I2-2 General Purpose Immersion Temperature Sensor
Locking Screw Cover, Multiple Conduit Holes
2-3/16 2
[55.88] [50.80] 4X ø0.896˝ [22.76 MM]
1/2˝ NPT CONDUIT KNOCKOUTS

FOR 1/2˝ NPT THERMOWELL CONNECTION


4-1/16
[103.12]
L
L = 7.000˝ FOR 6˝ THERMOWELL
L = 5.000˝ FOR 4˝ THERMOWELL
2X ø0.743˝ [18.87 MM]
3/8˝ NPT CONDUIT KNOCKOUTS

The Series I2-2 General Purpose Immersion Temperature Sensor is ideal for SPECIFICATIONS Operating Temperature: -32 to 240°F
monitoring hot and chilled water lines throughout a building or mechanical room. The Accuracy: (-35.5 to 115.5 °C).
plastic housing is in the shape of a standard junction box with multiple knockouts for easy Platinum RTD: ±0.6% @ 32°F Probe Diameter: 1/4˝ (6.3 mm).
conduit access. The locking cover prevents unauthorized occupants from tampering with (0°C); Cable Length: 8˝.
the temperature sensor. The Sensor I2-2 can be ordered with a choice of 11 output options Nickel RTD: ±0.5°F @ 32°F (0°C); Probe Material: 304 SS.
that allow it to communicate to any standard building control system. Balco RTD: ±0.1% @ 32°F (0°C); Mounting: 1/2˝ threaded connection to
Thermistors: ±0.36°F from 32 to fit Series IW2 thermowell.
Note: A Series IW2 Thermowell must be used on pressurized air and water lines to 158°F (0 to 70°C).
prevent leakage around the probe.

Model Sensor Type Insertion Length Model Sensor Type Insertion Length
I2-21062 Pt 100 Ohm RTD 6˝ I2-21042 Pt 100 Ohm RTD 4˝
I2-22062 PT 1000 Ohm RTD 6˝ I2-22042 PT 1000 Ohm RTD 4˝
I2-23062 Ni 1000 Ohm RTD 6˝ I2-23042 Ni 1000 Ohm RTD 4˝
I2-24062 Balco 1000 Ohm RTD 6˝ I2-24042 Balco 1000 Ohm RTD 4˝
I2-25062 10K Ohm Type 2 Thermistor 6˝ I2-25042 10K Ohm Type 2 Thermistor 4˝
I2-26062 3K Ohm Thermistor 6˝ I2-26042 3K Ohm Thermistor 4˝
I2-27062 5K Ohm Thermistor 6˝ I2-27042 5K Ohm Thermistor 4˝
I2-28062 100K Ohm Thermistor 6˝ I2-28042 100K Ohm Thermistor 4˝
I2-29062 20K Ohm Thermistor 6˝ I2-29042 20K Ohm Thermistor 4˝
I2-2A062 2252 Ohm Thermistor 6˝ I2-2A042 2252 Ohm Thermistor 4˝
I2-2B062 10K Ohm Type 3 Thermistor 6˝ I2-2B042 10K Ohm Type 3 Thermistor 4˝
Thermowells ACCESSORY
Model Material Insertion Length IW-C, Thermowell Compound
IW2-262 304 SS 6˝
IW2-242 304 SS 4˝

Series
I2-4 Weather-Proof Immersion Temperature Sensor
TEMPERATURE

Twist Off Cover, Multiple Conduit Holes


2-7/32 4X ø0.896˝ [22.76 MM]
[56.16] 1/2˝ NPT CONDUIT KNOCKOUTS
3-31/32
[101.00] FOR 1/2˝ NPT THERMOWELL CONNECTION
3-3/32 [78.74]

1/4
[6.35]
L
L = 7.000˝ FOR 6˝ THERMOWELL
L= 5.000˝ FOR 4˝ THERMOWELL

The Series I2-4 Weather-Proof Immersion Temperature Sensor is ideal for SPECIFICATIONS Operating Temperature: -32 to 240°F
monitoring hot and chilled water lines feeding Air Handlers and Cooling Towers. The Accuracy: (-35.5 to 115.5 °C).
Temperature Sensors

plastic housing has a 1/4 turn twist off cover to reduce installation time. The multiple Platinum RTD: ±0.6% @ 32°F Probe Diameter: 1/4˝ (6.3 mm).
knockouts allow for easy conduit access to any side of the housing. The Series I2-4 can be (0°C); Cable Length: 8˝.
ordered with a choice of 11 output options that allow it to communicate to any standard Nickel RTD: ±0.5°F @ 32°F (0°C); Probe Material: 304 SS.
building control system. Balco RTD: ±0.1% @ 32°F (0°C); Mounting: 1/2˝ threaded connection to
Thermistors: ±0.36°F from 32 to fit Series IW2 thermowell.
Note: A Series IW2 Thermowell must be used on pressurized air and water lines to 158°F (0 to 70°C).
prevent leakage around the probe.
Model Sensor Type Insertion Length Model Sensor Type Insertion Length
I2-41062 Pt 100 Ohm RTD 6˝ I2-41042 Pt 100 Ohm RTD 4˝
I2-42062 PT 1000 Ohm RTD 6˝ I2-42042 PT 1000 Ohm RTD 4˝
I2-43062 Ni 1000 Ohm RTD 6˝ I2-43042 Ni 1000 Ohm RTD 4˝
I2-44062 Balco 1000 Ohm RTD 6˝ I2-44042 Balco 1000 Ohm RTD 4˝
I2-45062 10K Ohm Type 2 Thermistor 6˝ I2-45042 10K Ohm Type 2 Thermistor 4˝
I2-46062 3K Ohm Thermistor 6˝ I2-46042 3K Ohm Thermistor 4˝
I2-47062 5K Ohm Thermistor 6˝ I2-47042 5K Ohm Thermistor 4˝
I2-48062 100K Ohm Thermistor 6˝ I2-48042 100K Ohm Thermistor 4˝
I2-49062 20K Ohm Thermistor 6˝ I2-49042 20K Ohm Thermistor 4˝
I2-4A062 2252 Ohm Thermistor 6˝ I2-4A042 2252 Ohm Thermistor 4˝
I2-4B062 10K Ohm Type 3 Thermistor 6˝ I2-4B042 10K Ohm Type 3 Thermistor 4˝
Thermowells
Model Material ACCESSORY
Insertion Length
IW2-262 304 SS 6˝ IW-C, Thermowell Compound