Design of Purlins Beams and Columns of Roof Shed covered with glass

Moment
Strength Section Modulus
Sections Capacity
(Mpa) (cm3)
(KNm)
(cm3) mm3
38x38x2.5 158 3.76 3760 0.59408
50x50x2.5 158 7165 1.13207
ISMB100 158 36.6 36600 5.7828
ISMB125 158 71.2 71200 11.2496
ISMB150 158 95.7 95700 15.1206
Wind Load on Purlins
Dead Load
Thickness of Glass 12 mm
Load imposed 0.36 KN/m2 (36 kg/m2)
Live load 0.75 KN/m2 75 kg/m2
Gravity Load combination DL+LL
1.11 KN/m2 110kg/m2
Wind Intensity 1.2 KM/m2
Spacing 0.6 m
Length of Purlin= 2.5 m
Uplift 0.8 KN/m2 110kg/m2
UDL on purlins 0.5 KN/m 140 kg/m
Moment from Load 0.39 KNm
Purlin Section SHS 38x38x2.5
Hence Ok
Length of beam 6 m
No of purlins 10
load from each purlins 1.26 KN
Maximun moment at mid span
= 11.34 KN/m
Beam Provided = ISMB150
Hence Ok
Total load on columns = 12.6 KN
Critical Load on Column ISMB150
height of column 3500 mm
Moment of Inertia 468000 mm4
Critical Load on Column 75.3 KN
Hence Ok