Example 6-2:

The following data were obtained when a short-circuit test was performed upon a
100-kVA 2,400/240 V distribution transformer: ESC =
72 volts; ISC = 41.6 amp; PSC = 1,180 watts. All instruments were placed on the
high side, and the low side was short-circuited.
Calculate: (a) the equivalent resistance, impedance and reactance; (b) the percent
regulation at a power factor of 0.75 lagging.
Solution:

Example 6-3:
For the transformer of Example 6-2, calculate the copper losses when the load is
(a) 125 kVA, (b) 75 kVA, (c) 85 kW at a power
factor of 0.772.