According to the CCPS book “Bow Ties in Risk Management”, there are five main barrier types.
We use cookies to enhance your experience. By continuing to visit this site you agree to
our use of cookies. More info (http://wikipedia.org/wiki/HTTP_cookie)
An operator response to an alarm is considered an “Active Hardware + Human” barrier. To be
considered a complete barrier it must contain the following three elements; Detect (e.g., high-high
level indicator with alarm), Decide (e.g., the operator diagnoses the situation and initiates a
response), and Act (e.g., operator manipulates final control element manually or via the control
system).
Note that in the example diagrams below the barrier type is indicated by color code and label.
As shown in the bow tie diagram below, the three main barriers to prevent “Tank Overflow” (Top
Event) were “Fill Plan & Proactive Monitoring”, “Tank Level Alarms & Operator Response”,
and “Independent High-High Automatic Shut-Off”. The degradation factors for the Tank Level
Alarm barrier were identified as “Alarm Failure” and “Operators fail to respond appropriately to
alarms”. The degradation controls to prevent “Alarm Failure” are “Regular Maintenance and
Testing” and “Alarm failure easily identified in control room and prioritized fault repair
process”.
We use cookies to enhance your experience. By continuing to visit this site you agree to
our use of cookies. More info (http://wikipedia.org/wiki/HTTP_cookie)
Identifying these degradation controls highlights their importance to the prevention of a Major
Accident Event (MAE) such as tank overflow. If these controls had been adopted and applied
rigorously, it is possible that the failure of the level gauge indicating the tank was 2/3 full could have
been prevented or would have still drawn the operator’s attention to investigate the abnormal
situation.
Figure – Standard Bow Tie Showing Main Pathways and Degradation Factors (Prevention Side) Ref CCPS
To create a multi-level bowtie diagram for the Buncefield incident, the Top Event becomes the
failure of one of the barriers, in this example “Tank Level Alarms & Operator Response”. The
bow tie diagram then focuses in detail on the degradation factor “Operators fail to respond
appropriately to alarms”, which is now modelled as a threat. The barriers to prevent this threat
include “Alarm easily identified on HMI” and “Defined operator action in event of high level
alarm (auditable)”. As shown in the Level 1 Extension Bow Tie below, each barrier has additional
degradation factors and controls that can now be shown that would have made the main bow tie
diagram too complicated.
We use cookies to enhance your experience. By continuing to visit this site you agree to
our use of cookies. More info (http://wikipedia.org/wiki/HTTP_cookie)
Figure – Level 1 Extension Bow Tie Selected Barriers (Ref CCPS)
The benefit of calling out the additional level of detail would be in focusing the operations,
maintenance, and management team on what safety critical tasks should be performed to maximize
the reliability of the operator response to alarm barrier. It could reinforce to the team, and garner
management commitment, for the following critical alarm management activities:
• Performing alarm rationalization (including prioritization) to ensure all alarms are meaningful
• Maintenance and testing of alarms based on classification
• Developing Alarm Response Procedures to provide guidance to the operator when a barrier
alarm is generated
• Designing the Human Machine Interface (HMI) to maximize the operator’s situation
awareness
In conclusion it appears that bow tie diagrams have potential for use in alarm management,
particularly for alarms that are expected to help prevent major accident events. Bow tie diagrams
can highlight alarm management tasks to be performed. They also highlight alarm management
degradation controls, many of which are generic and could be applied to the entire alarm system.
Bow tie diagrams seem to provide a useful mechanism for integrating process safety, alarm
management, (and cybersecurity) risk assessment results into a common view.
Since this is a relatively new methodology, time will tell how far bow ties are adopted to support
alarm management.
References:
“Bow Ties in Risk Management: A Concept Book for Process Safety”
(https://www.aiche.org/ccps/resources/publications/books/bow-ties-risk-management-concept-book-process-
safety)CCPS in association with the Energy Institute, 2018.
“Bowtie Analysis for Alarm Management”, D. Hatch, and A. Geddes, IChemE Alarm Systems and Controls Seminar &
Tyneside Process Safety Forum 2018.
We use cookies to enhance your experience. By continuing to visit this site you agree to
our use
“The Buncefield of cookies.- More
Investigation” info (http://wikipedia.org/wiki/HTTP_cookie)
www.buncefieldinvestigation.gov.uk/reports/index.htm
WEBINAR: For additional information tune into the webinar “Do Bowties Have a Place in Alarm Management” on
April 22, 2020. (https://www.exida.com/Webinars/do-bow-ties-have-a-place-in-alarm-management)
Related Items
exida Alarm Management Services (https://www.exida.com/Alarm-Management)
We use cookies to enhance your experience. By continuing to visit this site you agree to
our use of cookies. More info (http://wikipedia.org/wiki/HTTP_cookie)
0 Comments exida Disqus' Privacy Policy
1 Login
Name
About Us
exida offers services, tools, and training to help organizations meet regulatory requirements,
achieve safe operations, and deliver results.
We work closely with our customers to achieve high-impact, cost-effective solutions for their
Functional Safety, Alarm Management, and IACS Cybersecurity challenges.
(https://www.linkedin.com/company/exida-com) (http://www.youtube.com/exidallc)
(http://www.instagram.com/exidallc) (https://twitter.com/exidaLLC)
(http://www.facebook.com/exidaLLC)
Contact
Germany +49-89-49000547
USA +1-215-453-1720
Canada +1-647-838-3377
India +91-99-30-250-104
Mexico +52-55-7572-4870
Subscribe
© 2000 - 2020 exida.com LLC Privacy Policy (https://www.exida.com/Home/Privacy-Policy)Terms
and Conditions (https://www.exida.com/Home/terms-and-conditions)
We use cookies to enhance your experience. By continuing to visit this site you agree to
our use of cookies. More info (http://wikipedia.org/wiki/HTTP_cookie)