Instructions in this manual are given as a guide to good practice in the installation, start-up and operation of the control system.
This document does not contain full service procedures for the correct operation of the equipment. To ensure the correct operation
of the machine, rules provided in this manual as well as IOM Machine should be followed.
The support of a qualified Service Engineer is strongly recommended to ensure optimal operation of the equipment as well as the
optimization of all available functionalities.
Note that this document may refer to optional components and certain functions, options or accessories may not be available for
the specific unit. The cover images are solely for illustration and form no part of any offer for sale or any sale contract.
IMPORTANT: All screenshots of the user interface provided in this manual include text in English. After changing the
language of the system, all labels will be in the language selected by the user.
Please read all instructions prior to proceeding with any work. Pay attention to all safety warnings.
The information provided herein is solely for the purpose of allowing customers to operate and service the equipment and it is not
to be reproduced, modified or used for any other purpose without the prior consent of the Manufacturer.
ACRONYMS/ABBREVIATIONS
In this manual, the refrigeration circuits are called circuit A and circuit B. Compressors in circuit A are labelled A1, A2, A3, whereas
compressors in circuit B are labelled B1, B2.
The cover photos are solely for illustration and form no part of any offer for sale or any sale contract. The manufacturer
reserves the right to change the design at any time without notice.
AQUACIAT EN - 2
CONTENTS
PREFACE................................................................ 2 8 - STANDARD CONTROL OPERATIONS AND
OPTIONS.......................................................... 30
ACRONYMS/ABBREVIATIONS............................. 2
8.1 Unit start/stop control.................................... 30
1 - SAFETY CONSIDERATIONS............................ 4 8.2 Heating / Cooling / Standby.......................... 31
1.1 Safety guidelines........................................... 4 8.3 Heating / Cooling selection........................... 32
1.2 Safety precautions......................................... 4 8.4 Supplementary heating (heat pumps)........... 32
2 - CONTROL OVERVIEW...................................... 5 8.5 Pump control................................................ 33
8.6 Hydronic kit option........................................ 34
2.1 Control system............................................... 5
8.7 Control point................................................. 34
2.2 System functionalities.................................... 5
8.8 Dry Cooler Free Cooling option.................... 35
2.3 Operating modes........................................... 5
8.9 Capacity limitation........................................ 36
2.4 Connect Touch............................................... 5
8.10 Capacity control............................................ 36
3 - CONTROL COMPONENTS............................... 6
8.11 Night mode................................................... 37
3.1 Chiller / Heat pump control............................ 6 8.12 Holidays........................................................ 37
3.2 Features overview......................................... 6 8.13 Desuperheater option................................... 37
4 - HARDWARE...................................................... 7 8.14 Defrost cycle for heat pumps........................ 37
4.1 Control boards............................................... 7 8.15 Free Defrost cycle for heat pumps................ 37
4.2 Electrical box................................................. 7 8.16 Master/Slave assembly................................ 37
4.3 Power supply to boards................................. 7 9 - DIAGNOSTICS ................................................ 38
4.4 Light emitting diodes..................................... 7 9.1 Control diagnostics....................................... 38
4.5 Pressure transducers..................................... 7 9.2 Alarms description........................................ 39
4.6 Temperature sensors..................................... 7
10 - MAINTENANCE ............................................. 42
4.7 Actuators....................................................... 8
4.8 Terminal block connections........................... 8
5 - HOW TO USE THE CONNECT TOUCH
INTERFACE..........................................................10
5.1 Connect Touch menu structure..................... 11
5.2 Connect Touch buttons................................. 12
5.3 Read the welcome screen............................ 13
5.4 Explore the synoptic screen.......................... 13
5.5 Start/Stop the unit......................................... 13
5.6 Set the schedule........................................... 14
5.7 Manage display settings............................... 15
5.8 Monitor unit parameters................................ 16
5.9 Modify unit parameters................................. 17
5.10 Override system configuration...................... 17
6 - WEB CONNECTION ........................................ 18
6.1 Web interface............................................... 18
6.2 Open the web interface................................. 18
6.3 Manage web browser settings...................... 18
7 - SETTING UP CONNECT TOUCH – DISPLAY MENU
STRUCTURE.................................................... 19
7.1 Main menu.................................................... 19
7.2 Configuration menu (CONFIG)..................... 25
7.3 Network Parameters menu (NETWORKS)... 29
7.4 Alarms menu................................................ 29
EN - 3 AQUACIAT
1 - SAFETY CONSIDERATIONS
1.1 Safety guidelines 1.2 Safety precautions
Installation, start-up and servicing of equipment can be Only personnel qualified in accordance with IEC (International
hazardous if certain factors particular to the installation are Electrotechnical Commission) recommendations may be
not considered: operating pressures, electrical components, permitted access to electrical components.
voltages, and the installation site (elevated plinths and built-up It is particularly recommended that all sources of electricity to
structures). the unit should be shut off before any work is begun. Shut off
Only qualified installation engineers and fully trained technicians the main power supply at the main circuit breaker or isolator.
are authorised to install and start the equipment. IMPORTANT: The equipment uses and emits electromagnetic
All instructions and recommendations provided in the service signals. Tests have shown that the equipment conforms
guide, installation and operation manuals, as well as on tags to all applicable codes with respect to electromagnetic
and labels fixed to the equipment, components and other compatibility.
accompanying parts supplied separately, must be read,
understood and followed. CAUTION
Failure to comply with the instructions provided by the Risk of electrocution! Even when the main circuit breaker or
manufacturer may result in injury or product damage. isolator is switched off, specific circuits may still be energised
●● Apply all safety standards and practises. as they may be connected to a separate power source.
●● Wear safety glasses and gloves.
●● Use the proper tools to move heavy objects. CAUTION
●● Move units carefully and set them down gently. Risk of burns! Electrical currents may cause components
to get hot. Handle the power cable, electrical cables and
CAUTION
conduits, terminal box covers and motor frames with great
Only qualified service technicians should be allowed to install care.
and service the equipment.
AQUACIAT EN - 4
2 - CONTROL OVERVIEW
2.1 Control system 2.2 System functionalities
AQUACIAT LD (Cooling-only units) and AQUACIAT ILD (Heat The system controls the start-up of the compressors needed to
pumps) units come with a Connect Touch control that serves as maintain the desired heat exchanger entering and leaving water
the user interface and configuration tool for the communicating temperature. It constantly manages the operation of the fans in
devices. order to maintain the correct refrigerant pressure in each circuit
Connect Touch is an electronic control system used to regulate and monitors safety devices that protect the unit against failure
the following types of units: and guarantee its optimal functioning.
AQUACIAT LD air-cooled liquid chillers
AQUACIAT ILD reversible heat pumps 2.3 Operating modes
Connect Touch can function as a stand-alone system or it may be The control can operate in three independent modes:
connected to the building management system using the Modbus ●● Local mode: The unit is controlled by commands from the
TCP/IP, BACnet/IP communication, or Lon communication. user interface.
The units may be fitted with standard fixed-speed fan control ●● Remote mode: The unit is controlled by dry contacts.
system or the optional variable-speed fan drives which can ●● Network mode: The unit is controlled by network
reduce the unit energy use during occupied and unoccupied commands (Modbus RTU). Data communication cable is
periods, provide condensing or evaporating pressure control used to connect the unit to the RS485 communication bus.
and smooth fan start. When the control operates autonomously (Local or Remote), it
For both chillers and heat pumps the system may control retains all of its control capabilities but does not offer any of the
fixed-speed pumps or variable-speed pumps with a hydronic features of the Network.
module.
CAUTION
IMPORTANT: This document may refer to some optional
Emergency stop! The Network emergency stop command
components and certain functions, options or accessories
stops the unit regardless of its active operating type.
may not be available for the specific unit.
EN - 5 AQUACIAT
3 - CONTROL COMPONENTS
3.1 Chiller / Heat pump control
The control manages a number of mechanisms that allow the
unit to operate effectively.
Connect Touch controls compressors, fixed or variable speed
fans, fixed or variable speed pumps for evaporator/condenser,
and more.
AQUACIAT EN - 6
4 - HARDWARE
4.1 Control boards 4.5 Pressure transducers
All boards making up the Connect Touch control system are Three types of transducers (high pressure, low pressure,
installed inside the electrical cabinet. They communicate via an water pressure) are used to measure various pressures in
internal LEN bus. each circuit. These transducers deliver 0 to 10 VDC. They are
The system may embrace two SIOB boards, where the first board connected to the SIOB board.
is used to manage all major inputs and outputs of the controller, Discharge pressure transducers
whereas the second SIOB board is used to support either the
(high pressure type)
third compressor of circuit A or two compressors of circuit B.
These transducers measure the discharge pressure in each
Note that the first SIOB board is also referred to as the main
circuit. They are used to control condensing pressure or high
board – the main board continuously monitors the information
pressure load shedding. Discharge pressure sensors are
received from various pressure and temperature probes.
mounted on the discharge line piping of each circuit.
Accordingly, the Connect Touch control starts the program that
controls the unit. Suction pressure transducers
At the same time, up to two (2) AUX1 boards can be installed. (low pressure type)
The first AUX1 board may provide additional inputs and outputs These transducers measure the suction pressure in each
used to monitor chiller water system cooling temperature circuit. They are used to control EXV, evaporating pressure (in
(Master/Slave assembly), leakage charge detection readings, heating mode) and monitor suction pressure safeties related to
electric heating or boiler operation. This board is used only the compressor operating envelope. Suction pressure sensors
for smaller units (units with only one fan) that have any of the are located on the common suction piping of each circuit.
aforementioned options available (electric heaters, boiler, etc.).
The second AUX1 board is optional and it is used for units with Pump inlet/outlet water pressure transducers
the dry cooler option. It provides information required to control (water pressure type, hydronic kit option)
the free cooling cycle. These transducers measure the hydronic kit pump inlet/outlet
water pressure and monitor the water flow. Pump inlet/outlet
4.2 Electrical box water pressure sensors are mounted on the optional hydronic kit.
The electrical box includes all boards controlling the unit and
the user interface. 4.6 Temperature sensors
Temperature sensors constantly measure the temperature of
4.3 Power supply to boards various components of the unit, ensuring the correct operation
All boards are supplied from a common 24 VAC supply referred of the system.
to earth. Water heat exchanger entering and leaving
In the event of a power supply interrupt, the unit restarts water temperature sensors
automatically without the need for an external command.
The water heat exchanger entering and leaving water
However, any faults active when the supply is interrupted are
temperature sensors are used for capacity control and safety
saved and may in certain cases prevent a given circuit or the
purposes.
unit from restarting.
Outdoor air temperature (OAT) sensor
CAUTION
This sensor measuring the outdoor air temperature is used for
Maintain correct polarity when connecting the power supply start-up, setpoint temperature reset and frost control.
to the boards, otherwise the boards may be damaged.
Suction gas temperature sensors
4.4 Light emitting diodes These sensors measure the suction gas temperature. They are
All boards continuously check and indicate the proper operation used for the EXV control. Suction gas temperature sensors are
of their electronic circuits. A light emitting diode (LED) lights on located at the suction side of each circuit.
each board when it is operating properly. Outdoor coil outlet suction gas temperature
The red LED flashing for a two-second period indicates
sensors
correct operation. A different rate indicates a board or a
software failure. When there are multiple outdoor coils in one refrigerant circuit
The green LED flashes continuously on all boards to these sensors are used in order to ensure that all outdoor coils
show that the board is communicating correctly over its are used equally.
internal bus (LEN bus). If the green LED is not flashing, Master/slave water sensor (optional)
this indicates a LEN bus wiring problem or a configuration
This sensor measures the common water temperature in the
issue.
master/slave system capacity control. It is installed only in the
case of master/slave units.
EN - 7 AQUACIAT
4 - HARDWARE
4.7 Actuators
NOTE: Please refer to the electrical scheme for more information about electrical terminal identification.
*Please note that for chillers only the On/Off contact configuration is applicable.
AQUACIAT EN - 8
4 - HARDWARE
Volt-free setpoint selection contact
This dry contact input is used to switch between setpoints. It is active only when the control is in Remote mode.
Cooling Heating
Stp 1 Stp 2 Stp 1 Stp 2
Setpoint selection contact [SP_SW] open closed open closed
Please note that when the LIM_SW1 is closed, then electric heating will be disabled.
EN - 9 AQUACIAT
5 - HOW TO USE THE CONNECT TOUCH INTERFACE
① ② ③ ④ ⑤ ⑥ ⑦
⑭
⑧
⑬ ⑨
⑪ ⑩
Connections
Connections are located on the bottom of the controller.
Features of Connect Touch user interface Connect Touch provides access to the following screens:
4.3" colour touch screen with quick display of alarms, Welcome screen (splash screen)
current unit operating status, etc. Synoptic screen
Resistive touch screen technology Operating mode selection screen
Web connectivity Data/configuration screens
Custom language support Password entry and language selection screen
Alarms screen
WARNING Parameter modification screen
If the user interface is not used for a long period, the Welcome Time schedule screen
screen is displayed, and then it goes blank. The control is
always active and the operating mode remains unchanged.
Press anywhere on the screen and the Welcome screen will
be displayed.
AQUACIAT EN - 10
5 - HOW TO USE THE CONNECT TOUCH INTERFACE
5.1 Connect Touch menu structure
Home Main Menu Log in / Log out Start / Stop Alarms Menu
Unit mode
Main menu
General Parameters Temperature Pressure
Configuration menu
ModbusTCP/IP Config.
Current Alarms
Alarm History
Legend:
Basic access
(0 = user password)
EN - 11 AQUACIAT
5 - HOW TO USE THE CONNECT TOUCH INTERFACE
5.2 Connect Touch buttons
HOME SCREEN
Home screen displayed Main Menu displayed Go back to the previous screen
OTHER SCREENS
Set force: Override the current command Displayed when the menu includes more
(if possible) than one page: Go to the previous page
AQUACIAT EN - 12
5 - HOW TO USE THE CONNECT TOUCH INTERFACE
5.3 Read the welcome screen 5.4 Explore the synoptic screen
The Welcome screen is the first screen shown after starting the The Synoptic screen allows you to monitor the vapour-
user interface. It displays the application name as well as the refrigeration cycle. The diagram indicates the current status of
current software version number. the unit, giving information on the unit capacity, the status of water
To exit the Welcome screen and go to the Home screen, heat exchanger pumps, and the pre-defined setpoint parameter.
press the Home button. All unit functions can be accessed by pressing the Main menu
button.
Home Start/Stop
① ② ③
① Home button
② Software version number
③ Information message box
EN - 13 AQUACIAT
5 - HOW TO USE THE CONNECT TOUCH INTERFACE
5.5 Start/Stop the unit (cont.) 5.6 Set the schedule
To start the unit The control incorporates two time schedules, where the first
1. Press the Start/Stop button. one (OCCPC01S) is used for controlling the unit start/stop,
2. Select the required Machine Mode. whereas the second one (OCCPC02S) is used for controlling
3. The Welcome screen will be displayed. the dual setpoint.
The control offers the user the possibility of setting eight
occupancy periods where each occupancy period includes the
following elements to be defined:
Day of the week: Select the days when the period is
occupied.
Occupancy time ("occupied from" to "occupied to"): Set
occupancy hours for the selected days.
Timed Override Extension: Extend the schedule if necessary.
This parameter can be used in the case of some unplanned
events. Example: If the unit is normally scheduled to run
between 8:00 to 18:00, but one day you want the air-
conditioning system to operate longer, then set this timed
override extension. If you set the parameter to "2", then the
occupancy will end at 20:00.
To stop the unit
To set the unit start/stop schedule
1. Press the Start/Stop button.
1. Go to the Main menu.
2. Confirm the unit shutdown by pressing Confirm Stop or
2. Navigate to the Configuration menu (logged-in users only)
cancel the unit shutdown by pressing the Back button.
and select Schedule (SCHEDULE).
3. Go to OCCPC01S.
4. Select appropriate check boxes to set the unit occupancy
on specific days.
5. Define the time of occupancy.
6. When the time schedule is set, the selected period will be
presented in the form of the green band on the timeline.
7. Press the Save button to save your changes or the Cancel
button to exit the screen without making modifications.
② ①
③ ④ ⑤ ⑥
AQUACIAT EN - 14
5 - HOW TO USE THE CONNECT TOUCH INTERFACE
5.7 Manage display settings 5.7.2 User login
The User Login screen allows the user to select the language of Only logged-in users can access configurable unit parameters.
the controller, change the system of measurement (imperial or By default, user password is "11".
metric) and provide a password to gain access to more control To log in as user
options. 1. Press the Login button to open User Login Screen.
To access the User Login screen, press the Login button in the 2. Press the Password box.
upper-right corner of the screen.
② ③ ④ ⑤
WARNING
5.7.3 Password change
It is strongly recommended to change the default password User password can be modified in the User Configuration
of the user interface to exclude the possibility of changing any menu.
parameters by an unqualified person.
To change your password
Only people qualified to manage the unit should be familiarized 1. Go to the Main menu.
with the password. 2. Navigate to the Configuration menu (logged-in users only)
and select User Configuration (USERCONF).
3. Select the User Password box and provide your new
password.
4. Press OK.The User Configuration screen appears.
5. Press the Save button to save your changes or the Cancel
button to exit the screen without making modifications
EN - 15 AQUACIAT
5 - HOW TO USE THE CONNECT TOUCH INTERFACE
5.7.4 Display language 5.8 Monitor unit parameters
Display language can be modified in the User Login Screen on The Main menu screen provides access to the main control
the user interface. parameters, including general parameters, inputs and outputs
To change a display language status, etc.
1. Press the Login button to open User Login Screen. To access the menu, press the Main menu button located
2. Select the new language of the display. in the upper-left part of the Synoptic screen.
Specific unit parameters can be accessed by pressing the
icon corresponding to the desired category.
To go back to the Synoptic screen, press the Home button.
IMPORTANT: Connect Touch allows users to add new General unit parameters
languages to the control.
The General parameters screen provides access to a set of
To learn more about language customization, please general unit parameters.
contact your local Manufacturer representative. To access the General parameters screen, go to the Main
menu and select General Parameters (GENUNIT).
5.7.5 System of measurement Press the Up/Down buttons to navigate between the
The control offers the possibility of selecting the system of screens.
measurement displayed on the user interface.
To change a system of measurement
1. Press the Login button to open User Login Screen.
2. Select the system of measurement.
①
① Forceable point
AQUACIAT EN - 16
5 - HOW TO USE THE CONNECT TOUCH INTERFACE
5.9 Modify unit parameters
The Configuration menu gives access to a number of
user-modifiable parameters such as pump configuration,
schedule menu, etc. The Configuration menu is password-
protected (see also "User login" on page 15).
② ③
① Forced value
② Set force
③ Auto
EN - 17 AQUACIAT
6 - WEB CONNECTION
6.1 Web interface 6.3 Manage web browser settings
The Connect Touch control can be accessed via a web browser Minimum web browser configuration:
(Internet Explorer, Mozilla Firefox, etc.). Connection is from a Internet Explorer (version 8 or higher) or Mozilla Firefox
PC using a web browser with Java. (version 26 or higher). In the advanced connection options
add the unit IP address to the exceptions list. Do not use
CAUTION a proxy server.
Use firewalls and VPN for secure connection. Java platform (version 6 or higher). In the control panel,
clear the Keep temporary files on my computer check box
and use a direct connection.
6.2 Open the web interface IMPORTANT: Two users can be connected simultaneously
To access the Connect Touch control, enter the IP address of with no priority between them. Note the last modification is
the unit in the address bar of the web browser. always taken into account.
CAUTION
For security reasons the unit cannot be started / stopped via
the web interface.
All other operations, including monitoring unit parameters
or unit configuration, can be performed via the web browser
interface.
AQUACIAT EN - 18
7 - SETTING UP CONNECT TOUCH – DISPLAY MENU STRUCTURE
7.1 Main menu
Icon Displayed text* Description Name
CAUTION
Since specific units may not include additional features, some
tables may contain parameters that cannot be configured for
a given unit.
EN - 19 AQUACIAT
7 - SETTING UP CONNECT TOUCH – DISPLAY MENU STRUCTURE
AQUACIAT EN - 20
7 - SETTING UP CONNECT TOUCH – DISPLAY MENU STRUCTURE
EN - 21 AQUACIAT
7 - SETTING UP CONNECT TOUCH – DISPLAY MENU STRUCTURE
AQUACIAT EN - 22
7 - SETTING UP CONNECT TOUCH – DISPLAY MENU STRUCTURE
EN - 23 AQUACIAT
7 - SETTING UP CONNECT TOUCH – DISPLAY MENU STRUCTURE
AQUACIAT EN - 24
7 - SETTING UP CONNECT TOUCH – DISPLAY MENU STRUCTURE
7.2 Configuration menu (CONFIG)
Icon Displayed text* Description Name
Network parameters
Network Parameters NETWORKS
(Modbus configuration)
CAUTION
Since specific units may not include additional features, some
tables may contain parameters that cannot be configured for
a given unit.
EN - 25 AQUACIAT
7 - SETTING UP CONNECT TOUCH – DISPLAY MENU STRUCTURE
AQUACIAT EN - 26
7 - SETTING UP CONNECT TOUCH – DISPLAY MENU STRUCTURE
EN - 27 AQUACIAT
7 - SETTING UP CONNECT TOUCH – DISPLAY MENU STRUCTURE
AQUACIAT EN - 28
7 - SETTING UP CONNECT TOUCH – DISPLAY MENU STRUCTURE
7.3 Network Parameters menu (NETWORKS)
Icon Displayed text* Description Name
NOTE: To learn more about the Modbus option and its configuration, please refer to Modbus documentation.
CAUTION
Since specific units may not include additional features, some
tables may contain parameters that cannot be configured for
a given unit.
EN - 29 AQUACIAT
8 - STANDARD CONTROL OPERATIONS AND OPTIONS
8.1 Unit start/stop control Start/stop force command [CHIL_S_S]: Start/stop force
command can be used to control the chiller state in the
The unit state is determined based on a number of factors,
Network mode.
including its operating type, active overrides, open contacts,
Command set to stop: The unit is halted.
master/slave configuration, or alarms triggered due to operating
Command set to start: The unit runs in accordance
conditions.
with schedule 1.
The table given below summarizes the unit control type [ctrl_typ]
Remote start/stop contact status [Onoff_sw]: Start/stop
and its running status with regard to the following parameters:
contact status can be used to control the chiller state in the
Operating type: This operation type is selected using the
Remote operating type.
Start/Stop button on the user interface.
Master control type [ms_ctrl]: When the unit is the
LOFF Local off master unit in a two-chiller master/slave arrangement, the
L-C Local on master unit may be set to be controlled locally, remotely or
L-SC Local schedule via network.
Rem Remote Start/stop schedule [chil_occ]: Occupied or unoccupied
Net Network status of the unit.
Mast Master unit Network emergency stop command [EMSTOP]:
If activated, the unit shuts down regardless of the active
operating type.
General alarm: The unit shuts down due to failure.
IMPORTANT: When the unit is stopping or there is a demand to stop the unit, compressors are stopped consecutively.
In case of emergency stop, all compressors are stopped at the same time.
AQUACIAT EN - 30
8 - STANDARD CONTROL OPERATIONS AND OPTIONS
8.2 Heating / Cooling / Standby
The Connect Touch control determines the heat/cool state of the unit.
CHILLERS MAY OPERATE ONLY IN COOLING MODE.
HEAT PUMPS MAY OPERATE IN COOLING OR HEATING MODE.
In the case of heat pumps, the user may enable the automatic heat/cool changeover option (auto_sel, HCCONFIG – Heat/Cool
Config).The option must be set manually by the user (by default, this automatic changeover is disabled).
●● When the outdoor air temperature exceeds the cooling threshold, then the cooling mode is started.
●● When the outdoor air temperature is below the heating threshold, then the heating mode is started.
●● When the outdoor air temperature is between the abovementioned changeover setpoints, then the unit is neither cooling
nor heating. It is in Standby mode which means that compressors are stopped and the water pump may be running with
no mechanical cooling or heating. However, it is possible to have the pump stopped in Standby mode if the [pump_sby]
parameter in the Pump Configuration menu (PUMPCONF) is set to "yes".
Control type Heat/Cool (Local) Heat/Cool (Remote) Heat/Cool (Network) Outdoor Air Temperature ** Operating mode
local cool - - - cool
local heat - - - heat
local auto* - - >cauto_sp + 1 K cool
local auto* - - <hauto_sp -1 K heat
local auto* - - hauto_sp + 1 K < oat < cauto_sp -1 K standby
local - on_cool - - cool
local - on_heat - - heat
local - on_auto - >cauto_sp +1 K cool
local - on_auto - <hauto_sp - 1 K heat
remote - on_cool - - cool
remote - on_heat - - heat
remote - on_auto - >cauto_sp + 1 K cool
remote - on_auto - <hauto_sp - 1 K heat
remote - on_auto - hauto_sp + 1K< oat < cauto_sp – 1K standby
network - - cool - cool
network - - heat - heat
network - - auto* >cauto_sp + 1 K cool
network - - auto* <hauto_sp - 1 K heat
network - - auto* hauto_sp + 1K< oat < cauto_sp - 1 K standby
* If auto changeover has been selected through user configuration; otherwise, by default set to "cooling".
** cauto_sp = cooling changeover setpoint;h auto_sp = heating changeover setpoint; oat = outdoor air temp.
EN - 31 AQUACIAT
8 - STANDARD CONTROL OPERATIONS AND OPTIONS
8.3 Heating / Cooling selection 8.4 Supplementary heating (heat pumps)
As mentioned earlier in the document Heating/Cooling selection AQUACIAT ILD heat pumps may be fitted with a boiler or
applies only to heat pumps. Heating/Cooling selection can be electric heaters.
controlled in various ways, depending on the active operating The boiler is used as heating replacement when mechanical
type. The cooling mode is selected by default. heating is not possible or insufficient due to low outdoor air
Heating/Cooling can be determined: temperature.
Locally at the unit using the HC_SEL item in the GENUNIT Electric heaters can be turned on to satisfy the heating
menu. demand when mechanical heating is insufficient.
Remotely via the heating/cooling selection contact if the
unit is in the Remote mode. 8.4.1 Boiler control
Via a network command if the unit is in the Network mode. The boiler can be activated when the unit is down due to a
Heating/Cooling mode can be set manually by the user or detected failure or it may also be used as supplementary
automatically by the control. When heating/cooling is automatic, heating when the operating conditions are not suitable for
the outdoor air temperature determines the heat/cool/ mechanical heating.
standby changeover (cauto_sp and hauto_sp, SETPOINT). Boiler is activated when the outdoor air temperature is below
The automatic changeover is optional and requires user the user-configured boiler OAT threshold, which is by default
configuration (HC_SEL, GENUNIT- General Parameters). set to -10°C (14°F).
To set boiler OAT threshold
To set cooling / heating / auto mode 1. Navigate to the Configuration menu (logged-in users only).
1. Navigate to the Main menu. 2. Select Heat/Cool Config (HCCONFIG).
2. Select General Parameters (GENUNIT). 3. Set Boiler OAT Threshold [boil_th].
3. Set Heat/Cool Select [HC_SEL]. Boiler OAT Threshold [boil_th]
1 Heating
2 Automatic changeover 8.4.2 Electric heating control
Electric heating stages can be activated as additional heating
To enable heating/cooling auto changeover when OAT is below the user-configured electric heating OAT
1. Navigate to the Configuration menu (logged-in users only). threshold, which is by default set to 5°C (41°F).
2. Select Heat/Cool Config (HCCONFIG). Electric heating is allowed when all of the following
conditions are met:
3. Set Auto Changeover Select [auto_sel].
Unit is running at 100% capacity.
Auto Changeover Select [auto_sel] Electric pull-down time elapsed [ehs_pull].
No/Yes Yes OAT is below the OAT threshold [ehs_th].
There are four electric heating stages where the last electric
To set cool changeover setpoint heating stage is used for back-up. It means that normally only
1. Navigate to the Main menu. three heating stages are allowed and the fourth one is used
only when the unit is down due to a detected fault or the heating
2. Select Setpoint (SETPOINT).
protection is active.
3. Set Cool Changeover Setpt [cauto_sp].
When EHS are installed in the optional water tank, the additional
Cool Changeover Setpt [cauto_sp] electric power can be limited using the “Tank EHS power Limit”
3.9 to 50.0ºC 23.9ºC parameter. The user can choose to use an alert when temperature
39.0 to 122.0ºF 75.0ºF elevation is not as efficient as expected (Tank EHS efficiency Alert).
AQUACIAT EN - 32
8 - STANDARD CONTROL OPERATIONS AND OPTIONS
8.5 Pump control 8.5.3 Automatic pumps selection
The control system can manage one or two water exchanger If two pumps are controlled and the reversing function has
pumps, determining each pump on/off state and its speed. Both been selected (PUMPCONF – Pump Configuration), the control
pumps cannot run together. The pump is turned on when this balances the pump run time to match the configured pump
option is configured and when the unit is running. changeover delay. If this delay has elapsed, the pump reversing
function is activated.
The pump is turned off when the unit is shut down due to an
alarm, unless the fault is a frost protection error. The pump can To set pump automatic rotation delay
be started in particular operating conditions when the water 1. Navigate to the Configuration menu (logged-in users only).
exchanger heater is active. 2. Select Pump Configuration (PUMPCONF).
If the pump has failed and another pump is available, the unit is 3. Set Pump Rotation Delay [pump_del].
stopped and started again with the second pump. If there is no
pump available, the unit shuts down. Pump Rotation Delay [pump_del]
24 to 3000h 48h
Configuration options may differ depending on the number and
type of pumps available (single speed pumps or variable speed
8.5.4 Customer pumps configuration
pumps).
Units fitted with external pumps may have fixed speed or variable
8.5.1 Variable speed pumps control speed pumps available.
AQUACIAT LD chillers and AQUACIAT ILD heat pumps may be Customer pumps may be configured as follows:
fitted with one or two variable speed pumps.
Pump available Pumps sequence (pump_seq, PUMPCONF)
Variable speed pumps give the possibility of saving the pumping
energy cost, providing precise water flow control and improving No pump 0 (no pump)
the overall performance of the system. The frequency inverter One pump 1 (one pump only)
continuously regulates the flow rate to minimize the pump power (fixed or variable speed)
consumption at full load and part load. Two pumps 2 (two pumps auto)
(fixed or variable speed) 3 (pump#1 manual)
Water flow management methods are as follows: 4 (pump#2 manual)
1) Fixed speed control (the control ensures a constant pump
speed based on compressor capacity).
Units with customer pumps are fitted with the flow switch,
2) Water flow control based on constant water delta pressure allowing for the water flow control. For more information about
(the control continuously acts on the pump speed to ensure actuators, see Water flow switch in section 4.7.
a constant delta pressure).
3) Water flow control based on constant delta T on the water 8.5.5 Pumps protection
exchanger. The control provides the option to automatically start the pump
IMPORTANT: Pump speed configuration can be performed each day at 14:00 for 2 seconds when the unit is off.
only by service technicians. If the unit is fitted with two pumps, the first pump is started on
even days and the second pump is started on odd days. Starting
8.5.2 Pumps configuration the pump periodically for a few seconds extends the lifetime of
The control can command internal fixed speed or variable the pump bearings and the tightness of the pump seal.
speed pumps as well as customer pumps (fixed speed or Periodical pump quick start can be selected via the Configuration
variable speed). Variable speed pumps may also be configured menu (PUMPCONF – Pump Configuration).
as fixed speed pumps.
To set periodical pump quick start
Basic pump configuration can be performed via the Configuration
1. Navigate to the Configuration menu (logged-in users only).
menu (PUMPCONF – Pump Configuration). Only logged-in users
can access the menu. The unit must be stopped. 2. Select Pump Configuration (PUMPCONF).
To set pumps sequence 3. Set Pump Sticking Protection [pump_per].
1. Navigate to the Configuration menu (logged-in users only). Pump Sticking Protection [pump_per]
2. Select Pump Configuration (PUMPCONF). No/Yes Yes
3. Set Water Pumps Sequence [pump_seq].
8.5.6 Eco pump mode
Water Pumps Sequence [pump_seq] When the unit is in Standby mode (heating or cooling demand
0 No Pump is satisfied), the Connect Touch control may be configured to
1 One Pump Only stop the pump periodically in order to save energy.
2 Two Pumps Auto
This option can be configured only by service technicians.
3 Pump#1 Manual
To verify the Eco Pump configuration
4 Pump#2 Manual
1. Navigate to the Main menu.
2. Select Miscellaneous Status (MSC_STAT).
3. Verify Eco Pump Mode Active [m_ecopmp].
EN - 33 AQUACIAT
8 - STANDARD CONTROL OPERATIONS AND OPTIONS
8.6 Hydronic kit option To verify the control point
1. Navigate to the Main menu.
The hydronic kit option allows for continuous monitoring of the
water flow rate (PUMPSTAT – Pump Status). 2. Select General Parameters (GENUNIT).
The hydronic kit provides the option to measure the following 3. Verify Control Point [CTRL_PNT].
parameters:
Inlet and outlet water pressure. 8.7.1 Active setpoint
Water exchanger flow rate. Two setpoints can be selected, where the first setpoint is used
The water flow rate is based on the pressure difference between during occupied periods, whereas the second one is used
the inlet and outlet pressures and the pressure drop curves. during unoccupied periods.
Hydronic kit option with variable speed pumps Depending on the current operation type, the active setpoint can
For units with variable speed pumps, this option allows for the be selected manually via the Main menu on the user interface,
automatic adjustment of the pump speed necessary to maintain with the volt-free user contacts, with network commands or
the correct water flow rate. automatically with the setpoint time schedule (schedule 2).
Water flow control can be based on compressor usage, constant The following tables summarise possible selections depending
delta pressure or constant temperature difference. See also on the control operating type (Local / Remote / Network) and
"Variable speed pumps control" on page 33. the following parameters:
Heating or Cooling operating mode [HC_SEL]: Heat/Cool
Select (GENUNIT – General Parameters).
8.7 Control point
Setpoint selection [SP_SEL]: Setpoint Select permits
The control point represents the water temperature that the selection of the active setpoint if the unit is in the Local
unit must produce. The required capacity can be decreased operating type (GENUNIT – General Parameters).
depending on the unit load operating conditions. Setpoint switch status [SETP_SW]: Remote Setpoint
Control point = Active setpoint + Reset Switch (INPUTS – Inputs).
Occupied state of dual setpoint time schedule [SP_OCC]:
The control point is calculated based on the active setpoint and
Schedule for setpoint selection.
the reset calculation. The forced value can be used instead of
any other setpoint calculation only when the unit is in the Network
operating type.
AQUACIAT EN - 34
8 - STANDARD CONTROL OPERATIONS AND OPTIONS
8.7.2 Reset 8.8 Dry Cooler Free Cooling option
Reset means the active setpoint is modified so that less AQUACIAT LD chillers may be fitted with a dry cooler that
machine capacity is required. In the cooling mode the setpoint enables power consumption reduction which amounts to energy
is increased, whereas in the heating mode it is decreased. and cost savings.
The reset can be based on the following possibilities: The installation of a dry cooler allows for "free cooling" – a method
OAT that gives the measure of the load trends for the of using low outdoor air temperature as an aid to chilling water
building. that is later used in the air-conditioning system. The system is
Return water temperature (ΔT provides the average the most effective when the outdoor air temperature is below
building load). 0°C (32°F).
Dedicated 4-20 mA input.
The reset source and the reset parameters can be configured Starting free cooling
in the Main menu (RESETCFG – Reset Config). In response to The free cooling mode is ENABLED when the free cooling
a change in the reset source (e.g. OAT), the setpoint is normally OAT [oat] is below the water loop temperature and the start
reset to optimise unit performance. threshold:
The amount of reset is determined by linear interpolation based
oat < wloop – start_th
on the following parameters:
A reference at which reset is zero (no reset value). oat : Free Cooling OAT
A reference at which reset is maximum (full reset value).
wloop : Free Cooling Water Loop Temperature
The maximum reset value.
start_th : Free Cooling Start Threshold (service access only)
Reset example in Cooling mode:
EN - 35 AQUACIAT
8 - STANDARD CONTROL OPERATIONS AND OPTIONS
8.9 Capacity limitation 8.10 Capacity control
Connect Touch control system allows for constant control of the The control adjusts the capacity to keep the water exchanger
unit capacity by setting its maximum allowable capacity. temperature at its setpoint. Compressors are started and
Capacity limitation is expressed in percentage, where a limit stopped in a sequence designed to equalize the number of
value of 100% means that the unit may run with its full capacity starts (value weighted by their operating time).
(no limitation is implemented). 8.10.1 Circuit loading sequence
The unit capacity can be limited: This function determines in which order the circuit capacity is
By means of user-controlled volt-free contacts. The unit changed. Compressor loading is managed by starting/stopping
capacity can never exceed the limit setpoint activated by compressors. Two types of sequencing, i.e. balanced and
these contacts. staged loading sequence, are available and can be configured
By demand limit [DEM_LIM] set via the communication by the user via the user interface (GENCONF – General Config).
protocol (System Manager or the Master unit in the Master/ Balanced loading sequence: The control maintains equal
Slave assembly control). capacity between all circuits as the machine loads and unloads.
By night mode limitation control. The demand limit value Balanced loading sequence is the default sequence employed
in the night mode is selectable if the value is below the by the control.
selected capacity limit.
Staged loading sequence: The control loads the lead circuit
To set limit setpoints completely before the lag circuit is started. When the load is
1. Navigate to the Main menu. decreasing, the lag circuit is unloaded first. Staged loading
2. Select Setpoint (SETPOINT). sequence is active when one of the circuits is shut down due
to its failure; the circuit is in capacity override mode; or the
3. Set Switch Limit Setpoint 1 / 2 / 3 [lim_sp1 / 2 / 3].
remaining circuits are shut down or fully charged.
Switch Limit Setpoint 1 / 2 / 3 [lim_sp1 / 2 / 3] To set the circuit loading sequence
0 to 100% 100% 1. Navigate to the Configuration menu (logged-in users only).
2. Select General Config (GENCONF).
To verify demand limit set by the master unit
3. Set Staged Loading Sequence [seq_typ].
1. Navigate to the Main menu.
2. Select General Parameters (GENUNIT). Staged Loading Sequence [seq_typ]
No/Yes No (staged loading NOT active)
3. Verify Active Demand Limit Val [DEM_LIM].
8.10.2 Capacity for multi-circuit units
Active Demand Limit Val [DEM_LIM]
0 to 100% 100% For units with more than one circuit, the lead/lag function
determines which circuit is the lead circuit and which circuit is
the lag circuit This function controls the start/stop sequence of
To set the night mode limit two refrigeration circuits called circuit A and circuit B.
1. Navigate to the Configuration menu (logged-in users only).
The circuit authorised to start first is the lead circuit. Lead circuit
2. Select General Config (GENCONF). is used first for capacity increases and at the same time should
3. Set Night Capacity Limit [nh_limit]. be decreased first when decreasing capacity. The lead/lag
circuits can be selected manually or automatically (Cir Priority
Night Capacity Limit [nh_limit]
Sequence, GENCONF – General Config).
0 to 100% 100% Manual lead/lag circuit determination: Circuit A or circuit
B selected as the lead circuit. The selected circuit takes
Based on the limit source, the active demand limit value [DEM_ priority over another circuit.
LIM] is set to the lowest possible value. DEM_LIM can be Automatic lead/lag circuit determination: The control
forced by Network. system determines the lead circuit to equalise the operating
time of each circuit (value weighted by the number of start-
ups of each circuit). As a result, the circuit with the lowest
To verify active demand limit value number of operating hours always starts first.
1. Navigate to the Main menu.
To set circuit priority
2. Select General Parameters (GENUNIT).
1. Navigate to the Configuration menu (logged-in users only).
3. Verify Active Demand Limit Val [DEM_LIM]. 2. Select General Config (GENCONF).
Active Demand Limit Val [DEM_LIM]
3. Set Cir Priority Sequence [lead_cir].
0 to 100% -
Cir Priority Sequence [lead_cir]
0 Auto
1 Circuit A lead
2 Circuit B lead
AQUACIAT EN - 36
8 - STANDARD CONTROL OPERATIONS AND OPTIONS
8.11 Night mode 8.14 Defrost cycle for heat pumps
Night mode allows users to configure the unit to operate with When the outdoor air temperature is low and the ambient
specific parameters in a specific time period. During the night humidity is high, the probability of frost forming on the surface
period, the unit capacity is limited. The number of operating of the outdoor coil increases. The frost covering the outdoor
fans is reduced (in cooling mode only), so that the noise level coil may decrease the air flow across the coil and lead to lower
is reduced. performance of the unit. To remove the frost from the coil, the
The night period is defined by a start time and an end time control initiates the defrost cycle when necessary.
that are the same for each day of the week. The Night mode During the defrost cycle, the circuit is forced into the cooling
settings or the maximum capacity value can be configured via mode. To prevent the water loop from cooling down, optional
the Configuration menu (GENCONF – General Config). electric heating may be started. The defrost cycle lasts until the
IMPORTANT: Only logged-in users can modify the night end of defrost temperature is achieved.
mode settings.
8.15 Free Defrost cycle for heat pumps
8.12 Holidays Free defrost is used in order to eliminate a relatively small
This function is used to define 16 holiday periods. Each period amount of frost that has formed on the surface of the coil.
is defined by three parameters: the month, the start day and the Contrary to the standard defrost session; in the case of the free
duration of the holiday period. defrost session the heat (energy) is absorbed from the air. When
running the free defrost, fans are activated and compressors are
During the holiday periods the controller will be in occupied
turned off. The free defrost is most efficient when the outside air
or unoccupied mode, depending on the periods validated as
temperature is above 1°C.
holidays. Each holiday period can be modified by the user via
the Configuration menu (HOLIDAY – Holiday Menu). IMPORTANT: In the case of a large amount of frost covering
the coil, the standard defrost cycle will be started.
To modify holiday periods
1. Navigate to the Configuration menu (logged-in users only).
8.16 Master/Slave assembly
2. Select Holiday (HOLIDAY).
The control system allows for master/slave control of two units
3. Choose the holiday period, e.g. HOLDY_01. linked by the network (proprietary protocol). The master unit
4. Set Holiday Start Month [HOL-MON], Start Day [HOL-DAY], can be controlled locally, remotely, or by network commands,
Duration (days) [HOL-LEN]. while the slave unit remains in Network mode. All control
Holiday Start Month [HOL-MON] commands to the master/slave assembly (start/stop, setpoint
0-12 0 selection, demand limit, etc.) are handled by the unit configured
Start Day [HOL-DAY] as the master. The commands are transmitted automatically to
0-31 0
the slave unit.
Duration (days) [HOL-LEN] If the master chiller is turned off while the master/slave function
0-99 0 is active, then the slave chiller will be stopped. Under certain
circumstances, the slave unit may be started first to ensure that
the run times of the two units are equalised.
In the event of a communication failure between the two units,
8.13 Desuperheater option
each unit will return to an autonomous operating mode until the
AQUACIAT LD chillers and AQUACIAT ILD heat pumps may fault is cleared. If the master unit is stopped due to an alarm,
be fitted with a desuperheater that allows for better energy the slave unit is authorised to start.
management.
IMPORTANT: Master/slave assembly can be configured
The desuperheater is used to extract the high pressure, high only by service technicians.
temperature heat from the refrigerant to "desuperheat" it to
a lower pressure refrigerant. The vapour that goes into the
desuperheater is not fully condensed; therefore, the refrigerant
vapour must be channelled to a separate heat exchanger
where the condensing process occurs.
To set minimal condensing setpoint
1. Navigate to the Main menu.
2. Select Setpoint (SETPOINT).
EN - 37 AQUACIAT
9 - DIAGNOSTICS
The control system has many fault tracing aid functions, 9.1.2 Alarms reset
protecting the unit against risks that could result in the failure Alarms can be reset without stopping the machine. Only
of the unit. logged-in users can reset alarms (see also "User login" on page
Connect Touch gives quick access to monitor all unit operating 15). The alarm can be reset either automatically or manually
conditions. If an operating fault is detected, the alarm is through the user interface or the web interface (Reset Alarms
triggered. menu).
Note that some alarms are used only to warn against potentially Note that the Reset Alarms menu displays up to five (5) alarm
dangerous situations and they may have no effect on the codes which are currently active on the unit.
unit when triggered; however, failure to acknowledge these To reset alarms manually
warnings may have negative impact on the operation of the 1. Press the Alarm button in the upper-right part of the screen.
system or the unit itself.
2. Select Reset Alarms (ALARMRST).
Please perform all corrective actions if indicated. For example,
in the case of alarms beginning with 130-xx, please contact 3. Set the Alarm Reset to "Yes" and press the Set Force
the service agency immediately in order to proceed with the button.
required servicing procedure(s).
CAUTION
In the event of a power supply interrupt, the unit restarts
automatically without the need for an external command.
However, any faults active when the supply is interrupted are
saved and may in certain cases prevent a circuit or a unit
from restarting.
AQUACIAT EN - 38
9 - DIAGNOSTICS
9.2 Alarms description
EN - 39 AQUACIAT
9 - DIAGNOSTICS
Code Name Description Reset Action taken Possible cause
10037 REPEATED_HIGH_ Circuit A Repeated High Automatic (no discharge gas None Repetitive capacity decreases
DGT_A_F Discharge Gas Overrides overrides within 30 min) or
Manual
10038 REPEATED_HIGH_ Circuit B Repeated High Automatic (no discharge gas None Repetitive capacity decreases
DGT_B_F Discharge Gas Overrides overrides within 30 min) or
Manual
10040 REPEATED_LOW_ Circuit A Repeated Low Suction Manual Circuit A shuts down Repetitive capacity decreases
SST_A_F Temp Overrides
10041 REPEATED_LOW_ Circuit B Repeated Low Suction Manual Circuit B shuts down Repetitive capacity decreases
SST_B_F Temp Overrides
10043 HEAT_LOW_EWT_F Low Entering Water Automatic None Low entering fluid temperature in
Temperature In Heating Heating mode
10063 HP_SWITCH_A_F Circuit A High pressure switch Manual Circuit A shuts down High pressure switch is open,
Failure compressor fault
10064 HP_SWITCH_B_F Circuit B High pressure switch Manual Circuit B shuts down High pressure switch is open,
Failure compressor fault
10097 SENSORS_SWAP_F Water Exchanger Temperature Manual Unit shuts down Input and output temperature
Sensors Swapped reversed
10099 FLUIDE_FAIL Possible Refrigerant Leakage Automatic None Refrigerant leak detected
Failure
10101 FC_PROCESS_F Free Cooling Process Failure Automatic Free Cooling is stopped Installation fault
10109 TANK_HTR_LOW_ Tank EHS low efficiency alert Automatic, if heat production None: Contact Electric heater damaged or dirty
EFFICIENCY_F returns to normal Manufacturer service
11202 WL_PRESS_ZERO_ Water Loop : Delta Pressure Automatic, if water pressure delta Unit shuts down Too low or high water pressure
ERROR_F Error returns to normal reading
11203 WL_PRESS_TOO_ Water Loop : Pressure Too Low Automatic, if water pressure Unit shuts down Pump inlet pressure is below 60 kPa
LOW_F reading returns to normal and the
alarm occurred up to 6 times in
the last 24 h (otherwise manual)
11204 WL_PUMP_NOT_ Water Loop : Pump Not Started Automatic Pump is stopped Too low or high pump pressure
STARTED_F reading
11206 WL_PUMP_ Water Loop : Pump Overload Automatic None Water pressure drop too low
OVERLOAD_F
11207 WL_LOW_FLOW_F Water Loop : Flow Too Low Automatic, if water flow reading Pump is stopped Water loop pressure drop too high
returns to normal
11208 WL_PRESS_CROSS_F Water Loop : Pressure Sensors Manual Unit shuts down Pressure sensors crossed
Crossed
11209 WL_LOW_PRESS_ Water Loop : Low Pressure Automatic, if water pressure None Water pressure is below 60 kPa
WARNING_F Warning reading returns to normal
12001 DP_A_F Circuit A Discharge Pressure Automatic, if sensor voltage Circuit A shuts down Defective transducer
Transducer Failure reading returns to normal
12002 DP_B_F Circuit B Discharge Pressure Automatic, if sensor voltage Circuit B shuts down Defective transducer
Transducer Failure reading returns to normal
12004 SP_A_F Circuit A Suction Pressure Automatic, if sensor voltage Circuit A shuts down Defective transducer
Transducer Failure reading returns to normal
12005 SP_B_F Circuit B Suction Pressure Automatic, if sensor voltage Circuit B shuts down Defective transducer
Transducer Failure reading returns to normal
12024 WP_IN_F Water Exchanger Entering Fluid Automatic, if sensor voltage Unit shuts down Defective transducer
Transducer Failure reading returns to normal
12025 WP_OUT_F Water Exchanger Leaving Fluid Automatic, if sensor voltage Unit shuts down Defective transducer
Transducer Failure reading returns to normal
15001 COOL_EWT_F Water Exchanger Entering Fluid Automatic, if thermistor reading Unit shuts down Defective thermistor
Thermistor Failure returns to normal
15002 COOL_LWT_F Water Exchanger Leaving Fluid Automatic, if thermistor reading Unit shuts down Defective thermistor
Thermistor Failure returns to normal
15003 DEFROST_T_A_F Circuit A Defrost Thermistor Automatic, if thermistor reading Cooling mode: Unit Defective thermistor
Failure returns to normal continues to operate
Heating mode: Circuit A
shuts down
15004 DEFROST_T_B_F Circuit B Defrost Thermistor Automatic, if thermistor reading Cooling mode: Unit Defective thermistor
Failure returns to normal continues to operate
Heating mode: Circuit B
shuts down
15010 OAT_F OAT Thermistor Failure Automatic, if thermistor reading Unit shuts down Defective thermistor
returns to normal
15011 CHWSTEMP_F MASTER/Slave Common Fluid Automatic, if thermistor reading Master/Slave operation is Defective thermistor
Thermistor Failure returns to normal disabled, each unit returns
to the stand-alone mode
AQUACIAT EN - 40
9 - DIAGNOSTICS
Code Name Description Reset Action taken Possible cause
15012 SUCTION_T_A_F Circuit A Suction Gas Thermistor Automatic, if thermistor reading Circuit A shuts down Defective thermistor
Failure returns to normal
15013 SUCTION_T_B_F Circuit B Suction Gas Thermistor Automatic, if thermistor reading Circuit B shuts down Defective thermistor
Failure returns to normal
15044 SGTC1_F Coil Suction Gas Thermistor Automatic, if thermistor reading Circuit A shuts down Defective thermistor
Sensor 1 Failure returns to normal
15045 SGTC2_F Coil Suction Gas Thermistor Automatic, if thermistor reading Circuit B shuts down Defective thermistor
Sensor 2 Failure returns to normal
15046 FC_WLOOP_F Free Cooling Water Loop Automatic, if thermistor reading Free cooling is stopped Defective thermistor
Thermistor Failure returns to normal
15047 FC_LWT_F Free Cooling Leaving Water Automatic, if thermistor reading Free cooling is stopped Defective thermistor
Thermistor Failure returns to normal
15048 FC_OAT_F Free Cooling OAT Water Automatic, if thermistor reading OAT sensor reading Defective thermistor
Thermistor Failure returns to normal (instead of FC OAT sensor)
is used
16001 DRV_FAN_A_F Circuit A Variable Speed Fan Automatic Circuit A shuts down Speed controller fault
Failure
17001 DRV_FAN_B_F Circuit B Variable Speed Fan Automatic Circuit B shuts down Speed controller fault
Failure
19001 DRV_WTR_PUMP_F Water pump Variable Speed Automatic Unit is restarted with Speed controller fault
Drive Failure another pump running. If no
pump is available, the unit
shuts down.
57001 SIOB_LOW_VOLT_ Circuit A SIOB Low Voltage Automatic, if the alarm occurred Unit shuts down Unstable electrical supply or
CIRA_F Failure up to 6 times in the last 24 h electrical issue
(otherwise manual)
57002 SIOB_LOW_VOLT_ Circuit B SIOB Low Voltage Automatic, if the alarm occurred Unit shuts down Unstable electrical supply or
CIRB_F Failure up to 6 times in the last 24 h electrical issue
(otherwise manual)
130nn SERVICE_ Service maintenance alert Manual None: Contact Servicing required
MAINTNANCE_ALERT Manufacturer service
13005 FGAS_ALERT Fgas check required Manual None: Contact Servicing required
Manufacturer service
NOTE: When the "action taken" given in the table above is defined as "none", it means that the alarm message is
displayed, but no action is taken on the unit.
EN - 41 AQUACIAT
10 - MAINTENANCE
In order to ensure the optimal operation of the equipment as well as the optimization of all the available functionalities, it is
recommended to activate a Maintenance Contract with your local Manufacturer Service Agency.
The contract will ensure your equipment is regularly inspected by specialists so that any malfunction is detected and corrected
quickly and no serious damage can occur to your equipment.
The Manufacturer provides a wide range of service contracts which embrace the assistance of highly qualified HVAC engineering
professionals ready to help if needed.The Maintenance contracts represent not only the best way to ensure the maximum operating
life of your equipment, but also, through the expertise of qualified personnel, the optimal tool to manage your system in a cost-
effective manner.
To find the best type of contract that will meet all of your expectations, please contact your local Manufacturer representatives.
AQUACIAT EN - 42
Siège social
Avenue Jean Falconnier B.P. 14
01350 Culoz - France
Tel. : +33 (0)4 79 42 42 42
Fax : +33 (0)4 79 42 42 10 CIAT Service
info@ciat.fr - www.ciat.com Tel. : 08 11 65 98 98 - Fax : 08 26 10 13 63