OFF after a out of multiple input Output of the maximum value Ts X
designated period of time contditions (X1-n) are ON. from multiple analog input
The value is output with the Y  K X X
MCD The external interface
operations are received from
X Y X Y input signal multiplied by 1  Ts Input 0 S OPS for analog values.
when an input turned OFF. X 02 Y Used for 2 out of 3 judgement X 02 Y signals (X1-n). P elements of Macro-block
S/S Y
M/N routes, etc. >H poroportional gain.
(ⅱ)Tp=1 Y signals.(Digital) X
S:Data set signal
W T:Timer setting(sec) n M:Parameter Xn Input signals are 20 at the MCD
X K:Proportional gain Y  0 Y sw X:Tracking value
W:Past time(sec) Input conditions are 20 at the maximum. Output 0 sw:Data set permission
maximum.
10 TDW Time Delay Wipe Out 26 FLC Flicker 40 LSL Low-value Selection 55 FX Polyline Function 54 AM Analog Memory 120 MCA Macro I/F Analog
It uses well as setting values by
Outputs ON when the input Output of flicker signals that X 01 Output of the value that is Ts increasing/decreasing push buttons.
Output of the minimum value performed with function When the increase or decrease demand input X
signal are turned ON. repeat ON/OFF for designated MCA
X Y from multiple analog input calculation for the input signal. I goes ON, increases or decreases the analog The external interface
Outputs OFF after the X Y time. X Y Y signal output.
signals (X1-n). AM elements of Macro-block
designed time continuation X 02
<L Y FX X1~X10:X-axis input
D
signals.(Analog)
even if the input signal is ON. X:Flicker ON(X=1),OFF(X=0) I:Increasing command Y
W Xn Input signals are 20 at the Y1~Y10:Y-axis output Tr D:Decreasing command MCA
T:Timer setting(sec) on:Output ON time(sec) Polyline pointas are 10 at the Ts:Tracking condition Tr:Tracking value
maximum. R:Change rate(/min)
W:Past time(sec) off:Output OFF time(sec) maximum. H/L:Output upper/lower-limit value

DI 107 DI
CED 112 CED
Input signal side of digital
CDI 137 CDI
CONTROL CONTROL
Digital signal line (thin line) Digital input signal from
connect between sheets X 201 DAN PLATE2
Digital input signal communication interface with A PLATE1
Analog signal line (bold line) CED:Digital other companies device Digital warning
124 CID AI CED 113 CED
Output signal side of digital
CAI 135 CAI
202 AAN
Input signal side of connect 108 AI Analog input signal from X
1 Analog input signal connect between sheets communication interface with A Anlog warning
inside sheet S-PB-1
FD-1 S-PB-1
CID CED:Digital other companies device
125 CID X 203 EVT MV
S-PB-2 S-PB-2

Output signal side of connect DO CEA 114 CEA CDO 138 CDO E Event PV
S-PB-3 FD-2 S-PB-3
1 110 DO Input signal side of analog Digital output signal from S-PB-4
inside sheet Digital output signal connect between sheets communication interface with FD-3
S-PB-4

CID SV S-PB-5 S-PB-5


other companies device
AO
CEA:Analog
CAO 136 CAO
S-PB-6 FD-4 S-PB-6 Netmation IDOL++
111 AO CEA 115 CEA Analog output signal from
S-PB-7 S-PB-7

Analog output signal


Output signal side of analog
connect between sheets communication interface with
S-PB-8

S-PB-9
FD-5 S-PB-8

S-PB-9
Main Control Elements List
other companies device
CEA:Analog MV-INC

MV-DEC
SV-INC

SV-DEC S-PB-10 S-PB-10 (Outline)


Appendix-1 Function Block Description

Appendix-1 Function Block Description


Appendix-1 describes the details of function blocks.
• Function
Functions and symbols for function blocks are explained here.
• Input/Output
This section describes codes, types and description of function block input/output signals.
No Type Description
1 A Analog
2 D Digital
3 I Integer
4 EA Event analog
5 ED Event digital

• Setting
This section describes properties of function block.
• Control parameter
This section describes parameters and default values of function block.
• Action
This section describes outline of action..
• Quality handling/Processing at initialization
This section describes quality propagation information and processing at initialization.

Appendix-1 Function Block Description


ELEMENT Logic Conjunction CODE 1 SYMBOL AND
PROCESS FUNCTIONS
FUNCTION
• Output of logical conjunction for multiple input conditions
• 20 input conditions at the maximum
• ON output only when all the input conditions are all ON
• OFF output even when there is only one OFF input condition

INPUT/OUTPUT

No Code Type Description


No.1 input X01 D Condition input (Max.20)
No.1 output Y D Logical Conjunction

SETTING
設定項目

CONTROL PARAMETER
Nothing

ACTION

Example of 3 condition input


EE

Input1

Input1

Input3

Output of logical conjunction for 3 input signals

QUALITY HANDLING/PROCESSING AT INITIALIZATION


【Quality Handling】No processing in consideration of quality
【Processing at Initialization】Nothing in particular

Appendix-1 Function Block Description


ELEMENT Logical Sum CODE 2 SYMBOL OR
PROCESS FUNCTIONS
FUNCTION
• Output of logical sum for multiple input conditions
• 20 input conditions at the maximum
• ON output even when one ON input condition is provided.
• OFF output only when all the input conditions are OFF.

INPUT/OUTPUT

No Code Type Description


No.1 input X01 D Condition input (Max.20)
No.1 output Y D Logical sum

SETTING
設定項目

CONTROL PARAMETER
Nothing

ACTION

Example of 3 condition input


EE

Input1

Input1

Input3

Output

Output of logical sum for 3 input signals

QUALITY HANDLING/PROCESSING AT INITIALIZATION


【Quality Handling】No processing in consideration of quality
【Processing at Initialization】Nothing in particular

Appendix-1 Function Block Description


ELEMENT Logical Negation CODE 3 SYMBOL NOT
PROCESS FUNCTIONS
FUNCTION
• Output of signals with reversed input condition
• OFF output for ON input conditions
• ON output for OFF input conditions
INPUT/OUTPUT

No Code Type Description


No.1 input X D Condition input
No.1 output Y D Logical Negation

SETTING
設定項目

CONTROL PARAMETER
Nothing

ACTION

Input

Output

Output of signals with reversed input signals

QUALITY HANDLING/PROCESSING AT INITIALIZATION


【Quality Handling】No processing in consideration of quality
【Processing at Initialization】Nothing in particular

Appendix-1 Function Block Description


ELEMENT Exclusive OR CODE 4 SYMBOL XOR
PROCESS FUNCTIONS
FUNCTION
• Output of exclusive OR for 2 input signals
• ON output for two different input conditions
• OFF output when two input conditions are the same.
INPUT/OUTPUT

No Code Type Description


No.1 input X1 D Input signals
No.2 input X2 D Input signals
No.1 output Y D Exclusive OR

SETTING
設定項目

CONTROL PARAMETER
Nothing

ACTION

Input1
Input1 Input2 Output
0 0 0
Input2
0 1 1
1 0 1
1 1 0
Output

QUALITY HANDLING/PROCESSING AT INITIALIZATION


【Quality Handling】No processing in consideration of quality
【Processing at Initialization】Nothing in particular

Appendix-1 Function Block Description


ELEMENT Set/Reset for Prioritized Set CODE 5 SYMBOL SSR
PROCESS FUNCTIONS
FUNCTION • ON output for ON set signals/OFF output for ON reset signals
• Retaining previous output for OFF set/reset signals
• Set signals are prioritized when both set/reset signals are ON.
• Used as warning memory to prevent abnormal status from resetting while the status is continuing.
Notice
• Arithmetic starts from the status the initial value designated by the parameter is output, when set/
reset signals are OFF for arithmetic-start initial state.
INPUT/OUTPUT

No Code Type Description


No.1 input S D Set-condition input
No.2 input R D Reset-condition input
No.1 output S D Arithmetic output
No.2 output R D NOT output of S

SETTING
設定項目

CONTROL PARAMETER

Parameter Abbr. Default Value External Input Range


Initial value IV 0 False:0,True:1

ACTION

Set Set Reset Output


0 0 Retaining
current state
Reset 0 1 0
1 0 1

Output 1 1 1

QUALITY HANDLING/PROCESSING AT INITIALIZATION


【Quality Handling】No processing in consideration of quality
【Processing at Initialization】Values set by the parameter will be initial values when both S/R are OFF.

Appendix-1 Function Block Description


ELEMENT Set/Reset for Prioritized Reset CODE 6 SYMBOL SRR
PROCESS FUNCTIONS
FUNCTION
• ON output for ON set signals/OFF output for ON reset signals
• Retaining previous output for OFF set/reset signals
• Reset signals are prioritized when both set/reset signals are ON.
• Used for mode switching by automatic/manual push buttons, etc.
Notice
• Arithmetic starts from the status the initial value designated by the parameter is output,
when set/reset signals are OFF for arithmetic-start initial state.
INPUT/OUTPUT

No Code Type Description


No.1 input S D Set-condition input
No.2 input R D Reset-condition input
No.1 output S D Arithmetic output
No.2 output R D NOT output of S

SETTING
設定項目

CONTROL PARAMETER

Parameter Abbr. Default Value External Input Range


Initial value IV 0 False:0,True:1

ACTION

Set Set Reset Output


0 0 Retaining
current state
Reset 0 1 0
1 0 1
1 1 0
Output

QUALITY HANDLING/PROCESSING AT INITIALIZATION


【Quality Handling】No processing in consideration of quality
【Processing at Initialization】Values set by the parameter will be initial values when both S/R are OFF.

Appendix-1 Function Block Description


ELEMENT ON Delay Timer CODE 7 SYMBOL OND
PROCESS FUNCTIONS
FUNCTION
• ON output if input signals have been continuously ON for the designated period after
they were turned ON.
• OFF output simultaneously when input signals are turned OFF.
Notice
• ON output when input signals are ON for arithmetic-start initial status.
INPUT/OUTPUT

No Code Type Description


No.1 input X D Input signal
No.2 input T A Timer count(sec.)(Parameter External Input)
No.1 output Y D Output after delay
No.2 output W A Remaining time (sec.)

SETTING
設定項目

CONTROL PARAMETER

Parameter Abbr. Default Value External Input Range


Timer count(sec.) T 0 Possible 0.0 ≦ T ≦ 2147483.5

ACTION

Input

Output
T T

QUALITY HANDLING/PROCESSING AT INITIALIZATION


【Quality Handling】The timer setting is negative or larger than 2147483.5 seconds, the quality of own-block
output should be a block arithmetic error.
【Processing at Initialization】If there is timer through pass at initialization, the output will be OFF even when
the input is ON.

Appendix-1 Function Block Description


ELEMENT OFF Delay Timer CODE 8 SYMBOL OFD
PROCESS FUNCTIONS
FUNCTION
• OFF output if input signals have been continuously OFF for the designated time after
they were turned OFF.
• ON output simultaneously when input signals are turned ON.

INPUT/OUTPUT

No Code Type Description


No.1 input X D Input signal
No.2 input T A Timer count(sec.)(Parameter External Input)
No.1 output Y D Output after delay
No.2 output W A Remaining time (sec.)

SETTING
設定項目

CONTROL PARAMETER

Parameter Abbr. Default Value External Input Range


Timer count(sec.) T 0 Possible 0.0 ≦ T ≦ 2147483.5

ACTION

Input

Output
T T

QUALITY HANDLING/PROCESSING AT INITIALIZATION


【Quality Handling】The timer setting is negative or larger than 2147483.5 seconds, the quality of own-block
output should be a block arithmetic error.
【Processing at Initialization】Nothing in particular

Appendix-1 Function Block Description


ELEMENT One Shot Pulse CODE 9 SYMBOL OSP
PROCESS FUNCTIONS
FUNCTION
• ON output when input signals are turned ON. OFF output after the signals are
continuously ON for the designated time.
• ON output should be continued for the designated time even when the input is turned
OFF within the time.
INPUT/OUTPUT

No Code Type Description


No.1 input X D Input signal
No.2 input T A Timer count(sec.)(Parameter External Input)
No.3 input TP D Forced reset
No.1 output Y D One shot output
No.2 output W A Remaining time (sec.)

SETTING
設定項目

CONTROL PARAMETER

Parameter Abbr. Default Value External Input Range


Timer count(sec.) T 0 Possible 0.0 ≦ T ≦ 2147483.5

ACTION

Input signal (X)

Output signal (Y)


Tim er setting (param eter)

QUALITY HANDLING/PROCESSING AT INITIALIZATION


【Quality Handling】The timer setting is negative or larger than 2147483.5 seconds, the quality of own-block
output should be a block arithmetic error.
【Processing at Initialization】If there is timer through pass at initialization, the output will be OFF even when
the input is ON.

Appendix-1 Function Block Description


ELEMENT Time Delay Wipe Out CODE 10 SYMBOL TDW
PROCESS FUNCTIONS
FUNCTION
• ON output when input signals are turned ON. OFF output after the signals are
continuously ON for the designated time.
• OFF output immediately after the input is turned OFF.
• Used for creation of One-Shot startup command signals, etc.
INPUT/OUTPUT

No Code Type Description


No.1 input X D Input signal
No.2 input T A Timer count(sec.)(Parameter External Input)
No.1 output Y D One shot output
No.2 output W A Remaining time (sec.)

SETTING
設定項目

CONTROL PARAMETER

Parameter Abbr. Default Value External Input Range


Timer count(sec.) T 0 Possible 0.0 ≦ T ≦ 2147483.5

ACTION

Input

Output
T T

QUALITY HANDLING/PROCESSING AT INITIALIZATION


【Quality Handling】The timer setting is negative or larger than 2147483.5 seconds, the quality of own-block
output should be a block arithmetic error.
【Processing at Initialization】If there is timer through pass at initialization, the output will be OFF even when
the input is ON.

Appendix-1 Function Block Description


ELEMENT Trigger ON CODE 11 SYMBOL TON
PROCESS FUNCTIONS
FUNCTION
• ON output only for one arithmetic cycle when the input signal is turned ON.
• Used for creation of One-Shot startup command signals, etc.
Notice
• While TDW is used as startup command for arithmetic logic that are not
• synchronized TON is used as startup command for arithmetic logic
• synchronized in the same control system.

INPUT/OUTPUT

No Code Type Description


No.1 input X D Input signal
No.1 output Y D Trigger ON

SETTING
設定項目

CONTROL PARAMETER
Nothing

ACTION

Input

Output

Arithmetic cycle

QUALITY HANDLING/PROCESSING AT INITIALIZATION


【Quality Handling】No processing in consideration of quality
【Processing at Initialization】OFF output even when the input is ON.

Appendix-1 Function Block Description


ELEMENT Trigger OFF CODE 12 SYMBOL TOF
PROCESS FUNCTIONS
FUNCTION

• ON output only for one arithmetic cycle when the input signal is turned OFF.
• Used for creation of One-Shot startup command signals, etc.

INPUT/OUTPUT

No Code Type Description


No.1 input X D Input signal
No.1 output Y D Trigger OFF

SETTING
設定項目

CONTROL PARAMETER
Nothing

ACTION

Input

Output

Arithmetic cycle

QUALITY HANDLING/PROCESSING AT INITIALIZATION


【Quality Handling】No processing in consideration of quality
【Processing at Initialization】OFF output even when the input is OFF.

Appendix-1 Function Block Description


ELEMENT Digital ON CODE 13 SYMBOL ON
PROCESS FUNCTIONS
FUNCTION

• Output of ON digital signals

INPUT/OUTPUT

No Code Type Description


No.1 output Y D ON

SETTING
設定項目

CONTROL PARAMETER
Nothing

ACTION
Outputs the ON signal.

QUALITY HANDLING/PROCESSING AT INITIALIZATION


【Quality Handling】No consideration of quality because there is not input.
【Processing at Initialization】Nothing in particular

Appendix-1 Function Block Description


ELEMENT Digital OFF CODE 14 SYMBOL OFF
PROCESS FUNCTIONS
FUNCTION

• Output of OFF digital signals

INPUT/OUTPUT

No Code Type Description


No.1 output Y D OFF

SETTING
設定項目

CONTROL PARAMETER
Nothing

ACTION
Outputs the OFF signal.

QUALITY HANDLING/PROCESSING AT INITIALIZATION


【Quality Handling】No consideration of quality because there is not input.
【Processing at Initialization】Nothing in particular

Appendix-1 Function Block Description


ELEMENT High Monitor CODE 15 SYMBOL HIM
PROCESS FUNCTIONS
FUNCTION

• ON output when the analog input signal exceeds the upper-limit setting value

INPUT/OUTPUT

No Code Type Description


No.1 input X A Input signal
No.2 input H A High limit(Parameter External Input)
No.1 output Y D Judgement result

SETTING
設定項目

CONTROL PARAMETER

Parameter Abbr. Default Value External Input Range


High limit H 99999 Possible

ACTION

Upper-limit
value
Input

Output

QUALITY HANDLING/PROCESSING AT INITIALIZATION


【Quality Handling】No processing in consideration of quality
【Processing at Initialization】Nothing in particular

Appendix-1 Function Block Description


ELEMENT Low Monitor CODE 16 SYMBOL LOM
PROCESS FUNCTIONS
FUNCTION

• ON output when the analog input signal exceeds the lower-limit setting value

INPUT/OUTPUT

No Code Type Description


No.1 input X A Input signal
No.2 input L A Low limit(Parameter External Input)
No.1 output Y D Judgement result

SETTING
設定項目

CONTROL PARAMETER

Parameter Abbr. Default Value External Input Range


Low limit L -99999 Possible

ACTION

Input

Lower limit
value

Output

QUALITY HANDLING/PROCESSING AT INITIALIZATION


【Quality Handling】No processing in consideration of quality
【Processing at Initialization】Nothing in particular

Appendix-1 Function Block Description


ELEMENT H/L Monitor CODE 17 SYMBOL HLM
PROCESS FUNCTIONS
FUNCTION
• ON output when the analog input signal exceeds the upper or lower-limit setting value
• Used for judging H/L warning for the signal
Notice
• OFF output when the input is equal to the upper or lower-limit setting value
• Block arithmetic error in the case the upper and lower-limit setting values are reversed.
INPUT/OUTPUT

No Code Type Description


No.1 input X A Input signal
No.2 input H A High limit(Parameter External Input)
No.3 input L A Low limit(Parameter External Input)
No.1 output Y D Judgement result

SETTING
設定項目

CONTROL PARAMETER

Parameter Abbr. Default Value External Input Range


Low limit L -99999 Possible L≦H
High limit H 99999 Possible L≦H

ACTION

Upper limit
value
Input

Lower limit
value

Output

QUALITY HANDLING/PROCESSING AT INITIALIZATION


【Quality Handling】If the high setting value is smaller than the low setting value, the quality of own-block output
should be a block arithmetic error.
【Processing at Initialization】Nothing in particular

Appendix-1 Function Block Description


ELEMENT High Monitor with Hysteresis CODE 18 SYMBOL HMH
PROCESS FUNCTIONS
FUNCTION
• ON output when the analog input signal exceeds the upper-limit setting value
• The setting value has the hysteresis.
• Used for preventing repeated warning occurrence when the signal is fluctuating around
the warning setting value.
INPUT/OUTPUT

No Code Type Description


No.1 input X A Input signal
No.2 input H A High value(Parameter External Input)
No.3 input DB A Hysteresis value(Parameter External Input)
No.1 output Y D Judgement result

SETTING
設定項目

CONTROL PARAMETER

Parameter Abbr. Default Value External Input Range


High value H 99999 Possible
Hysteresis value DB 0 Possible DB ≧ 0

ACTION

Upper-limit
value

Hysteresis
Input

Output

QUALITY HANDLING/PROCESSING AT INITIALIZATION


【Quality Handling】If the hysteresis width is smaller than 0, the quality of own-block output should be a block
arithmetic error.
【Processing at Initialization】Nothing in particular

Appendix-1 Function Block Description


ELEMENT Low Monitor with Hysteresis CODE 19 SYMBOL LMH
PROCESS FUNCTIONS
FUNCTION
• ON output when the analog input signal exceeds the lower-limit setting value.
• The setting value has the hysteresis.

INPUT/OUTPUT

No Code Type Description


No.1 input X A Input signal
No.2 input L A Low limit(Parameter External Input)
No.3 input DB A Hysteresis value(Parameter External Input)
No.1 output Y D Judgement result

SETTING
設定項目

CONTROL PARAMETER

Parameter Abbr. Default Value External Input Range


Low limit L -99999 Possible
Hysteresis value DB 0 Possible DB ≧ 0

ACTION

Input
Hysteresis

Lower
limit value

Output

QUALITY HANDLING/PROCESSING AT INITIALIZATION


【Quality Handling】If the hysteresis width is smaller than 0, the quality of own-block output should be a block
arithmetic error.
【Processing at Initialization】Nothing in particular

Appendix-1 Function Block Description


ELEMENT H/L Monitor with Hysteresis CODE 20 SYMBOL HLH
PROCESS FUNCTIONS
FUNCTION
• ON output when the analog input signal exceeds the upper or lowerlimit setting value.
• The setting value has the hysteresis.
• Used for preventing repeated warning occurrence when the signal is fluctuating around
the warning setting value.
• Block arithmetic error in the case the upper and lower-limit setting values are reversed.
INPUT/OUTPUT

No Code Type Description


No.1 input X A Input signal
No.2 input H A High limit(Parameter External Input)
No.3 input L A Low limit(Parameter External Input)
No.4 input DB A Hysteresis value(Parameter External Input)
No.1 output Y D Judgement result

SETTING
設定項目

CONTROL PARAMETER

Parameter Abbr. Default Value External Input Range


Low limit L -99999 Possible
High limit H 99999 Possible
Hysteresis value DB 0 Possible D ≧ 0,L+D ≦ H-D

ACTION
Upper setting
value

Input
Hysteresis

Lower setting
value

Output

QUALITY HANDLING/PROCESSING AT INITIALIZATION


【Quality Handling】If the hysteresis width is smaller than 0 or the low setting value added with the hysteresis
width is larger than the high setting value subtracted with the width , the quality of own-block
output should be a block arithmetic error.
【Processing at Initialization】Nothing in particular

Appendix-1 Function Block Description


ELEMENT Deviation Monitor CODE 21 SYMBOL DHL
PROCESS FUNCTIONS
FUNCTION • ON output when the difference of two analog input signals exceeds the setting values of
upper/lower limit
• Subtract Input2 from Input1 to get the difference
• Used for judging H/L warning for the deviation between control setting values and process
values
Notice
• OFF output when the difference is the same as the upper or lower limit value
• Block arithmetic error in the case of reversion of upper and lower limit values
INPUT/OUTPUT

No Code Type Description


No.1 input + A Input signal1 (X1)
No.2 input - A Input signal2 (X2)
No.3 input H A High limit(Parameter External Input)
No.4 input L A Low limit(Parameter External Input)
No.1 output Y D Judgement result

SETTING
設定項目

CONTROL PARAMETER

Parameter Abbr. Default Value External Input Range


Low limit L -99999 Possible L≦H
High limit H 99999 Possible L≦H

ACTION

Input2

Input1

Upper limit
0
Lower limit
Input1-Input2
Output

QUALITY HANDLING/PROCESSING AT INITIALIZATION


【Quality Handling】If the high setting value is smaller than the low setting value, the quality of own-block output
should be a block arithmetic error.
【Processing at Initialization】Nothing in particular

Appendix-1 Function Block Description


ELEMENT M Out of N CODE 23 SYMBOL M/N
PROCESS FUNCTIONS
FUNCTION
• ON output when more than M out of multiple input conditions are ON
• Input conditions are 20 at the maximum
• Used for 2 out of 3 judgement routes, etc.
INPUT/OUTPUT

No Code Type Description


No.1 input X01 D Condition input(Max.20)
No.1 output Y D Judgement result

SETTING
設定項目

CONTROL PARAMETER

Parameter Abbr. Default Value External Input Range


Signal count of M M 99999
(M out of M)

ACTION

Example of 2 out of 3 routes (M = 2)

Input1
M/N
Input2 002

Input3

Input1

Input2

Input3

Output

QUALITY HANDLING/PROCESSING AT INITIALIZATION


【Quality Handling】No processing in consideration of quality
【Processing at Initialization】Nothing in particular

Appendix-1 Function Block Description


ELEMENT Simple Addition CODE 27 SYMBOL ADD
PROCESS FUNCTIONS
FUNCTION

• Output of the value that is added with multiple input signals


• Input signals are 20 at the maximum.

INPUT/OUTPUT

No Code Type Description


No.1 input X01 A Input signal (Max. 20)
No.1 output Y A Addition result

SETTING
設定項目

CONTROL PARAMETER
Nothing

ACTION
Y=X01+X02+X03+・・・X20

QUALITY HANDLING/PROCESSING AT INITIALIZATION


【Quality Handling】The quality is transmitted by the OR of the input signal quality
【Processing at Initialization】Nothing in particular

Appendix-1 Function Block Description


ELEMENT Addition CODE 28 SYMBOL SUM
PROCESS FUNCTIONS
FUNCTION

• Add the value of two input signals multiplied by each gain to the signals

INPUT/OUTPUT

No Code Type Description


No.1 input X1 A Input signal1
No.2 input X2 A Input signal2
No.3 input K1 A Gain for input No.1(Parameter External Input)
No.4 input K2 A Gain for input No.2(Parameter External Input)
No.1 output Y A Addition result

SETTING
設定項目

CONTROL PARAMETER

Parameter Abbr. Default Value External Input Range


Gain for input No.1 K1 1 Possible
Gain for input No.2 K2 1 Possible

ACTION
Y=X1 × K1+X2 × K2

QUALITY HANDLING/PROCESSING AT INITIALIZATION


【Quality Handling】The quality is transmitted by the OR of No.1 and No. 2 input
【Processing at Initialization】Nothing in particular

Appendix-1 Function Block Description


ELEMENT Subtraction CODE 29 SYMBOL DLT
PROCESS FUNCTIONS
FUNCTION

• Output of the subtraction value of two input signals

INPUT/OUTPUT

No Code Type Description


No.1 input + A Input signal1
No.2 input - A Input signal2
No.1 output Y A Subtraction result

SETTING
設定項目

CONTROL PARAMETER
Nothing

ACTION
Y=X1-X2

QUALITY HANDLING/PROCESSING AT INITIALIZATION


【Quality Handling】The quality is transmitted by the OR of the input signal quality
【Processing at Initialization】Nothing in particular

Appendix-1 Function Block Description


ELEMENT Multiplication CODE 30 SYMBOL MUL
PROCESS FUNCTIONS
FUNCTION

• Output of the multiplication value of two input signals

INPUT/OUTPUT

No Code Type Description


No.1 input X1 A Input signal1
No.2 input X2 A Input signal2
No.1 output Y A Multiplication result

SETTING
設定項目

CONTROL PARAMETER
Nothing

ACTION
Y=X1 × X2

QUALITY HANDLING/PROCESSING AT INITIALIZATION


【Quality Handling】The quality is transmitted by the OR of the input signal quality.
【Processing at Initialization】Nothing in particular

Appendix-1 Function Block Description


ELEMENT Division CODE 31 SYMBOL DIV
PROCESS FUNCTIONS
FUNCTION

• Output of the division value of two signals

INPUT/OUTPUT

No Code Type Description


No.1 input N A Input signal1
No.2 input D A Input signal2
No.1 output Y A Division result

SETTING

CONTROL PARAMETER
Nothing

ACTION
Y=N/D

QUALITY HANDLING/PROCESSING AT INITIALIZATION


【Quality Handling】The quality is transmitted by the OR of the input signal quality.
The quality of My Block output should be a block arithmetic error at the zero division.
【Processing at Initialization】Nothing in particular

Appendix-1 Function Block Description


ELEMENT Absolute Value CODE 32 SYMBOL ABS
PROCESS FUNCTIONS
FUNCTION
• Output of absolute values of input signals
• Used for acquiring absolute values of values fluctuated by +,-. e.g.) deviation signals etc.

INPUT/OUTPUT

No Code Type Description


No.1 input X A Input signal
No.1 output Y A Absolute value

SETTING

CONTROL PARAMETER
Nothing

ACTION

X 0

Y 0

QUALITY HANDLING/PROCESSING AT INITIALIZATION


【Quality Handling】The input quality is transmitted to the output.
【Processing at Initialization】Nothing in particular

Appendix-1 Function Block Description


ELEMENT Square-Root Extraction CODE 33 SYMBOL ROT
PROCESS FUNCTIONS
FUNCTION

• Output of square-root of input signals

INPUT/OUTPUT

No Code Type Description


No.1 input X A Input signal
No.1 output Y A Square-root extraction value

SETTING

CONTROL PARAMETER
Nothing

ACTION

Input>0 Output= Input

Input≦0 Output=0

QUALITY HANDLING/PROCESSING AT INITIALIZATION


【Quality Handling】The input quality is transmitted to the output.
The quality of My Block output should not be a block
【Processing at Initialization】Nothing in particular

Appendix-1 Function Block Description


ELEMENT Exponentiation CODE 35 SYMBOL PWR
PROCESS FUNCTIONS
FUNCTION

• Output of input-signal exponentiation

INPUT/OUTPUT

No Code Type Description


No.1 input a A Input signal1
No.2 input b A Input signal2
No.1 output Y A Exponentiation value

SETTING

CONTROL PARAMETER
Nothing

ACTION
Y=ab

QUALITY HANDLING/PROCESSING AT INITIALIZATION


【Quality Handling】The quality is transmitted by the OR of the input signal quality.
The quality of My Block output should be a block arithmetic error when the input1 is
negative.
【Processing at Initialization】Nothing in particular

Appendix-1 Function Block Description


ELEMENT Analog Zero Output CODE 36 SYMBOL ZER
PROCESS FUNCTIONS
FUNCTION
• Output of 0% analog signal
• Used for setting values

INPUT/OUTPUT

No Code Type Description


No.1 output Y A 0.0

SETTING

CONTROL PARAMETER
Nothing

ACTION
Outputs the 0.0 signal.

QUALITY HANDLING/PROCESSING AT INITIALIZATION


【Quality Handling】No consideration for quality because there is no input.
【Processing at Initialization】Nothing in particular

Appendix-1 Function Block Description


ELEMENT Analog Maximum-Value Output CODE 37 SYMBOL INF
PROCESS FUNCTIONS
FUNCTION
• Output of 3.40 × 1038 analog signal
• Used for setting value for change rate, etc.

INPUT/OUTPUT

No Code Type Description


No.1 output Y A 3.40 × 1038

SETTING

CONTROL PARAMETER
Nothing

ACTION
Outputs the ∞ signal.

QUALITY HANDLING/PROCESSING AT INITIALIZATION


【Quality Handling】No consideration for quality because there is no input.
【Processing at Initialization】Nothing in particular

Appendix-1 Function Block Description


ELEMENT Fixed Value Setting CODE 38 SYMBOL SG
PROCESS FUNCTIONS
FUNCTION

• Output of the analog signal designated in the parameter

INPUT/OUTPUT

No Code Type Description


No.1 output Y A Setting value

SETTING

CONTROL PARAMETER

Parameter Abbr. Default Value External Input Range


Set value S 0

ACTION
Y=S

QUALITY HANDLING/PROCESSING AT INITIALIZATION


【Quality Handling】No consideration for quality because there is no input.
【Processing at Initialization】Nothing in particular

Appendix-1 Function Block Description


ELEMENT High-Value Selection CODE 39 SYMBOL HSL
PROCESS FUNCTIONS
FUNCTION
• Output of the maximum value from multiple analog input signals
• 20 input signals at the maximum

INPUT/OUTPUT

No Code Type Description


No.1 input X01 A Input signal(Max.20)
No.1 output Y A The Max. value

SETTING

CONTROL PARAMETER
Nothing

ACTION

EExam
xa m pp le
le ooff 3 in p u t s ig n a ls

In p ut1

In p ut2

In p ut3

O utp u t

O u tp u t th e m a x im u m va lue fro m 3
in p u t s ig n a ls

QUALITY HANDLING/PROCESSING AT INITIALIZATION


【Quality Handling】Transmission of the acquired maximum value quality after judging the value without
considering the quality
【Processing at Initialization】Nothing in particular

Appendix-1 Function Block Description


ELEMENT Low-Value Selection CODE 40 SYMBOL LSL
PROCESS FUNCTIONS
FUNCTION
• Output of the maximum value from multiple analog input signals
• 20 input signals at the maximum

INPUT/OUTPUT

No Code Type Description


No.1 input X01 A Input signal(Max.20)
No.1 output Y A The Min. value

SETTING

CONTROL PARAMETER
Nothing

ACTION

Example of 3 input signals

Input 1

Input 2

Input 3

Output the maximum value from 3 input signals

Output

QUALITY HANDLING/PROCESSING AT INITIALIZATION


【Quality Handling】Transmission of the acquired minimum value quality after judging the value without
considering the quality
【Processing at Initialization】Nothing in particular

Appendix-1 Function Block Description


ELEMENT Intermediate Value Selection CODE 41 SYMBOL MED
PROCESS FUNCTIONS
FUNCTION

• Output of the intermediate value from three analog input signals

INPUT/OUTPUT

No Code Type Description


No.1 input X1 A Input signal 1
No.2 input X2 A Input signal 2
No.3 input X3 A Input signal 3
No.1 output Y A The intermediate value

SETTING

CONTROL PARAMETER
Nothing

ACTION

Input 1

Input 2

Input3

Output

QUALITY HANDLING/PROCESSING AT INITIALIZATION


【Quality Handling】Transmission of the acquired intermediate value quality after judging the value without
considering the quality
【Processing at Initialization】Nothing in particular

Appendix-1 Function Block Description


ELEMENT Restriction of Upper/Lower Limit CODE 42 SYMBOL LMT
PROCESS FUNCTIONS
FUNCTION
• Output of the input signal multiplied by upper and lower limit restriction
• Used for restrictions for process input's range over, etc.

INPUT/OUTPUT

No Code Type Description


No.1 input X A Input signal
No.2 input H A High limit (Parameter External Input)
No.3 input L A Low limit (Parameter External Input)
No.1 output Y A Restriction value of Upper/Lower Limit

SETTING

CONTROL PARAMETER

Parameter Abbr. Default Value External Input Range


Low limit L -99999 Possible L≦H
High limit H 99999 Possible L≦H

ACTION

Input

Upper limit

Output
Lower limit

QUALITY HANDLING/PROCESSING AT INITIALIZATION


【Quality Handling】The quality of No. 1 input is transmitted. If the high setting value is smaller than the low
setting value, the quality of own-block output should be a block arithmetic error.
【Processing at Initialization】Nothing in particular

Appendix-1 Function Block Description


ELEMENT Linear Conversion CODE 43 SYMBOL LIN
PROCESS FUNCTIONS
FUNCTION
• Output by liner interpolation of two-point polyline for input signals
• The outside of the polyline is output of Y value at both ends.

INPUT/OUTPUT

No Code Type Description


No.1 input X A Input signal
No.1 output Y A Output value

SETTING

CONTROL PARAMETER

Parameter Abbr. Default Value External Input Range


X1 X1 0 X1 ≦ X2
Y1 Y1 0
X2 X2 10000 X1 ≦ X2
Y2 Y2 10000

ACTION

Y2

Output

Y1

X1 Input X2

QUALITY HANDLING/PROCESSING AT INITIALIZATION


【Quality Handling】The input quality is transmitted to the output. If X1>X2, the quality of own-block output
should be a block arithmetic error.
【Processing at Initialization】Nothing in particular

Appendix-1 Function Block Description


ELEMENT Primary Delay CODE 44 SYMBOL LAG
PROCESS FUNCTIONS
FUNCTION

• Output of the value that is performed with primary-delay calculation for the input signal

INPUT/OUTPUT

No Code Type Description


No.1 input X A Input signal
No.2 input T A Time constant (Parameter External Input)
No.3 input TP D Tracking
No.1 output Y A Primary-delay value

SETTING

CONTROL PARAMETER

Parameter Abbr. Default Value External Input Range


Time constant T 0 Possible TP ≧ 0

ACTION

Tracking

Input

Output
1 T Time constantT
Output= Input
1+Ts

QUALITY HANDLING/PROCESSING AT INITIALIZATION


【Quality Handling】The quality of No. 1 input should be transmitted. If the primary-delay time constant is
negative, the quality of own-block output should be a block arithmetic error.
【Processing at Initialization】The output is tracked to the input value.

Appendix-1 Function Block Description


ELEMENT Change-Rate Restriction Unit CODE 46 SYMBOL RLT
PROCESS FUNCTIONS
FUNCTION
• Analog signal output is acquired with the input signal multiplied by designated change rate
• The input signal should be output as it is when the tracking signal is ON
• Use increasing-direction change rate for increasing input signal and decreasing-direction
change rate for the decreasing.

INPUT/OUTPUT

No Code Type Description


No.1 input X A Input signal
No.2 input RI A Increasing rate (Parameter External Input)
No.3 input RD A Decreasing rate (Parameter External Input)
No.4 input TP D Tracking
No.1 output Y A Change-rate restriction value

SETTING

CONTROL PARAMETER

Parameter Abbr. Default Value External Input Range


Increasing rate RI 99999 Possible RI ≧ 0
Decreasing rate RD 99999 Possible RD ≧ 0

ACTION

Tracking

Input

Increasing Decreasing
Output change rate change rate

QUALITY HANDLING/PROCESSING AT INITIALIZATION


【Quality Handling】The quality of No. 1 input should be transmitted. If the increasing change rate or the
decreasing change rate is negative, the quality of own-block output should be a block
arithmetic error.
【Processing at Initialization】The output is tracked to the input.

Appendix-1 Function Block Description


ELEMENT Dead Time CODE 48 SYMBOL DLY
PROCESS FUNCTIONS
FUNCTION • The input signal is output delayed for the designated time. The saved data is output after
intermediate interpolation.
• It is better the delay and arithmetic time are integral multiplication of the arithmetic cycle.
• The delay should be less than 65 times than that of arithmetic interval.(64 sample buffer)
INPUT/OUTPUT

No Code Type Description


No.1 input X A Input signal
No.2 input TP D Tracking
No.1 output Y A Output value

SETTING

CONTROL PARAMETER

Parameter Abbr. Default Value External Input Range


Dead time T 1 0 ≦ T ≦ 64DT
Calcuration interval DT 1 DT ≧ 0

ACTION

Input

Output

Time constantT

QUALITY HANDLING/PROCESSING AT INITIALIZATION


【Quality Handling】No. 1 input quality is transmitted to the output.
Even if the No. 1 input quality is abnormal, the ordinary calculation should be continued.
Tracking T will perform the same handling as that of ON right after No. 1 input quality is
returned normal.
If an arithmetic error occurs, the quality of own-block output should be a block arithmetic error.
【Processing at Initialization】The internal work should be filled with input values.The output becomes the input value.

Appendix-1 Function Block Description


ELEMENT Proportional Control CODE 49 SYMBOL P
PROCESS FUNCTIONS
FUNCTION

• The value is output with the input signal multiplied by proportional gain.

INPUT/OUTPUT

No Code Type Description


No.1 input X A Input signal
No.2 input K A Gain (Parameter External Input)
No.1 output Y A Output value

SETTING

CONTROL PARAMETER

Parameter Abbr. Default Value External Input Range


Gain K 1 Possible

ACTION

X
Y=X×K

QUALITY HANDLING/PROCESSING AT INITIALIZATION


【Quality Handling】The quality is transmitted by the OR of the input signal quality.
【Processing at Initialization】Nothing in particular

Appendix-1 Function Block Description


ELEMENT Proportional Integral (CSR) CODE 51 SYMBOL PI
PROCESS FUNCTIONS
FUNCTION
• Output of the value added with the proportional and integral calculation of the input signal.
• The internal integral value is restricted by (upper/lower limit restriction - leading signal).

INPUT/OUTPUT

No Code Type Description


No.1 input X A Input signal
No.2 input Tr A Tracking value
No.3 input Ts D Tracking condition
No.4 input FF A Leading signal
No.5 input IS A Input span (Parameter External Input)
No.6 input OS A Output span (Parameter External Input)
No.7 input HL A Output low limit (Parameter External Input)
No.8 input LL A Output high limit (Parameter External Input)
No.9 input K A Ratio gain (Parameter External Input)
No.10 input T A Time constant (Parameter External Input)
No.1 output Y A Output value

SETTING

CONTROL PARAMETER

Parameter Abbr. Default Value External Input Range


Input span IS 1 Possible IS > 0
Output span OS 1 Possible OS > 0
Output low limit HL -99999 Possible H≧L
Output high limit LL 99999 Possible H≧L
Ratio gain K 0 Possible K≧0
Time constant T 99999 Possible T>0

Appendix-1 Function Block Description


ACTION

Input 0

Ouput of
Integral

Y:PI Output P:Output of Proportion

Output lower

Output of PI (Before limit)

QUALITY HANDLING/PROCESSING AT INITIALIZATION


【Quality Handling】The OR of X/K/FF quality is transmitted if Ts=OFF
The OR of Tr/FF quality is transmitted if Ts=ON
If the input span or the output span is smaller than 0, the quality of own-block output should
be a block arithmetic error.
【Processing at Initialization】Tracking condition T will handle it as ON

Appendix-1 Function Block Description


ELEMENT Proportional Integral (QSR) CODE 52 SYMBOL PIQ
PROCESS FUNCTIONS
FUNCTION
• Output of the value added with the proportional and integral calculation of the input signal.
• The internal integral value is restricted by
(upper/lower limit restriction - leading signal - proportion).

INPUT/OUTPUT

No Code Type Description


No.1 input X A Input signal
No.2 input Tr A Tracking value
No.3 input Ts D Tracking condition
No.4 input FF A Leading signal
No.5 input IS A Input span (Parameter External Input)
No.6 input OS A Output span (Parameter External Input)
No.7 input HL A Output low limit (Parameter External Input)
No.8 input LL A Output high limit (Parameter External Input)
No.9 input K A Ratio gain (Parameter External Input)
No.10 input T A Time constant (Parameter External Input)
No.1 output Y A Output value

SETTING

CONTROL PARAMETER

Parameter Abbr. Default Value External Input Range


Input span IS 1 Possible IS > 0
Output span OS 1 Possible OS > 0
Output low limit HL -99999 Possible H≧L
Output high limit LL 99999 Possible H≧L
Ratio gain K 0 Possible K≧0
Time constant T 99999 Possible T>0

Appendix-1 Function Block Description


ACTION

Input 0

W:Output of Integral
P:Output of Proportion

Y:Output of PI

Output lower

QUALITY HANDLING/PROCESSING AT INITIALIZATION


【Quality Handling】The OR of X/K/FF quality is transmitted if Ts=OFF
The OR of Tr/FF quality is transmitted if Ts=ON
If the input span or the output span is smaller than 0, the quality of own-block output should
be a block arithmetic error.
【Processing at Initialization】Tracking condition T will handle it as ON

Appendix-1 Function Block Description


ELEMENT Differential Calculus CODE 53 SYMBOL D
PROCESS FUNCTIONS
FUNCTION

• Output of the value incompletely differentiated of input signals

INPUT/OUTPUT

No Code Type Description


No.1 input X A Input signal
No.2 input K A Gain (Parameter External Input)
No.3 input T A Time constant (Parameter External Input)
No.4 input TP D Reset SW
No.1 output Y A Output value

SETTING

CONTROL PARAMETER

Parameter Abbr. Default Value External Input Range


Gain K 0 Possible
Time constant T 100 Possible T≧0

ACTION

Reset

Inclination R(/sec)

Input

K×R

Output
0
Ts
Output=K ・Input
TC T 1+Ts

QUALITY HANDLING/PROCESSING AT INITIALIZATION


【Quality Handling】The quality of No. 1 input should be transmitted. If the time constant is negative, the quality
of ownblock
【Processing at Initialization】Tracking condition T will process as ON operation.

Appendix-1 Function Block Description


ELEMENT Polyline Function CODE 55 SYMBOL FX
PROCESS FUNCTIONS
FUNCTION
• Output of the value that is performed with function calculation for the input signal. Polyline
point is 10 at the maximum.
• If the X-axis value is not set, the polyline extends to the previous point for the smaller point
than the previous one.
• The outside of the polyline will be output of Y value at both ends.
INPUT/OUTPUT

No Code Type Description


No.1 input X A Input signal
No.1 output Y A Output value

SETTING

Appendix-1 Function Block Description


CONTROL PARAMETER

Parameter Abbr. Default Value External Input Range


X1 C1 0
Y1 C2 0
X2 C3 10000
Y2 C4 10000
X3 C5 0
Y3 C6 0
X4 C7 0
Y4 C8 0
X5 C9 0
Y5 C10 0
X6 C11 0
Y6 C12 0
X7 C13 0
Y7 C14 0
X8 C15 0
Y8 C16 0
X9 C17 0
Y9 C18 0
X10 C19 0
Y10 C20 0

ACTION

Output

Y5 Y6
Y4 Y7

Y3 Y8

Y2 Y9
Y1 Y10

Input
X1 X2 X3 X4 X5 X6 X7 X8 X9 X10

QUALITY HANDLING/PROCESSING AT INITIALIZATION


【Quality Handling】The input quality is transmitted to the output
【Processing at Initialization】Nothing in particular

Appendix-1 Function Block Description


ELEMENT Digital/Analog Conversion CODE 57 SYMBOL D/A
PROCESS FUNCTIONS
FUNCTION

• Designated analog value is output for the digital-input signal.

INPUT/OUTPUT

No Code Type Description


No.1 input X D Input signal
No.2 input S A Set value (Parameter External Input)
No.1 output Y A Conversion value

SETTING

CONTROL PARAMETER

Parameter Abbr. Default Value External Input Range


Set value S 1 Possible

ACTION

X 0

V
Y

QUALITY HANDLING/PROCESSING AT INITIALIZATION


【Quality Handling】No processing in consideration of quality
【Processing at Initialization】Nothing in particular

Appendix-1 Function Block Description


ELEMENT Arithmetic Cycle CODE 60 SYMBOL DT
PROCESS FUNCTIONS
FUNCTION

• The arithmetic cycle is fetched for the logic sheet.

INPUT/OUTPUT

No Code Type Description


No.1 output Y A Arithmetic cycle (msec)

SETTING
Nothing

CONTROL PARAMETER
Nothing

ACTION
The element outputs the arithmetic cycle of the logic sheet.

QUALITY HANDLING/PROCESSING AT INITIALIZATION


【Quality Handling】Always handle them as normal.
【Processing at Initialization】Nothing in particular

Appendix-1 Function Block Description


ELEMENT Digital constant CODE 64 SYMBOL DG
PROCESS FUNCTIONS
FUNCTION
• The element enables (on) or disables (off) digital output based on the on/off setting of
the parameter (digital).

INPUT/OUTPUT

No Code Type Description


No.1 output Y D On/off setting

SETTING

CONTROL PARAMETER

Parameter Abbr. Default Value External Input Range


Set value S 0

ACTION
No action

QUALITY HANDLING/PROCESSING AT INITIALIZATION


【Quality Handling】The quality of the output is always normal.
【Processing at Initialization】None.

Appendix-1 Function Block Description


ELEMENT Digital Switch CODE 101 SYMBOL SW
PROCESS FUNCTIONS
FUNCTION
• Output of switching 2 digital input signals according to the switching conditions
• Used for switching mode signals according to the conditions

INPUT/OUTPUT

No Code Type Description


No.1 input off D Input signals selected for sw=off
No.2 input on D Input signals selected for sw=on
No.3 input sw D Switch condition
No.1 output Y D Selection signal

SETTING

CONTROL PARAMETER
Nothing

ACTION

Input1

Input2

Switch Input swtich Output


0 Input1
1 Input2
Output

QUALITY HANDLING/PROCESSING AT INITIALIZATION


【Quality Handling】No processing in consideration of quality
【Processing at Initialization】Nothing in particular

Appendix-1 Function Block Description


ELEMENT Simple Analog Switch CODE 102 SYMBOL T
PROCESS FUNCTIONS
FUNCTION
• Output of switching two analog input according to the switching conditions
• Used for switching setting values according to the conditions

INPUT/OUTPUT
入出力

No Code Type Description


No.1 input off A Input signals selected for sw=off
No.2 input on A Input signals selected for sw=on
No.3 input sw D Switch condition
No.1 output Y A Selection signal

SETTING

CONTROL PARAMETER
Nothing

ACTION

Switch

Input 1
Output
Switch Output
Input 2
0 Input1
Switch output signals by ON/OFF input switch 1 Input2

QUALITY HANDLING/PROCESSING AT INITIALIZATION


【Quality Handling】Transmission of the selected input quality after judging the switch without considering the
quality of the switch signal sw
【Processing at Initialization】Nothing in particular

Appendix-1 Function Block Description


ELEMENT Analog Switch with Rate CODE 103 SYMBOL TR
PROCESS FUNCTIONS
FUNCTION
• Output of switching two analog input according to the switch conditions
• Output is changed by the set rate at switching time
INPUT/OUTPUT
入出力

No Code Type Description


No.1 input off A Input signals selected for sw=off
No.2 input on A Input signals selected for sw=on
No.3 input sw D Condition input
No.4 input Ron A OFF → ON change rate (Parameter External Input)
No.5 input Roff A ON → OFF change rate (Parameter External Input)
No.1 output Y A Selection signal

SETTING

CONTROL PARAMETER

Parameter Abbr. Default Value External Input Range


OFF → ON change rate Ron 99999 Possible Ron ≧ 0
ON → OFF change rate Roff 99999 Possible Roff ≧ 0
Limit after change MD 0 Y:1,N:0

ACTION

Switch

Input2 ChangeR2 ChangeR1 Output Switch Output


0 Input1
Input1
1 Input2

QUALITY HANDLING/PROCESSING AT INITIALIZATION


【Quality Handling】Transmission of the selected input quality after judging the switch without considering the
quality of switch signal T
Do not consider the quality of change rate (R1/R2)
If the change rate (/min) for switching from XON to XOFF and vice verse, is smaller than 0,
the quality of own-block output should be a block arithmetic error.
【Processing at Initialization】Output of selected input signals

Appendix-1 Function Block Description


ELEMENT Analog Switch with Differential Rate CODE 104 SYMBOL TRD
PROCESS FUNCTIONS
FUNCTION
• Output of switching two analog input according to the switch conditions
• Should be reduced according to the rate set with deviation of target input at the time of switch
INPUT/OUTPUT
入出力

No Code Type Description


No.1 input off A Input signals selected for sw=off
No.2 input on A Input signals selected for sw=on
No.3 input sw D Condition input
No.4 input Ron A OFF → ON change rate (Parameter External Input)
No.5 input Roff A ON → OFF change rate (Parameter External Input)
No.1 output Y A Selection signal

SETTING

CONTROL PARAMETER

Parameter Abbr. Default Value External Input Range


OFF → ON change rate Ron 99999 Possible Ron ≧ 0
ON → OFF change rate Roff 99999 Possible Roff ≧ 0

ACTION

Input Switch

Input2
Output

Input1

0
0
Change Rate1
Change Rate2
Deviation(Input2/O) Deviation (Input1/O)

QUALITY HANDLING/PROCESSING AT INITIALIZATION


【Quality Handling】Transmission of the selected input quality after judging the switch without considering the
quality of switch signal T
Do not consider the quality of change rate (R1/R2)
If the change rate (/min) for switching from XON to XOFF and vice verse, is smaller than 0,
the quality of own-block output should be a block arithmetic error.
【Processing at Initialization】Output of selected input signals

Appendix-1 Function Block Description


ELEMENT Previous Digital Value CODE 105 SYMBOL OLD
PROCESS FUNCTIONS
FUNCTION

• Output of input signals by lagging one arithmetic cycle

INPUT/OUTPUT
入出力

No Code Type Description


No.1 input X D Input signal
No.1 output Y D Previous Digital Value

SETTING

CONTROL PARAMETER
Nothing

ACTION

Input

Output

Arithmetic Cycle

QUALITY HANDLING/PROCESSING AT INITIALIZATION


【Quality Handling】No processing in consideration of quality
【Processing at Initialization】Output of input values

Appendix-1 Function Block Description


ELEMENT Previous Analog Value CODE 106 SYMBOL OLA
PROCESS FUNCTIONS
FUNCTION

• Input signals are output delaying one arithmetic cycle.

INPUT/OUTPUT
入出力

No Code Type Description


No.1 input X A Input signal
No.1 output Y A Previous Analog Value

SETTING

CONTROL PARAMETER
Nothing

ACTION

Output

Input
Arithmetic cycle

QUALITY HANDLING/PROCESSING AT INITIALIZATION


【Quality Handling】Previous value for work memory is transmitted to output in the next arithmetic cycle after
saving the value as well as the quality.
【Processing at Initialization】The input value will be output.

Appendix-1 Function Block Description


ELEMENT Digital Input CODE 107 SYMBOL DI
PROCESS FUNCTIONS
FUNCTION

• Output the engineering value for DI module input signals

INPUT/OUTPUT
入出力

No Code Type Description


No.1 output Y D ON/OFF value of DI

SETTING

CONTROL PARAMETER
Nothing

ACTION
The element outputs a single point of the input signal (which is entered in the plant) in the DI module
as an engineering value.

QUALITY HANDLING/PROCESSING AT INITIALIZATION


【Quality Handling】Copy the quality previously calculated by DI processing
【Processing at Initialization】Nothing in particular

Appendix-1 Function Block Description


ELEMENT Analog Input CODE 108 SYMBOL AI
PROCESS FUNCTIONS
FUNCTION
• Output the engineering value for AI module input signals
• TC input will output the result performed to the extent of correction

INPUT/OUTPUT
入出力

No Code Type Description


No.1 output Y A AI engineering value

SETTING

CONTROL PARAMETER

Parameter Abbr. Default Value External Input Range


Input limit low(%) IL -0.8
Input limit high(%) IH 104

ACTION
The element outputs a single point of the input signal (which is entered in the plant) in the AI module
as an engineering value.

QUALITY HANDLING/PROCESSING AT INITIALIZATION


【Quality Handling】Copy the quality previously calculated by AI processing
The quality that is not usually transmitted is transmitted as well.
Moreover, if the value exceeds the highest input value, it is over the upper range. If it is less
than the lowest input value (%), it is over the lower range.
【Processing at Initialization】Nothing in particular

Appendix-1 Function Block Description


ELEMENT Pulse Input CODE 109 SYMBOL PU
PROCESS FUNCTIONS
FUNCTION

• Output of the PI-module input signal as the pulse value

INPUT/OUTPUT
入出力

No Code Type Description


No.1 output Y A Pulse counter value

SETTING

CONTROL PARAMETER
Nothing

ACTION
The element outputs a single point of the input signal (which is entered in the plant) in the DI module
as a pulse.

QUALITY HANDLING/PROCESSING AT INITIALIZATION


【Quality Handling】Copy the quality previously calculated by PI processing
【Processing at Initialization】Nothing in particular

Appendix-1 Function Block Description


ELEMENT Digital Output CODE 110 SYMBOL DO
PROCESS FUNCTIONS
FUNCTION

• Output of the input signal from DO module

INPUT/OUTPUT
入出力

No Code Type Description


No.1 Input X D Output command

SETTING

CONTROL PARAMETER
Nothing

ACTION
The element outputs the input signal to the plant.

QUALITY HANDLING/PROCESSING AT INITIALIZATION


【Quality Handling】Copy the quality previously calculated by DO processing.
【Processing at Initialization】Nothing in particular

Appendix-1 Function Block Description


ELEMENT Analog Output CODE 111 SYMBOL AO
PROCESS FUNCTIONS
FUNCTION

• Output of the input signal converted with the engineering range, from AO module

INPUT/OUTPUT
入出力

No Code Type Description


No.1 Input X A Output command (engineering value)

SETTING

CONTROL PARAMETER

Parameter Abbr. Default Value External Input Range


Output limit low(%) OL -10
Output limit high(%) OH 110

ACTION
The element outputs the input signal to the plant.

QUALITY HANDLING/PROCESSING AT INITIALIZATION


【Quality Handling】Copy the quality previously calculated by AO processing.
Moreover, if the value exceeds the highest input value, it is over the upper range. If it is less
than the lowest input value (%), it is over the lower range.
【Processing at Initialization】Nothing in particular

Appendix-1 Function Block Description


ELEMENT Digital Connection between Sheet CODE INPUT:112 OUTPUT:113 SYMBOL CED
PROCESS FUNCTIONS
FUNCTION
• Elements to show connection of digital signals between the different sheet without any
arithmetic performance
• Used for both input and output.
• Same objects should exist as the output.

INPUT/OUTPUT
入出力

No Code Type Description


No.1 input X D Input signal
No.1 output Y D Output signal

SETTING

CONTROL PARAMETER
Nothing

ACTION
Connect same digital signals between different sheets

QUALITY HANDLING/PROCESSING AT INITIALIZATION


【Quality Handling】The output are copied with input signal quality and sent with the quality even between
systems The input side will have abnormal quality with data-access incapability due to
reception stop
【Processing at Initialization】Nothing in particular

Appendix-1 Function Block Description


ELEMENT Analog Connection between Sheet CODE INPUT:114 OUTPUT:115 SYMBOL CEA
PROCESS FUNCTIONS
FUNCTION
• Elements to show connection of analog signals between the different sheet without any
arithmetic performance
• Used for both input and output.
• Same objects should exist as the output.
INPUT/OUTPUT
入出力

No Code Type Description


No.1 input X A Input signal
No.1 output Y A Output signal

SETTING

CONTROL PARAMETER
Nothing

ACTION
Connect same analog signals between different sheets

QUALITY HANDLING/PROCESSING AT INITIALIZATION


【Quality Handling】The output are copied with input signal quality and sent with the quality even between
systems
The input side will have abnormal quality with data-access incapability due to reception stop
【Processing at Initialization】Nothing in particular

Appendix-1 Function Block Description


ELEMENT Connection Inside Sheet CODE INPUT:124 OUTPUT:125 SYMBOL CID
PROCESS FUNCTIONS
FUNCTION
• These are elements to show connection in the same sheet and not performed with any
arithmetics.
• Used for all the data types of analog, digital, and integer.
• Used for both input/output.
• Elements with the same name should exist in the sheet as the output.
INPUT/OUTPUT
入出力

No Code Type Description


No.1 input X A/D/I Input signal
No.1 output Y A/D/I Output signal

SETTING

CONTROL PARAMETER
Nothing

ACTION
The element connects the same signals on the same sheet.

QUALITY HANDLING/PROCESSING AT INITIALIZATION


【Quality Handling】All the qualities are transmitted.
【Processing at Initialization】Nothing in particular

Appendix-1 Function Block Description


ELEMENT Null Digital CODE 126 SYMBOL NLD
PROCESS FUNCTIONS
FUNCTION

• No action for digital input signals

INPUT/OUTPUT
入出力

No Code Type Description


No.1 input X D Digital signal

SETTING
Nothing

CONTROL PARAMETER
Nothing

ACTION
The element performs no operation.

QUALITY HANDLING/PROCESSING AT INITIALIZATION


【Quality Handling】No processing in consideration of quality
【Processing at Initialization】Nothing in particular

Appendix-1 Function Block Description


ELEMENT Null Analog CODE 127 SYMBOL NLA
PROCESS FUNCTIONS
FUNCTION

• No action for analog input signals

INPUT/OUTPUT
入出力

No Code Type Description


No.1 input X A Analog signal

SETTING
Nothing

CONTROL PARAMETER
Nothing

ACTION
The element performs no operation.

QUALITY HANDLING/PROCESSING AT INITIALIZATION


【Quality Handling】No processing in consideration of quality
【Processing at Initialization】Nothing in particular

Appendix-1 Function Block Description


ELEMENT Arithmetic Order Reversed Digital CODE 132 SYMBOL RVD
PROCESS FUNCTIONS
FUNCTION
• Output of the digital input signals without any action
• The connection is handled as disconnected when the arithmetic order is calculated.
(The arithmetic order is always reversed for the loop place. With this element, the
arithmetic order is reversed for the input line.)

INPUT/OUTPUT
入出力

No Code Type Description


No.1 input X D Digital signal
No.1 output Y D Digital signal

SETTING
Nothing

CONTROL PARAMETER
Nothing

ACTION
Y=X

QUALITY HANDLING/PROCESSING AT INITIALIZATION


【Quality Handling】Copy the input-signal quality to the output.
【Processing at Initialization】Nothing in particular

Appendix-1 Function Block Description


ELEMENT Arithmetic Order Reversed Analog CODE 133 SYMBOL RVA
PROCESS FUNCTIONS
FUNCTION
• Output of the analog input signals without any action
• When the arithmetic order is calculated, it is handled as disconnected.
(The arithmetic order is always reversed for the loop place. With this element, the
arithmetic order is reversed for the input line.)

INPUT/OUTPUT
入出力

No Code Type Description


No.1 input X A Analog signal
No.1 output Y A Analog signal

SETTING
Nothing

CONTROL PARAMETER
Nothing

ACTION
Y=X

QUALITY HANDLING/PROCESSING AT INITIALIZATION


【Quality Handling】Copy the input-signal quality to the output.
【Processing at Initialization】Nothing in particular

Appendix-1 Function Block Description


ELEMENT Digital Warning CODE 201 SYMBOL DAN
DATA LOGGAR FUNCTIONS
FUNCTION
• Input signal process values are judged by ON/OFF for warning
• The same handling is done when the refailed input is ON
• Time stamp can be updated but never returned

INPUT/OUTPUT

No Code Type Description


No.1 input X D Input signal
No.2 input Su D Warning inhibit condition(can be omitted)
No.3 input Re D Refailure (should be One Shot)
No.1 output Y D Warning occurrence (omitted if not used)
No.2 output NC D Warning unconfirmed (omitted if not used)
No.3 output NR D Warning returned (omitted if not used)

SETTING

CONTROL PARAMETER
初期化時の処理

Parameter Abbr. Default Value External Input Range


Annunciate level LVL 1
Print out inservice PR 1 0:exclusive, 1:used
Region REG 0

ACTION
No action

QUALITY HANDLING/PROCESSING AT INITIALIZATION


【Quality Handling】No processing in consideration of quality
【Processing at Initialization】No processing for warning occurrence (No transmission to event trace)

Appendix-1 Function Block Description


ELEMENT Analog Warning CODE 202 SYMBOL AAN
DATA LOGGAR FUNCTIONS
FUNCTION
• Input signal process values are judged for warning by settingvalue input or parameters
• There are 3 types of judgement as follows
•Upper limit (H)
•Lower limit (L)
•Change rate (R)
INPUT/OUTPUT

No Code Type Description


No.1 input X A Input signal
No.2 input S A Setting value(Parameter External Input)
No.3 input Su D Warning inhibit condition
No.1 output Y D Warning occurrence
No.2 output NC D Warning unconfirmed
No.3 output NR D Warning returned

SETTING

CONTROL PARAMETER
初期化時の処理

Parameter Abbr. Default Value External Input Range


Threshold S 9999
Hysteresis DB 0 DB ≧ 0
Category(1:H 2:L 3:R) ANN 1 1:H,2:L,3:R
Annunciate level LVL 1
Print out inservice PR 1 0:Exclusive,1:Used
Region REG 0

ACTION
No action

QUALITY HANDLING/PROCESSING AT INITIALIZATION


【Quality Handling】If the dead band is negative, the quality of Own-block output should be a block arithmetic error
【Processing at Initialization】No processing for warning occurrence (No transmission to event trace)

Appendix-1 Function Block Description


ELEMENT Event CODE 203 SYMBOL EVT
DATA LOGGAR FUNCTIONS
FUNCTION

• Event judgement by ON/OFF of input signal process values

INPUT/OUTPUT

No Code Type Description


No.1 input X D Input signal
No.2 input Su D Event inhibit condition (can be omitted)
No.1 output Y D Event occurrence

SETTING

CONTROL
初期化時の処理 PARAMETER

Parameter Abbr. Default Value External Input Range


Annunciate level LVL 1
Print out PR 1 0:Exclusive,1:Used
Region REG 0

ACTION
No action

QUALITY HANDLING/PROCESSING AT INITIALIZATION


【Quality Handling】No processing in consideration of quality
【Processing at Initialization】No processing for warning occurrence (No transmission to event trace)

Appendix-1 Function Block Description


ELEMENT Quality Fetch Digital CODE 205 SYMBOL QGD
DATA LOGGAR FUNCTIONS
FUNCTION

• Acquiring each quality code status by ON/OFF from input-signal quality information

INPUT/OUTPUT

No Code Type Description


No.1 input X D Input signal
No.1 output RO D Range-over upper limit (Reserved)t
No.2 output RU D Range-over lower limit (Reserved)
No.3 output AE D Data access incapability
No.4 output CN D Scan exclusion
No.5 output DS D Data set
No.6 output UK D Unfixed My Element output
No.7 output CE D Block arithmetic error

SETTING
Nothing

CONTROL
初期化時の処理 PARAMETER
Nothing

ACTION
No action

QUALITY HANDLING/PROCESSING AT INITIALIZATION


【Quality Handling】Calculate with the above calculation expression.
The output qualities are all normal
【Processing at Initialization】Nothing in particular

Appendix-1 Function Block Description


ELEMENT Quality Fetch Analog CODE 206 SYMBOL QGA
DATA LOGGAR FUNCTIONS
FUNCTION

• Acquiring each quality code status by ON/OFF from input-signal quality information

INPUT/OUTPUT

No Code Type Description


No.1 input X A Input signal
No.1 output RO D Range-over upper limit
No.2 output RU D Range-over lower limit
No.3 output AE D Data access incapability
No.4 output CN D Scan exclusion
No.5 output DS D Data set
No.6 output UK D Unfixed My Element output
No.7 output CE D Block arithmetic error

SETTING
Nothing

CONTROL
初期化時の処理 PARAMETER
Nothing

ACTION
No action

QUALITY HANDLING/PROCESSING AT INITIALIZATION


【Quality Handling】Calculate with the above calculation expression.
The output qualities are all normal
【Processing at Initialization】Nothing in particular

Appendix-1 Function Block Description


ELEMENT Average Value CODE 209 SYMBOL AVE
DATA LOGGAR FUNCTIONS
FUNCTION • Calculate the average value of input data that is not approved as the calculation exclusion
conditions
• While the value is output continuing the average processing until the trigger is ON, the
internal is reset and starts new-average from next time
Calculation precision
• Internal work variables should be twice as precise as the reals
• Please note valid digit number decreases as the sampling frequency increases
INPUT/OUTPUT

No Code Type Description


No.1 input X A Input signal
No.2 input Su D Calcuration exclusion conditions
No.3 input sw D Memory trigger
No.1 output Y A Average value

SETTING

CONTROL
初期化時の処理 PARAMETER

Parameter Abbr. Default Value External Input Range


Calcuration interval DT 1 Divisor of 3600(sec)

ACTION
No action

QUALITY HANDLING/PROCESSING AT INITIALIZATION


【Quality Handling】If the sampling cycle exceeds the arithmetic cycle by 2147483647 scaling factor or is
smaller by 0.5 scaling factor, the quality of Own-block output should be a block arithmetic
error.
If the input signal quality is not fixed with the output, it should be calculated considering the
calculation condition is OFF.
The output quality should be incapable of data access when the calculation exclusion
conditions are approved continuously for memory trigger entry.
【Processing at Initialization】Nothing in particular

Appendix-1 Function Block Description


ELEMENT PB operation CODE 403 SYMBOL PB
LOOP PLATES
FUNCTION

• The element outputs the PB operation signal from OPS as a One-Shot signal.

INPUT/OUTPUT

No Code Type Description


No.1 input X ED PB operation instruction
No.1 output Y D One-Shot signal

SETTING
Nothing

CONTROL PARAMETER
初期化時の処理
Nothing

ACTION
No action

QUALITY HANDLING/PROCESSING AT INITIALIZATION


【Quality Handling】The quality is always normal.
【Processing at Initialization】None.

Appendix-1 Function Block Description


ELEMENT Increasing/decreasing operation CODE 404 SYMBOL S/S
LOOP PLATES
FUNCTION

• The element accepts the increase/decrease operation for analog values (SV, MV) from OPS.

INPUT/OUTPUT

No Code Type Description


No.1 input X A Input signal
No.2 input S EA Data setting signal
No.3 input sw D Data setting permission
No.4 input H A High limit (Parameter External Input)
No.5 input L A Low limit (Parameter External Input)
No.1 output Y A Output value
No.2 output OH D Upper limit of Output
No.3 output OL D Lower limit of Output

SETTING

CONTROL PARAMETER
初期化時の処理

Parameter Abbr. Default Value External Input Range


Low limit L 0 Possible H≧L
High limit H 1 Possible H≧L

ACTION
No action

QUALITY HANDLING/PROCESSING AT INITIALIZATION


【Quality Handling】The quality of input X is transmitted when T is 0.
The quality is normal when T is 1.
【Processing at Initialization】None.

Appendix-1 Function Block Description


ELEMENT Single analog set & sub PBs type CODE 411 SYMBOL OPX
LOOP PLATES
FUNCTION

3 digit display 1
3 digit display 2
3 digit display 3
PV, MV, SV display
Sub PB 2
and operation

……
Sub PB 10

INPUT/OUTPUT

No Code Type Description


No.1 input S-PB-2 D Status of sub PB 2
No.2 input S-PB-3 D Status of sub PB 3
No.3 input S-PB-4 D Status of sub PB 4
No.4 input S-PB-5 D Status of sub PB 5
No.5 input S-PB-6 D Status of sub PB 6
No.6 input S-PB-7 D Status of sub PB 7
No.7 input S-PB-8 D Status of sub PB 8
No.8 input S-PB-9 D Status of sub PB 9
No.9 input S-PB-10 D Status of sub PB 10
No.10 input MV-I-PRH D (not used)
No.11 input MV-D-PRH D (not used)
No.12 input SV-I-PRH D SV increase prohibition
No.13 input SV-D-PRH D SV decrease prohibition
No.14 input V1 A (not used)
No.15 input V2 A (not used)
No.16 input V3 A (not used)
No.17 input V1CLR A Display color of the first numeric value
No.18 input V2CLR A Display color of the second numeric value
No.19 input V3CLR A (not used)
No.20 input S-PB-2-CLR A Externally specified display color
(sub PB 2 only)
No.21 input S-PB-2-STR A (not used)
No.22 input PV A PV value
No.23 input MV A (not used)
No.24 input SV A SV value
No.25 input ANN1 A First warning value
No.26 input ANN2 A Second warning value
No.27 input REF A Reference value
No.28 input PVCLR A Externally entered PV color
No.29 input MVCLR A (not used)
No.30 input SVCLR A Externally entered SV color
*The MV value cannot be displayed or operated since the MV value cannot be set onthe single analog set & sub PBs loop plate.

Appendix-1 Function Block Description


No Code Type Description
No.1 output Tagging ED (not used)
No.2 output S-PB-2-Set ED Operation of sub PB 2
No.3 output S-PB-3-Set ED Operation of sub PB 3
No.4 output S-PB-4-Set ED Operation of sub PB 4
No.5 output S-PB-5-Set ED Operation of sub PB 5
No.6 output S-PB-6-Set ED Operation of sub PB 6
No.7 output S-PB-7-Set ED Operation of sub PB 7
No.8 output S-PB-8-Set ED Operation of sub PB 8
No.9 output S-PB-9-Set ED Operation of sub PB 9
No.10 output S-PB-10-Set ED Operation of sub PB 10
No.11 output MV-Set EA (not used)
No.12 output SV-Set EA SV setting value

SETTING

CONTROL PARAMETER
初期化時の処理
Nothing

ACTION
No action

QUALITY HANDLING/PROCESSING AT INITIALIZATION


【Quality Handling】The analog input signals change the display of numeric values on the loop plate depending
on the quality.
When data is not set: ******
When data is set: Displayed in cyan
【Processing at Initialization】None.

Appendix-1 Function Block Description


ELEMENT Multiple analog set & sub PBs type CODE 412 SYMBOL OPX
LOOP PLATES
FUNCTION

3 digit display 1
3 digit display 2
3 digit display 3
PV, MV, SV display
Sub PB 2
and operation

……
Sub PB 10

INPUT/OUTPUT

No Code Type Description


No.1 input S-PB-2 D Status of sub PB 2
No.2 input S-PB-3 D Status of sub PB 3
No.3 input S-PB-4 D Status of sub PB 4
No.4 input S-PB-5 D Status of sub PB 5
No.5 input S-PB-6 D Status of sub PB 6
No.6 input S-PB-7 D Status of sub PB 7
No.7 input S-PB-8 D Status of sub PB 8
No.8 input S-PB-9 D Status of sub PB 9
No.9 input S-PB-10 D Status of sub PB 10
No.10 input MV-I-PRH D MV increase prohibition
No.11 input MV-D-PRH D MV decrease prohibition
No.12 input SV-I-PRH D SV increase prohibition
No.13 input SV-D-PRH D SV decrease prohibition
No.14 input V1 A (not used)
No.15 input V2 A (not used)
No.16 input V3 A (not used)
No.17 input V1CLR A Display color of the first numeric value
No.18 input V2CLR A Display color of the second numeric value
No.19 input V3CLR A Display color of the third numeric value
No.20 input S-PB-2-CLR A Externally specified display color
(sub PB 2 only)
No.21 input S-PB-2-STR A (not used)
No.22 input PV A PV value
No.23 input MV A MV value
No.24 input SV A SV value
No.25 input ANN1 A First warning value
No.26 input ANN2 A Second warning value
No.27 input REF A Reference value
No.28 input PVCLR A Externally entered PV color
No.29 input MVCLR A Externally entered MV color
No.30 input SVCLR A Externally entered SV color
*The MV value cannot be displayed or operated since the MV value cannot be set onthe single analog set & sub PBs loop plate.

Appendix-1 Function Block Description


No Code Type Description
No.1 output Tagging ED (not used)
No.2 output S-PB-2-Set ED Operation of sub PB 2
No.3 output S-PB-3-Set ED Operation of sub PB 3
No.4 output S-PB-4-Set ED Operation of sub PB 4
No.5 output S-PB-5-Set ED Operation of sub PB 5
No.6 output S-PB-6-Set ED Operation of sub PB 6
No.7 output S-PB-7-Set ED Operation of sub PB 7
No.8 output S-PB-8-Set ED Operation of sub PB 8
No.9 output S-PB-9-Set ED Operation of sub PB 9
No.10 output S-PB-10-Set ED Operation of sub PB 10
No.11 output MV-Set EA MV setting value
No.12 output SV-Set EA SV setting value

SETTING

CONTROL
初期化時の処理 PARAMETER
Nothing

ACTION
No action

QUALITY HANDLING/PROCESSING AT INITIALIZATION


【Quality Handling】The analog input signals change the display of numeric values on the loop plate depending
on the quality.
When data is not set: ******
When data is set: Displayed in cyan
【Processing at Initialization】None.

Appendix-1 Function Block Description


ELEMENT 2 bargraph & sub PBs type CODE 413 SYMBOL OPX
LOOP PLATES
FUNCTION

3 digit display 1
3 digit display 2
2 bargraph display
Sub PB 2

……
Sub PB 10

INPUT/OUTPUT

No Code Type Description


No.1 input S-PB-2 D Status of sub PB 2
No.2 input S-PB-3 D Status of sub PB 3
No.3 input S-PB-4 D Status of sub PB 4
No.4 input S-PB-5 D Status of sub PB 5
No.5 input S-PB-6 D Status of sub PB 6
No.6 input S-PB-7 D Status of sub PB 7
No.7 input S-PB-8 D Status of sub PB 8
No.8 input S-PB-9 D Status of sub PB 9
No.9 input S-PB-10 D Status of sub PB 10
No.10 input V1 A (not used)
No.11 input V2 A (not used)
No.12 input V3 A (not used)
No.13 input V1CLR A Display color of the first numeric value
No.14 input V2CLR A Display color of the second numeric value
No.15 input V3CLR A (not used)
No.16 input S-PB-2-CLR A Externally specified display color (sub PB 2 only)
No.17 input S-PB-2-STR A (not used)
No.18 input PVA A PVA value
No.19 input PVB A PVB value
No.20 input ANN1 A First warning value
No.21 input ANN2 A Second warning value
No.22 input REF A Reference value
No.23 input PVACLR A Externally entered PV color
No.24 input PVBCLR A Externally entered SV color
*The MV value cannot be displayed or operated since the MV value cannot be set onthe single analog set & sub PBs loop plate.

Appendix-1 Function Block Description


No Code Type Description
No.1 output Tagging ED (not used)
No.2 output S-PB-2-Set ED Operation of sub PB 2
No.3 output S-PB-3-Set ED Operation of sub PB 3
No.4 output S-PB-4-Set ED Operation of sub PB 4
No.5 output S-PB-5-Set ED Operation of sub PB 5
No.6 output S-PB-6-Set ED Operation of sub PB 6
No.7 output S-PB-7-Set ED Operation of sub PB 7
No.8 output S-PB-8-Set ED Operation of sub PB 8
No.9 output S-PB-9-Set ED Operation of sub PB 9
No.10 output S-PB-10-Set ED Operation of sub PB 10

SETTING

CONTROL PARAMETER
初期化時の処理
Nothing

ACTION
No action

QUALITY HANDLING/PROCESSING AT INITIALIZATION


【Quality Handling】The analog input signals change the display of numeric values on the loop plate depending
on the quality.
When data is not set: ******
When data is set: Displayed in cyan
【Processing at Initialization】None.

Appendix-1 Function Block Description


ELEMENT 3 bargraph & sub PBs type CODE 414 SYMBOL OPX
LOOP PLATES
FUNCTION

3 digit display 1
3 digit display 2
3 digit display 3

3 bargraph display Sub PB 2

……
Sub PB 10

INPUT/OUTPUT

No Code Type Description


No.1 input S-PB-2 D Status of sub PB 2
No.2 input S-PB-3 D Status of sub PB 3
No.3 input S-PB-4 D Status of sub PB 4
No.4 input S-PB-5 D Status of sub PB 5
No.5 input S-PB-6 D Status of sub PB 6
No.6 input S-PB-7 D Status of sub PB 7
No.7 input S-PB-8 D Status of sub PB 8
No.8 input S-PB-9 D Status of sub PB 9
No.9 input S-PB-10 D Status of sub PB 10
No.10 input V1 A (not used)
No.11 input V2 A (not used)
No.12 input V3 A (not used)
No.13 input V1CLR A Display color of the first numeric value
No.14 input V2CLR A Display color of the second numeric value
No.15 input V3CLR A Display color of the third numeric value
No.16 input S-PB-2-CLR A Externally specified display color (sub PB 2 only)
No.17 input S-PB-2-STR A (not used)
No.18 input PVA A PVA value
No.19 input PVB A PVB value
No.20 input PVC A PVC value
No.21 input ANN1 A First warning value
No.22 input ANN2 A Second warning value
No.23 input REF A Reference value
No.24 input PVACLR A Externally entered PV color
No.25 input PVBCLR A Externally entered SV color
No.26 input PVCCLR A Externally entered SV color
*The MV value cannot be displayed or operated since the MV value cannot be set onthe single analog set & sub PBs loop plate.

Appendix-1 Function Block Description


No Code Type Description
No.1 output Tagging ED (not used)
No.2 output S-PB-2-Set ED Operation of sub PB 2
No.3 output S-PB-3-Set ED Operation of sub PB 3
No.4 output S-PB-4-Set ED Operation of sub PB 4
No.5 output S-PB-5-Set ED Operation of sub PB 5
No.6 output S-PB-6-Set ED Operation of sub PB 6
No.7 output S-PB-7-Set ED Operation of sub PB 7
No.8 output S-PB-8-Set ED Operation of sub PB 8
No.9 output S-PB-9-Set ED Operation of sub PB 9
No.10 output S-PB-10-Set ED Operation of sub PB 10

SETTING

CONTROL PARAMETER
初期化時の処理
Nothing

ACTION
No action

QUALITY HANDLING/PROCESSING AT INITIALIZATION


【Quality Handling】The analog input signals change the display of numeric values on the loop plate depending
on the quality.
When data is not set: ******
When data is set: Displayed in cyan
【Processing at Initialization】None.

Appendix-1 Function Block Description


ELEMENT Main PB & sub PBs type CODE 415 SYMBOL OPX
LOOP PLATES
FUNCTION

3 digit display 1
3 digit display 2
Main PB 1 3 digit display 3

……
Sub PB 2

Main PB 5

……
Sub PB 10

INPUT/OUTPUT

No Code Type Description


No.1 input S-PB-2 D Status of sub PB 2
No.2 input S-PB-3 D Status of sub PB 3
No.3 input S-PB-4 D Status of sub PB 4
No.4 input S-PB-5 D Status of sub PB 5
No.5 input S-PB-6 D Status of sub PB 6
No.6 input S-PB-7 D Status of sub PB 7
No.7 input S-PB-8 D Status of sub PB 8
No.8 input S-PB-9 D Status of sub PB 9
No.9 input S-PB-10 D Status of sub PB 10
No.10 input FD-1 D ON/OFF status of main PB 1
No.11 input FD-2 D ON/OFF status of main PB 2
No.12 input FD-3 D ON/OFF status of main PB 3
No.13 input FD-4 D ON/OFF status of main PB 4
No.14 input FD-5 D ON/OFF status of main PB 5
No.15 input V1 A First numeric value
No.16 input V2 A Second numeric value
No.17 input V3 A Third numeric value
No.18 input V1CLR A Display color of the first numeric value
No.19 input V2CLR A Display color of the second numeric value
No.20 input V3CLR A Display color of the third numeric value
No.21 input S-PB-2-CLR A Externally specified display color (sub PB 2 only)
No.22 input S-PB-2-STR A (not used)
No.23 input FA-1-1 A Externally specified display color of main PB 1
No.24 input FA-1-2 A (not used)
No.25 input FA-2-1 A Externally specified display color of main PB 2
No.26 input FA-2-2 A (not used)
No.27 input FA-3-1 A Externally specified display color of main PB 3
No.28 input FA-3-2 A (not used)
No.29 input FA-4-1 A Externally specified display color of main PB 4
No.30 input FA-4-2 A (not used)
No.31 input FA-5-1 A Externally specified display color of main PB 5
No.32 input FA-5-2 A (not used)

Appendix-1 Function Block Description


No Code Type Description
No.1 output Tagging ED (not used)
No.2 output S-PB-2-Set ED Operation of sub PB 2
No.3 output S-PB-3-Set ED Operation of sub PB 3
No.4 output S-PB-4-Set ED Operation of sub PB 4
No.5 output S-PB-5-Set ED Operation of sub PB 5
No.6 output S-PB-6-Set ED Operation of sub PB 6
No.7 output S-PB-7-Set ED Operation of sub PB 7
No.8 output S-PB-8-Set ED Operation of sub PB 8
No.9 output S-PB-9-Set ED Operation of sub PB 9
No.10 output S-PB-10-Set ED Operation of sub PB 10
No.11 output FDO-1 ED Operation of main PB 1
No.12 output FDO-2 ED Operation of main PB 2
No.13 output FDO-3 ED Operation of main PB 3
No.14 output FDO-4 ED Operation of main PB 4
No.15 output FDO-5 ED Operation of main PB 5

SETTING

CONTROL
初期化時の処理 PARAMETER
Nothing

ACTION
No action

QUALITY HANDLING/PROCESSING AT INITIALIZATION


【Quality Handling】The analog input signals change the display of numeric values on the loop plate depending
on the quality.
When data is not set: ******
When data is set: Displayed in cyan
【Processing at Initialization】None.

Appendix-1 Function Block Description


ELEMENT Indicators & sub PBs type CODE 416 SYMBOL OPX
LOOP PLATES
FUNCTION

3 digit display 1
3 digit display 2

Main numeric value 1 3 digit display 3


(numeric value display
and bar graph display) Sub PB 2

……

……
Main numeric value 5
(numeric value display
and bar graph display)
Sub PB 10

INPUT/OUTPUT

No Code Type Description


No.1 input S-PB-2 D Status of sub PB 2
No.2 input S-PB-3 D Status of sub PB 3
No.3 input S-PB-4 D Status of sub PB 4
No.4 input S-PB-5 D Status of sub PB 5
No.5 input S-PB-6 D Status of sub PB 6
No.6 input S-PB-7 D Status of sub PB 7
No.7 input S-PB-8 D Status of sub PB 8
No.8 input S-PB-9 D Status of sub PB 9
No.9 input S-PB-10 D Status of sub PB 10
No.10 input V1 A First numeric value
No.11 input V2 A Second numeric value
No.12 input V3 A Third numeric value
No.13 input V1CLR A Display color of the first numeric value
No.14 input V2CLR A Display color of the second numeric value
No.15 input V3CLR A Display color of the third numeric value
No.16 input S-PB-2-CLR A Externally specified display color (sub PB 2 only)
No.17 input S-PB-2-STR A (not used)
No.18 input FA-1-1 A Numeric data of main numeric value 1
No.19 input FA-1-2 A Externally specified color of main numeric value 1
No.20 input FA-2-1 A Numeric data of main numeric value 2
No.21 input FA-2-2 A Externally specified color of main numeric value 2
No.22 input FA-3-1 A Numeric data of main numeric value 3
No.23 input FA-3-2 A Externally specified color of main numeric value 3
No.24 input FA-4-1 A Numeric data of main numeric value 4
No.25 input FA-4-2 A Externally specified color of main numeric value 4
No.26 input FA-5-1 A Numeric data of main numeric value 5
No.27 input FA-5-2 A Externally specified color of main numeric value 5

Appendix-1 Function Block Description


No Code Type Description
No.1 output Tagging ED (not used)
No.2 output S-PB-2-Set ED Operation of sub PB 2
No.3 output S-PB-3-Set ED Operation of sub PB 3
No.4 output S-PB-4-Set ED Operation of sub PB 4
No.5 output S-PB-5-Set ED Operation of sub PB 5
No.6 output S-PB-6-Set ED Operation of sub PB 6
No.7 output S-PB-7-Set ED Operation of sub PB 7
No.8 output S-PB-8-Set ED Operation of sub PB 8
No.9 output S-PB-9-Set ED Operation of sub PB 9
No.10 output S-PB-10-Set ED Operation of sub PB 10

SETTING

CONTROL PARAMETER
初期化時の処理
Nothing

ACTION
No action

QUALITY HANDLING/PROCESSING AT INITIALIZATION


【Quality Handling】The analog input signals change the display of numeric values on the loop plate depending
on the quality.
When data is not set: ******
When data is set: Displayed in cyan
【Processing at Initialization】None.

Appendix-1 Function Block Description


2 × 660 MW KHARGONE SUPER THERMAL
POWER PROJECT
L&T-MHPS BOILERS PRIVATE LIMITED 
(FORMERLY KNOWN AS L&T‐MHI BOILERS PRIVATE LIMITED) 
LOGIC DIAGRAM / SCHEME OF Doc. No.: 66100-1002-01
SECONDARY AIR DAMPER CONTROL Rev. No.: 00
Larsen & Toubro Ltd. Date: 26.07.2016

Appendix-2: Macro Details


Macro
S. No. Description
Name

Auto / Manual / Standby Selector: As the name implies, this macro determines the operation mode of corresponding
Control loop i.e., Auto, Manual or Standby.
1 ASMS Auto Mode is selected when Auto PB is pressed and Auto condition is available. Standby mode is selected when
Auto PB is pressed but Auto condition is not available. Manual mode is selected when either Manual PB is pressed
or Manual condition is available.

Double Redundant Circuit (Auto): In case of dual redundant analog instruments, this Macro is used to give a single
output (based on the status of input signals). When both input signals are healthy, Selected signal (out of the two) is
given as output of DRCA macro. In case anyone signal becomes faulty, the output switches to the healthy signal,
2 DRCA *
provided Interlock IN mode is selected. If Interlock OUT mode is selected, then the above mentioned switching has
to done manually. This macro also generates various alarms based on healthiness of input signal or based on
deviation between the two.

Drive Macro :

Following are the major functions of this Macro:


1) Generating Demand signals for Analog drives.
3 DRIP 2) Generating Tracking signal for the corresponding Control loop. This tracking signal can either be Demand
signal, Feedback signal or Read back signal. By default, Demand signal is selected however, Feedback & Read
back signals can also be selected, as these settings are individually configurable for each macro.
3) Generation of various Alarms like FB deviation high, RB deviation high, FB signal abnormal, RB signal
abnormal, Drive abnormal etc.
4) Reversing demand signals for Reverse Acting drives.

This macro gives flow output in volumetric or mass flow terms for a given DP signal. It also has the provision of
4 FLOW
temperature & pressure compensation.

Operational Permit: This macro is used wherever Face plate provision is available in the logic. Function of this macro
is to give Operation permit based on which switching between Auto signal (from PI controller or FX etc.) to Manual
5 OPMT
signal (from Face plate) is done. Another function of this macro is to prohibit increase or decrease in manual signal
issued from face plate incase upper / lower limit is exceeded.

Process Value color input: It is a display macro. From logic point of view, its major function is to generate Process
value hi, hi hi, lo & lo lo alarms. The set points for these alarms are set in H1inA (Hi alarm), H2inA (Hi Hi alarm),
6 PVC L1inA (Lo alarm) & L2inA (Lo Lo alarm) pins of this macro. The SG blocks (Set points) input to these pins are visible
in the Logic sheet. In case, these SG values are set at default values i.e., 99999, -99999 then No alarm will be
raised.

Process Value color 3 input: This macro is same as PVC macro. Only difference being that PVC macro is used for
7 PVC3
single analog input whereas, PVC3 macro is used for triple redundant analog inputs i.e., with TRCA macro.

Signal Abnormal Macro: This macro checks the quality of analog input signal and outputs its quality status. e.g., If
8 SABN
the input signal is abnormal, output of SABN will be 1.

Triple Redundant Circuit (Auto): In case of triple redundant analog instruments, this Macro is used to give a single
output (based on the status of input signals). When all input signals are healthy, then Mean value is given as output
of macro. In case anyone signal becomes faulty, the output switches to the next healthy signal, provided Interlock IN
9 TRCA *
mode is selected. If Interlock OUT mode is selected, then the above mentioned switching has to done manually. This
macro also generates various alarms based on healthiness of input signal or based on deviation between the input
signals.

10 VDSI Valve display indication: This is a display macro which indicates Valve related parameters in HMI.

“*” Please Note these Macro shall be as per DCS supplier’s standard.
A B C D E F G H I

1 1

2 2

3 3

4 4

5 5

6 6
REMARKS

© THIS DRAWING/DOCUMENT IS THE PROPERTY OF AND CONTAINS CONFIDENTIAL PROPRIETARY INFORMATION OF L&T-MHPS BOILERS PVT. LTD. AND SHALL NOT BE REPRODUCED, USED, DISCLOSED OR TRANSMITTED
IN WHOLE OR IN PART UNLESS AUTHORISED IN WRITING BY L&T-MHPS BOILERS PVT. LTD.
© THIS DRAWING/DOCUMENT IS THE PROPERTY OF AND CONTAINS CONFIDENTIAL PROPRIETARY INFORMATION OF L&T-MHPS BOILERS PVT. LTD. AND SHALL NOT BE REPRODUCED, USED, DISCLOSED OR TRANSMITTED
IN WHOLE OR IN PART UNLESS AUTHORISED IN WRITING BY L&T-MHPS BOILERS PVT. LTD.
A B C D E F G H I

ATPB
AUTO PB
MCD

ATCMD
AUTO COMMAND S S AUTO MODE
MCD S
1 CAUT
1
ACND R MCD

MCD
AUTO CONDITION R

STANDBY MODE
MNPB CSTB

MCD
MANUAL PB MCD

MCND
MANUAL CONDITION AUTO COMMAND
MCD DAUT

INIT
MCD

MCD
INITIALIZING
2 MANUAL MODE
2
TAG MANU

MCD
TAGGING MCD

3 3

4 4

SPDI1 SPDO1
5 5
MCD MCD

SPDI2 SPDO2

MCD MCD

SPDI3 SPDO3

MCD MCD

SPDI4 SPDO4

MCD MCD

SPDO5
6 OFF MCD
6

SPDO6

OFF MCD

TITLE : AUTO / STAND-BY / MANUAL SELECTOR Rev.


REMARKS

SHEET NO.

MITSUBISHI ASMS
HEAVY INDUSTRIES, LTD
© THIS DRAWING/DOCUMENT IS THE PROPERTY OF AND CONTAINS CONFIDENTIAL PROPRIETARY INFORMATION OF L&T-MHPS BOILERS PVT. LTD. AND SHALL NOT BE REPRODUCED, USED, DISCLOSED OR TRANSMITTED
IN WHOLE OR IN PART UNLESS AUTHORISED IN WRITING BY L&T-MHPS BOILERS PVT. LTD.
© THIS DRAWING/DOCUMENT IS THE PROPERTY OF AND CONTAINS CONFIDENTIAL PROPRIETARY INFORMATION OF L&T-MHPS BOILERS PVT. LTD. AND SHALL NOT BE REPRODUCED, USED, DISCLOSED OR TRANSMITTED
IN WHOLE OR IN PART UNLESS AUTHORISED IN WRITING BY L&T-MHPS BOILERS PVT. LTD.
$ % & ' ( ) * + ,

$1$/2*,1387$ $1$/2*287387$
0&$ 0&$

$,$ $6

$1$/2*
52
58 RII
52 287387 6(/(&7,21
 4*$
RQ ; 
$( 7 46$ 0&$
58
VZ 26

$1$/2*,1387% / 
$1$/2*287387%
+ 
0&$ 0&$

$,%  66B+/0 %6
 ;
+/ 2/'
52
58
4*$
$(
 
$1$/2*%6(/(&7,21 $1$/2*%
0&' 6(/(&7,21
3%% 6 6
6 0&'

%6/
5
5

$1$/2*$
 6(/(&7,21 
$1$/2*$6(/(&7,21 0&'

$6/
0&'

3%$

6,*1$/
$%1250$/
0&'

$%1
 %6,*1$/ 
$%1250$/
0&'

%$%1
$6,*1$/
$%1250$/
,17(5/2&.2873% 0&'

$$%1
0&'

3%2
,17(5/2&.287
6 6
2/' 6 0&'
 
287
5
5

,17(5/2&.,1
,17(5/2&.,13%
0&'
0&'
,1
3%,

/ 
 + 
 ; < $%'(9,$7,21
 + /
+,*+ 
$3&581%$&.23(5$7( 66B'+/
6'+B7,0
0&'
0&'
6'+
(;$%1

'28%/(5('81'$17&,5&8,7 5HY
7,7/( :
$872 -
6+((712
0,768%,6+,
+($9<,1'8675,(6/7'
'5&$

© THIS DRAWING/DOCUMENT IS THE PROPERTY OF AND CONTAINS CONFIDENTIAL PROPRIETARY INFORMATION OF L&T-MHPS BOILERS PVT. LTD. AND SHALL NOT BE REPRODUCED, USED, DISCLOSED OR TRANSMITTED
IN WHOLE OR IN PART UNLESS AUTHORISED IN WRITING BY L&T-MHPS BOILERS PVT. LTD.
$ % & ' ( ) * + ,

63, 632

0&' 0&'

 63, 632

0&' 0&'

63, 632

0&' 0&'

63, 632

0&' 0&'

63, 632
0&' 0&'

 

21'B63
; <
2)) '
7 

21'B63
 2))
; <
' 
7 

21'B63
; <
2)) '
7 

2)'B63
; <
2)) '
7 

 2)'B63 
; <
2)) '
7 

2)'B63
; <
2)) '
7 

7':B63
; <
2)) '

 7  
7':B63
; <
2)) '
7 

7':B63
; <
2)) '
7 

 

'28%/(5('81'$17&,5&8,7 5HY
7,7/( :
$872 -
6+((712
0,768%,6+, '5&$
+($9<,1'8675,(6/7'

© THIS DRAWING/DOCUMENT IS THE PROPERTY OF AND CONTAINS CONFIDENTIAL PROPRIETARY INFORMATION OF L&T-MHPS BOILERS PVT. LTD. AND SHALL NOT BE REPRODUCED, USED, DISCLOSED OR TRANSMITTED
IN WHOLE OR IN PART UNLESS AUTHORISED IN WRITING BY L&T-MHPS BOILERS PVT. LTD.
© THIS DRAWING/DOCUMENT IS THE PROPERTY OF AND CONTAINS CONFIDENTIAL PROPRIETARY INFORMATION OF L&T-MHPS BOILERS PVT. LTD. AND SHALL NOT BE REPRODUCED, USED, DISCLOSED OR TRANSMITTED
IN WHOLE OR IN PART UNLESS AUTHORISED IN WRITING BY L&T-MHPS BOILERS PVT. LTD.
A B C D E F G H I

DEM AO
DEM AO RO
MCA LIN MCA
RU 1QB
CONTROL DEMAND CONTROL DEMAND RB1 Readback Signal 1 QGA
X1=-10.0 RBO FBO N
Y1=-10.0 N N AE
X2=110.0
2SE Y2=110.0 sw sw TRKS 1SB
TRK SIGNAL
1 L off
T
off
T MCA
N 1
RB SINNAL 1 RB1
RB1I sw on on RBSO
off RO
MCA TR LIN MCA
on RB SIGNAL RU 2QB
RB2I
RB2 X1=-10.0 RB2 Readback Signal 2 QGA
Y1=-10.0 N
X2=110.0 AE
MCA
Y2=110.0
RB SIGNAL
FBI
2 FBI
2SB
FBO N
FB SIGNAL
MCA MCA
FB SIGNAL
FBON1 RB1-RB2 DEV H Set value RB1out 12D ARD ONT
FB SELECTION-1 12D V V 1
MCD SG RB1 Readback Signal 1 MCA
2 FBO
V
- H T
2
S03 FB = TRK S=10.0 RB2out
FBON2 N DEM-RB DEV H Set value(Common) + X X Y 12R
RB2 Readback Signal 2 MCA ABS H
ARD B
MCD SG V SVclr H=input T=input
FB SELECTION-2 + H T
S=10.0
RB DEV OND Timer value SVS SOV Status Color MCA
INIT - X X Y DRB
AO AO signal ABS H
MCD
INITIALIZE RBO
SG
ONT 1
N 1 RSAB H=input ARB T=input
RSA Readback signal abnormal + H 1 T
S02 RB = TRKS S=1.0
DEM-FB DEV H set value MCD
B - X X Y DRB
FDH DFD DRDH
ABS H 2
FDHEX E
SG V DRD DEM-RB DEV H output ARB
MCD H=input T=input
S=10.0 H 2
MCD
FB DEV OND Timer value FSAB DRB DEM-RB1 DEV H
DFD ONT FSA FB Signal Abnormal 1
RUNBACK OPERATE SG MCD
3 H 2 B DRD
H
3
S04 DEM-FB DEH check ON S=1.0 DFDH
DFD DEM-FB DEV H output DRB DEM-RB2 DEV H
MCD
DFB DEM-FB DEV H H 2
D 2SE RB2 signal Selected
LCKCND LABO L
MCD
LOCK CONDITION LCN LAB Loop Abnormal
MCD
D O
LCKRST LARP RO FDH
MCD
LOCK RELESE LRR LAR Loop Abnormal Reset Permit
MCD
E
S P RU FQA
FBI Feedback Signal QGA
LABRST LCKCMD B
MCD
LOOP ABN RESET LRS LCM SV Lock CMD
MCD
AE
T D
SABCND LRPMT DFD ONT FSA
MCD
SIGNAL ABNORMAL SAB RLS SV Relese Permit
MCD
V 2 B
C P
4 SABRST 1SBN + H T 4
SIGNAL ABNORMAL RESET 1SB RB1 Signal Abnormal
DEM Demand Signal
- X X Y DFB
MCD D N
MCD ABS H D
DABCND 2SBN H=99999.0T=0.0
MCD
DRIVE ABNORMAL DAB 2SB RB2 Signal Abnormal
MCD
C N
S01 RB Signal auto change over permit
DABRST 12DH

MCD
DRIVE ABNORMAL RESET DRS 12R RB1-RB2 DEV H
MCD
ARB AO-RB1 DEV H S
S
S 2SE
T B 1 L
ALLRST RQAB
ALL ABNORMAL RESET ARS RQA Readback signal quality abnormal R
MCD MCD
T B R
MANU FQAB

MCD
MANUAL CONDITION MAN FQA FB signal Quality abnormal
MCD
U B
DR1DH ARB AO-RB2 DEV H
5 RB Auto change over use : (Use=1 / No use=0) DRB DEM-RB1 DEV H 2 5
MCD
1
S01 DG S01
DR2DH
S=0 DRB DEM-RB2 DEV H
MCD MCD
2
RB Auto change over use SABO 1QB RB1 signal Quality abnormal
Always RB = TRK use : (Use=1 / No use=0) N
OFF MCD
X Y RQA
S02 DG S02
B
SARP
S=0 2QB RB2 signal Quality abnormal T=0.5
MCD OFF MCD
N
Always RB = TRK use DABO
Always FB = TRK use : (Use=1 / No use=0) DAB Drive Abnormal
MCD
O 1SB RB1 Signal Abnormal
S03 DG S03
N
DARP
S=0 DAR Drive Abnormal Reset Permit X Y RSA
6 MCD
P
MCD
B 6
Always FB = TRK use DRVM 2SB RB2 Signal Abnormal T=0.5
Always DEM-FB DEV check use : (Use=1 / No use=0) MAN N
MCD
U 2SE RB2 signal Selected
S04 DG S04
SAB L
S=0 C FORCED MANUAL
MCD
Always DEM-FB DEV check use
TITLE : DRIVE MACRO (I/P TYPE) -1/2 Rev.
REMARKS

SHEET NO.
MITSUBISHI DRIP-1
HEAVY INDUSTRIES, LTD

© THIS DRAWING/DOCUMENT IS THE PROPERTY OF AND CONTAINS CONFIDENTIAL PROPRIETARY INFORMATION OF L&T-MHPS BOILERS PVT. LTD. AND SHALL NOT BE REPRODUCED, USED, DISCLOSED OR TRANSMITTED
IN WHOLE OR IN PART UNLESS AUTHORISED IN WRITING BY L&T-MHPS BOILERS PVT. LTD.
A B C D E F G H I

SV Lock ind. color Reset Condition Color


S=114.0 S=7.0
SG SG

on on
off off
SG T T SVS
1 1
S=3.0 sw sw

LCN LOCK CONDITION S S LCM


D
S D
LRR LOCK RELESE
S
R
R RLS
P

2 2

DAB
O
DAB DRV ABN CONDITION S S
C S
DRS DRV ABN RESET
R
3 T
LRS LOOP ABN RESET X Y R
3
T
ARS ALL ABN RESET T=0.5 DAR
T P

LAR
P

LAB
O
4 4

5 5

SPAI01 SPAO01

MCA MCA
6 SPAI02 SPAO02 6
MCA MCA
SPDI01 SPDO01

MCD MCD

TITLE : DRIVE MACRO ( I/P TYPE ) -2/2 Rev.


REMARKS

SHEET NO.

MITSUBISHI DRIP-2
HEAVY INDUSTRIES, LTD
© THIS DRAWING/DOCUMENT IS THE PROPERTY OF AND CONTAINS CONFIDENTIAL PROPRIETARY INFORMATION OF L&T-MHPS BOILERS PVT. LTD. AND SHALL NOT BE REPRODUCED, USED, DISCLOSED OR TRANSMITTED
IN WHOLE OR IN PART UNLESS AUTHORISED IN WRITING BY L&T-MHPS BOILERS PVT. LTD.
© THIS DRAWING/DOCUMENT IS THE PROPERTY OF AND CONTAINS CONFIDENTIAL PROPRIETARY INFORMATION OF L&T-MHPS BOILERS PVT. LTD. AND SHALL NOT BE REPRODUCED, USED, DISCLOSED OR TRANSMITTED
IN WHOLE OR IN PART UNLESS AUTHORISED IN WRITING BY L&T-MHPS BOILERS PVT. LTD.
A B C D E F G H I

AI Aout

MCA
ANALOG INPUT LIN
X1 X1
LIN MCA

X1=0.0 X2 X2 X1=0.0
Y1=0.0 Y1=0.0
ANALOG OUTPUT
X2=100.0 X2=1.0
Y2=1.0 Y2=100.0

1 S=1.0 1
SG

TEMP CONPENSATION VALUE


TCMP off
on
MCA T TCV
sw

PRESS CONPENSATION VALUE


PCMP off
on
MCA T PCV
sw TEMP CONPENSATION VALUE
2 Temp compensation value use :(Use=1 / Nouse=0)
X
TCV
2
SG H TCV MCA

S=0.0 H=0.9

PRESS CONPENSATION VALUE


Press compensation value use :(Use=1 / Nouse=0) PCV
X
SG H PCV MCA

S=0.0 H=0.9
SPAI01 SPAO01

MCA MCA

SPAI02 SPAO02

MCA MCA
3 3

SPDI01 SPDO01

MCD MCD

SPDI02 SPDO02

MCD MCD
4 4
SPDI03 SPDO03

MCD MCD

SPDI04 SPDO04

MCD MCD

SPDI05 SPDO05

MCD MCD

5 5

6 6

TITLE : FLOW SIGNAL CALCULATION MACRO Rev.


REMARKS

SHEET NO.

MITSUBISHI FLOW
HEAVY INDUSTRIES, LTD
© THIS DRAWING/DOCUMENT IS THE PROPERTY OF AND CONTAINS CONFIDENTIAL PROPRIETARY INFORMATION OF L&T-MHPS BOILERS PVT. LTD. AND SHALL NOT BE REPRODUCED, USED, DISCLOSED OR TRANSMITTED
IN WHOLE OR IN PART UNLESS AUTHORISED IN WRITING BY L&T-MHPS BOILERS PVT. LTD.
© THIS DRAWING/DOCUMENT IS THE PROPERTY OF AND CONTAINS CONFIDENTIAL PROPRIETARY INFORMATION OF L&T-MHPS BOILERS PVT. LTD. AND SHALL NOT BE REPRODUCED, USED, DISCLOSED OR TRANSMITTED
IN WHOLE OR IN PART UNLESS AUTHORISED IN WRITING BY L&T-MHPS BOILERS PVT. LTD.
A B C D E F G H I

Ain Aout

MCA
ANALOG INPUT ANALOG OUTPUT MCA

1 OPC
1
MCD
MANUAL MODE

OPRH

MCD
OPERATION PERMIT MCD

FORCE COMMAND OPP

MV INCREASE PERMIT MCD


ULMT
IPRH
MCD
2 2
UPPER LIMIT

LOWER LIMIT MV DECREASE PERMIT MCD


LLMT
DPRH
MCD

INIT

MCD

INITIALIZE

3 3

4 4

5 5

6 MCD MCD
6
SPI1 SPO1

MCD MCD
Rev
SPI2 SPO2 TITLE : OPERATIONAL PERMIT

MCD MCD
SHEET NO.
SPI3 SPO3
MITSUBISHI OPMT
HEAVY INDUSTRIES, LTD
© THIS DRAWING/DOCUMENT IS THE PROPERTY OF AND CONTAINS CONFIDENTIAL PROPRIETARY INFORMATION OF L&T-MHPS BOILERS PVT. LTD. AND SHALL NOT BE REPRODUCED, USED, DISCLOSED OR TRANSMITTED
IN WHOLE OR IN PART UNLESS AUTHORISED IN WRITING BY L&T-MHPS BOILERS PVT. LTD.
© THIS DRAWING/DOCUMENT IS THE PROPERTY OF AND CONTAINS CONFIDENTIAL PROPRIETARY INFORMATION OF L&T-MHPS BOILERS PVT. LTD. AND SHALL NOT BE REPRODUCED, USED, DISCLOSED OR TRANSMITTED
IN WHOLE OR IN PART UNLESS AUTHORISED IN WRITING BY L&T-MHPS BOILERS PVT. LTD.
A B C D E F G H I
Ain THA

MCA
ANALOG INPUT THROUGH ANALOG OUTNPUT MCA
X
RO RO Aout
PV
OFF
QGA
RU
QSA
ANALOG OUTNPUT MCA
H set value L set value
RU
OFF S=-99999.0
SG S=99999.0 SG
PV
AE SAB
1 N off off 1
on H1S on L1S
H1A T V
H1 SV L1A T V
L1SV
sw sw

H color L color H2 color L2 color H3 color L3 color H4 color L4 color ABN color
S=414.0 S=414.0 S=414.0 S=414.0 S=414.0 S=414.0 S=414.0 S=414.0 S=304.0 D01

SG SG SG SG SG SG SG SG SG H L
Default Color COLOR NUMBER X
H1 H1
X
L1 L1
S=1.0 on on on on on on on on on Cout H L
off off off off off off off off off DB H=input DB L=input
SG T T T T T T T T T MCA
DB=0.0 DB=input
HIGH ALARM1 sw sw sw sw sw sw sw sw sw
DB
Hin H1 ALM OND
X Y H1ALM
MCD
2 MCD HIGH ALARM 1
H2 set value L2 set value
2
T=0.0 S=-99999.0
Lin
H1 L1 ALM OND SG S=99999.0 SG
X Y L1ALM
MCD
LOW ALARM 1 MCD LOW ALARM 1
off off
T=0.0 on H2S on L2S
H2in L1 H2 ALM OND H2A T V
H2SV L2A T V
L2SV
X Y H2ALM sw sw
MCD
HIGH ALARM 2 MCD HIGH ALARM 2
H2 T=0.0 D01
L2in L2 ALM OND
MCD
LOW ALARM 2 X Y L2ALM

LOW ALARM 2 H L
MCD
T=0.0 X X
L2 H2 H2 L2 L2
H3in HIGH ALARM 3 H3 ALM OND H L
X Y H3ALM DB H=input DB L=input
MCD
DB=0.0 DB=input
3 T=0.0
MCD HIGH ALARM 3 3
L3in
H3 L3 ALM OND DB
X Y L3ALM
MCD
LOW ALARM 3 H3 set value L3 set value
MCD LOW ALARM 3
T=0.0 S=-99999.0
H4in L3 H4 ALM OND SG S=99999.0 SG
X Y H4ALM
MCD
HIGH ALARM 4 off off
T=0.0
MCD HIGH ALARM 4 on H3S on L3S
L4in
H4 L4 ALM OND H3A T V
H3SV L3A T V
L3SV

MCD LOW ALARM 4 X Y L4ALM sw sw


MCD LOW ALARM 4
T=0.0
SABN SIGNAL ABNOMAL L4 SABND D01
X Y
MCD MCD
H L
4 SAB T=3.0 X X 4
N SIGNAL ABNOMAL H
H3 H3
L
L3 L3
DB H=input DB L=input
H1inA HIGH ALARM SET VALUE 1 Alarm set value Analog Input use : 1=use HIGH ALARM SET VALUE 1 H1SV DB=0.0 DB=input
H1S
MCA H1A DG D01
V
MCA DB
S=0
L1inA LOW ALARM SET VALUE 1 LOW ALARM SET VALUE 1 L1SV H4 set value L4 set value
L1S
MCA L1A Common DB value V
MCA SG S=99999.0 SG S=-99999.0

H2inA HIGH ALARM SET VALUE 2 SG DB


HIGH ALARM SET VALUE 2 H2SV off off
S=0.0 H2S on H4S on L4S
MCA H2A
V
MCA H4A T V
H4SV L4A T V
L4SV
sw sw
L2inA LOW ALARM SET VALUE 2 LOW ALARM SET VALUE 2 L2SV
5 L2S 5
MCA L2A MCA D01
V

H3inA HIGH ALARM SET VALUE 3 HIGH ALARM SET VALUE 3 H3SV H L
H3S X X
MCA H3A MCA H4 H4 L4 L4
V H L
DB H=99999.0 DB L=input
L3inA LOW ALARM SET VALUE 3 LOW ALARM SET VALUE 3 L3SV DB=0.0 DB=input
L3S
MCA L3A MCA DB
V

H4inA HIGH ALARM SET VALUE 4 HIGH ALARM SET VALUE 4 H4SV
H4S
MCA H4A MCA
V

L4inA LOW ALARM SET VALUE 4 SABN ALM OND LOW ALARM SET VALUE 4 L4SV
6 MCA L4A X Y L4S
MCA
6
OFF D V
T=0.0

TITLE : PROCESS VALUE COLOR INPUT Rev.


REMARKS

SHEET NO.

MITSUBISHI PVC
HEAVY INDUSTRIES, LTD
© THIS DRAWING/DOCUMENT IS THE PROPERTY OF AND CONTAINS CONFIDENTIAL PROPRIETARY INFORMATION OF L&T-MHPS BOILERS PVT. LTD. AND SHALL NOT BE REPRODUCED, USED, DISCLOSED OR TRANSMITTED
IN WHOLE OR IN PART UNLESS AUTHORISED IN WRITING BY L&T-MHPS BOILERS PVT. LTD.
© THIS DRAWING/DOCUMENT IS THE PROPERTY OF AND CONTAINS CONFIDENTIAL PROPRIETARY INFORMATION OF L&T-MHPS BOILERS PVT. LTD. AND SHALL NOT BE REPRODUCED, USED, DISCLOSED OR TRANSMITTED
IN WHOLE OR IN PART UNLESS AUTHORISED IN WRITING BY L&T-MHPS BOILERS PVT. LTD.
$ % & ' ( ) * + ,

52 ; < 2$% 52 ; < $$% 52 ; < &$%


4*$ 4*$ 4*$
1 1 1
7  7  7 

 $,2 $,$ $,&



; ; ;
0&$ 0&$ 0&$
26 $6 &6
52 52 52
46$ 0&$ 46$ 0&$ 46$ 0&$

58 +69
+$/021' 58 58
2)) 6  6  2)) 2))
+6 +2 +6 +2
9 ' $+ 9 ' &+
6* 6*
0&' 0&'
+ 7 + 7
+LQ$ RII ; ; < ; ; <
RQ +6 +2 + +
0&$ 7 9 ' '% 7 
$+
'% 7 
&+
'% '%
VZ 2+

 '
+ 7
0&'
+6
9
+2
' $+
+6
9
+2
' &+

; ; <
0&' 0&'
+ 2+
+ 7 + 7
'% 7  ; ; < ; ; <
'%
+ $+
+ &+
'% 7  '% 7 
+69
+$/021' '% '%
6  6  /6 /2 /6 /2
9 ' $/ 9 ' &/
6* 6*
0&' 0&'
/ 7 / 7
+LQ$ RII ; ; < ; ; <
RQ +6 +2 / /
0&$ 7 9 ' '% 7 
$/
'% 7 
&/
'% '%
VZ 2+
/6 /2 /6 /2
 '
+ 7
0&'
9 ' $/ 9 ' &/ 
; ; <
0&' 0&'
+ 2+
/ 7 / 7
'% 7  ; ; < ; ; <
'%
/ $/
/ &/
'% 7  '% 7 
/69
/$/021' '% '%
6  6 
6* 6*

/LQ$ RII
RQ /6 /2
0&$ 7 9 ' 52 ; < %$%
4*$
VZ 2/ 1
7 
 '
/ 7
0&' 
; ; <
/ 2/
'% 7  $,%
;
'% 0&$
/69
/$/021' %6
6  6  52
46$ 0&$
6* 6*
58
2))
/LQ$ RII +6 +2
RQ /6 /2 9 ' %+
0&$ 7 9 '
0&'
VZ 2/ + 7
; ; <
 '
/ 7
0&'
+ 
%+
; ; < '% 7 
'%
/ 2/
'% 7  +6 +2
9 ' %+
'%
0&'
+ 7
; ; <
+69$,XVH XVH +
6  %+
'% 7 
'%
'* '
/6 /2
9 ' %/
+69$,XVH XVH
0&'
6  / 7
; ; <
 '* '
/ %/

'% 7 
/69$,XVH XVH '%
6  /6 /2
9 ' %/
'* '
0&'
/ 7
/69$,XVH XVH ; ; <
6  / 7,7/( : PROCESS VALUE COLOR 3 INPUT -1/2 5HY
%/
'% 7 
'* ' '%

'%9$/8( 6+((712
6 
6* '%
39&
+($9<,1'8675,(6/7'

© THIS DRAWING/DOCUMENT IS THE PROPERTY OF AND CONTAINS CONFIDENTIAL PROPRIETARY INFORMATION OF L&T-MHPS BOILERS PVT. LTD. AND SHALL NOT BE REPRODUCED, USED, DISCLOSED OR TRANSMITTED
IN WHOLE OR IN PART UNLESS AUTHORISED IN WRITING BY L&T-MHPS BOILERS PVT. LTD.
$ % & ' ( ) * + ,

+&RORU
/&RORU
+&RORU
/&RORU
$%1&RORU
6  6  6  6  6 
6* 6* 6* 6* 6*

+& /& +& /& $%&


+& /& +& /& $%&
 'HIDXOW&RORU

6  RQ RQ RQ RQ RQ 2&2 RQ RQ RQ RQ RQ %&2
RII RII RII RII RII RII RII RII RII RII
6* 7 7 7 7 7 0&$ '& 7 7 7 7 7 0&$
VZ VZ VZ VZ VZ VZ VZ VZ VZ VZ

'&

2+ %+

2/ %/

 2+ %+ 

2/ %/

2$% %$%
1 1

%DU'HIDXOW&RORU
6  VZ VZ VZ VZ VZ 2&2 VZ VZ VZ VZ VZ %&2
RII RII RII RII RII RII RII RII RII RII
6* 7 7 7 7 7 0&$ %'& 7 7 7 7 7 0&$
RQ RQ RQ RQ RQ RQ RQ RQ RQ RQ
 
%'& +& /& +& /& $%& +& /& +& /& $%&

+& /& +& /& $%& +& /& +& /& $%&

 
RQ RQ RQ RQ RQ $&2 RQ RQ RQ RQ RQ &&2
RII RII RII RII RII RII RII RII RII RII
'& 7 7 7 7 7 0&$ '& 7 7 7 7 7 0&$
VZ VZ VZ VZ VZ VZ VZ VZ VZ VZ

$+ &+

$/ &/

 $+ &+ 
$/ &/

$$% &$%
1 1

VZ VZ VZ VZ VZ $&2 VZ VZ VZ VZ VZ &&2
RII RII RII RII RII RII RII RII RII RII
%'& 7 7 7 7 7 0&$ %'& 7 7 7 7 7 0&$
RQ RQ RQ RQ RQ RQ RQ RQ RQ RQ

 
+& /& +& /& $%& +& /& +& /& $%&

7,7/( : PROCESS VALUE COLOR 3 INPUT -2/2 5HY

6+((712

39&
+($9<,1'8675,(6/7'

© THIS DRAWING/DOCUMENT IS THE PROPERTY OF AND CONTAINS CONFIDENTIAL PROPRIETARY INFORMATION OF L&T-MHPS BOILERS PVT. LTD. AND SHALL NOT BE REPRODUCED, USED, DISCLOSED OR TRANSMITTED
IN WHOLE OR IN PART UNLESS AUTHORISED IN WRITING BY L&T-MHPS BOILERS PVT. LTD.
© THIS DRAWING/DOCUMENT IS THE PROPERTY OF AND CONTAINS CONFIDENTIAL PROPRIETARY INFORMATION OF L&T-MHPS BOILERS PVT. LTD. AND SHALL NOT BE REPRODUCED, USED, DISCLOSED OR TRANSMITTED
IN WHOLE OR IN PART UNLESS AUTHORISED IN WRITING BY L&T-MHPS BOILERS PVT. LTD.
A B C D E F G H I

1 1

2 2

3 3
RO

RU X Y
ANALOG INPUT MCA QGA MCD SIGNAL ABNORMAL
ANA T=3.0 SABN

AE

4 4

MCD RANGE OVER


RO

MCD RANGE UNDER


RU

MCD ACCESS ERROR


AE

5 5

OND
X Y
OFF D
T=0.0

6 6

Rev
TITLE : SIGNAL ABNORMAL MACRO LOGIC

SHEET NO.

MITSUBISHI SABN
HEAVY INDUSTRIES, LTD
© THIS DRAWING/DOCUMENT IS THE PROPERTY OF AND CONTAINS CONFIDENTIAL PROPRIETARY INFORMATION OF L&T-MHPS BOILERS PVT. LTD. AND SHALL NOT BE REPRODUCED, USED, DISCLOSED OR TRANSMITTED
IN WHOLE OR IN PART UNLESS AUTHORISED IN WRITING BY L&T-MHPS BOILERS PVT. LTD.
© THIS DRAWING/DOCUMENT IS THE PROPERTY OF AND CONTAINS CONFIDENTIAL PROPRIETARY INFORMATION OF L&T-MHPS BOILERS PVT. LTD. AND SHALL NOT BE REPRODUCED, USED, DISCLOSED OR TRANSMITTED
IN WHOLE OR IN PART UNLESS AUTHORISED IN WRITING BY L&T-MHPS BOILERS PVT. LTD.
$ % & ' ( ) * + ,

$,$
$1$/2*287387$
$,$ $6
$1$/2*,1387$
0&$ 0&$

 52

58
4*$
$( $1$/2*
$,% 287387 6(/(&7,21
$,% ; RQ RQ RQ 26
$1$/2*,1387% ; RII RII RII
0&$ 0(' 7 7 7 0&$
; VZ VZ VZ
52 26
58
4*$
$(
$,&
$1$/2*287387&
 $,&
$1$/2*,1387&
&6 
0&$ 0&$
6(
/
52
58 6(
4*$
/
$(
6( $1$/2*287387%
/ %6

0&$

$,$

  66B+/0
$$%1

 ; $%'
+/ 2/'
9
0&'
/ 
$,% + 
$%
$6,*1$/
 66B+/0 1 $%1250$/
 ; %&' 6,*1$/$%1250$/
+/ 2/'
9
/  %$%1

$,& +  0&'


 66B+/0
 ; &$' $% %6,*1$/
+/ 2/'
9 1 $%1250$/
/  6,*1$/$%1250$/
 + 
&$%1

0&'

$% &6,*1$/
1
6,*1$/$%1250$/ $%1250$/

$,& / 

+ 

01
+ /
$% 0 
626B'+/ 6'+
1
$,% / 
 '(9,$7,21+,*+
+ 

 + / 7  
$% ; <
626B'+/ 01
1
$,$ / 
 0  7

+  '(9,$7,21+,*+
26
+ / 6'+
$%
626B'+/
1
6* 0&'

6 

7
; <

7 

 (;$%1 581%$&.23(5$7( 
0&'

7,7/( : 75,3/(5('81'$17 5HY

0($685(0(17(AUTO) -
6+((712

0,768%,6+, TRCA-
+($9<,1'8675,(6/7'

© THIS DRAWING/DOCUMENT IS THE PROPERTY OF AND CONTAINS CONFIDENTIAL PROPRIETARY INFORMATION OF L&T-MHPS BOILERS PVT. LTD. AND SHALL NOT BE REPRODUCED, USED, DISCLOSED OR TRANSMITTED
IN WHOLE OR IN PART UNLESS AUTHORISED IN WRITING BY L&T-MHPS BOILERS PVT. LTD.
$ % & ' ( ) * + ,

6(
/

 $% 
1

6(
/

$%
1

 

6( 6,*1$/$%1250$/
/ $%1

0&'
$%
1

 01 
0 

06(
/

; <
,1
7 

 6'+ 

 3%2 
,17(5/2&.2873% ,17(5/2&.287
0&' 287
6 6
$% 6 0&'
1
5
$% 5
01 2/'
1
0 
$%
1
,17(5/2&.,1
3%, ,1
,17(5/2&.,13%
 0&' 0&' 
,1

75,3/(5('81'$17 5HY
7,7/( :
0($685(0(17(AUTO) -
6+((712

0,768%,6+, TRCA
+($9<,1'8675,(6/7'

© THIS DRAWING/DOCUMENT IS THE PROPERTY OF AND CONTAINS CONFIDENTIAL PROPRIETARY INFORMATION OF L&T-MHPS BOILERS PVT. LTD. AND SHALL NOT BE REPRODUCED, USED, DISCLOSED OR TRANSMITTED
IN WHOLE OR IN PART UNLESS AUTHORISED IN WRITING BY L&T-MHPS BOILERS PVT. LTD.
$ % & ' ( ) * + ,

%&'
9
 

$%'
9

&$'
9
6,*1$/$6(/(&7
$6/
 $6(/(&7,213%
3%$
6( 6,*1$/6(/(&7
59'
6
6
6
0&' 
/
0&' 5 6(
$% 5 /
1
6,*1$/$%1250$/
6,*1$/0(',$16(/(&7
&$' 06/
9
0&'

06(
/
%&'
 9 

$%'
9
6,*1$/%6(/(&7
%6/
%6(/(&7,213% 6( 6,*1$/6(/(&7 6 6
3%% /
59' 6 0&'

0&' 5 6(
$% 5 /
1
 6,*1$/$%1250$/ 
$%'
9

&$'
9

%&'
 9 
6,*1$/&6(/(&7
&6/
&6(/(&7,213% 6( 6 6
3%& /
59' 6 0&'

6,*1$/6(/(&7
0&' 5 6(
$% 5 /
1
6,*1$/$%1250$/

,1 01
0(',$16(/(&73% ,17(5/2&.,1 0 
3%0
 
0&'

75,3/(5('81'$17 5HY
7,7/( :
0($685(0(17(AUTO) -
6+((712

0,768%,6+, TRCA
+($9<,1'8675,(6/7'

© THIS DRAWING/DOCUMENT IS THE PROPERTY OF AND CONTAINS CONFIDENTIAL PROPRIETARY INFORMATION OF L&T-MHPS BOILERS PVT. LTD. AND SHALL NOT BE REPRODUCED, USED, DISCLOSED OR TRANSMITTED
IN WHOLE OR IN PART UNLESS AUTHORISED IN WRITING BY L&T-MHPS BOILERS PVT. LTD.
$ % & ' ( ) * + ,

63, 632

0&' 0&'

 63, 632

0&' 0&'

63, 632

0&' 0&'

63, 632

0&' 0&'

 
63, 632

0&' 0&'

21'B63
; <
2)) '
7 

21'B63
 2))
; <
' 
7 

21'B63
; <
2)) '
7 

2)'B63
; <
2)) '
7 

 2)'B63 
; <
2)) '
7 

2)'B63
; <
2)) '
7 

7':B63
; <
2)) '

 7  
7':B63
; <
2)) '
7 

7':B63
; <
2)) '
7 

 

75,3/(5('81'$17 5HY
7,7/( :
0($685(0(17(AUTO) - 
6+((712

0,768%,6+, TRCA
+($9<,1'8675,(6/7'

© THIS DRAWING/DOCUMENT IS THE PROPERTY OF AND CONTAINS CONFIDENTIAL PROPRIETARY INFORMATION OF L&T-MHPS BOILERS PVT. LTD. AND SHALL NOT BE REPRODUCED, USED, DISCLOSED OR TRANSMITTED
IN WHOLE OR IN PART UNLESS AUTHORISED IN WRITING BY L&T-MHPS BOILERS PVT. LTD.
© THIS DRAWING/DOCUMENT IS THE PROPERTY OF AND CONTAINS CONFIDENTIAL PROPRIETARY INFORMATION OF L&T-MHPS BOILERS PVT. LTD. AND SHALL NOT BE REPRODUCED, USED, DISCLOSED OR TRANSMITTED
IN WHOLE OR IN PART UNLESS AUTHORISED IN WRITING BY L&T-MHPS BOILERS PVT. LTD.
A B C D E F G H I

Pin Pout

MCA
POSITION SIGNAL POSITION SIGNAL MCA
RO
RU
POS Position signal QGA
AE SAB
OPND N
OPN OPENED PSA Position signal ABN
POS MCD
D B

1 MID
1
X
S=300.0 MID MIDDLE MCD
H
H=99.0
SG CLSD DB=0.0
CLS CLOSED OPN
MCD
Open pos color number D D
S=3.0 SG OC1 SABN
OPD OPEND Digital in

Close pos color number + OC2


SAB POS signal ABN
N
MCD
X
L
S=4.0 SG CC1 L=1.0
DB=0.0
CLS
S01 Pos. signal color ind avaliable
+ CC2
CLD CLOSED Digital in
D

2 Middle pos color number


S=114.0
RESET CONDITION
2
S=6.0 SG ABNORMAL SG Tagging
S=414.0 SG S=7.0 SG MID

Default color (Parts) on on on on on on on on C


off off off off off off off off
S=3.0 SG T T T T T T T T MCA
sw sw sw sw sw sw sw sw MID
COLOR NUMBER C
OPN OPEN COLOR SEL OPI
CLIN
C N
CLS CLOSE COLOR SEL
C
MID MIDDLE POSITION COLOR SEL
3 C
OPN
3
OPND OPEND DIGITAL IN C
MCD OPD

CLSD CLOSED DIGITAL IN


MCD CLD
CLS
DRAB C
MCD
DRIVE ABNORMAL S02 Actuator color ind avaliable

RSTC

MCD
RESET COMMAND
4 OPI 4
TAG N
MCD
TAGGING OPC OPEN Command
M

OPCMD OPEN COMMAND


OPC
MCD OC2 Openning color number OC1 Open color number
M
Default color (Lamp) CLIN
CLCMD CLOSE COMMAND on on OPLMP
CLC off off CLC CLOSE command
MCD
M
S=3.0 SG T T MCA
M
sw sw
OPEN POSITION
OPI OPN COLOR NUMBER
PSAB POSITION ABNORMAL N D
5 PSA 5
MCD
B
CC2 Closing color number CC1 Close color number
Pos. signal color ind avaliable(Use=1 / No use=0)
DG on on CLLMP
S=1 off off
S01 S01 T T MCA
sw sw
MCD CLOSE POSITION
POS. SIGNAL COLOR IND AVALIABLE CLIN
CLS COLOR NUMBER
D

Actuator color ind avaliable(Use=1 / No use=0)


6 6
DG
S=0 S02
S02

MCD

ACTUATOR COLOR IND AVALIABLE


TITLE : VALVE DISPLAY INDICATION Rev.

SHEET NO.

MITSUBISHI VDSI
HEAVY INDUSTRIES, LTD
© THIS DRAWING/DOCUMENT IS THE PROPERTY OF AND CONTAINS CONFIDENTIAL PROPRIETARY INFORMATION OF L&T-MHPS BOILERS PVT. LTD. AND SHALL NOT BE REPRODUCED, USED, DISCLOSED OR TRANSMITTED
IN WHOLE OR IN PART UNLESS AUTHORISED IN WRITING BY L&T-MHPS BOILERS PVT. LTD.
Project KHARGONE SUPER THERMAL POWER PROJECT (2X660MW)
Package Steam Generator Package
Document Title LOGIC DIAGRAM / SCHEME OF SECONDARY AIR DAMPER CONTROL
NTPC Document Number 9578-001-102-PVI-L-005
L&T MHPS Boilers Private Ltd NTPC Limited
(Formerly known as L&T-MHI Boilers Private Limited) (A Government of India Enterprises) LMB Document Number 51006-66100-1002-01
NTPC Comments dated 19-
S. No. Document Reference Description LMB Reply dated 06-12-2016 NTPC Comments dated 27-12-2016 LMB Reply dated 09-01-2017
08 2016
Comments on R0
Please note that Functional
9578-001-102-PVI-L-005
L&T to submit logic only after Writeup of SADC is already
1 LOGIC DIAGRAM / SCHEME OF GENERAL
approval of write up. approved in CAT IV by NTPC on
SECONDARY AIR DAMPER CONTROL
19.10.2016
9578-001-102-PVI-L-005 L&T to list all the soft and Please refer IO List (NTPC
2 LOGIC DIAGRAM / SCHEME OF GENERAL hard inter FG signal Doc. No. 9578-001-102-PVI-G-
SECONDARY AIR DAMPER CONTROL exchange 001)
As the IO list has not been
9578-001-102-PVI-L-005 Please refer IO List (NTPC
submitted, so list of all
3 LOGIC DIAGRAM / SCHEME OF GENERAL Doc. No. 9578-001-102-PVI-G-
SECONDARY AIR DAMPER CONTROL
signals applicable along with
001)
details to be attached.
Comments on R1
9578-001-102-PVI-L-005
LOGIC DIAGRAM / SCHEME OF REF DOC. NO. L-003 L&T to correct it. Noted & Incorporated
SECONDARY AIR DAMPER CONTROL

1. Please refer Page No. 171 of 199 of the


document: 9578-001-102-PVI-L-005 for brief
1. Write up of the macro's describing briefly all the explanation of the MACROs. For further details
9578-001-102-PVI-L-005
pin functionality to be provided by L&T. refer MACRO Logic (page No. 172 to 198 of the
LOGIC DIAGRAM / SCHEME OF GENERAL
2. L&T to provide a list of signals that are document: 9578-001-102-PVI-L-005)
SECONDARY AIR DAMPER CONTROL
generated or used in other logic diagrams. 2. Please note that the destination (sheet no.of the
respective logics) are already mentioned along
with the signals being generated in this logic.

This signal is continuous and will remain active till


9578-001-102-PVI-L-005 FCB/RUNBACK OPERATE (SHT How is this signal generated and how long will this Runback condition persists. For details refer 9562-
LOGIC DIAGRAM / SCHEME OF NO. FGSG09-MSSFPRS (FWBDP) signal be active.? Is it a pulse type or a continous 102-PVI-L-019_RECOMMENDED UNIT
SECONDARY AIR DAMPER CONTROL (i.e. 9 of PDF) signal. CONTROL LOGICS INCLUDING COORDINATED
MASTER CONTROL (CMC)

FURNACE PRESSURE (FURNACE


9578-001-102-PVI-L-005 These signals are windbox pressure signals not
TO WINDBOX DP CONTROL)
LOGIC DIAGRAM / SCHEME OF Furnace pressure signals. L&T to correct the Noted & Incorporated
(SHT NO. FGSG09-MSSWBILPR(
SECONDARY AIR DAMPER CONTROL same.
FWBDP) i.e. 10 of PDF)

WB INL PRESSURE (FURNACE


Please note that the Fx (as highlighted by NTPC in
9578-001-102-PVI-L-005 TO
Why L&T to clarify why the feedforward is not used the commented document) is GAIN for windbox to
LOGIC DIAGRAM / SCHEME OF WINDBOX DP CONTROL) (SHT
for this loop? furnace DP control based on number of windbox
SECONDARY AIR DAMPER CONTROL NO. FGSG09-
dampers in auto.
WBCDPCNT-01 i.e. 39 of PDF)