Jolim Consultant Co2 System

Revision 0

CARBON DIOXIDE CALCULATION

PROJECT :

BOMBA FILE NO. : Date :

LOCATION :

1 Design Criteria

Type of Hazard Dry Electrical


Deep Seated Fire

Type of System Total Flooding

Type of Cylinder High Pressure

Design Concentration (NFPA 12 Table 2-4.2.1) 50%

Volume Factor (NFPA 12 Table 2-4.2.1) 1.33 kg Co2/m³

Protection for Lourve Doors/Windows Fibreglass Curtain

2 Quantity of Co2 Gas

Length of room 6.80 m

Width of room 4.50 m

Height of room 5.00 m

Volume of room to be protected 153.0 m³

Basic quantity of Co2 gas Volume factor x room volume 203.49 kg Co2

Safety factor - 10% Basic quantity CO2+(Basic quantity CO2 x 10%) 223.84 kg Co2

/45
Recommended quantity of Co2 gas 225 kg Co2

i.e. 5 x 45 kg Co2