Professional Documents
Culture Documents
Wind and Solar PowerPlant Technical Requirement TT 30 2019 TT BCT en
Wind and Solar PowerPlant Technical Requirement TT 30 2019 TT BCT en
1. Wind and solar power plants must be capable of maintaining generation of active power
in following modes:
Maintaining generation of active power at the largest possible value (follow wind or solar
radiation);
Wind and solar power plants must be capable of adjust generation of active power as
commanded by the dispatch level in accordance with change of primary sources no more than 30
seconds with tolerance within ± 1% of rated power, specifically as follows:
- Generation of possible maximum power in case primary sources are lower than setpoint
value from the dispatch centre;
- Generation of power in accordance with dispatch instruction in case primary sources are
equal or greater than setpoint value from the dispatch centre;
2. Wind and solar power plant must be capable of maintaining generation of power for a
minimum period of time in proportion to frequency band prescribed in Table 8.
3. When the electricity system frequency is greater than 50,5Hz, wind and solar power plant
must reduce active power according to the relative slope of droop characteristics in the range from
2% to 10%. The relative slope setting value of the droop characteristics is calculated and
determined by the dispatch level:
50.5-fn
∆P = 20xPm x( )
50
Where:
- Pm : Active power in proportion to the point of time prior to power reduction (MW);
- fn : Electricity system frequency prior to power reduction (Hz).
4. Wind and solar power plants must be able to adjust reactive power according to the
characteristics as below:
a) In case a power plant generates an active power greater or equal to 20% of rated active
power and voltage in normal operation band, such power plant must be capable of adjusting
reactive power continuously in a power factor from 0.95 (corresponding to reactive power
generation mode) to 0.95 (corresponding to reactive power receiving mode) at connection point in
proportion to rate power;
b) In case a power plant generates an active power less than 20% of rated active power, such
power plant may reduce ability to receive or generate reactive power in accordance with
characteristics of the generating set;
a) Wind and solar power plants must be capable of adjust generation of reactive power and
voltage in following modes:
6. Wind and solar power plants at every time of connection to the grid must be capable of
maintaining generation of power in proportion to voltage range as follows:
b) Voltage from 0.3 pu to under 0.9 pu, minimum time is calculated in following formula:
Tmin = 4 x U - 0,6
Where:
c) Voltage from 0,9 pu to under 1,1 pu, wind and solar power plants must maintain continuous
generation;
d) Voltage from 1,1 pu to under 1,15 pu, wind and solar power plants must maintain
generation for three (03) seconds;
đ) Voltage 1,15 pu to under 1,2 pu, wind and solar power plants must maintain generation
for 0.5 seconds.