You are on page 1of 14

IEEE Transactions on Power Delivery, Vol. 12, No.

1, January 1997 15

A Comparison belween XLPE and EPR as Insulating Materials for HV Cables

G. Mazzanti, Member, IEEE G. C. Montanari, Senior Member, IEEE


Diparthento di Ingegneria Elettrica, University of Bologna, Viale Risorgimento 2,40 136 Bologna, Italy

Abstract-The performances of XLPE and EPR as materials A comparison between XLPE and EPR from the viewpoint
candidate for insulation of high voltage power cables are of their use in HV cables requires accurate knowledge of
investigated. Data obtained from laboratory tests performed on their endurance characteristics under the expected service
cable models aged under single thermal and electrical stresses, stresses, among which electric field and temperature (as well
as well as under the combination of the two stresses, are as the combination of the two), are the most challenging
considered. The drawing of eleci rical, thermal and multi-stress ones.
life lines provides a synthetic and exhaustive description of the Electro-thermal endurance characterization is based on a
behavior of the tested materials, :and allows the determination of large number of short and long-term life tests, that must be
endurance indices, useful for electrical, thermal and multi-stress realized according to suitable procedures. The relevant data
characterization. must be processed by means of appropriate statistical tools,
and life models, valid for single and multiple stresses, are
I. INTRODiUCTION needed for the derivation of the required endurance indices
and extrapolation close to service conditions.
Cross-linked Polyethylene (XLPE) is likely the most In general, life tests having the purpose of endurance
popular polymeric material among high voltage (HV) cable characterization and material comparison are not performed
manufacturers and electrical utilities all over the world. It is on full size cables, in order to simplify the procedures and
commonly used as the insulation for power cables operating reduce the costs which are, however, not negligible. Flat
up to the highest levels of service voltage. The recent specimens are commonly used (expecially when only basic
developments in manufacturing of XLPE-insulated cables, material characterization is needed, irrespective of the
e.g. triple extrusion, dry curing and extra-clean geometry of the insulation system), but also cable models, of
manufacturing, has led to the design and operation of 500 kV considerably smaller size than service cables, are employed.
XLPE insulated cables [l], and gives XLPE the chance of Using the latter makes tests more complex than for the
competing with the oil-paper insulation. former, but has the advantage that cable model geometry
On the other hand, the improvements in cable- (and hence the electric stress profile) is the same as for power
manufacturing techniques and in production of polymer cables. Even in the case of cable models, however, life tests
compounds and additives has considerably raised the under electro-thermal stress have mainly the purpose of
performances of other materiads suitable for application in material characterization and comparison, rather than of
high voltage systems, parl icularly Ethylene-Propylene providing direct insights on power cable design.
Rubber (EPR). This material is standardized as insulation for In this paper, the results of accelerated life tests performed
medium-voltage distribution cables in many countries [2-41, on XLPE and EPR-insulated cable models, subjected to
and is widely employed in some of them (e.g. in Italy), electrical, thermal and thermo-electrical stresses, are
showing good electrical, thermal, mechanical and presented and discussed with the purpose to compare the
environmental behavior [5-81. However, in order to compete thermo-electrical endurance characteristics of the two
with XLPE in the HV field (up to 130 kV), EPR must feature materials, and point out the possible advantages that each one
large values of design electrical field and current rating, has, compared to the other, in the perspective of the use as
besides, of course, acceptable losses. insulation for HV power cables. Focus is given to the
experimental and analytical techniques for endurance
investigation and material comparison, being aware that the
96 WM 216-2 PWRD A paper recommended and approved by the IEEE life data cannot be straightforwardly used for full-size cable
Insulated Conductors Committee of thi: IEEE Power Engineering Society for
presentation at the 1996 IEEEPES Winter Meeting, January 21-25, 1996, design.
Baltimore, MD. Manuscript submitted July 26, 1995; made available for
printing January 15, 1996. 11. DESCRIPTION OF TEST METHODOLOGY AND
PROCEDURES

The electric and thermal stresses can be considered as the


more severe ones for degradation of HV cables, when the
environmental aging factors can be neglected (due to, e.g.,
metal jacketing). Hence, the characterization of XLPE and

0885-8977/97/$10.00 0 1996 IEEE


16

EPR cable models has been achieved focusing to the effect of the life tests performed at relatively-high stresses. Comparing
these two stresses. Electrical and thermal stresses have been one graph with the other, the test operator can estimate life
applied singly or in combined way, giving particular points from life lines in one graph and introduce them in the
emphasis to the synergistic effect of the superimposition of other graph, thus singling out the couples of electrical and
temperature and electrical gradient. Thus, thermal life tests, thermal stresses that could give additional information on the
electrical life tests and combined electro-thermal life tests endurance characteristics of the material. This enables an
were performed on XLPE and EPR cable models. optimized design of further tests, particularly those at the
The so-called progressive censoring procedure [9, 101 was lowest-stress levels. Moreover, the CAM allows the constant-
applied to electrical and multi-stress life tests to obtain life graph, or isochronal graph, to be plotted, which consists
information on the aging mechanisms correlated to the failure of lines at chosen values of life. This graph provides
data, as well as to reduce the test times. The progressive estimates of the couples voltage-temperature corresponding
censoring procedure consists of removing some non-failed to a given life (at fixed failure probability). Therefore, it
specimens from the test at selected times (named censoring constitutes a useful tool for insulation design.
times), and measuring diagnostic properties, such as electric The drawing of life lines and isochronal lines, the
and tensile strength, conductivity, oxidation time, on these derivation of endurance indices and the subsequent
“censored“ specimens. The failed and non-failed specimens extrapolation to service stress levels on the basis of
are then processed all together by appropriate statistical experimental data is achieved by means of suitable life
methods [9], in order to achieve the estimates of the failure- models (valid for single and multiple stresses), that must be
times relevant to the test voltage. By this way, both failure chosen according to their ability of fitting satisfactorily the
times” and time-behavior of diagnostic properties are life points on the relevant graphs. Life models, as well as life
available at the end of each life test. points, are relevant to selected failure probabilities. Hence,
The life tests were performed with the purpose to enable appropriate failure probability distributions (e.g. the Weibull
the determination of the endurance characteristics of the distribution for electrical and multi-stress failure data [ 171)
material in a stress range as close as possible to the service must be used to assess life percentiles at the chosen failure
one. Since the realization of tests at stress levels comparable probability.
with the design ones would take unacceptably long times, the In order to make the results comparable, the same
tests must be performed according to a strategy that allows geometry and size of specimens was chosen for both XLPE
optimization between the need of reasonably-short test times and EPR.
and characterization of the low stress behavior [ l l ] . The The tested cable models are formed by:
whole test procedure can be thought of as divided into two - solid copper conductor, 1.8 mm in diameter;
steps: - semiconducting conductor shield, 0.5 mm thick (made by
- firstly, the determination of the short-term endurance carbon-black filled ethylene-vynilacetate copolymer or
characteristics of the material, obtained subjecting specimens carbon-black filled EPR for XLPE and EPR cables,
to high values of stresses, much larger than those expected in respectively);
service for cable insulation. This step takes relatively short - XLPE/EPR insulation 1.5 mm thick. The XLPE is
times if compared with the remaining test procedure, but it is realized by HDF4201, while EPR is a top compound for HV
fundamental in order to achieve thorough information on the applications.
unaged material, as well as to correctly plan long-term Geometry and dimensions are such that the voltage values
endurance tests; numerically coincide with the maximum electical field in the
- secondly, the determination of the long term endurance cable [7, 181. The outer shield was realized by metal coating
characteristics, obtained applying to the material lower and and/or taping semiconductive XLPE/EPR. The thermo-
lower stresses with respect to the first step. electrical life data reported in the following are relevant to
The so-called Combined Analysis Method (CAM) [ 12-16] specimens with taped outer semiconducting shield. At the
considerably helps in optimization of the choice of the cable ends, thermosetting resin conoids were realized,
electrical, thermal, and electro-thermal stress levels, partially covered by the outer shield, in order to deflect the
minimizing the number of required life tests and thus electric field at the shield borders.
reducing the waste of time and money for unnecessary tests.
The CAM supports a factorial-test procedure which is based 111. SINGLE-STRESS THERMAL AND ELECTRICAL
on the fact that material life under eIectrical and thermal LIFE TEST RESULTS AND MODELING
stress can be geometrically represented by a three-dimension
surface, the intersections of which with constant electric A. Thermal life test results and modeling
stress and temperature planes provide the electrical and
thermal life lines respectively. These lines can be plotted in The thermal life tests were performed on both XLPE and
the electrical and thermal graphs, resorting to the results of EPR cable models according to IEC 216 standard [19].
17
Different test temperatures have been considered, namely
150, 130, 110, 100 "C, for XLPE, and 160, 150, 130, 120 "C,
for EPR. Several diagnostic properties were measured (e.g.,
electric and tensile strength, weight, density), and different
end-points considered, in order to achieve a thermal
endurance evaluation homogenieous to the results of multi-
stress tests at low electrical field [20-221. In Fig.1, the
thermal life lines (at 50% faiilure probability) relevant to
XLPE and EPR cables are plotted in the so-called Arrhenius
paper, typically used for thermid endurance. They have been
derived choosing electric strength as diagnostic property, and
50% decrease with respect to the initial value (of the unaged
sample) as end-point. In the figure, the solid part of the lines
is drawn under the assumption1 of validity of the Arrhenius
model [19], which can be expressed as [12, 161:
Fig.1. Thermal life lines and experimental points obtained by tests
LT = LToexp(-B cT) (1) performed on XLPE ( 0 )and EPR (m)cable models (50% failure
probability). Diagnostic property is electric strength, end-point is 50% of
where LT is thermal life (i.e. time to failure when the initial value. Solid lines are drawn by the Arrhenius model, dashed lines
temperature is the only active stress), B is proportional to the show the possible tendency to threshold.
activation energy of the degradittion process, cT=( UTo)-(UT)
is the so-called conventional thermal stress, T is absolute B. Electrical life test results and modeling
temperature (in K), To is a reference temperature (e.g. the
room temperature or the the lowest value of the T range The electrical life tests were carried out at 50 Hz, at room
where the model holds) and LTo is the corresponding time to temperature (20"C), in both air and water [7, 8, 221. Besides
failure. power-frequency tests, a few high-frequency tests (up to 900
Referring to XLPE, it can be seen that the Arrhenius model Hz) were carried out at low electrical stresses, with the
fits well the experimental poin1.s. However, at the lowest test purpose to investigate the long-term trend of the electrical
temperature, i.e. 100°C, the chosen end-point was not life line. The dry-test results, more suitable for high-voltage
reached even after test times longer than life expected cables, are here considered.
according to model (1) (thus the test was censored after As to the initial electric strength, a slightly higher value
25,000 hours). This suggests the existence of a thermal was detected for XLPE cable models (80 kV/mm) in
threshold, for a temperature around 100°C [20]. A tendency comparison with EPR cable models (75 kV/mm).
to threshold at temperatures lower than 110°C is suggested The constant-voltage tests were performed at values
also by one of the diagnostic properties considered for EPR ranging from 75 to about 12 kV in the case of XLPE cables,
[21]. In Fig.1, the possible tendency to the threshold is and from 70 to 30 kV in the case of EPR cables. In Fig. 2, the
sketched, for both materials, by dashed lines. experimental points obtained by constant voltage tests carried
The statistical processing of test data in the linearity range out on XLPE and EPR cable models in air are reported in
has allowed the derivation of the values of the thermal semilog plot, together with the relevant electrical life lines.
endurance indices, i.e. the TI (Temperature Index, the Celsius The data has 50% failure probability, and the confidence
temperature colresponding to a time-to-end-point of 20,000 intervals of the life points have probability 95%. As can be
hours) and the HIC (Halving Interval in Celsius, the seen, in the case of EPR cables the life points fit a simple
temperature increase which yields an halving of time-to- exponential model (EM) in the test-stress range [7], of
failure, starting from the TI). The following values of equation:
TI(H1C) have been obtained, respectively, for XLPE and
EPR: lOl(7.8) and lll(8.4). As a first comment, it can be LE = LE, exp[-h(E-E,)]
said that the tested EPR shows, on the whole, better thermal
endurance characteristics than the tested XLPE, as shown by where LE is electrical life (i.e. time to breakdown), h is a
the higher TI value and the higher guessed thermal threshold. coefficient related to the electrical line slope, E, is the
As regards the activation energy of the degradation process highest value of applied electric stress (or the upper limit of
(which can be attributed to oxidation in the test-temperature the range where the model holds), and LE, is the
range [20, 21]), it can be observed that the thermal life line corresponding time to failure. On the other hand, also the
slopes (and thus the relevant activation energies) are quite inverse power model (IPM), of equation
close for both materials.
18
TABLE I
Estimated values of VEC and ET for XLPE and EPR, on the basis of
electrical life test data. Equations (2) and (3) are used for VEC calculation,
eq. (4) for ET estimation. In the case of XLPE, eqns. (2) and (3) are applied
in the linear part of the life line, ranging from 35 to 15 kV/mm Threshold
was not detected (n.d ) for EPR.

.
6

Life [h]
ET is the electrical threshold, and it appears both in the 4p-
Fig. 2. Semilog plot of electrical life lines and experimental points obtained ETM and in the 4p-IPTM; p is a parameter that depends on
by constant-voltage tests performed on XLPE ( 0 )and EPR (I)cable the way the threshold is approached.
models in air. Data is relevant to 50% failure probability and confidence Commonly, h and n are both referred to as Voltage
intervals of the life points have probability 95%. Endurance Coefficient, VEC [ 121. A large value of the VEC
(and, correspondingly, a small slope of the electrical life line
in E vs L coordinates) means good endurance of the material
L E = LE, (E/E,)-" (3) to electric stress. In the linear part of the XLPE life line, the
VEC is approximately coincident with h and ni, respectively,
(where n is the correspondent of h in the case of the IPM) for the 4p-ETM and the 4p-IPTM. A comparison between the
works very well, as proved by the values of the correlation VECs of XLPE and EPR is reported in Table I.
coefficient, R, larger than 0.99 for both the EM and the IPM It can be observed that even if EPR has a slightly lower
[7]. Therefore, in both cases a linear life line can fit well the initial electric strength, it has considerably higher VEC, thus
experimental data in the relevant E vs L graph (semilog for apparently better endurance characteristics on the whole (see
the EM, as in Fig.2, bilog for the IPM), and no evidence of also Fig. 2). However, the linear behavior of the EPR voltage
electrical threshold appears foc EPR cables. endurance line derived from laboratory tests would require
On the contrary, Figure 2 points out clearly the existence the use of probabilistic life models [24] in order to infer
of an electrical threshold (of approximately 11.5 kV/mm) for design stresses at the chosen probability, and, moreover, to
the tested XLPE cables. With threshold it is meant the value rescale the test results to the power cable size. On the
of electric stress below which electrical aging practically contrary, in the case of XLPE it has been shown in [23, 251
ceases and material life tends to so long times that it can be that a value of the design electrical stress lower than the
considered infinite, for modelistic purposes. This leads to laboratory-detected threshold would ensure that the failure
resort to threshold models for life investigation, which show probability is practically zero, independently of size effects
an upward curvature in E vs L plot, and, finally, tend to and life-percentile choice.
horizontality, i.e. to infinite life. In particular, two threshold Hence, the more significant electrical endurance indices
models, derived from eqns. (2) and (3), were shown to fit are the initial electric strength and the voltage endurance
satisfactorily electrical life data below 30 kV/mm [7, 16, 231, coefficient, n, in the case of EPR (and, in general, of no-
namely the 4-parameter Exponential Threshold Model (4p- threshold materials); the electrical threshold, in the case of
ETM), of equation XLPE (and, in general, of threshold materials). The use of an
appropriate life model allows the achievement of accurate
L E = LEH ~XP[-~(E-EH)]/[(E-ET)/(EH-ET)]' (4) estimates for such indices, which in turn provide fundamental
information for reliable electrical design.
and the 4-parameter Inverse Power Threshold Model (4p- However, cable design must account not only for the
IPTM), of equation electrical stress imposed by the applied voltage, but also for
the thermal stress and, particularly, the synergism of the two.
(5) This is the reason why cable design cannot.be restricted to
purely electrical considerations, and must refer to multi-stress
with endurance characteristics of the chosen material. Hence,
electro-thermal endurance characterization of XLPE and EPR
n(E) = ni/[ 1-(EH-E)/(E,-ET)]' cable models, dealt with in the next paragraph, is even more
important than the single-stress one in order to set up a
19

comparison between the perfcrmances of the two materials


40
when employed as insulation for HV cables. I
I

IV. MULTI-STRESS ELECTRO-THERMAL LIFE TEST


RESULTS AND MODELING .
,-.,
E
E
5
25
30 -

A. Results and modeling relevant to XLPE


3
c
20-

._
0

The thermo-electrical life tests performed on XLPE cables 10-

were carried out in oven, with values of voltage and


temperature in the ranges 4-30 kV, 60-110°C. The relevant 0
results are shown in the E vs log L plot of Fig. 3. The life la:
Life [h]
points have 50% failure probability, while the confidence
intervals are calculated at 9% probability. In the figure, the Fig. 3 . Electrical life lines at different temperatures, derived from the 4p-
so-called CAM points are also displayed. They have been ETM, fitting experimental and CAM points at 50% failure probability (with
derived from the thermal life graph (Fig.4) and the isochronal confidence intervals at probability 95%). XLPE cable models.
graph (Fig.5) according to the above-mentioned procedure.
The electrical life lines at different temperatures are drawn in
Fig. 3 on the basis of the 4pETM. The relevant values of CAMpoink

model parameters are reported in Table I1 as a function of Experimentalpoints

test temperature. They were derived by application of a A Thermal life tests

0 Tests at 4 kVlmm
weighted least square procedul e to the experimental points at
,g Tertsat8kVlmm
each test temperature. This means that a parametric form of

.
Tests at 10 kVlmm
the 4p-ETM was employed, namely
Tesk at I2 kVlmm

Tesk at 15 kVlmm

+ Testr at 21 kVlmm

x Task at 25 kVl"

T e r k at 28 kVlmm

I /
where temperature, T, and failure probability, P, are I 1
I /
additional parameters. Model (7) (as well as models ( 2 ) io' I I I I I / / I
through (5)) provides life viilues which correspond to a 20 50 100 150 200 250 300
[ 'Cl
selected value of P, e.g. 50%. It can be noted that the scale
parameter L&T,P) depends cm failure probability as well, Fig. 4. Thermal life lines at different levels of electrical stress, derived
since it is the life that model (7) provides for E=E,, while the fitting experimental and CAM points at 50% failure probability in the
other parameters are functiori of temperature, but do not Arrhenius paper. Confidence intervals have probability 95%. XLPE cables.
depend on failure probability. Failure-time percentiles at
different probabilities can be obtained resorting to the two-
parameter Weibull function, generally used to process
electrical breakdown data, that is
R
F(tF;E,T) = 1 - eXp[-(tF/CX) ] (8)

TAB LE I1
Model (7) parameter values coming from 4p-ETM applied to 50% life
percentiles relevant to XLPE cable models tested at 20, 60,90, and 110°C.

150 200 250 300

Fig. 5. Isochronal (E-T) lines fitting experimental and CAM points at 50%
failure probability, The threshold line is also displayed. XLPE cables.
20

where F is failure probability, tF is time-to-failure (life), and the other hand, with respect to the parametric models of the
a and 13 are scale and shape parameters, respectively, kind of (7), multi-stress models have the advantage of being
function of applied stresses. able to predict life values even at temperatures different from
In particular, a corresponds to the time-to-failure at the test ones, and to suggest expressions for the dependence
probability 63.2%, so that its dependence on stresses can be of endurance indices on the applied stresses. This is the
explained resorting to life models appropriate for the reason why it is worthwhile considering multi-stress models
material, applied to the life points at failure probability in the perspective of HV cable design.
63.2% [24, 251. D can be considered, as a first approximation, One of the simplest expression proposed for the combined
constant and equal to the average of the values obtained from electro-thermal threshold life model is [12, 161:
each life test. If the variance of D is large, this assumption can
affect the extreme percentiles of failure time [24-261 (in the exp [- B cT - h(E-E,) + b(E-Eo)cT]
case of XLPE here considered, acceptable errors come out). L = KnLn
” - (12)
From eqns. (8) and (7), the following expression for the 4- [(E - Eo)/(Eto-Eo)+ cT/cTto - 11’
parameter Exponential Threshold Probabilistic Model can be
obtained where K,L, is a scale parameter, B and h come from the
single-stress thermal and electrical exponential threshold
F ( ~,E;T)
F = 1- eXP{ -[ ( t / ~L E K ,&ET)/(EH-ET)I’
~ exp[h(E-EH )]r} models (eqns.(l), (4)), b accounts for the synergism between
the stresses, E, is the value below which electric stress is no
more able to damage the material in a suitable temperature
(9)
range, p is a shape parameter, Eto is the electrical threshold at
where LE,,,,,, is the value of LE, relevant to 63.2 % failure T=TOand Tto is the thermal threshold at E=Eo.
probability. Fixed a value of probability, P, it derives: Applied to the results of multi-stress life tests herein dealt
with, in the range 20-90°C, this model shows unsatisfactory
life data fitting [28]. Starting from the Eyring model [29],
and resorting to accurate expressions of the temperature
dependence of the parameters, in particular of the threshold,
another multi-stress life threshold model was proposed in
[28], that is:
which formally coincides with model (7) setting the
correspondence tF(P,E,T) = LE(T,P) and putting

L=
h
kT,E$exp( - T ) e x p ( g ) e x p [ - 3 exp( - +)E]

The probabilistic life model of eqns. (9), (10) yields


estimates of failure time at any selected probability (e.g. the
50% value reported in Table II), thus constitutes a valid tool
for cable design. It is noteworthy, however, that the life lines
at different probabilities tend to the same, unique value of where h, and k are Planck and Boltzmann constants; DS’,
threshold (as it can be derived from (10)). Hence, designing DH, To and rl are thermodynamic quantities. Model (13) fits
cable below the electrical threshold at the maximum service quite well the experimental results reported in Fig.3; in
temperature would be free of probabilistic considerations. particular, it provides threshold values in close agreement
The dependence of the parameters of model (7) on T is with model (7), as shown in Table 111.
still unexplained. Once a suitable expression has been
derived for such a dependence, a thoroughly-explained multi-
TABLE 111
stress electro-thermal life model can be obtained. The multi-
Electrical threshold values as a function of temperature, according to model
stress life models available in literature [ 161 generally feature
quite complex expressions (expecially in the case of (7) and model (13) for XLPE cable model data at 20, 60, and 90°C.
threshold models), with a large number of parameters.
Therefore, parameter calculation becomes a cumbersome
problem, which can be solved resorting to advanced
algorithms [27]. Moreover, the confidence bounds (and
hence the uncertainty) of parameter estimates considerably
increase with the number of parameters. For all this reasons,
the use of multi-stress models requires care and expertise. On
21

Figure 4 shows that the results of the multi-stress life tests temperatures larger than 90°C both experimental and CAM
can be drawn also in the Arrhenius plot. The life points are points suggest the presence of a long-time downward
relevant to 50% failure probability, with confidence intervals curvature for the electrical life lines. The results obtained
at probability 95%. The thermal life lines at different levels from thermal life tests in the absence of voltage are located in
of electrical stresses are drawn fitting experimental and CAM correspondence of Eo, that has been estimated to be 6
points. It is noteworthy that tlhe CAM points provide quite kV/mm (see Fig.9 reported later) [30].
useful information on life line drawing, particularly about the In the linearity range (Le s30-60 kV/mm), the IPM
tendency to thermal threshold. The thermal life line at 4 (eq.(3)) has been used to fit the experimental results in a
kV/mm is very close to the Anhenius one, thus suggesting parametric form with respect to temperature and for a given
for Eo a value of about 3 kV/mm. For gradients between 0 failure probability P, that is:
and 10 kV/mm, a significant life increase with decreasing
temperature can be observed, which leads to hypothesize the
presence of a thermal threshobd, fbnction of electrical stress.
Above 10 kV/mm, the thenrial life line slope diminishes Model (14) parameters were derived by application of the
considerably and the thermal threshold tends to disappear. least square procedure to the experimental and CAM points
For gradients higher than about 20 kV/mm, life is at each test temperature. These values are reported in Table
prevailingly affected by voltage, and thermal life lines IV.
become close to horizontality, for temperatures <IO0 OC. The values of the VEC, n, at the various test temperatures
The isochronal lines relevarit to the results of multi-stress take particular interest, since they give a first indication of
life tests, reported in Fig.5, i.e. the lines corresponding to the endurance properties of the tested EPR. It can be noted
constant values of life, have been drawn by means of that the VEC is still high even for temperatures exceeding the
experimental and CAM data. The CAM points were derived design one (9OOC according to main cable standards [2-4]),
either by a graphical procedure, based on life line plots of thus indicating good endurance of the tested EPR to
Figs. 3, 4, or applying models (7), (13). In particular, the combined electro-thermal stress.
threshold line is obtained by (7) and Table 11. The VEC variation with temperature seems to fit quite well
As can be seen, CAM points are fundamental for plotting a relationship of the kind:
accurately isochronal lines with a minimum amount of
experimental results. These lines in turn provide very useful n = no - b cT (15)
informations for cable design, since they enable the
determination of couples of electric and thermal stress that as shown by Fig.7, where the linear regression of the VEC
correspond to a given life (at the chosen failure probability). values vs temperature (reported in Table IV) is plotted in a
The shape and intersections of the isochronal lines for long coordinate system with abscissa proportional to the
lives provide a graphical index useful for material conventional thermal stress. This observation supports the
characterization, the Stress Clompatibility Index, SCI [ 12, use of a linear combined-stress life model (in the range 30-60
151. It is defined as the ratio of the area bounded by the the kV/mm, 20-100°C) valid for no-threshold materials, that is
pairs of values (E,T) of the chosen long-life line, to the area 112, 161
of the triangle defined by (E,,, To), (Eo, To), (Eo, Tto) (see
Fig.5). In the case of the tested XLPE cables, from Fig.5 a
value of SCIsl.3 is obtained for the threshold line. 100, I I I I I

B. Results and modeling relevant to EPR -


E
E
The thermo-electrical life tests performed on EPR cables E
were carried out in oven, with values of voltage and 8
temperature in the ranges 50-110 kV, 150-60°C. The relevant E
.Y

results are summarized in the log E vs log L plot of Fig. 6 . PW
The life points are relevant tlo 50% failure probability; the
confidence intervals are not rcported for the sake of graphic
clearness. In the figure, the CALMpoints are also displayed.
The electrical life lines of Fig.6 are obtained resorting to a Life [h]

graphical-procedure. An electric stress interval can be


Fig. 6. Electrical life lines at different temperatures,derived by graphically
observed (ranging from over 30 kV/mm up to the highest test
fitting the experimental and CAM points at 50% failure probability
stresses, i.e. 60-70 kV/mm) where the life points at each
(confidence intervals are omitted). EPR cable models.
temperature fit straight lines, while at long times and
22

TABLE V
Parameter values of model (16) calculated in the linearity range by the least
square procedure applied to multi-stress data at probability 50% relevant to
EPR cable models.

20
I

50
,
I00
---I
I

rc1

Fig 7 Plot of the VEC values (obtained by model (14) applied to multi-
stress EPR cable data) as a function of temperature, and relevant regression
line (eq (15))
-E
TABLE IV. E
s
\
Parameter values of model (14) derived from application of the least square
procedure to the experimental points at failure probability 50% in the
linearity range (Fig. 6). EPR cable models.

I
1
I
I
I
I
I
I
I
I
I
I
1
I
I
1
I
I
I
I
I
I
I
-[no-b cT]
L(E,T) Lo (EIE,) exp(-B cT)

Model (16) has phenomenological nature, but it can also be


derived on the basis of thermodynamic considerations, as it is
shown in [30]. The values of its parameters, reported in Table This is not enough to infer any threshold estimate.
V, are calculated in the linearity range, in bilog plot, by the Nonetheless, it must be pointed out that the very high values
least-square procedure, with the exception of B, which comes of VEC up to at least 100°C could hide the presence of an
from the value of HIC estimated for the thermal life line at electrical threshold, since extremely long test times would be
zero electrical stress (previously reported). From Table V, it required to prove or to exclude an upward curvature of the
results that all model parameters are temperature life lines for low electric field values.
independent, with the exception of Lo (which is function of Some more insights on thresholds come from Fig. 9, where
temperature due to thermodynamic reasons, as discussed in the multi-stress life points (with their confidence intervals at
~301). probability 95%) are reported in the Arrhenius graph,
The electrical life lines at different temperatures shown in together with the thermal life lines at different values of
Fig.8 are drawn according to model (16), on the basis of the electrical stress. The results of the thermal life tests
parameter values reported in Table V. As can be seen from (described above), as well as CAM points at 100,000 hours
comparison with experimental and CAM data, limited to the (see Fig. 10 reported later) lead to hypothesize the existence
linearity range, the validity of the assumed model is fairly of a thermal threshold, which decreases from about 105°C at
well verified. zero electric field down to about 90°C at 20 kV/mm. Hence,
Dealmg again with Fig. 6, it can be observed that at the existence of an electrical threshold for the electrical life
temperatures lower than 90°C there is no evidence of line at 90°C could be guessed at about 20 kV/mm. In this
threshold, but it was noted in [30] that the estimated life of case, if one considers lower temperature values, the threshold
100,000 hours at 20°C derived in log-log plot according to should not disappear but, on the contrary, should increase,
eq.(14), suggests a tendency to upward curvature of the life having an upper limit in the range 20-30 kV/mm at 20"C, as
line in semilog coordinates, which are the more appropriate suggested by the thermal life lines at 20 and 30 kV/mm of
ones when the possible tendency to threshold is investigated. Fig. 9. It follows that, considering the long time behavior, the
electrical life lines at low and intermediate temperatures
23

should exhibit a double curvature: an upward curvature in the The isochronal graph proves the very good multi-stress
low electric stress range, a downward curvature in an endurance characteristics of the tested EPR, and the
intermediate stress range and, finally, a linear behavior at effectiveness of CAM points in deriving the long-term
higher stresses (see in Fig. 6 the line at 9OOC). The upward material behavior, then infer design stresses. Indeed, only
curvature (and hence the threshold) should disappear for CAM points could enable plotting of the isochronal line at
temperatures higher than 105°C; in fact, for T2120"C Fig.9 100,000 hours (at a given failure probability), since the
provides finite life values at E=O kV/mm. longest multi-stress life test was carried out for less than
However, it must be underlined that these considerations 23,000 hours. The accuracy of such a line is obviously fairly
about threshold are mainly based on CAM points, that are limited, but an aid in long-life line drawing is given by the
estimated with quite large uncertainty. The confidence shapes of the lines relevant to shorter lives, which is quite
intervals are displayed for experimental and CAM points regular (see Fig. 10).
along the electric stress axis in Fig. 10, where the isochronal In the case of the tested EPR cables, a value of SCIEl.6 is
graph relevant to 50% failure probability is shown in log E vs obtained from Fig.10 for the 100,000 hour line, which again
cT coordinates. The confidence intervals of the CAM points supports the good thermo-electrical aging endurance of the
were estimated by the Monte Carlo method, under the material.
assumption of validity of linear models [30]. Probabilistic life models can be used even in this case to
estimate any life percentile. For example, from eqns. (S), and
(2)/(3) the following expressions for exponential and inverse-
power probabilistic life models can be obtained [24, 3 11:

It is noteworthy that, contrarily to XLPE, in the case of


EPR the estimation of design stresses must refer to
probabilistic models as (17) and (lS), since the electrical
threshold has not been detected. Therefore, an approach
taking into account size effect and failure probability (see [5,
241) is needed.

20 50 100 150 200 250 300 V. DISCUSSION AND COMPARISON


rc1
Fig 9. Thermal life lines at different levels of electrical stresses, derived From the above description of life test results, a quite
fitting experimental and CAM points at 50% failure probability in the accurate picture of the multi-stress behavior of the tested
Arrhenius paper (with confidence intervals at probability 95%). EPR cables. XLPE and EPR cable models comes out. The laboratory life
tests showed the good endurance characteristics of the two
materials when subjected to electrical and thermal stresses.
This is supported by the estimates of initial electric strength,
TI, HIC and stress compatibility index for both materials, but
I I 1
expecially by the high value of VEC in a wide temperature
range, in the case of EPR, and by the evidence of a quite
n large value of electrical threshold, in the case of XLPE.
E
The tested materials are expected to well behave even in
service conditions, provided that the design stresses are
10 chosen according to the isochronal lines depicted in Figs. 5
and 10. The previous modelistic analysis has put emphasis on
the tools needed to infer behavior of power cables on the
20 50 & ycl 150 200 250 300
basis of laboratory tests on models. These tools are:
- life models (eqns. (1)-(3), (7), (12), (13), (14), (16)),
which enable both the extrapolation of laboratory test results
Fig. 10. Isochronal (E-T) lines fitting experimental and CAM points at 50%
to long lives, comparable to the service ones, and the
failure probability (with confidence intervals at probability 95%). EPR
determination of endurance indices useful for a comparison
cables.
between the different materials (e.g. VEC, TI, HIC, SCI);
24

- probabilistic life models (eqns. (9), (17), (lg)), which value of the shape parameter of the Weibull distribution of
yield failure-time percentiles at any probability, particularly the voltage breakdown values, namely 34. Note that the value
the lowest ones used for cable design. of the design electrical field thus obtained is lower than the
The main discriminating factor between the tested XLPE guessed electrical threshold at 60°C (which should be larger
and EPR cables is the detection of the electrical threshold, than 20 kV/mm), thus providing a conservative cable design.
which was successful for XLPE, while could not be achieved As regards XLPE insulated cables, the electrical stress
in the case of EPR. This affects, of course, cable design, as corresponding to a failure time of 25 years at probability 5%
shown in the following example. and temperature of 60°C can be directly calculated from the
Referring to EPR, a linear model would seem appropriate life values at probability 50% using the 4-parameter
for life prediction and design-stress estimation. For example, Exponential Threshold Probabilistic Model (eq.(9)). The
the electrical stress corresponding to a failure time of 25 result is practically coincident with the clcctrical threshold at
years at probability 50% and temperature 60°C for EPR cable 60°C, i.e. 9.8 kV/mm. Hence, by choosing a design elcctric
models can be calculated resorting to the IPM (eq. (14)). The field value lower than the threshold estimated by the
result is 29.6 kV/mm if the parameters reported in Table IV laboratory tests performed on cable models, a theoretically
at 60°C are tought valid. Altematively, the use of multi-stress infinite life woud be expected, independently of failure
model (16), with the parameter values reported in Table V, probability and cable size.
would give a value of 29.9 kV/mm, which is in agreement According to this example, the use of EPR would
with the prediction of model (14). Taking into account also hypothetically enable a value of design electrical field for the
the CAM point at 100,000 hours, 6OoC, which lies at the HV power cable higher than that of XLPE. Actually, the
border of the linearity range, a value of 15.9 for the VEC and effect of environmental and mechanical stresses, as well as of
of 1.9 hours for the Weibull distribution scale parameter is technology in cable manufacturing, does not allow to refer in
obtained, thus leading to a lower value of electric field, practice to the above electric field values for cable design.
namely 28.8 kV/mm (note that the use of the EM, eq.(2), This holds particularly for EPR, whose performances depend
gives a value of 28 kV/mm, quite close to that of IPM). significantly on the kind of compounds and, therefore, on
However, this result could not be free of objections, since cable manufacturer, but also for XLPE. Referring to the
the existence of electrical threshold in the range 20-105°C latter, in fact, it must be recalled that recent improvements in
was suggested by the thermal life lines shown in Fig.9. compound formation, additive selection and manufacturing
Hence, a value of electric field which yields infinite life at procedures have enabled the development of high-
any failure probability could exist at 60°C. In summary, it performance XLPE materials, which exhibit much higher
can be argued that, for the tested EPR cables, linear models VEC in the linear part of the life line. This has considerably
could be successfully used for life prediction at very low raised the values of design electric fields, up to 15-20
electrical stresses and for temperatures lower than 1OO"C, kV/mm, and has given the chance of extremely high voltage
being aware that design stress estimation may be ratings for HV cables, up to 500 kV [ 11. The threshold values
conservative, due to the expected presence of electrical at the various temperatures should be, likely, much higher,
threshold. even if, in this case, the high value of VEC could obscure the
The determination of the electric stress value evidence of threshold at long test times, as observed for the
corresponding to an extreme value of failure probability, tested EPR.
generally considered for power cable design, e.g. 5%, can be Finally, a synthetic comparison between the tested cables
attained resorting to the generalized two-parameter is provided by the endurance indices reported in Table VI.
distribution of failure times and gradients, e.g. eqns. (17), On the whole, EPR shows a slightly better thermal and
(18). Starting from the most conservative 50% values, multistress endurance behavior, as highlighted by the SCI
namely 28.8 kV/mm for the IPM and 28 kV/mm for the EM, value.
and considering p=2.1, the values of 26.7 and 25.9 kV/mm TABLE VI
are obtained from IPM ((eq.(l8)) and EM (eq.(17)), Synthetic comparison between endurance indices for the tested XLPE and
respectively. EPR cable models
Finally, the size effect can be accounted for, resorting to
the well-known expression proposed in [32]. As an example,
2
let us consider a HV power cable with 630 mm conductor,
15 mm insulation thickness and 1000 m of length. The
maximum electrical field (i.e. the field on the inner
semiconductive shield) in the EPR power cable for 25 years
life, at 5% failure probability and 60"C, results 18.2 and 17.6
kV/mm using IPM and EM, respectively. The difference with
respect to the cable model is not too large, due to the high
25

VI. CONCILUSIONS [2] Japanese Cable Makers Association Standard, JCS no.
329-A.
The test procedures described in this paper led to obtain a [3] International Electrical Commission Cable Standard, IEC
thorough thermo-electrical characterization of XLPE and 502.
EPR insulations. The most significant difference between the [4] Insulated Cable Engineers Association Standard, ICEA
electrical endurance features of the two materials is the S-68-5 16.
presence of the electrical threshold. [5] E. Occhini, P. Metra, G. Portinari, B. Vecellio, "Thermal,
The existence of electrical 1hreshold for XLPE has been mechanical and electrical properties of insulation power
clearly inferred by conventional life tests, whereas in the case cables", JEEE Trans. Power Apparatus and Systems,
of EPR the threshold has only been supposed, particularly on vol. 102, July 1983, pp. 1942-1953.
the basis of the Combined Analysis Method. Even if it must [6] M. Brown, "Performance of ethylene-propylene rubber
be pointed out that this result cannot be extended insulation in medium and high voltage power cables",
straightforwardly to full-size c ables, there is the indication IEEE Trans. Power Apparatus and Systems, vol. 102,
that EPR cable design could proceed according to statistical February 1983, pp. 373-381.
procedures, while XLPE cable design could be free of these [7] M. Cacciari, G. C. Montanari, L. Simoni, A. Cavallini, A.
constraints. Motori, "Long-term electrical performance and life
A final comparison made on &e basis of endurance indices model fitting of XLPE and EPR insulated cables", IEEE
shows, on the whole, slightly better behavior of EPR with Trans. Power Delively, vol. 7, no. 2, April 1992, pp.
respect to XLPE. However, this result is valid for the tested 634-64 1.
materials and must be carefully extended to the two materials [SI G. Mazzanti, G. C. Montanari, A. Motori, P. Anelli,
in general. Actually, even if XLPE is, generally speaking, a "Comparison of electrical endurance tests performed on
well defined material, its behavior is significantly affected by cable models and strips of peeled EPR cables", IEEE
curing processes and additives. This problem is even more Trans. Diel. and El. Insul., vol. 2, no. 3, June 1995.
remarkable for EPR. In fact, the denomination EPR denotes [9] M. Cacciari, G. C. Montanari, "A method to estimate the
different kinds of ethylene-propylene compounds. Not only Weibull parameters for progressively censored tests",
cable manufacturing technologies, but also the quality of the IEEE Trans. Reliability, vol. 36, no. 1, April 1987, pp.
polymer and the type of compound and additives affect 87-93.
significantly the performance of the final product. Therefore, [ 101 G. C. Montanari, M. Cacciari, "Progressively-censored
data derived from tests on EPR cables should be generalized aging tests on XLPE insulated cable models", IEEE
even more carefully than for XLPE. Trans. El. Jnsul., vol. 23, no. 3, June 1988, pp. 365-372.
For this reason, and due to the fact that neither cable [l I] M. Cacciari, G. C. Montanari, "Optimum design of life
models, nor the way of stress application are an exact tests for insulating materials, systems and components",
representation of the actual conditions, it must be emphasized IEEE Trans. El. Ins., vol. 26, no. 6, December 1991, pp.
that the quantities which can lie deducted from the figures 1112-1123.
reported in this paper (e.g. electrical and thermal threshold, [ 121 L. Simoni, Fundamentals of endurance of electrical
endurance coefficients) cannot constitute the reference for insulating materials, CLUEB, Bologna, Italy, 1st issue
full-cable design. This goal can be reached applying the 1983,2nd issue 1994.
approach presented in this paper to full-size cables. [13] G. C. Montanari, G. Pattini, "Application of a new
method to the analysis of combined stress results",
VII. ACKNOWLEDGMENTS Proceedings of 4th ISH, n. 23.02, Athens, August 1983.
[14] G. C. Montanari, G. Pattini, "Planning of combined-
The research was carried out by the financial support of stress tests on insulating materials", Proceedings of ETG
M.U.R.S.T. (40%). The authors also acknowledge Pirelli Conference, Berlin, Germany, September 1985, pp.39-
Cavi S.p.A., and Prof. L. Simoni for his suggestions. 43.
[ 151 L. Simoni, "Application of a new geometrical approach
VIII. REFERENCES to determination of combined-stress endurance of
insulating materials", IEEE Trans. El. Jnsul., vol. 23, no.
[I] T. Kubota, Y. Takahashi, S. Sakuma, M. Watanabe, M. 3, June 1988, pp. 489-492.
Kanaoka, H. Yamanouchi, "Development of 500-kV [16] G. C. Montanari, L. Simoni, "Aging phenomenology
XLPE cables and accwories for long distance and modeling", IEEE Trans. El. Insul., vol. 28, no. 5,
underground transmission Line, Part I: Insulation design October 1993, pp. 755-776.
of cables", IEEE Trans. Power Delively, vol. 9, no. 4, [17] W. Nelson, Accelerated testing, John Wiley & Sons,
October 1994, pp.1738-1749. New York, 1990.
26

[18] G. C. Montanari, G. Pattini, "Electrical aging of EPR [28] G.C. Montanari, G. Mazzanti, "From thermodynamic to
cables", Materials Engineering, vol. 1, no. 2, August phenomenological multi-stress models for insulating
1990, pp. 605-613. materials without or with evidence of threshold",
[19] IEC 216, Guide for the determination of thermal Journal of Phys. D: Appl. Phys., vo1.27, May 1994,
endurance properties of electrical insulating materials, pp. 1691-1702.
1993. E291 S. Glasstone, K.J. Laidler, H.E. Eyring, The theory oj
[20] G.C. Montanari A. Motori, "Thermal endurance rate processes, Mc Graw Hill, New York, 1941.
evaluation of XLPE-insulated cables", Journal of Phys. [30] G.C. Montanari, 0. Mazzanti, L. Simoni, "Endurance of
D: Appl. PhyS.,vol. 24, 1991, pp.1172-1181. EPR-insulated cables subjected to electro-thermal
[21] G. Mazzanti, G.C. Montanari, A. Motori, "An insight stress", submitted to IEEE Trans. Diel. and El. Insul,
into thermal life testing and characterization of EPR 1995.
insulated cables", Journal of Phys. D: Appl. Phys., vol. [31] G. C. Montanari, M. Cacciari, "A failure probability
27, August 1994, pp. 2601-261 1. function for insulations with exponential life" (in
[22] G.C. Montanari, G. Pattini, L. Simoni, "Long-term italian), Metron, vol. XLVI, no. 1-4, December 1988,
behavior of XLPE insulated cable models", IEEE Trans. pp. 253-273.
Power Delivery, vol. PWRD-2, no. 3, July 1987, pp.
596-602.
[23] G. C. Montanari, M. Cacciari, "Electrical life threshold IX. BIOGRAPHIES
models for insulating materials subjected to electrical
and multiple stresses. Part 1: Investigation and Giovanni Mazzanti was bom in Bologna, Italy, on July 12th 1962 He
comparison of life models", IEEE Trans. El. Insul, vol. received his Doctor Degree in Nuclear Engineering in 1986 from the
27, no. 5, October 1992, pp. 974-986. University of Bologna, and his PhD in Electrical Engineering in 1992 from
[24] G. C. Montanari, M. Cacciari, "A probabilistic the same University In 1992 he joined the Institute of Industrial
Electrotechnics of the University of Bologna as a Researcher Since 1992 he
insulation life model for combined thermal-electrical is involved in studies in the field of characterization and aging investigation
stresses", IEEE Trans. El. Insul., vol. 20, no. 3, June of electrical insulating materials and systems He is IEEE member
1985, pp. 519-522.
[25] G. C. Montanari, M. Cacciari, "Electrical life threshold
models for insulating materials subjected to electrical Gian Carlo Montanari was born in Bologna, Italy, on November 11th
1955 He received his Doctor Degree in Electrical Engineering in 1979
and multiple stresses. Part 2: probabilistic approach to from the University of Bologna. In 1983 he joined the University of
generalized life models", IEEE Trans. El. Insul., vol. 27, Bologna as a Researcher and has become Professor of Electrical
no. 5, October 1992, pp. 987-999. Technology at the same university in 1986. He has worked since 1979 in
[26] M. Cacciari, G. C. Montanari, "Probabilistic models for the field of characterization and aging investigation of electrical insulating
materials and systems at the Institute of Industrial Electrotechnics of the
life prediction of insulating materials", Journal of Phys. University of Bologna. He is also engaged in the fields of harmonic
D: Appl. Phys., vol. 23, December 1990, pp. 1592-1598. compensation in electrical power systems, power electronics and statistics
[27] W.H. Press, B.P. Flannery, S.A. Tellkolsky, W.T. He is IEEE senior member, member of IEC 15E and IEC TC33 and AdCom
Vetterling, Numerical recipes, Cambridge, U.K., Member of IEEE DEIS
Cambridge Press, 1990.
27
DISCU,SSION mainly the purpose of:
- determining the properties of the unaged material (e.g.
LAMBERT PIERRAT, Senior Member, IEEE (General electric strength), as a first screening of its performances;
Technical Division, Electricite de France, 37 rue Diderot, - estimating the initial value of the Voltage Endurance
38040 Grenoble Cedex, France). Coefficient (VEC) through short-time life tests at high
The methodology proposeld by the authors allows an stresses. The initial VEC gives and idea of the slope of the
objective and economical comparison of the performances of life line, enabling a first guess of lifetimes at lower stresses;
the two insulating materials (XILPE and EPR). - properly choosing lower stress levels via the knowledge
The questions and comments are the following: of initial VEC, so that long-term tests can be performed in
1) the test procedure i,s divided into two stages reasonably long times.
corresponding to two very different time scales (short-term It is useful to carry out progressively longer life tests, at
and long-term endurance). Which are the technical and lower and lower stresses, since in this way information on
economical advantages of this procedure? Is it possible to each planned test is obtained, and a continuous monitoring on
reverse the time sequence of the two stages? the development of the whole test plan is performed. It is
2) the scope of thermal life-tests is the determination of worth-while remembering that if an excessively low value of
Arrhenius model paramaters, particularly the thermal stress is chosen, a test may last for too long times. In this
threshold, which is an essential parameter for the case, the test must be stopped before failure of a significant
comparison between the two insulating materials, which amount of sample specimens, so that time and money are
have the same activation energy. In Fig. 1, we see that AT1 wasted without obtaining the desired informations (time to
(namely, the difference between the two Temperature Index failure percentiles at the test stress).
values relevant to XLPE and EPR) is equal to 10°C; which This is the reason why the two stages (namely short-term
is the statistic confidence interval of this difference, and of and long-term endurance tests) cannot be reversed.
the regression lines relevant to 1he two materials? 2) Thermal life test data reported in the paper has been
3) the electrical life tests highlight the very different processed according to IEC 216 Standards, which provide
behavior of the two materials; Figures 1 and 2 show a expressions for the determination of the lower 95%
certain agreement, dealing with the better behavior of EPR confidence limits of the points of thermal life line, and the
as regards electrical and thermal endurance. But XLPE plotting of the relevant lower unilateral curve in Arrhenius
exhibits an interesting electrical threshold (E~m11.5 graph. As an example, in Fig. 1 the thermal life line and the
kV/mm). Is it possible to detect the existence and the relevant lower 95% confidence curve are plotted in Arrhenius
eventual value of a possible ET for EPR? graph for the tested EPR [I] (diagnostic property: electric
4) the use of probabilistic life models (EM and IPM, see strength; end point: 50% decrease with respect to the initial
eqns.(l7), (18)) leads, at a given failure probability equal to value).
5 % , to electric field levels no1 very different (respectively According to IEC 216, the lower 95% confidence limit of
25.9 and 26.7 kV/mm). The two models have the same TI, i.e. TC, must also be calculated since the value of TC
general form and their a-priori shape parameter (the same gives a quantitative evaluation of the uncertainty of the
for both models, i.e. pa2.1) corresponds approximately to a estimated value of TI. Considering for both tested materials
linearly-increasing failure-rate. The previous results have the same diagnostic property and end-point of Fig. 1, the value
been obtained introducing into ihe models very conservative found for TC was 108.6"C in the case of EPR (TI= 11 I'C),
characteristic 50% values (respmively 28 kV/mm and 28.8 and 98.7"C for XLPE (TI=lOl"C) [2]. Thus, due to the small
kV/mm). Which is the sensitivity of the results, if these difference between TC and TI in both cases, it can be
characteristic values and the given failure probability are confirmed that the difference between the TIS of the two
changed? materials is statistically significant.
I thank the autors for their answer and comments to this
discussion. Regression
-I
95x Confidence - - - - -

G. Mazzanti, G.C. Montanari. We thank Dr.


Pierrat for his interesting questions, which help to clarify
some points of the paper.

1) The endurance test procedure is basically splitted into


two stages, since short-term tests, involving relatively short
test-times and few specimens, tenable a correct planning of Fig. 1. Thermal-endurancegraph derived, for the tested EPR,
long-term tests, which require much longer test-times and according to IEC 2 16. Property electric strength, end-point
higher costs. Focusing now on short-term tests, they have 50%, test temperatures 160, 150, 130, 120°C (after [I]).
28

3) When a material features high values of both initial kV/mm, respectively. Probabilistic life models are sensitive to
electric strength and VEC, the eventual presence of an the value of failure probability of the target percentile: the
electrical threshold cannot be usually detected by lower the failure probability, the lower the design field.
conventional life tests (falling in the stage of the long-term Indeed, if failure probability is decreased from 5% to 1%,
endurance testing procedure: see point 1 above) in reasonable then electric field levels diminish to 24.6 and 25.4 kV/mm,
test times; this holds generally even if the threshold value is respectively. Also, probabilistic life models are sensitive to
high. Therefore, in these cases, information on the existence design life; the longer is design life, the lower is electric field
of the threqhold may come from non-conventional tests which level. Indeed, if design life is raised from 25 to 50 years, at
investigate 'more closely the degradation mechanisms. constant 5% failure probability, then field levels decrease to
Currently, the authors of the paper are performing studies to 24.3 and 25.5 kV/mm, respectively. Finally, probabilistic life
detect a threshold related to deep trapping of space charges, models are sensitive to the value of Weibull shape parameter,
following the theory described in [3]. (3. If (3 decreases, experimental lifetimes become more
In case that a threshold is not detected, cable design must scattered and, consequently, the field levels will diminish
proceed according to probabilistic criteria, even if a threshold with respect to the reference ones. Indeed, if p decreases from
in fact does exist and can be somehow indirectly guessed. 2.1 to 1, then field levels at probability 5% are lowered to
4) A probabilistic life model enables the calculation of 23.7 and 24.5 kV/mm respectively.
any chosen life percentile corresponding to a given stress From the comparison of these results, it can be concluded
(e.g. electric field and/or temperature), or, conversely, of the that the two models have a very similar behavior and provide
stress corresponding to any given life percentile (which could quite close estimates for any value of failure probability,
be called "target percentile"). Anyway, the scale parameter of design life and shape parameter.
the model is needed, and is obtained resorting to a life
percentile (which could be called "starting percentile")
derived directly from experimental results (usually the 50th REFERENCES
percentile). Different 50% starting percentile values were
available in the case of EPR cable models, according to [I] G. Mazzanti, G.C. Montanari, A. Motori, "An Insight into
different ways of treating life data. In the perspective of a Thermal Life Testing and Characterization of EPR Insulated
design procedure, the most conservative approach was Cables", Joumal of Physics D: Applied Physics, Vol. 27,
followed, and the starting percentiles corresponding to the pp.2601-2611, 1994.
lowest value of VEC were chosen. [2] G.C. Montanari, A. Motori, "Thermal Endurance
Probabilistic life models are affected by different Evaluation of XLPE Insulated Cables", Joumal of Physics D:
quantities, as can be proved by calculations. For example, let Applied Physics, Vol. 24, pp. 1172-1 181, 1991.
us assume here, as reference levels, the electric field values [3] L. Dissado, G. Mazzanti, G.C Montanari, "The
determined for EPR cable models (in the case of the most Incorporation of Space Charge Degradation into the Life
conservative VEC) with a design life of 25 years at 5% Model for Electrical Insulating Materials", IEEE Trans. on
failure probability; the values obtained by EM (eq. (17)) and Diel. and El. Ins., Vol. 2, n.6, pp. 1147-1 158, December
IPM (eq.(18)), reported in the paper, are 25.9 and 26.7 1995.

You might also like