You are on page 1of 1

Engine Parameter and Protection Setting List

NAME STANDARD PROTECTION FAULT STAGE DELAY s ENABLE FAILURE LEVEL


VALUE VALUE OR NOT
HIGE COIL TEMP <120O C 1 140O C 2 ENABLE ALARM
HIGH COIL TEMP <120O C 2 150O C 2 ENABLE TRIP AND STOP
MOTOR BEARING TEMP <80O C 1 80O C 5 ENABLE ALARM
HIGH
MOTOR BEARING TEMP <80O C 2 90O C 10 ENABLE TRIP AND STOP
HIGH
HIGH FUEL TEMP 55O C 1 95O C ENABLE ALARM
HIGH FUEL TEMP 55O C 2 98O C ENABLE TRIP AND STOP
HIGH CHARGE AIR TEMP <80O C 1 80O C ENABLE ALARM
HIGH CHARGE AIR TEMP <80O C 2 83O C ENABLE TRIP AND STOP
HIGH INTERCOOLER <70O C 1 75O C ENABLE ALARM
COOLANT TEMP
HIGH INTERCOOLER <70O C 2 78O C ENABLE TRIP AND STOP
COOLANT TEMP
HIGH LUBRICANT TEMP <95O C 1 99O C ENABLE ALARM
HIGH LUBRICANT TEMP <95O C 2 101O C ENABLE TRIP AND STOP
HIGH COOLANT TEMP <100O C 1 102O C ENABLE ALARM
HIGH COOLANT TEMP <100O C 2 104O C ENABLE TRIP AND STOP
HIGH EXHAUST TEMP <500O C 1 *525O C NOT ALARM
ENABLE
HIGH EXHAUST TEMP <500O C 2 *550O C NOT TRIP AND STOP
ENABLE
LOW LUBRICANT >5 BAR 1 3.5 bar ENABLE ALARM
PRESSURE
LOW LUBRICANT >5 BAR 2 3.2 bar ENABLE TRIP AND STOP
PRESSURE
LOW FUEL PRESSURE >6 BAR 1 4.3 bar ENABLE ALARM
LOW FUEL PRESSURE >6 BAR 2 3.8 bar ENABLE TRIP AND STOP
HIGH CRANCASE 0m BAR 1 10m bar 150 ENABLE ALARM
PRESSUER
HIGH CRANCASE 0mBAR 2 15m bar ENABLE TRIP AND STOP
PRESSUER
LOW COOLANT BAR 1 0.7 bar ENABLE ALARM
PRESSURE
LOW COOLANT BAR 2 *0.7 bar ENABLE TRIP AND STOP
PRESSURE
LOW COOLANT LEVEL 1 ENABLE ALARM
LOW COOLANT LEVEL 2 ENABLE TRIP AND STOP
LOW SUPPLY VOLTAGE 24v 1 23v ENABLE ALARM
LOW SUPPLY VOLTAGE 24v 2 *18v ENABLE TRIP AND STOP
HIGH SUPPLY VOLTAGE 24v 1 28v ENABLE ALARM
HIGH SUPPLY VOLTAGE 24v 2 *30v ENABLE TRIP AND STOP
INTERCOOLANT Bar 1 0.7 bar ENABLE ALARM
PRESSURE LOW
INTERCOOLANT Bar 2 *0.7 bar ENABLE TRIP AND STOP
PRESSURE LOW
FREQUENCY VOLTAGE 50Hz/11kv 30 ENABLE ALARM
FAILURE
ECU <900 C 95O C ENABLE TRIP AND STOP