Professional Documents
Culture Documents
Timber-framed Construction
for Townhouse Buildings Timbe
Class 1a Desig
r Floo
n guide ring and construction.
Design and construction guide for BCA compliant for inst
allatio
Technica
sound and fire-rated construction
WoodSolutions is resourced by Forest and Wood Products Australia
l Desi
n
gn Guid
e issu
ed by
Forest
and Woo
Technical Design Guide issued by Forest and Wood Products Australia d Prod
ucts
Australia
Introduction 4
Preliminary Design 8
Floor Design 12
Stability Design 25
CLT Connections 48
Guide 50 • Appendix 2 • Worked Example for a CLT Mass Timber Panel Apartment Building Page 3
Introduction:
Contents Worked Example Scope -
CLT Mass Timber-Panel Mid-Rise Structure
The building utilised for this worked example is the WoodSolutions mid-rise model apartment building. It was
designed to provide a basis for defining, comparing and presenting different mid-rise timber-based construction
solutions and it is utilised in a range of different WoodSolutions mid-rise resources, where it provides a
prototypical situation for modelling spatial, loading, fire and noise resistance conditions. WoodSolutions have
referred to this building in several design guides.
More information on the mid-rise model apartment building can be found in Design Guide #27 Rethinking
Apartment Building Construction. In this Appendix it is used to illustrate some of the structural analysis
methods and approaches which may be adopted in the design of a mid-rise timber building using only Cross
Laminated Timber (CLT) panels, optimising it for a specific product.
The worked examples:
• Provide guidance to the structural engineer to assist in understanding some of the key steps required in the design of
timber mid-rise buildings but are not a full set of structural computations as will be required in a real project.
• Discuss key decision points and assumptions. The calculation steps are provided with a narrative to highlight the key
steps. Simple calculation steps are not presented, nor are detailed steps copied from design standards.
• Are based on one set of engineering assumptions that may or may not be valid for a particular design.
• Present one possible approach to the engineering design. It is not intended that all the calculations necessary in design
are presented here, or that the methods are the only valid methods.
• Make simplifying assumptions on architecture. The engineering design has not been completed as part of an iterative
design process, and so broad assumptions on what is feasible have been made.
Had this worked example been completed as a real project, an iterative design process would have been utilised, and
feedback to the client and design team would have been provided in order to inform discussion, e.g. on construction time, a
particular facade finish, deflection criteria from the lift manufacturer, acoustic or thermal efficiency requirements beyond the
code compliance.
As far as reasonably practical, hand-based methods of analysis have been used. Reference is made to computer analysis
where appropriate. It is the intention of the worked examples to present the thought behind the process, which is best
highlighted through hand calculations.
The worked examples in Appendices 1 & 2 present element design for both lightweight timber-framed construction and CLT
construction respectively. The calculations of the different element types follow a similar format and so some crossreferencing
is possible. But the systems are designed to different loads and assumptions and so cannot be easily swapped like-for-like.
Guide 50 • Appendix 2 • Worked Example for a CLT Mass Timber Panel Apartment Building Page 4
Overview
Contentsof the Design Process -
Mass Timber Panel Mid-Rise Structure
As discussed in Section 1.2.2, while design of a building in practice is an iterative process, it does generally
follow the following the three phases and design steps. This worked example illustrates computations for the
steps identified below.
1
Phase 1: Preliminary Design
Step 1: Building layout and performance considerations –
Early Contractor Involvement (ECI):
Project team to discuss and determine:
• overall building design and layout
• performance requirements for: structure, fire, acoustics, robustness, etc.
Guide 50 • Appendix 2 • Worked Example for a CLT Mass Timber Panel Apartment Building Page 5
WoodSolutions
Contents Mid-rise
Model Apartment - Building Overview
The WoodSolutions mid-rise model apartment building was designed to meet high-end consumer needs, including large
and open room layouts. An emphasis was placed on characterising a building that could apply to many suburban/urban
apartment situations across Australia. The model apartment typical floor plan is shown Figure A2.1, the building has a
breadth of 34 m and a depth of 22.5 m, providing a 765 m2 floor plate per level. Visualisations of the model apartment are
provided in Figure A2.2. A section through the model apartment are provided in Figure A2.3. A summary of the design
approaches utilised including relevance and reasons is provided in Table A2.1.
cleaner
refuse lift lift cup'd
balcony UNIT 06 chute
90m²
Building
Depth (y) LIFT LOBBY
22.5m
comms riser water riser electrical riser
UNIT 03 balcony
94m²
Retail Riser
Retail Riser
DRAWING
NUMBER
A009
DRAWING
NUMBER
1 Typical Plan
A007 1 : 100
2 3D View 2
A009
Guide 50 • Appendix 2 • Worked Example for a CLT Mass Timber Panel Apartment Building Page 6
DRAWING TITLE
3D
1 2 3 4
1
6 A006
D E
ROOF
PLANT RL 26890
ROOF
Total building
height -26.2m
RL 23520
LEVEL 7
RL 20350
LEVEL 6
BALCONY BALCONY
RL 17180
LEVEL 5
BALCONY
RL 14010
LEVEL 4
BALCONY
Apartments -
CL
floor-floor
1100
RL 10840
1540
LEVEL 3
height 3.1m
365
1265
BALCONY BALCONY
CL
RL 7670
LEVEL 2
Retail - floor-floor
LEVEL 1
height 4.5m
BACK OF HOUSE
RL 0
GROUND FLOOR
BASEMENT
: \ U s e r s \ c . m u g e l i \ D o c u m e n t s \ 16 0 1 2 8 _ T D A _ N e w . r v t
1
6 A006
Table A2.1: WS model apartment: Summary of design approaches utilised including relevance and reasons. PROJECT:
5 / 0 2 / 2 0 16 9 : 3 6 : 5 2 A M
Height • 8-storey design height above ground level, • The apartment levels provide a habitable height
SCALE 1 : 100 @ A1 CHECK. Checker
including 7 apartment levels and 1 retail level. plus depth for the structure and services within
DRAWN Author AUTH. DesignerSTATUS.
P LOT DATE :
PROJECT DISCIP. ZONE DOCUMENT NO. REV
DRAWING
A006
NUMBER
Area • A floor plate area of 765 m2. The apartment • Feedback and analysis indicate that many
levels include 42 SOUs (94–96 m2 each). suburban mid-rise apartment buildings fit
• The retail level assumes three shops varying in this scenario.
area from 77–150 m2. It also includes a foyer
area, an entrance to basement car parking,
utility meter rooms, an electrical substation and
a waste area.
Key set out • Plant room, lift shaft or machinery room, • The width of the building accommodates
criteria public corridor, public lobby. the size and set-out of the large, high-end
apartments.
• The grid layout accommodates car parking in
the basement.
Building • The building is considered to be strata titled, • Strata title creates the need for each title to be
ownership including the retail area on the ground floor. defined as a separate Sole Occupancy Unit
and fire under the NCC, which creates fire and noise
separation performance requirements.
Setbacks • External wall distances are (at minimum) less • The location of the building relative to other
than 1.5 m from the property boundary. buildings or properties affects the façade fire
resistance requirements.
Guide 50 • Appendix 2 • Worked Example for a CLT Mass Timber Panel Apartment Building Page 7
Phase 1 Preliminary Design
Step 1: Building layout and performance considerations – Early Contractor Involvement (ECI)
The architect determines the massing, orientation, floor plan, façade design and building area functions, see Figures A1.1 –
A1.3 and Table A1.1 for general specifications and details.
Determination of Performance Requirements and Preliminary Structural Advice
The architect and design team (including acoustic & fire consultants) have determined the following:
• FRL: Class 2 building, 26.2 m, 8-storeys ➔ Type A construction, therefore, requires an FRL of 90/90/90; therefore
- walls and ceilings to be lined with 1 layer of 16 mm fire-rated plasterboard
• Acoustic Performance:
- Walls: Airborne, Rw+Ctr ≥ 50, between apartments use double leaf discontinuous walls (see Fig A2.4)
Floor elements
to span
continuously
over apartment
walls, 11.25 m
lengths, approx.
max 5.62 m
spans
Loadbearing
walls as
indicated on
plan and in
table.
Guide 50 • Appendix 2 • Worked Example for a CLT Mass Timber Panel Apartment Building Page 8
Preliminary floor member sizing
The walls between apartments are required to be discontinuous for acoustics, the CLT wall panel will be used as a
loadbearing wall, and a second non-loadbearing stud wall leaf will be utilised to assist with acoustic performance.
The CLT floor panels will span continuously over the apartment walls, total length 11.25 m lengths, therefore approx. two
5.62m spans.
Preliminary sizing of floor cassettes can be obtained from
• Approximate span to depth ratio estimate (see section 3.5.1) for a 5layer panel: span: depth = 25-27,
therefore 5,620/25 = 225 mm
• Tables in DG# 46 Guide to Wood Construction Systems, see Figure A2.6. Load multi-res, continuous, 225 mm thickness.
0 2m 4m 6m 8m 10m
Notes:
Single span Continuous span a: Domestic - SDL=0.5, Q=1.5
Multi Res - SDL=1, Q=2
Office - SDL=1.5, Q=3
Heavy - SDL=2, Q=5
Figure A2.6: CLT floor panel size estimate using WSDG#46 CLT floor span table (Table 13).
Guide 50 • Appendix 2 • Worked Example for a CLT Mass Timber Panel Apartment Building Page 9
Figure A2.7: CLT floor panel size estimate using WSDG #46. Live load assumptions include: apartments 1.5kPa,
balconies 2kPa and lift shaft lobby 4kPa.
Figure A2.8: Wall breakup based on tributary breadths and restraint conditions.
Guide 50 • Appendix 2 • Worked Example for a CLT Mass Timber Panel Apartment Building Page 10
Preliminary loading for the five different wall types yields the following loads for each wall by level:
G - Walls Loads
2 x 16 mm fire-rated plasterboard 0.96 kN/m
Insulation 0.50 kN/m
CLT 115 Wall Self-weight (465 kg/m ) 3
0.58 kN/m
Studs 0.10 kN/m
Services 0.3 kN/m
Other allowance (prelim stages) 0.5 kN/m
Total Wall Load 3 kN/m
G - Floor Loads
2 mm carpet 0.96 kN/m
Acoustic layer 0.4 kPa
CLT 225 floor selfweight (465 kg/m ) 3
1.05 kPa
13 mm fire-grade plasterboard 0.13 kPa
Frame work 0.05 kPa
75 mm glasswool batts (14 kg/m3) 0.014 kPa
13 mm standard plasterboard 0.13 kPa
Internal walls (squashed load) 0.22 kPa
Other allowance (prelim stages) 0.50 kPa
Total 2.6 kPa
Q - Live Load
Apartment 1.5 kPa
Table A2.2: WS model apartment: wall panel sizes based on suppliers’ Design Guide.
kN/m WT1 kN/m WT2 kN/m WT3 kN/m WT4 kN/m WT5
Roof 20 CL3 - 85 39 CL3 - 85 34 CL3 - 85 41 CL3 - 85 4 CL3 - 85
7 40 CL3 - 85 79 CL3 - 85 68 CL3 - 85 83 CL3 - 85 7 CL3 - 85
6 59 CL3 - 85 118 CL3-105 102 CL3 - 85 124 CL3-105 11 CL3-105
5 79 CL3 - 85 158 CL3-105 135 CL3-105 166 CL3-105 14 CL3-105
4 99 CL3 - 85 197 CL3-105 169 CL3-105 207 CL3-105 18 CL3-105
3 119 CL3-105 236 CL3-115 203 CL3-105 248 CL3-115 22 CL3-115
2 139 CL3-105 276 CL3-115 237 CL3-115 290 CL3-115 25 CL3-115
Guide 50 • Appendix 2 • Worked Example for a CLT Mass Timber Panel Apartment Building Page 11
Step 3: Vertical Load - Roof and Floor Design
𝑤𝑤
" = 𝐺𝐺 + 0.4𝑄𝑄
The structural performance of CLT is relatively unique due to the deformation caused by the crosslayers relative shear
stiffness. This phenomenon, known as rolling shear reduces the effectiveness of the outer layers, and hence the section
properties of the CLT panels.
The Gamma method will be used for this calculation, and is only applicable to 'Simply Supported' conditions. This is also
known as 'mechanically jointed beam theory', where the middle transverse layer is considered a connection for the parallel
layers.
3. Calculate Gamma for each layer Eurocode 5
34
𝜋𝜋 ' 𝐸𝐸" 𝐴𝐴" E1 , A 1
𝛾𝛾" = 1 + h1
𝑏𝑏 '
𝐺𝐺+ ⋅ 𝑑𝑑 ⋅ 𝑙𝑙012
γ1
E1’, A1’
E 2, A 2
γ2 h2
E2’, A2’
γ3
h3
E2 , A 2
5𝑤𝑤 𝐿𝐿 * 𝑗𝑗,
∆"#$ =
384×𝐸𝐸𝐼𝐼344
j2 2.00
Δmax 18.51 mm
Maximum deflection at mid-span
L/Δ = 324 ≥ 300 therefore Okay
Although the span is continuous, the floor has been designed as simply supported at this early stage. It's considered
potentially a good way to start designing as you can't be 100% certain how a chosen supplier. A conservative estimate
for J2 is 2, although estimates by proHolz is 1.8 for this building type.
Guide 50 • Appendix 2 • Worked Example for a CLT Mass Timber Panel Apartment Building Page 13
CL5 - 225 Deflection Using Shear Analogy Approach
An alternative method for calculating CLT Stiffness is by using the Shear Analogy method, and is adopted in the USA/
Canada. In contrast to the Gamma Method, the Shear Analogy Method calculates the deformation due to bending and shear
for each individual layer, for a range of boundary conditions. This method can account for a reduced stiffness of internal
layers, as sometimes adopted by Australian CLT suppliers.
Σ = 6.04E+12
𝑏𝑏&'' 𝑡𝑡")
𝐼𝐼" = + 𝑏𝑏&'' 𝑡𝑡" ℎ".
12
)
Guide 50 • Appendix 2 • Worked Example for a CLT Mass Timber Panel Apartment Building Page 14
CL5 - 225 Deflection Using Shear Analogy Approach (continued)
4. Calculate Section Properties (Shear Analogy Method) FP Innovations CLT Handbook - 3.4.1
∆ " = ∆% + ∆'
𝑤𝑤𝑤𝑤𝑤𝑤𝑤𝑤𝑤 ∆' 𝑖𝑖𝑖𝑖 𝑑𝑑𝑑𝑑𝑑𝑑𝑑𝑑𝑑𝑑𝑑𝑑𝑑𝑑𝑑𝑑𝑑𝑑𝑑𝑑𝑑𝑑 𝑑𝑑𝑑𝑑𝑑𝑑 𝑡𝑡𝑡𝑡 𝑏𝑏𝑏𝑏𝑏𝑏𝑏𝑏𝑏𝑏𝑏𝑏𝑏𝑏
𝑤𝑤𝑤𝑤𝑤𝑤𝑤𝑤𝑤 ∆4 𝑖𝑖𝑖𝑖 𝑑𝑑𝑑𝑑𝑑𝑑𝑑𝑑𝑑𝑑𝑑𝑑𝑑𝑑𝑑𝑑𝑑𝑑𝑑𝑑𝑑𝑑 𝑑𝑑𝑑𝑑𝑑𝑑 𝑡𝑡𝑡𝑡 𝑠𝑠𝑠𝑠𝑠𝑠𝑠𝑠𝑠
5𝑤𝑤 𝐿𝐿 *
∆"#$ =
384×𝐸𝐸𝐼𝐼#11
j2 2.00
Maximum deflection at mid-span
Δmax 19.13 mm
Although the span is continuous, the floor has been designed as simply supported at this early stage.
Guide 50 • Appendix 2 • Worked Example for a CLT Mass Timber Panel Apartment Building Page 15
CLT CL5/225 Calculate Dynamic Performance
The Dynamic performance of a floor is governed by 3 factors: stiffness (stiffer floors perform better), mass (heaver floors
perform better) and damping floors with additional layers (furniture, etc) perform better. For the rest of the design we usedthe
stiffness calculated using the Gamma approach.
Refer to Section 3.6 for the detailed description on the vibration of floors. In this section we design for vibration using the
modification on Eurocode 5, as outlined in 3.6.5.
2. More detailed analysis of acceleration (required only if natural frequency is below 8 Hz)
Funamdental Freq Fourier Coefficient Forcing Frequency
3.4 < f1 <4.6 0.20 ff
4.6 < ff < 5.1 0.20 ff
5.1 < ff < 6.9 0.006 ff
ff > 6.9 0.006 6.90
𝑃𝑃( 𝑎𝑎" 𝑓𝑓" 1 3
𝐹𝐹" = 0.4
≤ 0.05 𝑚𝑚/𝑠𝑠
𝑚𝑚,-. 𝑓𝑓" 3 𝑓𝑓" 3
( 𝑓𝑓 ) − 1 + (2𝐷𝐷 𝑓𝑓 )
1 1
P0 700.00
N, mass of one person
af 0.01 Fourier coefficient
ff 6.60 Natural frequency
fF 6.60 Forcing frequency
D 1.50 Damping (1.5% for light finish)
𝑀𝑀"#$ = 𝑚𝑚 ×0.5×𝑏𝑏#--
Mgen 118.51 kg
a 0.03
OK
3. Check the deflection of the floor under a 1 kN point load, <1.5mm
𝐿𝐿 , 𝐸𝐸𝐸𝐸*
𝐵𝐵"## =
1.1 𝐸𝐸𝐸𝐸+
Calculate the overall stiffness of the transverse layer. This is assumed to be simply supported and therefore considered
conservative
beff ti3/12(mm4) beff ti hi2 (mm4) Ei (MPa) EiIi (Nmm2)
t2 7.6E+06 9.1E+07 0.0E+00 5.92E+11
t4 7.6E+06 0.0E+00 9.1E+07 0.0E+00 6000.00 0.00 5.92E+11
Σ = 1.18E+12
𝑃𝑃𝐿𝐿)
∆#$% = < 1.5𝑚𝑚𝑚𝑚
48𝐸𝐸𝐸𝐸.// 𝑏𝑏.//
Guide 50 • Appendix 2 • Worked Example for a CLT Mass Timber Panel Apartment Building Page 16
CLT CL5/225 Floor Panel - Bending and Shear
f'b (MPa) f's (MPa) f'r (MPa) E0 (MPa) E90 (MPa) G0 (MPa) GR (MPa)
SG8 12.00 3.80 1.20 8000.00 266.67 533.33 53.33
Refer to Xlam Australia Pty Ltd Design Guide for material properties
Refer to Section 3.6 for the detailed description on the vibration of floors. In this section we will design for vibration using the
modification on Eurocode 5, as outlined in 3.6.5.
𝑤𝑤𝑤𝑤𝑤𝑤𝑤𝑤𝑤 𝜏𝜏' = 𝑓𝑓𝑓+ 𝑜𝑜𝑜𝑜 𝑓𝑓𝑓-
Shear failure can occur in both rolling shear and longitudinal shear Section 3.6.2
𝑉𝑉" = 𝜑𝜑𝑘𝑘& 𝑘𝑘' 𝑘𝑘( 𝑓𝑓*, 𝐴𝐴*
L 5.60 m
W4 Calculation
Adjacent Openings 0.00 m
%&'
𝑅𝑅𝑅 = ( = 7.00 m (per m) Trib breadth
W5 Calculation
Adjacent Openings 0.00 m
%&
𝑅𝑅𝑅 = = 2.10 m Trib breadth
'
W4 W5
G (kN/m) Q (kN/m) G (kN/m) Q (kN/m)
Roof 17.8 3.5 4.5 1.1
7 37.3 14.0 22.8 6.7
6 56.8 24.5 42.3 17.2
5 76.3 35.0 61.8 27.7
4 95.7 45.5 81.2 38.2
3 115.2 56.0 100.7 48.7
2 134.7 66.5 120.2 59.2
L1 -Trans 238.0 77.0 165.7 69.7
Ground
Guide 50 • Appendix 2 • Worked Example for a CLT Mass Timber Panel Apartment Building Page 18
CLT Wall Panel Design Example
L 2875.00 mm
beff 1000.00 mm
𝑒𝑒" = 𝑡𝑡% ⁄15
eT 7.67 mm
0.13
0.92
PG 134.71 kN/m
PQ 66.50 kN/m
𝑤𝑤" = 1.2𝐺𝐺 + 1.5𝑄𝑄
wu 265.02 kN/m ULS
)
𝑡𝑡"
𝑦𝑦" = $ 𝑡𝑡& +
2
&*"+,
𝑏𝑏&'' 𝑡𝑡")
𝐼𝐼" = + 𝑏𝑏&'' 𝑡𝑡" ℎ".
12
𝐸𝐸𝐸𝐸 = $ 𝐸𝐸% 𝐼𝐼% = Nmm2
9.5E+11
%'(
The EI effective, with gamma value of 1 can be used for strength checks. Therefore gamma is not calculated for this wall
design.
Guide 50 • Appendix 2 • Worked Example for a CLT Mass Timber Panel Apartment Building Page 19
CLT Wall Panel Design Example
Guide 50 • Appendix 2 • Worked Example for a CLT Mass Timber Panel Apartment Building Page 20
CLT Wall Panel Design - Axial Capacity
𝜑𝜑𝜑𝜑 = 𝜑𝜑$ 𝑘𝑘& 𝑘𝑘' 𝑘𝑘( 𝑘𝑘&) 𝑓𝑓𝑓, 𝐴𝐴, AS1720.1 - CL 3.3.1.1
φ b 0.85 k4 1.00
k6 1.00 f'c (MPa) 18.00
𝐸𝐸𝐼𝐼"## 2
𝑍𝑍"## =
× 2.1E+06 mm3 with gamma of 1 for strength checks
=
𝐸𝐸( 𝑡𝑡,
k12 b 1.00 slenderness coefficient for floor, assumed no torsion
k1 0.57 0.57 0.80 1
𝑀𝑀∗ = 𝑁𝑁× 𝑒𝑒(
LC1 LC2 LC3 LC4
φM 12 12 17 21 kNm
M* 1.39 1.55 1.75 1.44 kNm
12% 13% 10% 7%
𝜎𝜎"∗ 𝜎𝜎)∗
+ =
𝑓𝑓𝑓",' 𝑓𝑓𝑓),' 83.1% 92.1% 74.3% 49.0% OK
𝜎𝜎"∗
(
𝜎𝜎*∗
% + = 72.9% 80.9% 65.0% 42.7% OK
𝑓𝑓 ",' 𝑓𝑓𝑓 *,'
Guide 50 • Appendix 2 • Worked Example for a CLT Mass Timber Panel Apartment Building Page 21
CLT Compression Perpendicular To Grain
Api
𝑑𝑑/
𝐴𝐴",$ = 𝑀𝑀𝑀𝑀𝑀𝑀 (𝑏𝑏, + , 𝑘𝑘2 𝑏𝑏, ) × 𝑏𝑏/
Section 4.33
4
b4 115.00 mm panel thickness above
d3 225.00 mm wall thickness below
k7 1 length of bearing of member
b3 1000 mm
Api 1.7E+05 mm2
2. Calculate perpendicular to grain compressive strength
𝜑𝜑𝑁𝑁#,% = 𝜑𝜑𝑘𝑘( 𝑘𝑘) 𝑘𝑘* 𝑘𝑘+ 𝑓𝑓𝑓% 𝐴𝐴%
f'p 8.9 MPa Refer supplier supplier for properties (XLam Design Guide Version 1.0)
φ 0.8 k4 1
k6 1 k7 1
LC1 LC2 LC3 LC4
k1 0.57 0.57 0.80 1
G (L3) 115.2 kN
Q (L3) 56.0 kN
LC1 LC2 LC3 LC4 Load Case 1: 1.35G
N* 155.6 160.7 171.9 160.7 kN Load Case 2: 1.2G + 1.5Qwl
φN(d.p) 4058.4 4058.4 5696.0 7120.0 kN Load Case 2: 1.2G + 1.5Q
Load Case 4: 1.2G + W + Q
Guide 50 • Appendix 2 • Worked Example for a CLT Mass Timber Panel Apartment Building Page 22
CLT Wall Panel - Shortening At L2 Example
L 2875.00 mm G 134.7 kN
dfloor 225.00 mm Q 66.5 kN
161.31
𝑤𝑤" = 𝐺𝐺 + 0.4𝑄𝑄 kN
2. Calculate Shrinkage Parallel to Grain
𝛿𝛿",ℓ = 𝑈𝑈ℓ Δ𝑚𝑚𝑚𝑚 𝐿𝐿
u 0.0027 Tangential moisture movement, radiata pine
ul 0.0000675 mm/mm/%change in MC
(Δmc) 3 %
δ(s,l) = 0.58 mm
3. Calculate Shrinkage Perpendicular to Grain Refer to Section 4.3.1
𝑗𝑗(𝑁𝑁",* 𝑑𝑑(,*
𝛿𝛿",$ = &
./0012 𝐸𝐸$,* 𝐴𝐴$,*
j2 2.00
Nc,I 161.31 kN
dp (outer) 135.0 mm
Ei (outer) 266.67 MPa
dp (inner) 90.00 mm
Ei (inner) 200.00 MPa
Api 1.7E+05 mm2
δ(c,l)= 1.80 mm
njoints 2.00
δgap 0.60 mm
δj 1.20 mm
𝜹𝜹𝑻𝑻𝑻𝑻𝑻𝑻𝑻𝑻𝑻𝑻 = 𝜹𝜹𝒔𝒔,𝓵𝓵 + 𝜹𝜹𝒔𝒔,𝒑𝒑 + 𝜹𝜹𝒄𝒄,𝓵𝓵 + 𝜹𝜹𝒄𝒄,𝒑𝒑 + 𝜹𝜹𝒋𝒋 = 7.67 mm *Transfer structure not considered in this calculation
Guide 50 • Appendix 2 • Worked Example for a CLT Mass Timber Panel Apartment Building Page 23
CLT Wall Panel - Differential Shortening Example
The differential shortening, for this example is calculated between W4 and W5, which upon inspection seem to be the CLT
walls with the maximum and minimum loads respectively. Best practice is to determine the shortening of each wall within the
building via spreadsheet or design software.
P2 (11.2m)
W4 - Large Load
P1 (11.2m)
W5 - Small Load
1. Calculate for W4
1. Calculate for W5
Guide 50 • Appendix 2 • Worked Example for a CLT Mass Timber Panel Apartment Building Page 24
CLT - Stability System
CLT buildings act like a honey comb structure, with each CLT wall resisting the lateral forces within the building. The CLT
core panels will not be designed to act compositely, and act as individual walls.
It is important to input the correct panel lengths, as they are manufactured to determine the correct relative stiffness
of each wall.
For this worked example, a hand computation via excel, and a computer analysis will be undertaken.
The computer analysis will break each panel up individually to determine the relative stiffness of each panel and the total
stiffness of the building.
The hand computation undertaken via Excel, willl be used for model verification purposes, and therefore a much more
simplistic approach will be undertaken breaking all of the shear walls into a combination of 2.5m, 4.5m and 8m panel
widths as shown in the following figure.
Guide 50 • Appendix 2 • Worked Example for a CLT Mass Timber Panel Apartment Building Page 25
CLT - Lateral Distribution (Hand Computation Model)
In order to determine the lateral load distribution for each wall, the relative stiffness of each shear wall must be calculated.
The stiffness (K) is a function of unit force (kN) per unit deformation (mm).
The deformation of the shear wall is a function of bending deformation, shear deformation, expansion of the tie rods and
displacement in one of the two joints between wall and ceiling.
For the purpose of this exercise, the stiffness of three walls will be checked and input. This 'hand computation' is only for
demonstration and verification of the computer software, and each wall should be checked individually for design.
Computer software can be used as a more accurate tool for structural analysis of lateral loads.
Guide 50 • Appendix 2 • Worked Example for a CLT Mass Timber Panel Apartment Building Page 26
CLT - In Plane Stiffness - Panel Contribution
In order to determine the lateral load distribution for each wall, the relative stiffness of each shear wall must be calculated.
The stiffness (K) is a function of unit force (kN) per unit deformation (mm).
The deformation of the shear wall is a functino of bending deformation, shear deformation, expansion of the tie rods and
displacement in one of the two joints between wall and ceiling.
For the purpose of this exercise, the stiffness of three walls will be checked and input. This 'hand computation' is only for
demonstration and verification of the computer software, and each wall should be checked individually for design.
Fk 1kN b
δb δb δs δs
F F
(a) (b)
1. Calculate in-plane bending deformation of the shear wall pro-Holz - CLT Structural Design 10.5.3
&
#$ %
I = '(
2. Calculate shear deformation of the shear wall pro-Holz - CLT Structural Design 10.5.3
𝐹𝐹% ℎ
𝛿𝛿" =
𝐺𝐺𝐴𝐴)
Gmean 533 533 533 MPa Properties from supplier handbooks (G = 533 for E = 8000 product)
Gv 400 400 400 MPa
As 225,000 405,000 720,000 mm2
Guide 50 • Appendix 2 • Worked Example for a CLT Mass Timber Panel Apartment Building Page 27
CLT - In Plane Stiffness - Connection Contribution
δr δr
δsl δsl
F F
(c) (d)
3. Calculate expansion of the tie rods pro-Holz - CLT Structural Design 10.5.3
(𝐹𝐹& ×𝑏𝑏)
𝐹𝐹" =
ℎ
Vertical stiffness can be found in connection suppliers handbook - which needs to be converted into a horizontal stiffness
via trigonometry.
cz 12381 N/mm vertical stiffness from connection supplier
n 2 number of expansion rods per end of panel
Convert vertical stiffness (cz) into horizontal stiffness
ℎ𝑑𝑑% 𝐹𝐹%
𝑑𝑑" = 𝑐𝑐" =
𝑏𝑏 𝑑𝑑'
𝐹𝐹 ℎ'
𝛿𝛿" = '%
𝑏𝑏 𝑐𝑐" 𝑛𝑛
4. Displacement in one of the two joints between wall and ceiling (Titan) pro-Holz - CLT Structural Design 10.5.3
$
𝛿𝛿" = &'%
(
Guide 50 • Appendix 2 • Worked Example for a CLT Mass Timber Panel Apartment Building Page 28
CLT - In Plane Stiffness - Connection Contribution
The deformation of the shear wall is a function of bending deformation in the shear wall, shear deformation in the shear wall,
expansion of the tie rods and displacement in one of the two joints between wall and ceiling.
5. Determine total displacement, per unit force pro-Holz - CLT Structural Design 10.5.3
𝛿𝛿" = 𝛿𝛿$ +𝛿𝛿& +𝛿𝛿' +𝛿𝛿(
W1 W2 W3
δt = 0.12 0.05 0.03 mm/kN
% Contribution
δt (mm) δm δv δz δf Total
Note that for shorter walls, the expansion of the tie rods reduces the stiffness the most - due to the shorter lever arm.
Guide 50 • Appendix 2 • Worked Example for a CLT Mass Timber Panel Apartment Building Page 29
CLT Wall Stiffness and Centre of Stiffness
The following section calculates the load distribution, which is generic and not unique to CLT. The lateral load distribution for
this worked example is calculated via a hand model, with rigid diaphragms assumed.
For stiffness calculations, the walls have been assumed to be broken up into a combination of 2.5 m, 4.5 m and 8 m panels.
Note this is a simplification as the purpose of this worked example is to show the process only and verify the adopted
computer software.
1. Calculate stiffness for each wall
Wall No L (m) Model Input Direction yi (m) xi (m) K (N/mm) Kx (N/mm) Ky (N/mm)
W1 8.4 T3 x 22.4 0 37584 37584 0
W2 11.2 T3+T1 x 16.7 0 45633 45633 0
W3 3.3 T1 x 11.2 0 8049 8049 0
W4 11.2 T3+T1 x 6.3 0 45633 45633 0
W5 8.4 T3 x 0 0 37584 37584 0
W6 8.4 T3 x 22.4 0 37584 37584 0
W7 11.8 T3+T1 x 16.7 0 45633 45633 0
W8 3.3 T1 x 11 0 8049 8049 0
W9 11.8 T3+T1 x 6.3 0 45633 45633 0
W10 8.4 T3 x 0 0 37584 37584 0
W11 4.5 T2 y 0 9.5 18651 0 18651
W12 4.5 T2 y 0 16.9 18651 0 18651
W13 4.5 T2 y 0 23.90 18651 0 18651
W14 3.3 T1 y 0 9.5 8049 0 8049
W15 5.0 T2 y 0 23.9 18651 0 18651
W16 4.9 T2 y 0 9.5 18651 0 18651
W17 3.3 T1 y 0 23.9 8049 0 8049
W18 4.5 T2 y 0 9.5 18651 0 18651
W19 4.5 T2 y 0 16.9 18651 0 18651
W20 4.5 T1 y 0 23.9 8049 0 8049
CA-1 6.7 T2 x 6.8 0 18651 18651 0
CA-2 2.4 T1 y 0 13.4 8049 0 8049
CA-3 2.4 T1 y 0 20.1 8049 0 8049
CA-4 6.7 T2 x 9.2 0 18651 18651 0
CB-1 2.4 T1 y 0 13.4 8049 0 8049
CB-2 5.7 T2 x 13.1 0 18651 18651 0
CB-3 5.7 T2 x 15.5 0 18651 18651 0
CB-4 2.4 T1 y 0 19.1 8049 0 8049
164.1m ∑ 423570 186897
20
Centre of Stiffness
15
10 Refer previous pages for Wall Labels
5
-5 -5 0 5 10 15 20 25 30 35 40
Guide 50 • Appendix 2 • Worked Example for a CLT Mass Timber Panel Apartment Building Page 30
CLT Wall Panel - Seismic Load Distribution
In this section, load distribution through the bracing walls is determined based on wall stiffness. This analysis also considers
the torsional effect associated with eccentric loading required in seismic design.
Guide 50 • Appendix 2 • Worked Example for a CLT Mass Timber Panel Apartment Building Page 31
CLT Wall Panel - Seismic Load Distribution (cont)
𝐹𝐹. 𝐾𝐾,)
𝐹𝐹#$%&',. =
∑ 𝐾𝐾,.
Guide 50 • Appendix 2 • Worked Example for a CLT Mass Timber Panel Apartment Building Page 32
CLT Wall Panel - Earthquake Loads per Floor
wc 0.3
hi 3.1 m
A 756 m2
1 52 kN Gconc
14.75 kPa
Guide 50 • Appendix 2 • Worked Example for a CLT Mass Timber Panel Apartment Building Page 33
CLT Wall Panel - Seismic Load Distribution
The calculated Earthquake action is applied at ht position +/- 0.1b, from the nominal centre of mass. Apply the eccentricity in
the same direction at all levels, and orient to produce the maximum 100% and 30% loads. The load cases are simplified by
taking the absolute number for each wall.
For this scenario, the Absolute values are used to reduce the overall number of load cases.
3. Calculate load on each wall for load cases specified in AS1170.4 (based on 1kN)
Note, each wall has been checked to determine load attraced for a 1kN force.
Next, the real loads are applied to the building to determine the force acting on each wall.
Guide 50 • Appendix 2 • Worked Example for a CLT Mass Timber Panel Apartment Building Page 34
CLT Wall Panel - Inter-Storey Drift & Wall Loads
Note, each wall has been checked to determine load attraced for a 1kN force. Next, the real loads are applied to the building
to determine the force acting on each wall.
4. Calculate loads for each wall at each floor
Forces for the wind loads
F (kN) Eq R 7 6 5 4 3 2 Cumulative*
Guide 50 • Appendix 2 • Worked Example for a CLT Mass Timber Panel Apartment Building Page 35
Wind Loads Derivation
Vr 45 Region A3
M d 1.0
Mz,cat
1.0
Ms 1.0
M t 1.0
Vsit 45 m/s
Guide 50 • Appendix 2 • Worked Example for a CLT Mass Timber Panel Apartment Building Page 36
Wind Load Distribution
Drift x (mm) Drift x (mm) *Using the cumulative loads of each level
R 0.1 mm 0.4 mm
7 0.3 mm 1.1 mm
6 0.5 mm 1.8 mm
5 0.7 mm 2.5 mm
4 0.9 mm 3.2 mm
3 1.1 mm 3.9 mm
2 1.4 mm 4.6 mm
Max Drift 1.4 mm 4.6 mm
Total Drift 6.5 mm 22.1 mm
Guide 50 • Appendix 2 • Worked Example for a CLT Mass Timber Panel Apartment Building Page 37
CLT Wall Panel - Wind Load Distribution
The lateral load attracted for each wall,
Wall No kix 1kN x% kiy 1kN y%
is proportional to the stiffness of the
W1 37584 8.9% 0 0.0% individual wall to the building stiffness in
W2 45633 10.8% 0 0.0% the same direction.
Guide 50 • Appendix 2 • Worked Example for a CLT Mass Timber Panel Apartment Building Page 38
4. Calculate individual wall loads (wind)
R 7 6 5 4 3 2 Cumulative*
F (kN) Wx 44 88 88 88 88 88 88 573
W1 - x 4 4 4 4 4 4 4 27
W2 - x 5 5 5 5 5 5 5 33
W3 - x 1 1 1 1 1 1 1 6
W4 - x 5 5 5 5 5 5 5 33
W5 - x 4 4 4 4 4 4 4 27
W6 - x 4 4 4 4 4 4 4 27
W7 - x 5 5 5 5 5 5 5 33
W8 - x 1 1 1 1 1 1 1 6
W9 - x 5 5 5 5 5 5 5 33
W10 - x 4 4 4 4 4 4 4 27
W11 - y 7 7 7 7 7 7 7 47
W12 - y 7 7 7 7 7 7 7 47
W13 - y 7 7 7 7 7 7 7 47
W14 - y 3 3 3 3 3 3 3 20
W15 - y 7 7 7 7 7 7 7 47
W16 - y 7 7 7 7 7 7 7 47
W17 - y 3 3 3 3 3 3 3 20
W18 - y 7 7 7 7 7 7 7 47
W19 - y 7 7 7 7 7 7 7 47
W20 - y 3 3 3 3 3 3 3 20
CA-1 - x 2 2 2 2 2 2 2 14
CA-2 - y 3 3 3 3 3 3 3 20
CA-3 - y 3 3 3 3 3 3 3 20
CA-4 - x 2 2 2 2 2 2 2 14
CB-1 - y 3 3 3 3 3 3 3 20
CB-2 - x 2 2 2 2 2 2 2 14
CB-3 - x 2 2 2 2 2 2 2 14
CB-4 - y 3 3 3 3 3 3 3 20
Guide 50 • Appendix 2 • Worked Example for a CLT Mass Timber Panel Apartment Building Page 39
CLT Shear Wall Actions
Check
W3
G 2.2 kPa
A 24.0 m2
G (kN) 0.9G - Fw
R 52 50
7 104 98
6 156 145
5 208 190
*No tension in wall
4 260 233
Note, computer model
3 313 276 confirms no tension in
2 365 318 East/West direction
3. Critical load cases
Guide 50 • Appendix 2 • Worked Example for a CLT Mass Timber Panel Apartment Building Page 40
CLT Shear Wall
The distribution of the forces to the shear walls typically depends on the flexibility of the diaphgragm. A rigid diaphragm can
be assumed as described in the main section of the CLT Design Guide. Shear walls distribute the forces of the diaphragms
in-plane.
1. Calculate actions
V* (F) 12 kN cumulative
M* 38 kNm
f'b (MPa) f's (MPa) f'r (MPa) E0 (MPa) E90 (MPa) G0 (MPa) GR (MPa)
SG8 14 3.8 1.2 8000 266.66 533.33 53.33
SG6 10 3.8 1.2 6000 200 400 40
Guide 50 • Appendix 2 • Worked Example for a CLT Mass Timber Panel Apartment Building Page 41
CLT - Shear Wall Design (In-Plane Bending)
1. Calculate the section properties of the in-plane bending Reference
E 8000 MPA
𝑑𝑑$𝑏𝑏 &
𝐼𝐼 =
12
b 90 mm
d 3900
Z 228150000 mm3
𝜑𝜑𝜑𝜑 = 𝜑𝜑$ 𝑘𝑘&𝑘𝑘'𝑘𝑘(𝑘𝑘) 𝑘𝑘&*𝑓𝑓$ 𝑍𝑍-..
φb 0.85 k1 1 k4 1
k6 1 k9 1 k12 1
φM 2715 kNm
M* 38.43 kNm
Okay
Guide 50 • Appendix 2 • Worked Example for a CLT Mass Timber Panel Apartment Building Page 42
CLT - Shear Wall Design (In-Plane Shear)
1. Shearing-off failure of the boards along a joint pro-Holz - CLT Structural Design 5.8
a. Calculate shear capacity along joints
& &
𝑓𝑓",$,% = 𝜙𝜙 ) 𝑘𝑘+ ) 𝑘𝑘, ) 𝑘𝑘- ) 𝑓𝑓",%
φs 0.8 k1 1
k6 1 k4 1
V* 12 kN
tp 35 mm Ao critical (transverse layer thinner)
L 4 m
Ao 136500 mm2 area across length of panel
τ 0 = τ90 =
0.09 MPa shear stress along the panel
9.5% OK
Guide 50 • Appendix 2 • Worked Example for a CLT Mass Timber Panel Apartment Building Page 43
CLT - Diaphragm Design
The distribution of the forces into the lateral load-resisting system depends on the flexibility of the diaphragm (rigid or flexible).
A diaphragm is considered to be flexible, if its deformation is more than twice the average inter-story drift at that level. For
flexible diaphragms, the load can be determined by the tributary area approach.
Looking at the calculated loads, the diaphragm between W1 and W2 appears to be critical and will be designed for.
M = ql2/8
V = ql/2
ho
riz
on
tal
loa ea
r
dq sh
f'b (MPa) f's (MPa) f'r (MPa) E0 (MPa) E90 (MPa) G0 (MPa) GR (MPa)
SG8 12 3.8 1.2 8000 266.66 533.33 53.33
SG6 10 3.8 1.2 6000 200 400 40
Guide 50 • Appendix 2 • Worked Example for a CLT Mass Timber Panel Apartment Building Page 44
CLT - Diaphragm Loads
The diaphragm loads are calculated by combining the reactions of all of the shear walls along the diapgragm, and then
applying them as an equivalent line load. The diaphragm will be checked for L7, deemed twith critical Earthquake loads.
1. Shearing-off failure of the boards along a joint
Resultant forces
W1 18.4 kN
W2 18.0 kN
W3 2.5 kN
W4 17.7 kN
W5 18.5 kN
Total Load (kN) 56.6 kN
Wall Length 22.5 m
Equiv line load 2.5 kN/m across D1, D2, D3, D4
Diaphragm Dimensions
tp 135 mm 3 layers of 45 mm in-plane
b 2400 mm panel cross length
L 5300 mm
Guide
50 • Appendix 2 • Worked Example for a CLT Mass Timber Panel Apartment Building Page 45
CLT - Diaphragm Design
Reference
𝑑𝑑$𝑏𝑏 &
𝐼𝐼 =
12
b 135
Ieff 1.5552E+11 mm4 In plane moment of inertia
Eieff 1.24416E+15
φb 0.85 k1 1 k4 1
k6 1 k9 1 k12 1
φM 2715 kNm
M* 38.43 kNm
Okay
Guide 50 • Appendix 2 • Worked Example for a CLT Mass Timber Panel Apartment Building Page 46
CLT - Diaphragm Shear Check
1. Shearing-off failure of the boards along a joint pro-Holz - CLT Structural Design 5.8
a. Calculate shear capacity along joints
& &
𝑓𝑓",$,% = 𝜙𝜙 ) 𝑘𝑘+ ) 𝑘𝑘, ) 𝑘𝑘- ) 𝑓𝑓",%
φs 0.8 k1 1
k6 1
V* 7 kN
tp 90 mm Ao critical (transverse layer thinner)
L 4 m
Ao 216000 mm2 area across length of panel
τ 0 = τ90 =
0.03 MPa shear stress along the panel
3.2% OK
2.5% Okay
Guide 50 • Appendix 2 • Worked Example for a CLT Mass Timber Panel Apartment Building Page 47
CLT - Connection Summary
There are multiple appraoches to CLT connection design. What is presented in this worked example is just one method,
and it must be noted that the full complexity of the design isn't explored. Engineers need to also design for additional
cases including robustness, fire and temporary support cases.
The configuration selected for this worked example is illustrated below.
The distribution of the forces in the panel is outlined in the illustration below.
Tensile forces - the tensile force, induced by the moment on each floor is resisted by the tensile brackets
indicated by 'A' below.
Shear forces - are transferred from the diaphragm to the shear walls by the angle brackets indicated by 'B' in the
illustration below.
The cumulative shear and tensile forces - are then transferred from floor to floor by screws, indicated by
Illustration A and B below.
Illustration A Illustration B
Guide 50 • Appendix 2 • Worked Example for a CLT Mass Timber Panel Apartment Building Page 48
CLT - Screw Design - Withdrawal
tp 175 mm
1. Determine withdrawal capacity in the wall section (threaded part of screw) Eurocode 5 (EC5)
𝑛𝑛()) 𝑓𝑓*+,$ 𝑑𝑑% 𝑙𝑙()) 𝜌𝜌$ =.>
𝑓𝑓",$,% = 4 ×
a) withdrawal
4 of timber 1
1.2𝑐𝑐𝑐𝑐𝑐𝑐 ∅ + 𝑠𝑠𝑠𝑠𝑠𝑠 ∅ 350
neff 1
neff 1.00
fax,k 12 N/mm2 characteristic value of withdrawal, from supplier (Spax EC5 V09.2015)
d1 8 mm outer thread diameter
leff 200 mm penetration depth (in the wall system only)
p 465 kg/m3
ϕ 0 degrees side grain
fax,rk 20.1 kN through wall panel
2. Determine withdrawal capacity in the floor section (a, withdrawal, and b, head pull-through) Eurocode 5 (EC5)
𝑛𝑛()) 𝑓𝑓*+,$ 𝑑𝑑% 𝑙𝑙()) 𝜌𝜌$ =.>
𝑓𝑓",$,% = 4 ×
a) withdrawal
4 of timber 2
1.2𝑐𝑐𝑐𝑐𝑐𝑐 ∅ + 𝑠𝑠𝑠𝑠𝑠𝑠 ∅ 350
Note the withdrawal mechanism check isn't required for partially threaded screws, as there is no withdrawal
capacity apart from the head (there is no threaded section through the floor)
𝜌𝜌$ 2.4
𝑓𝑓",$,% = 𝑛𝑛()) 𝑓𝑓"(*+,$ 𝑑𝑑"-
b) head pull-through
350
neff 1
neff 1.00
p 465
dh 20 mm
fhead,k 14 MPa
fh,k,1 7.03 kN
fh,k,1 adopted 7.03 kN withdrawal value
Guide 50 • Appendix 2 • Worked Example for a CLT Mass Timber Panel Apartment Building Page 49
CLT Connection - Johanson Theory
tp 175 mm
𝐹𝐹
",$%,& = 𝑓𝑓*,+,% ⋅ 𝑡𝑡+ ⋅ 𝑑𝑑
0.082𝑝𝑝$ 𝑑𝑑%-../
𝑓𝑓",$,% =
4 4 embedment strength of timber, non pre-drilled (parallel to grain of CLT)
2.5𝑐𝑐𝑐𝑐𝑐𝑐 ∅ + 𝑠𝑠𝑠𝑠𝑠𝑠 ∅
pk 465 kg/m3 timber density
d1 8 mm
ϕ 90 degrees
f(ℎ,𝑘,1) 20.43 MPa
tpa 225 mm
𝐹(𝑣,𝑅𝑘,𝑎) 36.8 kN
*+.-
𝑓𝑓
",$,% = 20𝑑𝑑
**in wall (parallel to grain)
d 8 mm
tpb 200
𝑓(ℎ,𝑘,1) 21.2 MPa
𝐹_(𝑣,𝑅𝑘,𝑏) 33.9 kN
Guide 50 • Appendix 2 • Worked Example for a CLT Mass Timber Panel Apartment Building Page 50
CLT Connection - Johanson Theory (cont)
d) Plastic failure of Screw and Embedment Failure in Timber 1 (floor component) Eurocode 5 (EC5)
𝑓𝑓.,/,% ⋅ 𝑡𝑡/ ⋅ 𝑑𝑑 4𝛽𝛽 2 + 𝛽𝛽 𝑀𝑀7,$% 𝐹𝐹:;,$%
𝐹𝐹",$%,& = 1,05 ⋅ ⋅ 2𝛽𝛽 1 + 𝛽𝛽 + − 𝛽𝛽 +
2 + 𝛽𝛽 𝑓𝑓.,/,% ⋅ 𝑑𝑑 ⋅ 𝑡𝑡/8 4
My,Rk 20000 Nmm characteristic value of yield moment (as defined in ETA)
F𝑣,𝑅𝑘,𝑑 14.80 kN
e) Plastic failure of Screw and Embedment Failure in Timber 1 (wall component) Eurocode 5 (EC5)
𝑓𝑓.,/,% ⋅ 𝑡𝑡1 ⋅ 𝑑𝑑 4𝛽𝛽 1 + 2𝛽𝛽 𝑀𝑀8,$%
𝐹𝐹",$%,& = 1,05 ⋅ ⋅ 2𝛽𝛽1 1 + 𝛽𝛽 + − 𝛽𝛽
1 + 2𝛽𝛽 𝑓𝑓.,/,% ⋅ 𝑑𝑑 ⋅ 𝑡𝑡11
𝐹𝑣,𝑅𝑘,𝑒 12.20 kN
𝐹𝑣,𝑅𝑘,f 4.73 kN
Guide 50 • Appendix 2 • Worked Example for a CLT Mass Timber Panel Apartment Building Page 51
CLT Connection - Johanson Theory (cont)
A B C D E F G
36.78 33.94 25.51 14.80 12.20 4.73
kN kN kN kN kN kN
𝑅𝑅",$ = 𝜙𝜙 ' 𝑘𝑘) ' 𝑘𝑘)* ' 𝑘𝑘)+ ' 𝑘𝑘), ' 𝑛𝑛 ' 𝑄𝑄/
φb 0.85 k14 1
k13 1 k17 1
n 1 screws
Lateral load case
k1 1.14
𝑅𝑑,𝑗 4.58 kN
V* 12 kN note lateral load case only, at L3 junction
Wall Length 3.9
V*/m 3.0
Min Spacing 1542 mm min spacing calculated
Adopt 300mm spacing
Guide 50 • Appendix 2 • Worked Example for a CLT Mass Timber Panel Apartment Building Page 52
CLT Connection - Johanson Theory (cont)
∅𝑁𝑁$% = ∅𝑘𝑘(𝑘𝑘()𝑘𝑘(*𝑛𝑛𝑄𝑄-
φs 0.8
k1 1.14 AS1720.1
k13 1 side grain
k14 1 single shear
Qk 70 kN From connection manufacturer
(Rotho Titan TTF 200selected)
n 1
ϕ𝑁𝑑𝑗 63.8 kN
N* Fastener 11.6 kN
Image: Soundproofing Solutions DocPlater.Net
Required Fasteners 1
Note - no tension. Pull-out screws with 150mm embedment included for robustness purposes
∅𝑁𝑁$% = ∅𝑄𝑄(
φs 0.8
Qk 31.4 kN From connection manufacturer
(Rotho Titan WHT 340 Selected)
ϕ𝑁𝑑𝑗i 25.12 kN/connection
*No tension - Okay
Guide 50 • Appendix 2 • Worked Example for a CLT Mass Timber Panel Apartment Building Page 53
CLT Shear Wall Actions
Check CA1
hi 3.1 m
b 2.7 m #$%$
Fw=
&
F (kN) Cumulative V* (kN) M* (kNm) T=C (kN)
R 7 7 23 8
7 7
14 67 25
6 6 21 131 48
5 5 26 210 78
4 4 30 303 112
3 3 33 406 150
2 2 36 516 191
G 2.6 kN/m
G 7.0 kN/floor
*Note, no floor spans onto core wall. Therefore, dead load from wall SW only.
2. Check for tension
-142.0 kN No tension
Guide 50 • Appendix 2 • Worked Example for a CLT Mass Timber Panel Apartment Building Page 54
CLT Connection - Core - L5
ϕV𝑑𝑗 63.8 kN
V* 26 kN
N 1 Minimum fasteners required
ϕT𝑑𝑗 5.6 kN
T* -49.8 kN
N 9.0 "Minimum screws each face
required (for tension)"
Adopt 100mm spacing Okay
ϕT𝑑𝑗 25.1 kN
T* -49.8 kN
N 2 Minimum fasteners required
Not included in WE
Guide 50 • Appendix 2 • Worked Example for a CLT Mass Timber Panel Apartment Building Page 55
Now
availab
for fre le
downl e
oad
Collect
the full set
of resources
for your library
Over 50 technical guides cover aspects ranging from design to durability, specification to detailing.
Including worked drawings, they are an invaluable resource for ensuring timber-related projects comply with the
National Construction Code (NCC). Download them now from WoodSolutions.com.au, the website for wood.
1 Timber-framed Construction for Townhouse Buildings Class 1a 30 Timber Concrete Composite Floors
2 Timber-framed Construction for Multi-residential 31 Timber Cassette Floors
Buildings Class 2 & 3 32 EXPAN Long Span Roofs - LVL Portal Frames and Trusses
3 Timber-framed Construction for Commercial Buildings 33 EXPAN Quick Connect Moment Connection
Class 5, 6, 9a & 9b 34 EXPAN Timber Rivet Connection
4 Building with timber in bushfire-prone areas 35 EXPAN Floor Diaphragms in Timber Buildings
5 Timber service life design - design guide for durability 36 EXPAN Engineered Woods and Fabrication Specification
6 Timber-framed Construction - sacrificial timber construction joint 37 Mid-rise Timber Buildings (Class 2, 3 and 5 Buildings)
7 Plywood box beam construction for detached housing 37R Mid-rise Timber Buildings, Multi-residential (Class 2 and 3)
8 Stairs, balustrades and handrails Class 1 Buildings – construction 37C Mid-rise Timber Buildings, Commercial and Education
9 Timber flooring - design guide for installation Class 5, 6, 7, 8 and 9b (including Class 4 parts)
10 Timber windows and doors 38 Fire Safety Design of Mid-rise Timber Buildings
11 Timber-framed systems for external noise 39 Robustness in Structures
12 Impact and assessment of moisture-affected, 40 Building Timber-framed Houses to Resist Wind
timber-framed construction 41 Timber Garden Retaining Walls Up to 1m High
13 Finishing timber externally 42 Building Code of Australia Deemed to Satisfy Solutions for
14 Timber in Internal Design Timber Aged Care Buildings (Class 9c)
15 Fire Design 43 Reimagining Wood-based Office Fitout Systems -
16 Massive Timber Construction Systems: Design Criteria and Concepts
Cross-Laminated Timber (CLT) 44 CLT Acoustic Performance
17 Alternative Solution Fire Compliance, Timber Structures 45 Code of Practice - Fire Retardant Coatings
18 Alternative Solution Fire Compliance, Facades 46 Wood Construction Systems
19 Alternative Solution Fire Compliance, Internal Linings 47 Timber Bollards
20 Fire Precautions During Construction of Large Buildings 48 Slip Resistance & Pedestrian Surfaces
21 Domestic Timber Deck Design 49 Long-span Timber Floor Solutions
22 Thermal Performance in Timber-framed Buildings 50 Mid-rise Timber Building Structural Engineering
23 Using Thermal Mass in Timber-framed Buildings 51 Cost Engineering of Mid-rise Timber Buildings
24 Thermal Performance for Timber-framed Residential
Construction
25 Rethinking Construction - Consider Timber
26 Rethinking Office Construction - Consider Timber
27 Rethinking Apartment Building Construction - Consider Timber
28 Rethinking Aged Care Construction - Consider Timber
29 Guide 50 •Industrial
Rethinking Appendix 2 •Construction
Shed Worked Example forTimber
- Consider a CLT Mass Timber Panel Apartment Building Page 56