FLOWSERVE
—
PROJECT: MNPL
CUSTOMER : KALPATARU POWER TRANSMISSION LTD
‘CUSTOMER PO: 2300123191
DOCUMENT: GAD Rev-1
COMMENTS RESOLUTION SHEET
Section/Ref GAIL/Mecon/KPTL comments Rev-0 | FICPL reply vide Rev-1
General Mention the type of sealant used Noted & incorporated (Sealant:-733)
General Surface preparation and painting Incorporated
details
General Remove the quantity Noted & done
General Mention the one material in BOM for | Noted & done
Plug
General ‘Add name plate details 3s per ‘Name plate details enclosed:
API6D.Also add name of Mecon & Mecon & GAIL name added in Separate
GAIL inthat Tag plate
General End flange dimension standard Incorporated
ASME 16.5(2020)
5007986-110 | Provide the detailed view of butt | Incorporated
(tuin-aP-1755- | weld ends as per ASME 16.25
21-RV-10)
5007986-110 | Mention 300 mm distance b/w Gear | incorporated
(1wnan-ap-1755- | box bottom & sealant extension top
21-PRV-10)
5007986-110 Height of extended column form Incorporated
(MININ-AP-1755- | Valve opening centre shall be 3000
21-pav-10) | mm
For all flanged
Specify flange dimension tolerance as
No tolerance for the Flange dimension as
valves per ASME16.5 ( per ASME 16.5
2020)
5007986-60 | Mention socket dimension as per | ASME 16.11 & 855353 willnot have
(wwin-ap-a75s- | 835353 difference forthe size.
21-PRV-60) : -
'5007985-70'to | Test pressure for UCBtoeb revised | Revised as desired
90 to 155 bar ( body) & 114 bar ( seat) Please note that Max test pressure for
LCB as per Standard is 144 bar only.
Flowserve recommends not to
overpressure the valves beyond standard
lirnit
Mention the GAIL PO no issued to
Kalapataru
Incorporated