CATERPILLAR’
Works Load Test Report
‘Sales Order /Item _ 1700697227100
Genset Model DE220E0 ‘Genset Serial No CATOOG71VECWO1708
Engine Type C74 Panel Type EMCP41
Engine Serial No KRGO2983, DC Volts 12
Alternator Type -R2473L4 AVR Model = MKV
Alternator Serial No LWKO0168
Standby
KVA Rating KVA AT PF Voltage 400/230 vy 3—Phase
KW Rating Kw
FLC aT PF. AMPS, Frequency 50 Hz
Prime
KVA Rating 200.00 KVA AT 0.80 PF
KW Rating 1600 KW
FLC 0.80 _P.F, 289 AMPS
Test Results
| Coad Tests:
% Load He Volt Amps kw
0 50.0 400.0 00 00
25 500 400.0 58.0 40.0
50 50.0 400.0 115.0 80.0
75 50.0 400.0 1730 1200
100 50.0 400.0 231.0 160.0
110 50.0 400.0 254.0 176.0
Functional Tests:
Battery Charger Operation (Optional) NA
Hertz and Voltage Control within Specified Limits OK
Coolant Temperature within Specified Limits 0K
Lube Oil Operating Pressure with Specified Limits ok
Low Lube Oil Pressure Shutdown Functional ok
Coolant Temperature Shutdown Functional ok
‘All Additional Shutdowns Functional OK
NB: All Load tests were carried out at 1.0 Power Factor (Resistive Load)
Certification of Tests
We hereby certify that the above Generating Set performed normally with no undue
signs of stress and that the above minimum values were achieved during Load Test
(within the tolerance specified under 1808528)
Test Engineer:
TestDate. 2016/11/15