Total KW 97,804.00
Total ghs 115,337.35
Ex. % rise in
power use 85.80
In your response you state that you expect an increase in electricity consumption of 80%.
Since this is quite a substantial increase that may have an effect on the design of the system, kindly motivate why you expe
We have an ongoing building structure which should be completed later in this year into next year. After doing all the pow
12 hours a day x 22 days a month x 12 months in a year.
Also please let us know the current kWh rate you pay to ECG.
Using a typical month like January 2019, the following are what we have for each of our three main meters:
Sheet factory: GHS 1.153 per Kwh
Trusses factory: GHS 1.046 per Kwh
Security: GHS 0.777 per Kwh
Lastly kindly let us know the thickness of roofing sheets, and describe the roof (eg. wooden purlins, metal rafters)
Thickness of the roofing sheet is 0.5mm
The roof structure is of metal rafters and wooden purlins
New Yard New Building Site
GHS KWH GHS
182.23
162.99
37.37
19.49
26.92
429.00 317.8482 443.08
s, metal rafters)
200kva Genset Run April 2018 - April 2019