You are on page 1of 1
CATERPILLAR’ Works Load Test Report ‘Sales Order /Item _ 1700697227100 Genset Model DE220E0 ‘Genset Serial No CATOOG71VECWO1708 Engine Type C74 Panel Type EMCP41 Engine Serial No KRGO2983, DC Volts 12 Alternator Type -R2473L4 AVR Model = MKV Alternator Serial No LWKO0168 Standby KVA Rating KVA AT PF Voltage 400/230 vy 3—Phase KW Rating Kw FLC aT PF. AMPS, Frequency 50 Hz Prime KVA Rating 200.00 KVA AT 0.80 PF KW Rating 1600 KW FLC 0.80 _P.F, 289 AMPS Test Results | Coad Tests: % Load He Volt Amps kw 0 50.0 400.0 00 00 25 500 400.0 58.0 40.0 50 50.0 400.0 115.0 80.0 75 50.0 400.0 1730 1200 100 50.0 400.0 231.0 160.0 110 50.0 400.0 254.0 176.0 Functional Tests: Battery Charger Operation (Optional) NA Hertz and Voltage Control within Specified Limits OK Coolant Temperature within Specified Limits 0K Lube Oil Operating Pressure with Specified Limits ok Low Lube Oil Pressure Shutdown Functional ok Coolant Temperature Shutdown Functional ok ‘All Additional Shutdowns Functional OK NB: All Load tests were carried out at 1.0 Power Factor (Resistive Load) Certification of Tests We hereby certify that the above Generating Set performed normally with no undue signs of stress and that the above minimum values were achieved during Load Test (within the tolerance specified under 1808528) Test Engineer: TestDate. 2016/11/15