Volume 2, Issue 1 Neutral Conductor and
Transformer Overload Problems
In this issue
we discuss the Harmonic Concerns at a Battery Charging Plant
solutions that
The Problem
Square D identified
The plant engineer at an automobile battery charging facility needed to
when solving replace the aging 600 V bus duct in the plant. He was struggling with
problems with conflicting claims from bus duct vendors about the use of 200% neutral
neutral overloads conductor rating in the proposed bus duct. He knew that battery chargers
and transformer produce significant amounts of harmonic currents, but was it necessary to
heating. specify 200% neutrals… and pay the price premium?
▼
The second reason for the
72 A small number of actual
▼
failures is explained by
another NEC requirement for
72 A
▼
phase wires. This rule says that
phase conductors (and over-
current protective devices)
cannot be sized smaller than
123 A
▼
purpose. 0
Monday Tuesday Wednesday
The k-factor rating is related Figure 6: Square D calculation, illustrating the true capacity of
to the harmonic content of the transformer.
Dealing with the transformer loading issue
was more difficult. As a stopgap measure, the Square D’s
plant engineer closed a tie circuit breaker on Power
this double-ended substation (to share the Management
harmonic loading among two transformers). Operation
This temporarily reduced the overloading offers complete
concern, but can lead to worse problems and power quality consulting services to
is generally not recommended. The plant has ensure that power problems do not
not decided on a long-term solution. The only impact your operation. Contact our
certainty is that catastrophic failure of power management experts for
transformers or bus duct would cost millions information about the following:
of dollars in damaged product and lost sales. • Power Quality Consulting
Facing that economic risk, the plant will most • Energy Management Consulting
certainly decide on a permanent solution.
• Harmonic Filters
• Power Factor Correction
Additional Reading
These two documents give more information • Power Management Training and
about harmonics and neutral currents: Technical Support
• Testing Reveals Surprising k-Factor Diversity, • Digital Simulation Studies
class number 7455, order number EC&M 4/93 • Remote Monitoring Services
• Harmonics and Electrical Equipment Neutrals, • Data Collection and Analysis
order number 0104PD9501
• Neutral Currents in Three Phase Wye Systems, Our number is 1-888-PWR-MGMT.
order number 0104ED9501
Bulletin No. 3000HO9601 10M DL 3/98 1997 Square D All Rights Reserved