This document lists engine parameters and their standard values, protection settings including fault stages, delays, and failure levels. There are 27 parameters listed including temperatures of coils, bearings, fuel, charge air, coolant, lubricant and exhaust as well as pressures of lubricant, fuel, crankcase, coolant, intercoolant and supply voltage. Each parameter has standard value, two protection stages with fault values and levels that will trigger an alarm or trip and stop the engine.
Original Description:
This is a engine parameter protection setting list of MTU diesel genset 16 v 4000 g23
This document lists engine parameters and their standard values, protection settings including fault stages, delays, and failure levels. There are 27 parameters listed including temperatures of coils, bearings, fuel, charge air, coolant, lubricant and exhaust as well as pressures of lubricant, fuel, crankcase, coolant, intercoolant and supply voltage. Each parameter has standard value, two protection stages with fault values and levels that will trigger an alarm or trip and stop the engine.
This document lists engine parameters and their standard values, protection settings including fault stages, delays, and failure levels. There are 27 parameters listed including temperatures of coils, bearings, fuel, charge air, coolant, lubricant and exhaust as well as pressures of lubricant, fuel, crankcase, coolant, intercoolant and supply voltage. Each parameter has standard value, two protection stages with fault values and levels that will trigger an alarm or trip and stop the engine.
NAME STANDARD PROTECTION FAULT STAGE DELAY s ENABLE FAILURE LEVEL
VALUE VALUE OR NOT HIGE COIL TEMP <120O C 1 140O C 2 ENABLE ALARM HIGH COIL TEMP <120O C 2 150O C 2 ENABLE TRIP AND STOP MOTOR BEARING TEMP <80O C 1 80O C 5 ENABLE ALARM HIGH MOTOR BEARING TEMP <80O C 2 90O C 10 ENABLE TRIP AND STOP HIGH HIGH FUEL TEMP 55O C 1 95O C ENABLE ALARM HIGH FUEL TEMP 55O C 2 98O C ENABLE TRIP AND STOP HIGH CHARGE AIR TEMP <80O C 1 80O C ENABLE ALARM HIGH CHARGE AIR TEMP <80O C 2 83O C ENABLE TRIP AND STOP HIGH INTERCOOLER <70O C 1 75O C ENABLE ALARM COOLANT TEMP HIGH INTERCOOLER <70O C 2 78O C ENABLE TRIP AND STOP COOLANT TEMP HIGH LUBRICANT TEMP <95O C 1 99O C ENABLE ALARM HIGH LUBRICANT TEMP <95O C 2 101O C ENABLE TRIP AND STOP HIGH COOLANT TEMP <100O C 1 102O C ENABLE ALARM HIGH COOLANT TEMP <100O C 2 104O C ENABLE TRIP AND STOP HIGH EXHAUST TEMP <500O C 1 *525O C NOT ALARM ENABLE HIGH EXHAUST TEMP <500O C 2 *550O C NOT TRIP AND STOP ENABLE LOW LUBRICANT >5 BAR 1 3.5 bar ENABLE ALARM PRESSURE LOW LUBRICANT >5 BAR 2 3.2 bar ENABLE TRIP AND STOP PRESSURE LOW FUEL PRESSURE >6 BAR 1 4.3 bar ENABLE ALARM LOW FUEL PRESSURE >6 BAR 2 3.8 bar ENABLE TRIP AND STOP HIGH CRANCASE 0m BAR 1 10m bar 150 ENABLE ALARM PRESSUER HIGH CRANCASE 0mBAR 2 15m bar ENABLE TRIP AND STOP PRESSUER LOW COOLANT BAR 1 0.7 bar ENABLE ALARM PRESSURE LOW COOLANT BAR 2 *0.7 bar ENABLE TRIP AND STOP PRESSURE LOW COOLANT LEVEL 1 ENABLE ALARM LOW COOLANT LEVEL 2 ENABLE TRIP AND STOP LOW SUPPLY VOLTAGE 24v 1 23v ENABLE ALARM LOW SUPPLY VOLTAGE 24v 2 *18v ENABLE TRIP AND STOP HIGH SUPPLY VOLTAGE 24v 1 28v ENABLE ALARM HIGH SUPPLY VOLTAGE 24v 2 *30v ENABLE TRIP AND STOP INTERCOOLANT Bar 1 0.7 bar ENABLE ALARM PRESSURE LOW INTERCOOLANT Bar 2 *0.7 bar ENABLE TRIP AND STOP PRESSURE LOW FREQUENCY VOLTAGE 50Hz/11kv 30 ENABLE ALARM FAILURE ECU <900 C 95O C ENABLE TRIP AND STOP