Temperature Correction Factor for Tan Delta Measurement

Sr.
Oil temperature Deg. C Correction factor(K)
No.
1 10 0.8
2 15 0.9
3 20 1.0
4 25 1.12
5 30 1.25
6 35 1.40
7 40 1.55
8 45 1.75
9 50 1.95
10 55 2.18
11 60 2.42
12 65 2.70
13 70 3.00

If Tan Delta of bushing /winding/CVT/CT is measured at oil temperature T Deg. C.


Then Tan Delta at 20 Deg. C shall be as given below:

Tan Delta at 20 Deg. C = (Tan Delta at Temp T Deg. C )/ Factor K.