Professional Documents
Culture Documents
Keywords: Power systems are experiencing noticeable changes in operation with the integration of a large number
Bus protection renewable sources, which are generally connected to the grid through inverters. With significant modulation
PV plant in voltage and current during fault by the embedded controllers in the inverters, available grid protection
Differential protection
schemes are vulnerable. The theoretical analysis and simulated case studies reveal the influencing factors on the
Sequence components
malfunction of the conventional busbar differential protection while connected to an inverter based resource.
Inverter based resources
This paper proposes a differential protection method for the busbar, connecting inverter based resources to
the grid, based on composite sequence currents. The performance of the proposed method is immune to the
variations due to control action in the inverter based resource and change in grid codes. The IEEE 9-bus system
interconnecting a PV plant is used to evaluate the proposed method where the comparative assessment reveals
its superiority.
∗ Corresponding author.
E-mail address: soumitri.jena89@gmail.com (S. Jena).
https://doi.org/10.1016/j.ijepes.2021.107665
Received 13 July 2021; Received in revised form 14 September 2021; Accepted 23 September 2021
Available online 22 October 2021
0142-0615/© 2021 Elsevier Ltd. All rights reserved.
S. Jena et al. International Journal of Electrical Power and Energy Systems 136 (2022) 107665
and phase angle by the inverter may limit the performance of the mitigating the associated variation in fault characteristics. To evaluate
differential relay when used for the bus connecting IBR to the grid. the proposed method, the IEEE 9-bus system interconnecting a PV plant
Large phase angle difference between both side currents results in mal- is used. The performance of the proposed method is demonstrated for
function of conventional current differential protection at times when different internal and external faults with change in PV plant capacity,
the current magnitudes become comparable, such as faults involving fault condition and system parameters, with CT saturation, change in
significant resistance. The failure of substation busbar protection causes grid codes and found to be consistent. The comparative assessment with
severe consequences like massive power outage, equipment damage conventional differential protection depicts its superior performance.
and stability concern [23]. Therefore, in the presence of IBR there is
a scope to develop reliable busbar protection methods. 2. System description
In this work, the limitations of conventional differential protection
for the busbar connecting a PV (photovoltaic) plant to the grid are The problem highlighted in this work and the evaluation of pro-
demonstrated and a method using composite sequence currents is pro- posed method are carried out on IEEE 9-bus test system [24] inte-
posed. It uses positive sequence components for the differential current grating a PV plant, as shown in Fig. 1. Simulations are carried out
and negative and zero sequence components for the restraining current in PSCAD/EMTDC software package [25]. The generator connected at
to derive the decision. As the negative sequence current is being sup- bus-9 is replaced by a PV plant which comprises parallel combination
pressed by the control action of such inverter based resource and zero of PV units to collectively generate a maximum of 30 MW power. Each
sequence current not available for ungrounded fault conditions, the use PV unit consists of two parallel PV arrays followed by two-stage DC–DC
of positive sequence currents as differential current substantiates for all and DC–AC conversion. A 33/230 kV step-up transformer is utilized to
fault conditions. The restraining current is being emphasized to avoid connect the grid. The phasor values used are estimated using one-cycle
maloperation due to CT saturation for external fault conditions. Use of discrete Fourier transform with a signal sampling rate of 3.84 kHz.
negative and zero sequence components as restraining current prevents The two-stage control scheme of the PV plant is depicted in Fig. 2.
the unwanted maloperation due to CT saturation. The proposed method In the first stage, a DC booster has been used to maximize the power
remains unaffected by the control action of the inverters, thereby output from the PV (𝑉𝑝𝑣 , 𝐼𝑝𝑣 ) panels using MPPT control [26]. The
2
S. Jena et al. International Journal of Electrical Power and Energy Systems 136 (2022) 107665
3
S. Jena et al. International Journal of Electrical Power and Energy Systems 136 (2022) 107665
4. Proposed method
The performance of conventional current differential relay is tested 4.1. Internal faults
on the system of Fig. 5 for different internal faults with variation in
IBR and grid parameters. The steady-state operating points are shown 4.1.1. AG fault
in Fig. 6 with the relay settings as per Table 1. Fault resistance, length For a phase-A-ground (AG) fault on the busbar, the corresponding
of grid connecting line and grid equivalent impedance are varied at a sequence network is shown in Fig. 7(a). As the negative sequence cur-
time for different PV plant output level, by keeping other parameters rent contributed by the IBR is negligible during the fault, corresponding
as fixed. The observations from the obtained results are as follows: path is considered as an open circuit in the sequence network. With
4
S. Jena et al. International Journal of Electrical Power and Energy Systems 136 (2022) 107665
𝐼̇ 𝑀1 + 𝐼̇ 𝑁1 = 𝐼̇ 𝑀2 + 𝐼̇ 𝑁2 = 𝐼̇ 𝑀0 + 𝐼̇ 𝑁0 (7)
where 𝐼̇ 𝑀 , and 𝐼̇ 𝑁 are the IBR and grid side currents, respectively, and
𝐼̇ 𝑀2 = 0. Subscripts 1, 2 and 0 represent the positive, negative and zero
sequence components, respectively.
The relationship in (7) can be rewritten as,
( )
|𝐼̇ 𝑀1 + 𝐼̇ 𝑁1 | = 0.5 |𝐼̇ 𝑀2 + 𝐼̇ 𝑁2 | + |𝐼̇ 𝑀0 + 𝐼̇ 𝑁0 | (8)
| | | | | |
Considering the left side of (8) having positive sequence currents
as the 𝐼𝐷𝐼𝐹 and right side consisting of negative and zero sequence
current as the 𝐼𝑅𝐸𝑆 , the trajectory of relay operating point for AG fault
can be found on the blue dotted line in Fig. 8. The trajectory position
above the set differential characteristic (with 𝑘 = 0.25), as shown in
Fig. 8, ensures correct detection of such a fault type. Such a selection of
differential and restraining currents provides sufficient security in the
protection scheme and even for other types of faults analysed below.
4.1.2. BC fault
Fig. 7(b) represents the sequence network for BC fault. The relation
Fig. 7. Sequence networks for (a) AG (b) BC and (c) BCG faults on the system.
between sequence currents can be expressed as,
5
S. Jena et al. International Journal of Electrical Power and Energy Systems 136 (2022) 107665
4.3. Overall description of the proposed method Fig. 10. Current waveforms from (a) PV plant and (b) grid for AG fault on the busbar;
(c) phase angle difference of both side currents.
The proposed protection method is evaluated and compared with Fig. 11. Response of (a) conventional scheme and (b) proposed method for LG fault.
6
S. Jena et al. International Journal of Electrical Power and Energy Systems 136 (2022) 107665
Fig. 15. Performance of (a) conventional scheme (b) proposed method during internal
faults with different grid equivalent impedance.
Fig. 16. Performance of (a) conventional scheme (b) proposed method during internal
Fig. 12. Current waveforms from (a) PV plant and (b) grid for AB fault on the busbar;
faults with change in PV integration.
(c) phase angle difference of both side currents.
are simulated on the busbar. The steady state operating points in such
fault scenarios for the conventional scheme and proposed method are
presented in Fig. 15(a) and (b). It is observed from Fig. 15(a) that
the conventional scheme fails to operate for higher grid impedance
values (weaker grids). Performance of the proposed method, as seen
in Fig. 15(b), remains consistent in correctly identifying the internal
faults even with the change in grid parameters.
7
S. Jena et al. International Journal of Electrical Power and Energy Systems 136 (2022) 107665
Fig. 17. Performance of (a) conventional scheme (b) proposed method during internal Fig. 19. Performance of proposed scheme for (a) NA-GC, (b) EU-GC during AG fault.
faults with change in line length.
8
S. Jena et al. International Journal of Electrical Power and Energy Systems 136 (2022) 107665
Declaration of competing interest [18] Zadeh MRD, Sidhu TS, Klimek A. Implementation and testing of directional
comparison bus protection based on iec61850 process bus. IEEE Trans Power
Deliv 2011;26(3):1530–7. http://dx.doi.org/10.1109/TPWRD.2010.2060213.
The authors declare that they have no known competing finan-
[19] Zou G, Gao H. A traveling-wave-based amplitude integral busbar protection
cial interests or personal relationships that could have appeared to technique. IEEE Trans Power Deliv 2012;27(2):602–9. http://dx.doi.org/10.
influence the work reported in this paper. 1109/TPWRD.2012.2184561.
[20] Kang Y-C, Lim U-J, Kang S-H, Crossley P. A busbar differential protection relay
References suitable for use with measurement type current transformers. IEEE Trans Power
Deliv 2005;20(2):1291–8. http://dx.doi.org/10.1109/TPWRD.2004.834325.
[21] Guzman A, Qin B-L, Labuschagne C. Reliable busbar protection with advanced
[1] Government of India: Ministry of New and Renewable Energy. Guidelines for
zone selection. IEEE Trans Power Deliv 2005;20(2):625–9. http://dx.doi.org/10.
implementation of scheme for setting up of 750 MW grid-connected solar PV
1109/TPWRD.2004.834671.
power projects under batch-1. 2013, URL https://www.seci.co.in/web-data/docs/
[22] Villamagna N, Crossley P. A ct saturation detection algorithm using symmet-
final-VGF_750MW_Guidelines_for-grid-solar-power-projects.pdf.
rical components for current differential protection. IEEE Trans Power Deliv
[2] Kabiri R, Holmes DG, McGrath BP. Control of active and reactive power ripple
2006;21(1):38–45. http://dx.doi.org/10.1109/TPWRD.2005.848654.
to mitigate unbalanced grid voltages. IEEE Trans Ind Appl 2015;52(2):1660–8.
[23] Exploring the IEEE C37.234 guide for protective relay application to power
[3] Shuai Z, Shen C, Yin X, Liu X, Shen ZJ. Fault analysis of inverter-interfaced
system buses. IEEE Trans Power Deliv 2011;26(2):936–43. http://dx.doi.org/10.
distributed generators with different control schemes. IEEE Trans Power Deliv
1109/CPRE.2011.6035602.
2018;33(3):1223–35.
[24] Banaiemoqadam A, Hooshyar A, Azzouz MA. A control-based solution for
[4] Blaabjerg F, Teodorescu R, Liserre M, Timbus AV. Overview of control and
distance protection of lines connected to converter-interfaced sources during
grid synchronization for distributed power generation systems. IEEE Trans Ind
asymmetrical faults. IEEE Trans Power Deliv 2020;35(3):1455–66. http://dx.doi.
Electron 2006;53(5):1398–409.
org/10.1109/TPWRD.2019.2946757.
[5] Camacho A, Castilla M, Miret J, Vasquez JC, Alarcón-Gallo E. Flexible voltage
[25] Manitoba HVDC Research Centre, PSCAD ver. 4.6, EMTD (software package),
support control for three-phase distributed generation inverters under grid fault.
Winnipeg, MB, Canada.
IEEE Trans Ind Electron 2012;60(4):1429–41.
[26] De Brito MAG, Galotto L, Sampaio LP, e Melo GdA, Canesin CA. Evaluation of
[6] Hasanien HM. An adaptive control strategy for low voltage ride through
the main mppt techniques for photovoltaic applications. IEEE Trans Ind Electron
capability enhancement of grid-connected photovoltaic power plants. IEEE Trans
2012;60(3):1156–67.
Power Syst 2016;31(4):3230–7.
[27] North American Electric Reliability Corporation. Reliability guideline: Im-
[7] Wang Y, Ren B. Fault ride-through enhancement for grid-tied pv systems with
provements to interconnection requirements for BPS-connected inverter-based
robust control. IEEE Trans Ind Electron 2018;65(3):2302–12.
resources. 2019, URL https://www.nerc.com/comm/PC_Reliability_Guidelines_
[8] Firouz Y, Farhadkhani S, Lobry J, Vallée F, Khakpour A, Durieux O. Numerical
DL/Reliability_Guideline_IBR_Interconnection_Requirements_Improvements.pdf.
comparison of the effects of different types of distributed generation units
[28] Schweitzer Engineering Laboratories, SEL-487B-1 Bus Differential Relay,
on overcurrent protection systems in mv distribution grids. Renew Energy
SEL-487B-1 bus differential relay, Pullman, WA-USA. URL https://cms-
2014;69:271–83.
cdn.selinc.com/assets/Literature/Product%20Literature/Data%20Sheets/487B-
[9] Chen L-H. Overcurrent protection for distribution feeders with renewable
1_DS_20200229.pdf?v=20200417-200934.
generation. Int J Electr Power Energy Syst 2017;84:202–13.
[29] Villamagna N, Crossley PA. A ct saturation detection algorithm using symmet-
[10] Hooshyar A, Azzouz MA, El-Saadany EF. Distance protection of lines emanating
rical components for current differential protection. IEEE Trans Power Deliv
from full-scale converter-interfaced renewable energy power plants—Part I:
2006;21(1):38–45. http://dx.doi.org/10.1109/TPWRD.2005.848654.
Problem statement. IEEE Trans Power Deliv 2015;30(4):1770–80.
[30] Ziegler G. Numerical differential protection: principles and applications. John
[11] Paladhi S, Pradhan AK. Adaptive distance protection for lines connecting
Wiley & Sons, USA; 2012.
converter-interfaced renewable plants. IEEE J Emerg Sel Top Power Electron
[31] European Grid Code. Ordinance on system services by wind energy plants
(Early Access) 2020.
(system service ordinance—SDLWindV). 2010, URL www.erneuerbare-energien.
[12] Jia K, Li Y, Fang Y, Zheng L, Bi T, Yang Q. Transient current similarity based
de/fileadmin/ee-import/files/english/pdf/application/pdf/sdl_windv_en.pdf.
protection for wind farm transmission lines. Appl Energy 2018;225:42–51.
[32] EN 50549-1:2019: Requirements for generating plants to be connected in parallel
[13] Kar S, Samantaray SR. Time-frequency transform-based differential scheme for
with distribution networks - Part 1: Connection to a LV distribution network
microgrid protection. IET Gener Transm Distrib 2014;8(2):310–20.
- Generating plants up to and including Type B. European Committee for
[14] Jena MK, Samantaray SR. Data mining based intelligent differential relaying for
Electrotechnical Standardization; 2019.
transmission lines including UPFC and wind farms. IEEE Trans Neural Netw Learn
[33] EN 50549-2:2019: Requirements for generating plants to be connected in parallel
Syst 2016;27(1):8–17.
with distribution networks - Part 2: Connection to a MV distribution network
[15] Jena MK, Samantaray SR, Tripathy L. Decision tree-induced fuzzy rule-based
- Generating plants up to and including Type B. European Committee for
differential relaying for transmission line including unified power flow controller
Electrotechnical Standardization; 2019.
and wind-farms. IET Gener Transm Distrib 2014;8(12):2144–52.
[16] Mishra DP, Samantaray SR, Joos G. A combined wavelet and data-mining
based intelligent protection scheme for microgrid. IEEE Trans Smart Grid
2016;7(5):2295–304.
[17] Eissa MM. A novel digital directional technique for bus-bars protection. IEEE
Trans Power Deliv 2004;19(4):1636–41. http://dx.doi.org/10.1109/TPWRD.
2004.835271.