Professional Documents
Culture Documents
Functional Overview
Tie Breaker
Zone 1 Zone 2 ANSI NUMBERS/ACRONYMS AND FUNCTIONS
52-6
16 SEC Access Security (Serial, Ethernet)
27/59 Over- and Undervoltage
50 Overcurrent
50BF Breaker Failure Overcurrent
52-1 52-2 52-3 52-4 52-5
51 Time-Overcurrent
85 RIO SEL MIRRORED BITS Communications
87 Current Differential
3 3 3 3 3 3 3 3
DFR Event Reports
HMI Operator Interface
Analog and To Other LGC Expanded SELOGIC Control Equations
Digital Data Switches MET High-Accuracy Metering
Measured with
Merging Unit Switch RTU Remote Terminal Unit
To Other 2 SER Sequential Events Recorder
Relay Relays
Ethernet
Port ADDITIONAL FUNCTIONS
Process
Bus SMB Station Battery Monitor
50 50 50 50 50 50 50 27 ADDITIONAL FEATURES
59
Open CT Detection
51 51 51 51 51 51 51 Three Independent Check Zones
Disconnect Status and Monitoring Logic for
60 Disconnects
50BF 50BF 50BF 50BF 50BF 50BF 50BF Single-Relay Application: 2 Three-Phase Zones for
as many as 7 Terminals
Two-Relay Application: 3 Three-Phase Zones for
87 87 as many as 10 Terminals
Zone 1 Zone 2 Three-Relay Application: 6 Single-Phase Zones for
as many as 12 Terminals
The SEL-487B subscribes to as many as seven while the SEL-401 can provide basic phase overcurrent
IEC 61850-9-2LE data streams that are published by and breaker-failure protection in the absence of commu-
merging units, such as the SEL-421-7 Protection, Auto- nication. The data may be synchronized via IRIG-B time
mation, and Control System with Sampled Values or input or IEEE 1588-2008 PTP. As shown with blue lines
SEL-401 Protection, Automation, and Control Merging in Figure 1, the SEL-487B performs breaker control
Unit. The SEL-421-7 provides full backup protection through GOOSE communications.
Protection Features
The SEL-487B SV Subscriber Relay offers a compre- is false (the disconnect is open), the relay dynamically
hensive busbar protection feature. The relay supports one removes the currents from the differential elements. This
interface board which can be configured for different is also true for the trip output. When the SELOGIC con-
options of digital inputs and outputs. trol equation of a terminal is false, the relay issues no trip
signal to that terminal. Table 1 shows a simple case
With the flexibility of the expanded SELOGIC control where the disconnect status is the only condition for the
equations, you need no external auxiliary relays to con- relay to consider.
figure the relay for complex busbar arrangements. The
SEL-487B provides station-wide protection through the Table 1 Conditions for Automatic Terminal Assignment
use of as many as six zones of differential protection,
advanced zone selection algorithms, and per-terminal SELOGIC Consider
Control Terminal in Issue
breaker failure and overcurrent protection. Example of Condition
Equation Protection Trip?
Result Calculations?
SELOGIC control equations provide the mechanism by By including the circuit breaker auxiliary contact in one
which the user enters the conditions for assigning the of the SELOGIC control equations (Figure 3), we can
currents to the differential elements when these condi- cause the value of the SELOGIC control equation to be
tions are met. When a SELOGIC control equation false when the circuit breaker is open, removing the cur-
becomes true (e.g., the disconnect is closed), the relay rent from the differential element calculations. This
dynamically assigns the current to the differential ele- capability ensures the stability of the busbar protection.
ments. Conversely, when the SELOGIC control equation By our use of SELOGIC control equations and normal
Current (Amperes)
5
Busbar End-Zone Primary
Fault Fault Current IO1
52
0
5
IO2
F1 0
Current IRT
Input I21
External
Fault
Fault
Detection Logic Internal
Fault
Figure 5 External Fault Detection Logic Increases
Differential Element Security
Detection
50
IO2
0
–50 Subsidence
Disconnect Status Monitor Table 5 shows the four possible disconnect auxiliary con-
tact combinations and how the relay interprets each com-
Figure 8 shows the disconnect open and close contact bination.
relationship. During the open-to-close operation, the 89b
Table 5 Disconnect Status as a Function of the
contact must open (disconnect is CLOSED) during the Auxiliary Contacts
transition zone before the main contact arcing starts. The
89a contact must close in this transition zone. 89a 89b
Relay 89 Status
Interpretation
During the close-to-open operation, the 89b contact must
0 0 closed
close during the transition zone after the main contact
arcing is extinguished (disconnect is OPEN), as shown in 0 1 open
Figure 8. The 89a contact must open in this transition 1 0 closed
zone.
1 1 closed
Figure 8 Disconnect Switch Auxiliary Contact Requirements for the Zone Selection Logic; No CT Switching Required
Six Independent Settings Groups Selecting a group also selects logic settings. Program
group logic to adjust settings for different operating con-
Increase Operation Flexibility ditions, such as station maintenance, seasonal operations,
and emergency contingencies.
The relay stores six settings groups. Select the active set-
tings group by control input, command, or other pro-
grammable conditions. Use these settings groups to Applications
cover a wide range of protection and control contingen-
cies. Figure 9 shows a station with a single bus and a bus tie
breaker. Figure 10 shows a station with a double-bus
Selectable settings groups make the SEL-487B ideal for configuration.
applications requiring frequent settings changes and for
adapting the protection to changing system conditions.
Zone 1 Zone 2
52
3 3
q
52 52 52 52 52
IW IX
SEL-401 #4
Process Bus
Network
PTP Time Source
q DC connections for breaker
GOOSE Publications status and control
1. TRIP01–TRIP21 w No physical connection.
Published data do not contain
SEL-487B SV valid analog measurements
Subscriber
Zone 1
3 3 3
q q 3 q
IW IW VY IW
SEL-421 SV
SEL-401 #1 SEL-401 #2
Publisher
IX IX IX
q q q
3 3 3
Control House
SEL-421 SV Process Bus PTP Time Source
Subscriber #1 Network
SEL-421 SV
Subscriber #2 q DC connections for breaker
status and control
SEL-487B SV w No physical connection.
Subscriber Published data do not contain
GOOSE Publications valid analog measurements
1. TRIP01–TRIP18
For stations with 10 to 21 terminals, use three separate plete flexibility because they can close any disconnect at
SEL-487B Relays. Each of the 21 analog current inputs any time without compromising the busbar protection.
in each relay measures only one phase, with six dedi- This is possible because the relay dynamically computes the
cated zones of protection available. Each relay operates station connection replica by using the patented zone-selec-
independently. In this application, operators have com- tion algorithm.
=>>SET T <Enter>
1: PMV01,THETA
(assign the alias “THETA” to math variable PMV01)
2: PMV02,TAN
(assign the alias “TAN” to math variable PMV02)
=>>SET L <Enter>
1: # CALCULATE THE TANGENT OF THETA
2: TAN:=SIN(THETA)/COS(THETA)
(use the aliases in an equation)
Edge Trigger R_TRIG, F_TRIG Operates at the change of state of an internal function.
Math Functions SQRT, LN, EXP, COS, SIN, ABS, Combine these to calculate other trigonometric functions,
ACOS, ASIN, CEIL, FLOOR, LOG i.e., TAN: = SIN(THETA)/COS(THETA).
Arithmetic *, /, +, - Uses traditional math functions for analog quantities in an easily programma-
ble equation.
Comparison <, >, <=, >=,=, <> Compares the values of analog quantities against predefined thresholds or
against each other.
Boolean AND, OR, NOT Combines variables, and inverts the status of variables.
Precedence Con- () Allows as many as 14 sets of parentheses.
trol
Comment # Provides for easy documentation of control and protection logic.
➤ IEC 61850 Data Server. The SEL-487B, equipped MMS File Services
with embedded IEC 61850 Ethernet protocol,
provides data according to predefined logical node This service of IEC 61850 Manufacturing Message
objects. Each relay supports as many as seven Specification (MMS) provides support for file transfers
simultaneous client associations. Relevant Relay completely within an MMS session. All relay files that
Word bits are available within the logical node can be transferred via FTP can also be transferred via
data, so you can use the IEC 61850 data server in MMS file services.
the relay to monitor the status of relay elements,
inputs, outputs, or SELOGIC control equations.
MMS Authentication
➤ Configuration of as many as 256 Virtual Bits
within GOOSE messaging to represent a variety of When enabled via a setting in the Configured IED
Boolean values available within the relay. The Description (CID) file, the relay will require authentica-
Virtual Bits the relay receives are available for use tion from any client requesting to initiate an MMS ses-
in SELOGIC control equations. sion. The client request must be accompanied by the
➤ As many as 64 remote analog outputs that you can
Access Level 2 password.
assign to virtually any analog quantity available in
the relay. You can also use SELOGIC math ACSELERATOR Architect
variables to develop custom analog quantities for
assignment as remote analog outputs. Remote USE ACSELERATOR Architect® SEL-5032 Software to
analog outputs using IEC 61850 provide peer-to- manage the logical node data for all IEC 68150 devices
peer transmission of analog data. Each relay can on the network. This Windows-based software provides
receive as many as 256 remote analog inputs and easy-to-use displays for identifying and binding
use those inputs as analog quantities within IEC 61850 network data among logical nodes using
SELOGIC control equations. IEC 61850-compliant CID files. Architect uses CID files
to describe the data the IEC 61850 logical node will pro-
vide within each relay.
Type Description
Additional Features
Front-Panel Display tons with indicating LEDs for local control functions.
Target and pushbutton identification can be custom-con-
The SEL-487B front panel includes a 128 x 128 pixel figured with easily changed slide-in labels. Use the capa-
(76.2 mm x 76.2 mm or 3 in x 3 in) LCD screen; 24 LED bilities of the SEL-487B front panel to integrate a wide
target indicators; and 12 direct-action control pushbut- range of control and system annunciation functions.
The LCD is controlled by the navigation pushbuttons, tion of target LEDs, operator control pushbuttons, and
automatic messages the relay generates, and user- pushbutton LEDs. The blank slide-in label set is included
programmable display points. with the SEL-487B. Functions are simple to configure
using QuickSet.
The rotating display scrolls through any active, non-
blank display points. If none are active, the relay scrolls You can use templates supplied with the relay or hand-
through displays of the differential operating and written on blank labels supplied with the relay to print
restraint quantities and the primary current and voltage labels.
values. Metering screens can be enabled and displayed in
an order defined by the user. Each display remains for a
user-settable period of time before the display continues Control Inputs and Outputs
scrolling. Any message generated by the relay because of
an alarm condition takes precedence over the rotating Select one interface board with a variety of contact input
display. and output configurations, including the following:
➤ Optoisolated, level-sensitive contact inputs
➤ High-current interrupting contact outputs
Status and Trip Target LEDs
➤ High-speed, high-current interrupting contact
The SEL-487B front panel provides 24 programmable outputs
tricolor LED indicators and 12 direct-action control
pushbuttons. The relay is available in 4U chassis height. The 4U chas-
sis requires the selection of one expansion I/O board.
Assign the control inputs for disconnect auxiliary contact
Configurable Front-Panel Labels status and breaker auxiliary contact status. Set the input
debounce time independently for each input or as a
Customize the SEL-487B front panel to fit your needs. group. Each control output is programmable through the
Use SELOGIC control equations and slide-in configurable use of SELOGIC control equations.
front-panel labels to change the function and identifica-
Table 8 Flexible Metering Capabilities and Large Screen Display Eliminate Need for Panel Instruments
Capabilities Description
V01, V02, V03 Fundamental phase voltage magnitude and angle in primary and secondary values
I01, I02, . . ., I21 Fundamental phase current magnitude and angle in primary and secondary values
IOP, IRT, IREF Operating and restraint currents for each zone, check zone, and the reference current
Bus Zones in Protection Zone n Names of the bus-zones in Protection Zone n (where n = 1 to 6)
PTR, CTR PT ratio and CT ratio for each terminal
POL Polarity of each CT
➤ Relay/terminal identification
Event Reporting and Sequential
➤ Event date and time
Events Recorder (SER) ➤ Event type
Event Reports and SER features simplify post-fault anal- ➤ Event number
ysis and help improve your understanding of both simple
➤ Time source
and complex protective scheme operations. These fea-
tures also aid in testing and troubleshooting relay settings ➤ Active settings group
and protection schemes. ➤ Targets asserted during the fault
➤ Current magnitudes and angles for each terminal
Oscillography and Event Reporting ➤ Voltage magnitudes and angles
In response to a user-selected internal or external trigger, ➤ Terminals tripped for this fault
the voltage, current, and element status information con- ➤ Bus-zones in Protection Zone n (n = 1–6)
tained in each event report confirms relay, scheme, and
system performance for every fault. The SEL-487B pro- With an appropriate setting, the relay will send an Event
vides as fast as 8 kHz sampling rates for analog quanti- Summary in ASCII text automatically to one or more
ties in a COMTRADE file format. It also provides 12 serial ports for each triggering of an event report.
sample-per cycle and 4 sample-per-cycle event reports
that sample filtered analog quantities. The relay stores in
nonvolatile memory as much as 5 seconds of 8 kHz event SER
data and 24 seconds of 1 kHz event data. Relay settings Use this feature to gain a broad perspective of relay ele-
operational in the relay at the time of the event display at ment operation. Items that trigger an SER entry are
the end of each filtered event report. selectable and can include as many as 250 monitoring
Use event report settings in the relay to assign as many as points such as I/O change of state and element pickup/
20 analog quantities for inclusion in the filtered event dropout. The relay SER stores the latest 1000 events.
reports. Use relay-calculated values such as check zone
operate and restraint current, or use SELOGIC automation
or protection math variables. Substation Battery Monitor for DC
Each SEL-487B provides event reports for analysis with
Quality Assurance
software such as SYNCHROWAVE® Event SEL-5601 The SEL-487B measures and reports the substation bat-
Software. With SYNCHROWAVE Event, you can display tery voltage for one battery system. The relay provides
events within the same time stamp range from as many as alarm, control, and dual ground detection for one battery
three different relays in one window to make the fault and charger. The battery monitor includes warning and
analysis easier and more meaningful. Because the differ- alarm thresholds that you can monitor with the
ent relays time-stamp the events with values from their SEL-3530 Real-Time Automation Controller (RTAC)
individual clocks, be sure to time-synchronize the and use to trigger messages, telephone calls, or other
SEL-487B with an IRIG-B or PTP clock input to use this actions. The relay reports measured dc voltage in the
feature. METER display via serial or Ethernet port communica-
tions, on the LCD, and in the Event Report. Use the event
Event Summary report data to see an oscillographic display of the battery
voltage. Monitor the substation battery voltage drops
Each time the relay generates a standard event report, it during trip, close, and other control operations.
also generates a corresponding Event Summary. This is a
concise description of an event that includes the follow-
ing information:
Relay Dimensions
Specifications
Note: The SEL-487B SV Subscriber Relay uses a SV-based remote data UL Listed to U.S. and Canadian safety standards
acquisition system. Operating times will be delayed by the configured (File E212775; NRGU, NRGU7)
channel delay, CH_DLY. Use caution when setting the relay coordination
CE Mark
times to account for this added delay. See SV Network Delays on page 17.19
in the SEL-400 Series Relays Instruction Manual for more details on this RCM Mark
setting.
Note: The metering and protection element accuracies specified for the
SEL-487B SV Subscriber Relay are valid only when using SEL SV
General
publisher relays. Third-party SV publisher devices are supported, but Power Supply
hardware accuracies and analog filtering need to be considered to determine
the effect on SEL-487B performance. 24–48 Vdc
Fast Hybrid (High-Speed High-Current Interrupting) Current Drawn: <5 mA at nominal voltage
<8 mA for 110 V option
Rated Voltage: 48–250 Vdc
Sampling Rate: 2 kHz
Operational Voltage Range: 0–300 Vdc
Operating Time: Pickup 0 µs (resistive load)
Dropout 8 ms (resistive load)
Profiles: Default, IEEE C37.238-2011 (Power Protective Bonding: IEC 60255-27:2013, Section 10.6.4.5.2
Profile) <0.1 @ 12 Vdc, 30 A for 1 min
Synchronization Accuracy: ±100 ns @ 1-second synchronization Object Penetration: IEC 60529:2001 + CRGD:2003
intervals when communicating directly Protection Class: IP30
with master clock Max Temperature of Parts
Operating Temperature and Materials: IEC 60255-27:2013, Section 7.3
Flammability of Insulating IEC 60255-27:2013, Section 7.6
–40° to +85°C (–40° to +185°F)
Materials: Compliant
Note: LCD contrast impaired for temperatures below –20° and above +70°C.
Electromagnetic (EMC) Immunity
Humidity
Product Standards: IEC 60255-26:2013
5% to 95% without condensation IEC 60255-27:2013
IEEE C37.90-2005
Weight (Maximum)
Surge Withstand Capability IEC 61000-4-18:2006 + A:2010
4U Rack Unit: 6.5 kg (14.5 lb) (SWC): IEEE C37.90.1-2012
Slow Damped Oscillatory, Common and
Terminal Connections Differential Mode:
Rear Screw-Terminal Tightening Torque, #8 Ring Lug ±1.0 kV
±2.5 kV
Minimum: 1.0 Nm (9 in-lb) Fast Transient, Common and
Maximum: 2.0 Nm (18 in-lb) Differential Mode:
User terminals and stranded copper wire should have a minimum ±4.0 kV
temperature rating of 105°C. Ring terminals are recommended.
Incremental Restraint and Operating Threshold Current Supervision 5 A Model: 0.50–50 A, 0.01 A steps
1 A Model: 0.10–10.0 A, 0.01 A steps
Setting Range: 0.1–10.0 pu
Accuracy
Accuracy: ±5% ± 0.02 • INOM
5 A Model: ±0.05 A, ±3% of setting
Sensitive Differential Current Alarm
1 A Model: ±0.01 A, ±3% of setting
Quantity: 9 total, 1 per zone
(6 standard zones, 3 check zones) Transient Overreach: <5% of setting
Setting Range: 0.05–1.00 pu Maximum Pickup Time: 1.5 cycles
Accuracy: ±5% ± 0.02 • INOM Maximum Reset Time: <1 cycle
Timer Setting Range: 50–6000 cycles Timers Setting Range: 0–6000 cycles, 1/12-cycle steps
(BFPUnn, RTPUnn)
Instantaneous/Definite-Time Overcurrent Elements 0–1000 cycles, 1/12-cycle steps
Phase Current Setting Range (BFISPnn, BFIDOnn)
5 A Model: OFF, 0.25–100.00 A secondary, Time Delay Accuracy: 1/12 cycle, ±0.1% of setting
0.01 A steps Disconnect Monitor
1 A Model: OFF, 0.05–20.00 A secondary, Number: 60
0.01 A steps
Timer Setting Range: 0–99999 cycles, 1 cycle step
Accuracy (Steady State)
5 A Model: ±0.05 A, ±3% of setting
Breaker Status Monitor
Number: 21
1 A Model: ±0.01 A, ±3% of setting
Transient Overreach: <5% of setting Coupler Security Logic
Timer Setting Range: 0.00–99999.00 cycles, 1/6-cycle steps Number: 4
Timer Accuracy: ±0.1% of settings ±1/6 cycle Timer Setting Range: 0–1000 cycles, 1/12 cycle step
Metering Accuracy
All metering accuracies are based on an ambient temperature of 20°C
and nominal frequency.
Currents
Phase Current Magnitude
5 A Model: ±0.2% plus ± 4 mA (2.5–15 A sec)
1 A Model: ±0.2% plus ± 0.8 mA (0.5–3.0 A sec)
Phase Current Angle
All Models: ±0.2° in the current range
(0.5–3.0) • INOM
Differential Currents per Zone (Steady State)
IOP, IRT: ±5.0% ± 0.02 • INOM
IOPCZ, IRTCA: ±5.0% ± 0.02 • INOM
Voltages
Phase Voltage Magnitude
300 V Maximum Inputs: ±2.5% ± 1 V (5–33.5 V)
±0.1% (33.5–300 V)
Phase Angle
300 V Maximum Inputs: ±1.0° (5–33.5 V)
±0.5° (33.5–300 V)
Notes
*PDS487B-06*
This product is covered by the standard SEL 10-year warranty. For warranty details, visit
selinc.com or contact your customer service representative.