2. Power on control. 3. When the control is fully powered up Press the “Reset” pushbutton on the 840D NCU 4. Wait for display on NCU to show #6 5. Set S3 to 0 and push the “Reset” pushbutton. 6. Wait for display on NCU to show #6 7. Turn S4 to Position #2 - PS LED is ON. 8. Turn S4 to Position #3 - PS LED is OFF. 9. When PS LED comes on turn S4 to Position #2 then immediately back to position #3. 10. PS LED should now be blinking. 11. Set S4 to position #0. – PR LED should go to a solid green after a few seconds. ** If it is not procedure was not done correctly. Repeat PLC steps #1 through 4.** 12. Set S4 to position #2 13. Press “Reset” pushbutton on 840D. Note: The PLC and NC are now cleared. After that load the NC&PLC backups