Professional Documents
Culture Documents
Operating Manual: Control For Hammer Mills DFZC, DFZP and DFZK
Operating Manual: Control For Hammer Mills DFZC, DFZP and DFZK
2 Safety 7
2.1 Part of the operating instructions ................................................................. 7
2.2 Intended use ................................................................................................. 7
2.3 Technical condition ........................................................................................ 7
2.4 ATEX designation .......................................................................................... 7
2.5 Personnel qualification .................................................................................. 7
3 Technical data 8
3.1 Housing ......................................................................................................... 8
3.2 Display ........................................................................................................... 8
3.3 Environmental conditions .............................................................................. 8
3.4 Electrical data ................................................................................................ 8
3.5 Interfaces ....................................................................................................... 9
3.6 Miscellaneous ................................................................................................ 9
3.7 Design versions ............................................................................................. 10
4 Description 11
4.1 Nameplate ..................................................................................................... 11
4.2 Operating principle ........................................................................................ 11
4.2.1 Throughput control ........................................................................ 15
4.2.2 Hammer mill .................................................................................. 15
4.2.3 Dosing ............................................................................................ 16
4.2.4 Heavy particle flap ........................................................................ 17
4.2.5 Outlet cone .................................................................................... 17
4.2.6 Discharge ....................................................................................... 17
4.2.7 Gravity flow diverter (option) ......................................................... 18
4.2.8 Temperature monitoring (option) ................................................... 18
4.2.9 Vibration monitoring (option) ......................................................... 18
4.2.10 Magnetic door and back-up probe ............................................... 18
4.2.11 Profibus interface .......................................................................... 18
4.2.12 Profinet interface (option) .............................................................. 18
4.2.13 EtherNet/IP interface (option) ....................................................... 19
4.3 Time charts .................................................................................................... 20
4.3.1 Standard sequence ....................................................................... 20
4.3.2 Emptying time ................................................................................ 20
4.3.3 Timeout .......................................................................................... 21
5 Connection 22
5.1 Overview ........................................................................................................ 22
5.1.1 Hammer mill control ...................................................................... 22
5.1.2 Throughput control ........................................................................ 23
Bühler AG
MEAG-DFCQ-66802-12-1-1908-en-US
2 Table of contents
5.2 Main circuit board EBD 1311 ....................................................................... 24
5.2.1 Jumpers EBD 1311 ....................................................................... 25
5.2.2 Connection for power supply ........................................................ 25
5.2.3 Profibus DP or RS-485 SIO_2 ..................................................... 25
5.2.4 CAN interface ................................................................................ 26
5.2.5 24 V inputs .................................................................................... 26
5.2.6 24 V outputs .................................................................................. 29
5.2.7 0 … 5 V or 0/4 … 20 mA analog inputs ..................................... 31
5.2.8 0/4 to 20 mA analog outputs ........................................................ 31
5.3 Decentralized IO modules ............................................................................ 32
5.3.1 Digital IO module EBD 1318 ........................................................ 32
5.3.2 Jumpers EBD 1318 ....................................................................... 32
5.3.3 Digital IO expansion module 1 ..................................................... 33
5.3.4 Digital IO expansion module 2 ..................................................... 34
5.3.5 Digital IO expansion module 5 ..................................................... 35
5.3.6 Digital IO expansion module 6 ..................................................... 35
5.3.7 Analog IO module EBD 1317 ....................................................... 37
5.3.8 Analog jumper for IO expansion module EBD 1317 ................... 37
5.3.9 Analog IO expansion module 1 .................................................... 38
5.3.10 Analog IO expansion module 2 .................................................... 38
5.4 Display unit EBD 1316 ................................................................................. 39
5.4.1 Circuit board EBD 1316 ................................................................ 39
5.4.2 Description of electric terminals X50 ............................................ 40
5.4.3 Description of electric terminals X52 ............................................ 40
5.4.4 Jumpers EBD 1316 ....................................................................... 40
5.5 Wiring of vertical hammer mill control DFZK ............................................... 41
5.6 Wiring of throughput adjuster (only main circuit board) .............................. 43
5.7 Wiring of throughput adjuster (with CAN modules) ..................................... 45
6 Operation 47
6.1 Keys and lamps ............................................................................................ 47
6.2 Display operating elements .......................................................................... 48
6.3 Parameters and parameter groups .............................................................. 48
7 Configuration 50
7.1 Setting the application .................................................................................. 50
7.2 Device-specific settings ................................................................................. 50
7.3 Using the input wizard .................................................................................. 51
7.4 Optimizing the controller settings ................................................................. 51
7.5 Configuring and calibrating the temperature monitoring ............................. 51
7.6 Setting frequency converter of the feed roller ............................................. 52
7.6.1 Cutter ATV 320 ............................................................................. 52
7.6.2 Cutter ATV 312/31 ........................................................................ 54
7.7 Controlling the mill motor with frequency converter .................................... 55
7.7.1 Configuring the frequency converter cutter ATV 930 (example) . 57
7.7.2 Configuring the frequency converter DANFOSS VLT 5000 ........ 58
7.8 Special applications ...................................................................................... 58
7.8.1 Control on the discharge conveyor with fan (pneumatic suction
conveying system) ......................................................................... 58
7.8.2 Screw metering (TCON.FEED = SCREW) .................................. 63
7.9 Resetting parameters to factory settings ..................................................... 63
8 Parameters 64
8.1 Notes on the parameter details .................................................................... 64
Bühler AG
MEAG-DFCQ-66802-12-1-1908-en-US
Table of contents 3
8.2 Application parameters ................................................................................. 64
8.2.1 USER (operating parameters) parameter group .......................... 64
8.2.2 MAN (manual operation) parameter group .................................. 66
8.2.3 TCON (configuration parameters) parameter group .................... 70
8.2.4 SYS (system configuration) parameter group .............................. 80
8.2.5 ADC (Analog/Digital Converter) parameter group ....................... 87
8.2.6 ADCT (Analog/Digital Converter Temperature) parameter group 90
8.2.7 1317 (CAN module EBD 1317) parameter group ....................... 91
8.2.8 CTRL (controller configuration) parameter group ........................ 93
8.2.9 PBDP (Profibus DP) parameter group ......................................... 94
8.2.10 ENET (Ethernet) parameter group ............................................... 97
8.2.11 TCP (Ethernet TCP/IP) parameter group ..................................... 100
8.2.12 SERV (service information) parameter group .............................. 102
11 Appendix 127
11.1 CAN expansion modules .............................................................................. 127
11.1.1 Types ............................................................................................. 127
11.1.2 Connection ..................................................................................... 127
11.1.3 LED display ................................................................................... 128
11.2 Remote control .............................................................................................. 129
11.2.1 Installation version ......................................................................... 129
11.2.2 Table or wall version ..................................................................... 130
11.2.3 Connect to MDDR main circuit board SIO_0 .............................. 131
Bühler AG
MEAG-DFCQ-66802-12-1-1908-en-US
4 Table of contents
1 Important information
1.1 Availability of the instructions
These instructions constitute part of the product.
► Retain the instructions and other applicable documents over the entire life-
time of the product and keep them at hand for reference.
► Pass on the instructions and other applicable documents to the each subse-
quent owner or operator of the product.
The documents for fieldbus and serial interface are written for the programmers.
The descriptions are therefore available only on request and only in German or
English.
x = Documentation version
1.3 Contact
► If you have any questions, please contact the nearest branch of the Bühler
Group. See www.buhlergroup.com.
► Keep the instructions handy.
► Keep the machine number handy.
Bühler AG
MEAG-DFCQ-66802-12-1-1908-en-US
Chapter 1 Important information 5
1.5 Presentation conventions
1.5.1 Explanation of warning messages
DANGER
Nature and source of the danger.
The danger will result in death or severe injuries.
► Measures to protect against the danger.
WARNING
Nature and source of the danger.
The danger may result in death or severe injury.
► Measures to protect against the danger.
CAUTION
Nature and source of the danger.
The danger may result in injuries.
► Measures to protect against the danger.
CAUTION
Nature and source of the danger.
The danger may result in property damage.
► Measures to protect against property damage.
Bühler AG
MEAG-DFCQ-66802-12-1-1908-en-US
6 Chapter 1 Important information
2 Safety
2.1 Part of the operating instructions
These instructions are an integral part of the respective operating instructions.
Lack of knowledge of the operating instructions may lead to the risk of malfunc-
tions or impairments of the product.
► Only charge qualified personnel with tasks described in these operating in-
structions.
► Ensure that personnel comply with the local laws and regulations in order to
work safely, keeping the dangers in mind.
► Define and communicate work responsibilities. Provide keys and passwords
to designated staff only.
Bühler AG
MEAG-DFCQ-66802-12-1-1908-en-US
Chapter 2 Safety 7
3 Technical data
3.1 Housing
Throughput control
3.2 Display
Designation Value Unit
Height 300 mm
Width 210 mm
Depth 80 mm
Bühler AG
MEAG-DFCQ-66802-12-1-1908-en-US
8 Chapter 3 Technical data
Power supply for throughput control
24 V inputs (8/14)
24 V outputs (8/20)
3.5 Interfaces
■ Profibus-DP: Profibus-slave, 9-pin D-sub socket
■ USB: USB device interface for service
■ CAN: CAN interface for expansion modules
■ RJ-45 socket: Profinet, EtherNet/IP, Ethernet TCP/IP (optional)
3.6 Miscellaneous
■ Flash memory for program and data logger
■ Battery-powered RAM for parameters: Data protection for at least 20 years
■ Noise emission (emission): EN 50081-1 class B complied with
■ Noise immunity (immunity): EN 50082-2 industrial sector complied with
Bühler AG
MEAG-DFCQ-66802-12-1-1908-en-US
Chapter 3 Technical data 9
3.7 Design versions
■ Control system for hammer mill including throughput control (device type
DFZK)
■ Throughput control (device type FCM)
□ Installation version 24 V for assembling the cabinet
□ Compact device 24 V or 100 … 240 V AC
Bühler AG
MEAG-DFCQ-66802-12-1-1908-en-US
10 Chapter 3 Technical data
4 Description
4.1 Nameplate
■ Vertical hammer mill with 1 (DFZK-1) or 2 (DFZK-2) mills and one feeder
(DFAV).
■ As throughput control (FCM = Flow Control Mode) for other vertical hammer
mills. The capacity of the mill is controlled by adjusting the feed roller and
feed gap of the feeder.
The control system controls and monitors the grinding process of vertical ham-
mer mills and hammer mills. Depending on the application, the control system
performs the following functions. See page 70, parameter “TCON.DFCQ”.
Bühler AG
MEAG-DFCQ-66802-12-1-1908-en-US
Chapter 4 Description 11
Function Vertical hammer Throughput adjust-
mill DFZK er FCM
Determining the direction of rota- X -
tion of the motors, depending on
the operating hours.
Starting, stopping and braking the X -
motors.
Switching off the motors after idle X -
times of the mill.
Generating alarms to monitor the X X
operating state.
Communication with the control X X
system via fieldbus.
Measuring and evaluating the X X
grinding chamber temperature (op-
tion).
Measuring and evaluating the ma- X X
chine vibrations (option).
Controlling the automatic gravity X -
flow diverter for DFZK-2 (option).
Bühler AG
MEAG-DFCQ-66802-12-1-1908-en-US
12 Chapter 4 Description
Fig. 4.2 DFZK-1
(1) Product probe upper surge (9) Segment slide gate linear actuator
hopper
(2) Electric motor fan (10) Heavy particle flap linear actuator
(3) Back-up probe (11) Magnetic door limit switch
(4) Main motor (12) Zero-speed detector
(5) Cone linear actuators (13) Temperature sensor grinding cham-
ber (optional)
(6) Product probe discharge (14) Vibration monitor (optional)
(7) Electric motor discharge (15) Back-up safety device
(8) Gearmotor
Bühler AG
MEAG-DFCQ-66802-12-1-1908-en-US
Chapter 4 Description 13
Fig. 4.3 DFZK-2
(1) Product probe upper surge (9) Gearmotor
hopper
(2) Electric motor fan (10) Segment slide gate linear actuator
(2×)
(3) Back-up probe (11) Heavy particle flap linear actuator
(4) Gravity flow diverter linear (12) Magnetic door limit switch
actuator
(5) Main motor (2×) (13) Zero-speed detector (2×)
(6) Cone linear actuators (2×) (14) Temperature sensor grinding cham-
ber (2× optional)
(7) Product probe discharge (2×) (15) Vibration monitor (2× optional)
(8) Electric motor discharge (16) Back-up safety device
Bühler AG
MEAG-DFCQ-66802-12-1-1908-en-US
14 Chapter 4 Description
4.2.1 Throughput control
The throughput control FCM only covers the basic function of the DFAV, DFZC
and DFZP feeders. The feed roller and feed gap are adjusted by means of the
measured motor current in order to regulate the capacity of the hammer mill.
No additional sensors are measured and no motors can be switched on or off
either.
A
+C5
D B
C
DFCQ
+C3
DFCQ
Start
With two hammer mills, the second main motor first starts after the delay
TCON.T6. A current transformer measures the present motor output. The "mo-
tor is turning" signal thereby occurs. If there is no current, an error message is
displayed and the mill stops.
Bühler AG
MEAG-DFCQ-66802-12-1-1908-en-US
Chapter 4 Description 15
When the time TCON.T6 has elapsed, the air-circulating fan starts on the feed-
er (DFAV). See page 79, parameter “TCON.T6”. The motor contactor of the
fan sends an acknowledgement signal to the control system (DFCQ) as confir-
mation that the fan is running. If there is no signal, an error message is output
and the feeder does not start.
Stop
The mill should not be operated longer than 15 minutes without any product
since the air circulation can cause overheating. The mill is stopped by deactiva-
tion of the 24 V start command. The air-circulating fan switches off first, fol-
lowed by the main motor. With two mills (DFZK-2), both main motors switch off
at short intervals.
If the mill runs without any product (no load), the mill switches off automatically
after the time TCON.T3 has elapsed. See page 79, parameter “TCON.T3”.
After an automatic stop, the mill restarts automatically when the following condi-
tions are met:
If the mill is stopped during the dosing process, the discharge time TCON.T1 ex-
pires first. See page 78, parameter “TCON.T1”.. This ensures that no product
is left behind in the grinding chamber and the mill can restart automatically. If
product is left behind in the grinding chamber, the main motor cannot start. The
product must be removed manually.
It takes approx. 10 ... 15 minutes for the mill to slow down to standstill. This
time can be reduced, for example, for changing sieves. The motor can be
slowed down with the "activate brake" signal. As a result, the motor is control-
led for the time TCON.T2.x with reversed direction of rotation. See page 78,
parameter “TCON.T1”. The motor is thereby slowed down and the run-down
time minimized to approx. 1 minute.
4.2.3 Dosing
Dosing release
When all motors are turning, the control system requires a second 24 V signal
for dosing release. This signal releases the feeder (DFAV).
The release takes place when the following conditions are met:
Bühler AG
MEAG-DFCQ-66802-12-1-1908-en-US
16 Chapter 4 Description
Starting
A set point specified in percent is used for regulation. The set point corre-
sponds to 100 % of the rated power of the main motor.
The control system regulates the optimum utilisation of the main motor by
means of the segment slide gate gap and the speed of the feed roller. If two
mills (DFZK-2) are present, the two segment slide gate settings are corrected
until the power consumption of both mills is distributed evenly.
Stopping
The control system remains in this state until all conditions have been met for a
restart.
The heavy particle flap can only be opened when the feeder is not active. The
feeder cannot be started while opening and closing the heavy particle flap.
When opening the heavy particle flap, the linear cylinder retracts. When closing
the heavy particle flap, the linear cylinder extends.
The outlet cone can only be opened or closed when the rotor is not moving.
The two linear cylinders never travel at exactly the same speed for produc-
tion-related reasons. Therefore, the position of both cylinders is measured by
means of a pulse counter. If the position difference of both cylinders is too
great, the position is adjusted by slowing down the faster cylinder momentarily.
4.2.6 Discharge
When the main motor is running, the “Start discharge” signal is displayed. The
discharge conveyor must acknowledge that it is running by means of a re-
sponse. If the discharge conveyor does not return this message within 10 sec-
onds, the main motor stops. If there is no response from the discharge convey-
or, the response signal must be wired to the start signal. After the main motor
has stopped, the “Start discharge” signal first switches off after an overrun time
of 60 seconds. Additionally, capacity monitoring of the discharge conveyor can
be activated with the parameter TCON.TRANS. See page 76, parameter
“TCON.TRANS”.
Bühler AG
MEAG-DFCQ-66802-12-1-1908-en-US
Chapter 4 Description 17
4.2.7 Gravity flow diverter (option)
The gravity flow diverter is used for selecting the mill when two mills are pres-
ent. It is activated with the dosing release. When the dosing release is present
for both mills, the middle position is approached. The position is preset with the
parameter TCON.FLMID. In this position the product is guided to both mills. If
the dosing release is only present for one mill, the gravity flow diverter changes
the position automatically and guides the product to the active mill only.
If the parameter “TCON.FLAP” is set to OFF, then the gravity flow diverter is
not adjusted automatically and remains in the current position.
There is a vibration sensor on the machine stand. This measures the vibrations
within the range of 0 … 64 mm/s. Two vibration limits can be set with the pa-
rameters TCON.VIB_W and TCON.VIB_A. See page 78, parameter
“TCON.VIB_W”. If the value TCON.VIB_W is exceeded for the programmable
time TCON.T VIB, a warning is displayed. See page 78, parameter
“TCON.T VIB”. The machine only stops when the value TCON.VIB_A is exceed-
ed for the time TCON.T VIB. See page 78, parameter “TCON.VIB_A”. The
present vibration value is displayed on the control system as a percentage of
the programmed limit, i.e. 100% corresponds to TCON.VIB_A.
The following process data, among other things, can be displayed on the proc-
ess control system:
If the Profibus is used, then set the parameter “SYS.REM” to REMP. Deactivate
the 24 V inputs “release main motor” and “release dosing” in this case
(“SYS.EIN” = OFF).
Bühler AG
MEAG-DFCQ-66802-12-1-1908-en-US
18 Chapter 4 Description
The following process data, among other things, can be displayed on the proc-
ess control system:
The circuit board Profinet - Ethernet fieldbus EBD 1326 (EKP-85388-810) is re-
quired. If Profinet is used, then set the parameter “SYS.REM” to REME and
“SYS.ENET” to P-NET.
The following process data, among other things, can be displayed on the proc-
ess control system:
Bühler AG
MEAG-DFCQ-66802-12-1-1908-en-US
Chapter 4 Description 19
4.3 Time charts
4.3.1 Standard sequence
DO 0.13 Fan
Dosing start
The correct start and stop sequence is always executed in the case of a simul-
taneous start and release signal. The feeder starts when the motors are turn-
ing. The main motors first deactivate after the idle time TCON.T1 has elapsed.
All of the product is thereby discharged from the mill.
DO 0.13 Fan
Dosing start
Bühler AG
MEAG-DFCQ-66802-12-1-1908-en-US
20 Chapter 4 Description
4.3.3 Timeout
The mill stops after the timeout TCON.T3 elapses in the following cases
This protects the cone from overheating. The mill starts automatically when
there is product in the inlet again.
DO 0.13 Fan
Dosing start
Bühler AG
MEAG-DFCQ-66802-12-1-1908-en-US
Chapter 4 Description 21
5 Connection
5.1 Overview
5.1.1 Hammer mill control
1 2
(1) Main circuit board EBD 1311 (3) Display circuit board EBD 1316
(2) Frequency converter of the (4) Power section depending on de-
feed roller sign version (a star-delta start here)
Bühler AG
MEAG-DFCQ-66802-12-1-1908-en-US
22 Chapter 5 Connection
5.1.2 Throughput control
1 2
Bühler AG
MEAG-DFCQ-66802-12-1-1908-en-US
Chapter 5 Connection 23
5.2 Main circuit board EBD 1311
Bühler AG
MEAG-DFCQ-66802-12-1-1908-en-US
24 Chapter 5 Connection
5.2.1 Jumpers EBD 1311
1 6 Pullup
2 5 Term
3 4 X71
Pulldown
B B
X81
A A
X41 B B
X60 X62 A A
V V V V
A A A A X70
X61 X63
X80
V V V V Pullup 1 6
A A A A Term 2 5
Pulldown 3 4
Fig. 5.2
X1 Pole Function
1 1 +24 V
2 0 V
2
3 PE
3
Switching with the X70 (left and right) and X71 (left) jumpers between Profibus
DP and RS-485 SIO_2:
■ B = Profibus DP
■ A = RS-485 SIO_2
Bühler AG
MEAG-DFCQ-66802-12-1-1908-en-US
Chapter 5 Connection 25
5
9
4
8
3
7
2
6
1
X Signal Description
X40:3 RS485_B Profibus-DP / RS-485 SIO_2, positive signal
X40:4 RTS Profibus DP standard
X40:5 0 V_EX Profibus DP standard
X40:6 +5 V_EX Profibus DP standard
X40:8 RS485_A Profibus-DP / RS-485 SIO_2, negative signal
2 2 0 V
3 3 CAN H
4 4 CAN L
X Signal Description
X100:1 +24 V +24 V secondary voltage. Supplies CAN
module with voltage.
X100:2 0 V 0 V and shield connection
X100:3 CAN H CAN positive signal
X100:4 CAN L CAN negative signal
5.2.5 24 V inputs
Bühler AG
MEAG-DFCQ-66802-12-1-1908-en-US
26 Chapter 5 Connection
X20/X21/X22 Terminal Function Function Function
X20 X21 X22
1 1 +24 V_IO +24 V_IO +24 V_IO
DI X3 Signal Description
0.0 X3:2 Emergency stop 24 V = operating status
for plant 0 V = plant is in emergency stop.
0.1 X3:3 Activate brake 24 V = when switching off the motors, the sig-
nal is checked. If it is active, the motors are
stopped with reverse current brake.
0.2 X3:6 Acknowledge 24 V = Impending, acknowledgeable alarms
alarm are deleted with the positive flank when the
alarm condition is no longer active.
0.3 X3:7 Not used -
Bühler AG
MEAG-DFCQ-66802-12-1-1908-en-US
Chapter 5 Connection 27
DI X12 Signal Description
0.12 X12:2 Fan is running 24 V = response that fan is running.
X12:3 See digital outputs.
0.14 X12:6 Discharge 1 run- 24 V = response that discharge conveyor of
ning mill 1 is running. If no discharge is present,
provide a jumper to 24 V at the input.
X12:7 See digital outputs.
Bühler AG
MEAG-DFCQ-66802-12-1-1908-en-US
28 Chapter 5 Connection
5.2.6 24 V outputs
D0 X2 Signal Description
0.0 X2:1 Alarm mill 1 0 V = alarm, if SYS.AINV = ON
0.1 X2:2 Alarm mill 2 0 V = alarm, if SYS.AINV = ON
0.2 X2:3 Set point of 24 V-pulse signal 0 … 1 KHz
feed roller Set point for frequency converter.
1 kHz = 100 Hz on the gearmotor
Idle state = motor stopped = 24 V
0.3 X2:4 Not used -
Bühler AG
MEAG-DFCQ-66802-12-1-1908-en-US
Chapter 5 Connection 29
Outputs 24 V on input plugs
2 2 - - - -
3 3 - - - DO_0.13
4 4 GND GND GND GND
5 5 +24 V_IO +24 V_IO +24 V_IO +24 V_IO
6 6 - - - -
7 7 - - - DO_0.15
8 8 GND GND GND GND
2 2 - - -
3 3 - - DO_0.25
4 4 GND GND GND
5 5 +24 V_IO +24 V_IO +24 V_IO
6 6 - - -
7 7 - - DO_0.27
8 8 GND GND GND
Bühler AG
MEAG-DFCQ-66802-12-1-1908-en-US
30 Chapter 5 Connection
5.2.7 0 … 5 V or 0/4 … 20 mA analog inputs
2 2 + AI_0.1 + AI_0.5
3 3 + AI_0.2 + AI_0.6
4 4 + AI_0.3 + AI_0.7
5 5 +5 V +5 V
6 6 GND GND
7 7 GND GND
X4 Terminal Function
1 1 + AO_0.0
2 2 GND
3 3 + AO_0.1
4 4 GND
5 5 GND
Bühler AG
MEAG-DFCQ-66802-12-1-1908-en-US
Chapter 5 Connection 31
The function of the analog outputs depends on the configuration of the control
system.
AO X4 Signal Description
TCON.MILL = 1 (DFZK-1) TCON.MILL = 2 (DFZK-2)
0.0 X4:1 + 0/4 … 20 mA Setpoint of feed roller Dependent on TCON.AOUT
X4:2 - 20 mA = 100 Hz - ACTV actual output of mill 1
- SETV setpoint of the feed roller
for mill 1 and 2
- MOTF setpoint or actual speed
of main motor 1
0.1 X4:3 + 0/4 … 20 mA Actual output of the mill Dependent on TCON.AOUT
X4:4 - 20 mA = ADC.AOMAX - ACTV actual output of mill 2
or - SETV setpoint of the feed roller
Target speed of main motor for mill 2 (currently not used)
20 mA = 60 Hz - MOTF setpoint or actual speed
if (TCON.MOTOR = FC or of the main motor mill 2
BR FC)
and “TCON.MOTCAN” = “OFF”
The digital IO module EBD 1318 is used for the input and output of digital sig-
nals. The module has 12 configurable IOs. The application software defines
whether an IO is operated as input or output.
1 1 1
H100 H104 H108
2 2 2
CAN
H101 H105 H109
3 3 3
1
4 4 4
2
5 5 5
3
H102 H106 H110 H150
6 6 6 4
H103 H107 H111
7 7 7 X100
8 8 8 ON ON
OFF OFF
X101 X102 X103 1 2
X99
Out 0… 3
Out 4… 7 EBD1318 3 4
Out 8…11
X112 S100
X99 OFF = bus termination deactivated. All modules except the last module
on the bus.
ON = bus termination activated. Last module on the bus.
X112 ON = outputs are fed from modules (default setting).
Bühler AG
MEAG-DFCQ-66802-12-1-1908-en-US
32 Chapter 5 Connection
5.3.3 Digital IO expansion module 1
Dx X Signal Description
1.0 X101:2 Close cone switch 24 V = close cone.
1.1 X101:3 Machine stop button 24 V = machine controls stopping (no
emergency stop).
1.2 X101:6 Cone pulse signal 24 V pulse signal = counting pulse for
right measuring position of the cone.
1.3 X101:7 Zero-speed detector 24 V = main motor is stationary.
1.4 X102:2 Cone closed 24 V = the cone is closed.
1.5 X102:3 Cone full level 24 V = level probe is uncovered (operat-
ing status).
0 V = level probe is covered (alarm sta-
tus).
1.6 X102:6 Cone pulse signal 24 V pulse signal = counting pulse for
left measuring position of the cone.
1.7 X102:7 Heavy particle flap 24 V = manually open heavy particle flap.
button
1.8 X103:2 Open cone switch 24 V = open cone.
1.9 X103:3 Move cone to the 24 V = move linear cylinder to the right of
right the cone.
1.10 X103:6 Move cone to the 24 V = move linear cylinder to the left of
left the cone.
1.11 X103:7 Move cone lamp Lamp of the move cone button.
Lamp is lit when main motor is stationary.
Cone can be opened.
Lamp flashes slowly when a sieve change
has been requested.
Lamp flashes rapidly when the cone is
locked.
Bühler AG
MEAG-DFCQ-66802-12-1-1908-en-US
Chapter 5 Connection 33
5.3.4 Digital IO expansion module 2
Dx X Signal Description
2.0 X101:2 Close cone switch 24 V = close cone.
2.1 X101:3 Machine stop button 24 V = machine controls stopping (no
emergency stop).
2.2 X101:6 Cone pulse signal 24 V pulse signal = counting pulse for
right measuring position of the cone.
2.3 X101:7 Zero-speed detector 24 V = main motor is stationary.
2.4 X102:2 Cone closed 24 V = the cone is closed.
2.5 X102:3 Cone full level 24 V = level probe is uncovered (operat-
ing status).
0 V = level probe is covered (alarm sta-
tus).
2.6 X102:6 Cone pulse signal 24 V pulse signal = counting pulse for
left measuring position of the cone.
2.7 X102:7 Heavy particle flap 24 V = manually open heavy particle flap.
button
2.8 X103:2 Open cone switch 24 V = open cone.
2.9 X103:3 Move cone to the 24 V = move linear cylinder to the right of
right the cone.
2.10 X103:6 Move cone to the 24 V = move linear cylinder to the left of
left the cone.
2.11 X103:7 Move cone lamp Lamp of the move cone button.
Lamp is lit when main motor is stationary.
Cone can be opened.
Lamp flashes slowly when a sieve change
has been requested.
Lamp flashes rapidly when the cone is
locked.
Bühler AG
MEAG-DFCQ-66802-12-1-1908-en-US
34 Chapter 5 Connection
5.3.5 Digital IO expansion module 5
Dx X Signal Description
5.0 X101:2 Upper surge hop- 24 V = upper surge hopper level probe is
per low level covered (operating status).
0 V = upper surge hopper level probe is un-
covered (alarm status).
5.1 X101:3 DFAV full level 24 V = DFAV level probe is uncovered (op-
erating status).
0 V = level probe is covered (alarm status).
5.2 X101:6 Magnetic door 24 V = magnetic door is closed.
5.3 X101:7 Not used -
5.4 X102:2 Segment slide 24 V pulse signal = counting pulse for
gate pulse measuring position of the segment slide
gate.
5.5 X102:3 Segment slide 24 V = segment slide gate is open or
gate limit switch closed at limit position.
5.6 X102:6 Open segment 24 V = segment slide gate is opened.
slide gate
5.7 X102:7 Close segment 24 V = segment slide gate is closed.
slide gate
5.8 X103:2 Heavy particle 24 V pulse signal = counting pulse for
flap pulse measuring position of the heavy particle flap.
5.9 X103:3 Heavy particle 24 V = heavy particle flap is open or closed
flap limit switch at limit position.
5.10 X103:6 Open heavy parti- 24 V = heavy particle flap is opened.
cle flap
5.11 X103:7 Close heavy parti- 24 V = heavy particle flap is closed.
cle flap
Bühler AG
MEAG-DFCQ-66802-12-1-1908-en-US
Chapter 5 Connection 35
Installed in: terminal box DFAV-1/2.
Dx X Signal Description
6.0 X101:2 Not used -
6.1 X101:3 Not used -
6.2 X101:6 Not used -
6.3 X101:7 Not used -
6.4 X102:2 Segment gate pulse 24 V pulse signal = counting pulse for
measuring position of the segment gate.
6.5 X102:3 Segment gate limit 24 V = segment gate is open or closed
switch at limit position.
6.6 X102:6 Opening segment 24 V = segment gate is opened.
gate
6.7 X102:7 Closing segment 24 V = segment gate is closed.
gate
6.8 X103:2 Gravity flow diverter 24 V pulse signal = counting pulse for
pulse signal measuring position of the gravity flow
diverter.
6.9 X103:3 Gravity flow diverter 24 V = Gravity flow diverter is at limit po-
limit switch sition mill 1 or mill 2.
6.10 X103:6 Gravity flow diverter 24 V = Move the gravity flow diverter in
of mill 2 the direction of mill 2.
6.11 X103:7 Gravity flow diverter 24 V = Move the gravity flow diverter in
of mill 1 the direction of mill 1.
Bühler AG
MEAG-DFCQ-66802-12-1-1908-en-US
36 Chapter 5 Connection
5.3.7 Analog IO module EBD 1317
The CAN analog module EBD 1317 is used for the temperature monitoring or vi-
bration monitoring options. On the module is a temperature sensor that meas-
ures the current ambient temperature.
1 1 R 0 EBD 1317
V X290
AI0 2 AI4 2 A
Bühler AG
MEAG-DFCQ-66802-12-1-1908-en-US
Chapter 5 Connection 37
5.3.9 Analog IO expansion module 1
4 4 0 V 0 V 0 V 0 V
X Signal Description
X210:1 +OUT 5 V or 24 V output voltage. Setting via jumper X280 (0/1).
X210:2 AI 1.0 Temperature sensor of mill 1 (PT100, PT1000)
X210:3 AI 1.1 PTC main motor mill 1
X210:4 0 V shield 0 V and shield connection
Set the function of the input at the parameter EBD 1317.AI1.x. Use shielded ca-
bles. Connect shield to electric terminal 4.
4 4 0 V 0 V 0 V 0 V
Bühler AG
MEAG-DFCQ-66802-12-1-1908-en-US
38 Chapter 5 Connection
X Signal Description
X210:1 +OUT 5 V or 24 V output voltage. Setting via jumper X280 (0/1).
X210:2 AI 1.0 Temperature sensor of mill 2 (PT100, PT1000)
X210:3 AI 1.1 PTC main motor mill 2
X210:4 0 V shield 0 V and shield connection
Set the function of the input at the parameter EBD 1317.AI1.x. Use shielded ca-
bles. Connect shield to electric terminal 4.
X54
X53
Bühler AG
MEAG-DFCQ-66802-12-1-1908-en-US
Chapter 5 Connection 39
5.4.2 Description of electric terminals X50
2 2 0 V_Line 0 V
Bühler AG
MEAG-DFCQ-66802-12-1-1908-en-US
40 Chapter 5 Connection
5.5 Wiring of vertical hammer mill control DFZK
EBD 1317
X10:1 24V
X100 addr.1
A
optional
X10:2 DI 0.4
EBD 1318
B addr.2
X100
X10:3 DI 0.5
X20:1 24V
A
X20:2 DI 0.16
B DFAV +J1
X3AE:1 24V X3AE:1
X20:3 DI 0.17
X3AE:2 GND X3AE:2 EBD 1318
X3AE:3 CAN H X3AE:3 addr.5
X100
X3AE:4 CAN L X3AE:4
X14:1 AI 0.0 +
C EBD 1318
X14:6 0V
X100 addr.6
X14:7 Shield
X14:4 AI 0.3 +
D
X14:6 0V
X14:7 Shield
C X24:1 AI 0.4 +
X24:6 0V
X24:7 Shield
D X24:4 AI 0.7 +
X24:6 0V
X24:7 Shield
X4:3 AO 0.1 +
X4:4 0V E
X4:5 Shield
X2:1 DO 0.0 F
X2:6 0V
Remote X12:7 DO 0.15
X30 G
Display X12:8 0V
X2:2 DO 0.1
X2:6 0V F
Profibus X40 X22:7 DO 0.27
G
X22:8 0V
DFZK-2
Bühler AG
MEAG-DFCQ-66802-12-1-1908-en-US
Chapter 5 Connection 41
Abbre- Description
viation
A Start signal for dosing. This signal is not required while starting via
fieldbus (SYS.EIN).
B Start signal of the main motors. This signal is not required while
starting via fieldbus (SYS.EIN).
C Motor current or motor torque.
0/4 … 20 mA
D Analog setpoint specified for the mill power 0/4 to 20 mA. Is read on-
ly when SYS.REM = REMA.
E Analog actual value output of the mill.
0/4 … 20 mA
F Alarm output.
Function can be inverted via parameter SYS.AINV.
G Digital output of mill is in operation.
24 V = mill is running
Bühler AG
MEAG-DFCQ-66802-12-1-1908-en-US
42 Chapter 5 Connection
5.6 Wiring of throughput adjuster (only main circuit board)
L1 EBD 1311
100...240V AC PE
N
X1:1 +24V
24 V DC RD
X1:2 0V X13:1 DO 0.4 FORWARD
X13:2 DO 0.5 OR BACKWARD
X13:5 0V BK -24V
X10:1 24V
A BN E
X11:1 24V +24V
VT PULSES
X10:2 DI 0.4 X11:2 DI 0.8
X11:3 DI 0.9 GN ENDSTOP IN
YE ENDSTOP OUT
X20:1 24V
A
X20:2 DI 0.16 RD
X13:3 DO 0.6 FORWARD
X13:4 DO 0.7 OR BACKWARD
X13:6 0V BK
-24V
BN E
X21:1 24V +24V
X14:1 AI 0.0 + X21:2 DI 0.20 VT PULSES
B GN
X14:6 0V X21:3 DI 0.21 ENDSTOP IN
YE ENDSTOP OUT
X14:7 Shield
C X14:4 AI 0.3 +
X14:6 0V
X14:7 Shield
X2:3 DO 0.2 F
X2:6 0V
X24:1 AI 0.4 +
B X24:6 0V
X24:7 Shield
X4:1 AO 0.0 +
X4:2 0V G
X24:4 AI 0.7 + X4:5 Shield
C
X24:6 0V
X24:7 Shield X4:3 AO 0.1 +
X4:4 0V H
X4:5 Shield
X11:5 24V
X2:1 DO 0.0 I
D X2:5 0V
X11:7 DI 0.11
X12:7 DO 0.15
X12:8 0V J
Abbre- Description
viation
A Start signal for dosing. This signal is not required while starting via
fieldbus (SYS.EIN).
B Motor current or motor torque.
0/4 … 20 mA.
C Analog setpoint specified for the mill power 0/4 to 20 mA. Is read on-
ly when SYS.REM = REMA.
D Digital input for frequency converter error.
0 V = feed roller error.
E Linear cylinder for adjustment of the feed gap.
F Frequency converter setpoint of the feed roller (for Altivar ATV 31,
ATV 312 and ATV 320).
Pulse signal 0 … 1 kHz → 0 … 100 Hz.
G Frequency converter setpoint of the feed roller.
0/4 … 20 mA → 0 … 100 Hz.
Bühler AG
MEAG-DFCQ-66802-12-1-1908-en-US
Chapter 5 Connection 43
Abbre- Description
viation
H Analog actual value output of the mill.
0/4 … 20 mA = 0 … ADC.AOMAX
I Alarm output.
Function can be inverted via parameter SYS.AINV.
J Digital output of mill is in operation.
24 V = mill is running.
Bühler AG
MEAG-DFCQ-66802-12-1-1908-en-US
44 Chapter 5 Connection
5.7 Wiring of throughput adjuster (with CAN modules)
CAN EBD 1318
L1 EBD 1311 X100 Adr.5
100...240V AC X100
PE
N X102:6 DO 5.6 RD
FORWARD
X102:7 DO 5.7 OR
X1:1 +24V BACKWARD
24 V DC X102:8 0V BK -24DC
X1:2 0V
BN E
X102:1 24V +24DC
X10:1 24V X102:2 DI 5.4 VT
PULSES
X102:3 DI 5.5 GN
A ENDSTOP IN
YE
ENDSTOP OUT
X10:2 DI 0.4
X20:1 24V
EBD 1318
A X100 Adr.6
X20:2 DI 0.16 LINAK2
X102:6 DO 6.6 RD
FORWARD
X102:7 DO 6.7 OR
BACKWARD
X102:8 0V BK -24DC E
X102:1 24V BN
X14:1 AI 0.0 + +24DC
B X102:2 DI 6.4 VT
X14:6 0V PULSES
X102:3 DI 6.5 GN
ENDSTOP IN
X14:7 Shield YE
ENDSTOP OUT
X24:1 AI 0.4 +
B X24:6 0V X210:3 AI 1.1 F
X24:7 Shield X210:4 Shield
X2:3 DO 0.2 H
X11:5 24V X2:6 0V
D
X11:7 DI 0.11 X4:1 AO 0.0 +
X4:2 0V I
X4:5 Shield
X4:3 AO 0.1 +
X4:4 0V J
X4:5 Shield
X2:1 DO 0.0
X2:5 0V K
Profibus X40
X12:7 DO 0.15
X12:8 0V L
Abbre- Description
viation
A Start signal for dosing. This signal is not required while starting via
fieldbus (SYS.EIN).
B Motor current or motor torque.
0/4 … 20 mA.
C Analog setpoint specified for the mill power 0/4 to 20 mA. Is read on-
ly when SYS.REM = REMA.
Bühler AG
MEAG-DFCQ-66802-12-1-1908-en-US
Chapter 5 Connection 45
Abbre- Description
viation
D Digital input for frequency converter error.
0 V = feed roller error.
E Linear cylinder for adjustment of the feed gap.
F PT-100 temperature probes for monitoring grinding chamber tempera-
ture (optional).
G Vibration sensors (optional).
0/4 … 20 mA → 0.0 … 64 mm/s.
H Frequency converter setpoint of the feed roller (for Altivar ATV 31,
ATV 312 and ATV 320).
Pulse signal 0 … 1 kHz → 0 … 100 Hz.
I Frequency converter setpoint of the feed roller.
0/4 … 20 mA → 0 … 100 Hz.
J Analog actual value output of the mill.
0/4 … 20 mA = 0 … ADC.AOMAX
K Alarm output.
Function can be inverted via parameter SYS.AINV.
L Digital output of mill is in operation.
24 V = mill is running.
Bühler AG
MEAG-DFCQ-66802-12-1-1908-en-US
46 Chapter 5 Connection
6 Operation
6.1 Keys and lamps
Bühler AG
MEAG-DFCQ-66802-12-1-1908-en-US
Chapter 6 Operation 47
6.2 Display operating elements
H1 H2 H3 H4 H5 H6
lb
kg
S1 S2 S3 S4 S5 S6 S7 S8
H1 Remote control
H2 Upper surge hopper product display
Lit = product present
H3 Not used
H4 Manual operation mode
Flashing = manual operation mode active
H5 Not used
H6 Capacity range
Flashing = overload; Lit = actual/target deviation ≤ 10 %
H7 Weight unit (lb)
H8 Weight unit (kg)
S1 <Start/Stop> key
LED flashes if stopped manually.
S2 <Empty> key
LED is lit when emptying is active.
S3 <Clear alarm> / <Lamp test> / <Cancel> key.
When flashing, alarm is pending.
S4 <Function> key with special function depending on parameter.
When lit, special function is available.
S5 <Arrow> key for changing the parameter group or position when editing.
S6 <Data input> key for changing or applying values.
S7 <Plus> key for selecting the next parameter or increasing a value.
S8 <Minus> key for selecting the previous parameter or decreasing a value.
Bühler AG
MEAG-DFCQ-66802-12-1-1908-en-US
48 Chapter 6 Operation
The following illustration shows the structure of the parameter groups. P1, P2
and P3 represent the individual parameters.
USER
S5
S5
+ > 1s
S6
S5 S5 S5 S5 S5
… … … … … …
The control is operated via the USER parameter group and the subordinate pa-
rameter groups such as MAIN, SYS etc.
By default, the control's display changes to the first parameter of the USER pa-
rameter group after 600 seconds without user input.
Function Description
Invoke subordinate parameter
Press and for 1 second.
group.
Change to the next subordinate pa-
Press .
rameter group.
Select parameters. + to the next parameter.
Bühler AG
MEAG-DFCQ-66802-12-1-1908-en-US
Chapter 6 Operation 49
7 Configuration
7.1 Setting the application
Select the desired application with the “SYS.TYP” parameter.
Prerequisites:
Important
As a rule, the application of the control has already been set in the factory.
► Execute the following procedure only if the application has been reset or
has not been set.
5. Press again.
→ The parameter value lights up. The application is selected.
→ The program restarts automatically.
Bühler AG
MEAG-DFCQ-66802-12-1-1908-en-US
50 Chapter 7 Configuration
7.3 Using the input wizard
Enter parameter values with the input wizard.
Important
This procedure is used to change important settings that as a rule were facto-
ry-set.
► Execute this procedure only if the most important parameters were not
configured at the factory or if the control is to be reset.
2. Press .
→ The message ASSIST ON lights up briefly. The input wizard is activated.
→
flashes.
Bühler AG
MEAG-DFCQ-66802-12-1-1908-en-US
Chapter 7 Configuration 51
3. Check settings for CAN module EBD 1317.
► Check settings of jumpers on the CAN module. Check setting for each
channel. The setting depends on the sensor type.
Important
► Adjust the other parameters of the frequency converter to the motor.
► Lock the frequency converter with motor contactor.
► Only release the frequency converter when the grinding motors are
switched on.
Bühler AG
MEAG-DFCQ-66802-12-1-1908-en-US
52 Chapter 7 Configuration
CONF (1.3 CONFIGURATION)
FULL (FULL)
SIM- (SIMPLY START)
Code Name/Description of the Parame- Setpoint
ter
BFR Standard mot. freq According to motor nameplate
NPR Rated motor power According to motor nameplate
UNS Rated motor volt. According to motor nameplate
NCR Rated mot. current According to motor nameplate
FRS Rated motor freq. According to motor nameplate
NSP Rated motor speed According to motor nameplate
TFR Max frequency 100.0 Hz
TUN Auto tuning YES and press key for 2 seconds.
ITH Mot. therm. current According to motor nameplate
ACC Acceleration 3.0 s
DEC Deceleration 0.1 s
LSP Low speed 0.0 Hz
HSP High speed 100.0 Hz
Bühler AG
MEAG-DFCQ-66802-12-1-1908-en-US
Chapter 7 Configuration 53
CONF (1.3 CONFIGURATION)
FULL (FULL)
FLT- (FAULT MANAGEMENT)
Code Name/Description of the Parameter Setpoint
ATR- (AUTOMATIC RESTART)
ATR Automatic restart YES and press key for 2 sec-
onds.
TAR Max. restart time CT (Unlimited)
Connection example:
0 = Alarm
0 - 1 kHz
0 - 100 Hz
PTC
Following table is applicable for cutter ATV 312/31 (Bühler special design
UXE-36072-080).
The parameters are already configured in the factory. With this design version,
it is not possible to make settings with the Telemecanique software “Power
Suite”.
Bühler AG
MEAG-DFCQ-66802-12-1-1908-en-US
54 Chapter 7 Configuration
MENU Param- Description Set Value
eters
SET DEC Deceleration ramp time 0.1 S
SET HSP High speed 100.0 Hz
SET ITH Motor thermal protection - max. ther- 1.3 A
mal current
SET JPF Skip frequency 1.0 Hz
SET JF2 2nd skip frequency 3.0 Hz
SET SP2 2nd preset speed 50 Hz
DRC BFR Standard motor frequency 50 Hz
DRC UNS Nominal motor voltage given on the According to motor
rating plate nameplate
DRC FRS Nominal motor frequency given on According to motor
the rating plate nameplate
DRC NCR Nominal motor current given on the According to motor
rating plate nameplate
DRC NSP Nominal motor speed given on the rat- According to motor
ing plate nameplate
DRC COS Motor Cos Phi given on the rating According to motor
plate nameplate
DRC UFT Selection of the type of voltage/ CONSTANT TOR-
frequency ratio QUE
DRC TFR Maximum output frequency 100.0 Hz
CTL FR1 Configuration reference 1 PULSE INPUT (PUL)
CTL FR2 Configuration reference 2 ANALOG INPUT AI3
FUN STC Normal stop mode FREEWHEEL STOP
FUN ADC Standstill DC injection NO DC INJECTION
FLT ATR Automatic restart YES
FLT TAR Max. duration of restart process UNLIMITED
FLT LET Configuration of external fault STATE 0
FLT DRN Derated operation in the event of an YES
under voltage
I O TCT Start mode PFO
Bühler AG
MEAG-DFCQ-66802-12-1-1908-en-US
Chapter 7 Configuration 55
The actual value output of the frequency converter must show the following
characteristics:
0,4…20 [mA]
Mains FC
Hammer mill
Motor for
hammer mill
Product discharge
Important
► If the motor is overloaded, the frequency converters will reduce the
speed. This will reduce the throughput and the mill can run even fuller.
► Maximum permissible frequency of hammer mill = 60 Hz.
Bühler AG
MEAG-DFCQ-66802-12-1-1908-en-US
56 Chapter 7 Configuration
7.7.1 Configuring the frequency converter cutter ATV 930 (example)
Fig. 7.1 Configuration menu for analog output AQ1 and AQ2
Example of motor torque at the analog output AQ1
The analog output AQ1 (4 … 20 mA) should display the current motor torque in
the range of 0 to 150% of the rated torque.
In order to display the motor current in amperes and the motor torque in % in
the upper strip of the graphic terminal screen, make the following setting in the
menu “8.4 Customization (CUS)”:
Bühler AG
MEAG-DFCQ-66802-12-1-1908-en-US
Chapter 7 Configuration 57
Important
The device’s earth connection is with a minus connection of the 0/4 to 20
[mA] signal. This can lead to problems with some frequency converters.
► Use an isolating transformer between the frequency converter and the
DFCQ.
2. After starting the mill, check the display on the control unit DFCQ
(USER.ACTUAL). The utilization display in % must match the display on the
frequency converter (± approx. 3%).
Important
The device’s earth connection is with a minus connection of the 0/4 to 20
[mA] signal. This can lead to problems with some frequency converters.
► Use an isolating transformer between the frequency converter and the
DFCQ.
2. After starting the mill, check the display on the control unit DFCQ
(USER.ACTUAL). The utilization display in % must match the display on the
frequency converter (± approx. 3%).
Bühler AG
MEAG-DFCQ-66802-12-1-1908-en-US
58 Chapter 7 Configuration
The motor load characteristics for the discharge conveyor with fan behave in
the opposite fashion to a discharge conveyor with a mechanical component.
The current transformer value (ADC.CON 1.2) should lie marginally over the
nominal current of the fan motor.
The load for the discharge conveyor with fan is calculated as shown in the
graphic below:
(USER.LOAD.1)[%]
Load control by current measurement of the fan motor (control with DOL
starting or soft starter)
1. Read the current of the fan motor on case of a “minimum load” (maximal
current) in parameter ADC.I 1.2. This takes place in case of a maximum air
volume and without product. Round up this read current value by 5% and
enter with a negative sign (–) for ADC.MOT 1.2. Example: Enter display
100 A → ADC.MOT 1.2 = –105 A (105% of 100 A).
2. Read the current of the fan motor for “maximum load” (minimum current) in
parameter ADC.I 1.2. This takes place in case of a minimum air volume and
with a high product throughput at which the hammer mill sieve slowly gets
clogged and the following discharge conveyor is disrupted. In order to simu-
late this state, place a board upstream the air inlet at the gravity separator
and place paper bags on the other air inlets. Enter this read current value
for ADC.I0 1.2.
3. After starting the fan, check the load on the control unit DFCQ
(USER.LOAD.1). Approx. 0% should be displayed in case of a maximum air
volume and without product.
Load control via the motor torque of the fan motor (control with frequency
converter):
The motor torque should be used for the control instead of the current while us-
ing a frequency converter. An analog output of the frequency converter is used
for the output of the motor torque. Thus the current transformer is omitted.
The following example for the configuration of the analog outputs is applicable
for the cutter ATV 930.
Bühler AG
MEAG-DFCQ-66802-12-1-1908-en-US
Chapter 7 Configuration 59
Fig. 7.2 Configuration menu for analog output AQ1 and AQ2
Example of motor torque at the analog output AQ1
The analog output AQ1 (4 … 20 mA) should display the current motor torque in
the range of 0 to 110% of the rated torque.
Bühler AG
MEAG-DFCQ-66802-12-1-1908-en-US
60 Chapter 7 Configuration
Important
The device’s earth connection is with a minus connection of the 0/4 to 20
[mA] signal. This can lead to problems with some frequency converters.
► Use an isolating transformer between the frequency converter and the
DFCQ.
2. After starting the fan, check the load on the control unit DFCQ
(USER.LOAD.1). Approx. 0% should be displayed in case of a maximum air
volume and without product.
A dynamic pressure probe is used for the air volume measurement, which re-
cords the difference between a static and dynamic pressure and is displayed in
Pa (Pascal) [N/m2] by means of a differential pressure transmitter. The square
rooted 4 to 20 mA output signal is forwarded to the control system. This means
that the output signal in mA is proportional to the root of the dynamic pressure
φ is a device-specific factor and also considers the air density, which can how-
ever vary depending on the static pressure and temperature. However, the pre-
vious parameters are neglected for this application. φ is calculated according to
the specifications of the manufacturer and is in the area of approx. 1.06 for De-
bimo measuring rods.
Bühler AG
MEAG-DFCQ-66802-12-1-1908-en-US
Chapter 7 Configuration 61
The sensor shows a differential pressure, i.e. the difference between in dynamic
pressure in Pa (Pascal) [N/m2]. This means that if a differential pressure of
600 Pa is displayed, then this corresponds to a numerical value of 24.49 m/s.
Assume φ is 1.06, then the air velocity is 1.06 × 24.49 = 25.96 m/s. If φ is not
known, or for control purposes, the air velocity can be measured with an ane-
To be able to calculate the air volume in m3/min, the air velocity is required in m/
s and the pipe cross section in m2.
Air volume [m3/min] = air velocity [m/s] × 60 s/min × pipe cross section [m2]
Note: In case of the air volume measurement, the current values displayed in
amperes in the DFCQ correspond with the air volume in m3/min.
2. Read the air volume of the fan motor in case of a “minimum load” (i.e. max-
imum air volume, no product in sieve or in the pneumatic suction conveying
system, the air flows freely) in parameter ADC.I 1.2 (current value is dis-
played). This takes place in case of a maximum air volume and without
product. Round up this read air volume by 5% and enter with a negative
sign (–) for ADC.MOT 1.2.
► Example: Enter display 100 A → ADC.MOT 1.2 = –105 A (105% of
100 A).
3. Read the air volume of the fan motor in case of a “maximum load” (mini-
mum air volume, i.e. sieve or pneumatic suction conveying system is about
to clog) in parameter ADC.I 1.2 (current value is displayed). This takes
place in case of a minimum air volume and with a high product throughput
at which the hammer mill sieve slowly gets clogged and the following dis-
charge conveyor is disrupted. In order to simulate this state, place a board
upstream the air inlet at the gravity separator and place paper bags on the
other air inlets. Enter this read air volume for ADC.I0 1.2.
4. After starting the fan, check the load on the control unit DFCQ
(USER.LOAD.1). Approx. 0% should be displayed in case of a maximum air
volume and without product.
Bühler AG
MEAG-DFCQ-66802-12-1-1908-en-US
62 Chapter 7 Configuration
7.8.2 Screw metering (TCON.FEED = SCREW)
The machine can be operated with a feed screw conveyor instead of a feeder
DFAV.
In this case, the digital IO expansion module 5 is omitted. The main circuit
board provides the control signals.
3. Connect the alarm feedback of the frequency converter to X11:7 (DI 0.11). If
not present, connect the input with a 24 V jumper.
4. Connect the level probe of the upper surge hopper to the X11:6 (DI 0.10). If
not present, connect the input with a 24 V jumper.
CAUTION
All set values are overwritten.
► Re-enter all the parameters that are different from the factory setting.
Bühler AG
MEAG-DFCQ-66802-12-1-1908-en-US
Chapter 7 Configuration 63
8 Parameters
8.1 Notes on the parameter details
The letter after “Step” indicates to what extent the corresponding parameter is
locked for the modification when the input lock is activated. The following
values apply:
Step Description
No information. Parameters can always be adjusted.
L Parameter can be adjusted if LOCK parameter = OFF.
Locked if LOCK parameter = LOW/MED/HIGH.
M Parameter can be adjusted if LOCK parameter = OFF/LOW.
Locked if LOCK parameter = MED/HIGH.
H Parameter can be adjusted if LOCK parameter = OFF/LOW/MED.
Locked if LOCK parameter = HIGH.
The input lock is set with the “SYS.LOCK” parameter. It is deactivated by de-
fault.
The value of the “parameter number” stands for the parameter that is displayed
after a certain time if no button is pressed during this time. It is set in the
“SYS.SD” parameter.
If the SD parameter has the value 1, for example, the parameter of the USER
parameter group whose parameter number has the value 1 is used.
Bühler AG
MEAG-DFCQ-66802-12-1-1908-en-US
64 Chapter 8 Parameters
USER.LOAD.0 shows the load of the main motor of the mill 1.
Bühler AG
MEAG-DFCQ-66802-12-1-1908-en-US
Chapter 8 Parameters 65
USER.VIBR.x Current vibration value of mill x (1 or 2)
Unit: %
TCON.MOTCAN = ON: Actual speed of the main motor (current motor frequen-
cy read out by the frequency converter).
The following parameters of the MAN parameter group can be controlled man-
ually:
■ MAN.FROLL
■ MAN.FSLD
■ MAN.FSLD2
■ MAN.FAN
■ MAN.TRAN
■ MAN.TRAN2
■ MAN.MOT
■ MAN.MOT2
These parameters are displayed as in the following example (based on the ex-
ample “MAN.FROLL”).
Press .
Bühler AG
MEAG-DFCQ-66802-12-1-1908-en-US
66 Chapter 8 Parameters
MAN.FROLL Frequency of the feed roller
Range of val- 0 … 100 Level: L Default value: 0
ues:
Unit: Hz
► Set MAN.FSLD to 5 % before starting the feed roller. Otherwise, the slide
gate will touch against the roller.
Value Function
Value Function
Bühler AG
MEAG-DFCQ-66802-12-1-1908-en-US
Chapter 8 Parameters 67
► Switching between manual and automatic: press .
Value Function
Value Function
Value Function
Bühler AG
MEAG-DFCQ-66802-12-1-1908-en-US
68 Chapter 8 Parameters
MAN.FLPOS Position of linear cylinder for flap control
0 … 100
Range of val- Level: L Default value: 0
ues:
Unit: %
Value Function
► Define the middle position of the gravity flow diverter: See page 74,
parameter “TCON.FLMID”.
MAN.POSDIF.x Difference in position between linear cylinder on cone, left and right
Range of val- 0 … 100.0
ues:
Unit: mm
MAN.RUNH_R.x Operating hours for clockwise direction of rotation, main motor mill x
Unit: h
Bühler AG
MEAG-DFCQ-66802-12-1-1908-en-US
Chapter 8 Parameters 69
► Delete current value: press for 10 seconds.
Value Function
Value Function
1 Only one setpoint is available for both mills. If SYS.REM = REMA, only analog
input AI0.3 is active.
2 Both mills receive a setpoint. If SYS.REM = REMA, then both the analog inputs
AI0.3 and AI0.7 are active.
Bühler AG
MEAG-DFCQ-66802-12-1-1908-en-US
70 Chapter 8 Parameters
TCON.MILL Number of mills
Level: L Default value: 1
Value Function
1 1 mill.
2 2 mills.
Value Function
Value Function
AIN The motor current is measured via the analog input of the control.
Mill 1: AI 0.0
Mill 2: AI 0.4
REMOTE The motor current is transmitted via the fieldbus from the control system.
Transmitted data record 128/bytes 14...15
Value Function
AIN The motor current is measured via the analog input of the control.
Discharge conveyor 1: AI 0.1
Discharge conveyor 2: AI 0.5
REMOTE The motor current is transmitted via the fieldbus from the control system.
Transmitted data record 128/bytes 16...17
Bühler AG
MEAG-DFCQ-66802-12-1-1908-en-US
Chapter 8 Parameters 71
TCON.MOTPTC.x Temperature monitoring of main motor for mill x
Level: L Default value: ON
Value Function
OFF No monitoring.
ON The main motor's PTC is monitored.
Value Function
Bühler AG
MEAG-DFCQ-66802-12-1-1908-en-US
72 Chapter 8 Parameters
TCON.MODE Operating mode of the control
Level: L Default value: REG
Value Function
REG Regulates to a set point. The feed gap and the speed of the feed roller are
modified. This will enable the largest dosing range to be covered. An attempt is
made to operate the feed roller in the optimal speed range TCON.FMIN and
TCON.FMAX. The speed is monitored every 5 seconds and if necessary, the
feed gap is adjusted to bring the speed back within the optimal range.
FREQ Regulates to a set point. The feed gap remains at TCON.SMAX. It is not modi-
fied.
The dosing quantity is only influenced by the feed roller (0 … 100 Hz). This lim-
its the dosing range but can also be helpful for special applications. Modifica-
tions cannot be reacted to very quickly in this mode, as the influence of the
feed roller is less than the influence of the roller gap adjuster.
SLIDE Regulates to a set point. The feed roller speed remains at TCON.FMIN. It is
not modified. The dosing quantity is only influenced by the feed gap
(TCON.SMIN … TCON.SMAX). The slightest modification to the feed gap is
specified by the mechanical system. This mode is not recommended for prod-
ucts which require intensive grinding.
CONST Overload is regulated. If the actual mill load is less than the set point, no con-
trol will occur. Therefore, the control will not be activated until the mill load has
exceeded the set point. The controller is deactivated again when the load falls
below the set point again and the standard settings have been reached again.
The standard values for the feed roller and the feed gap are predefined with
TCON.FMAX and TCON.SMAX.
Value Function
Bühler AG
MEAG-DFCQ-66802-12-1-1908-en-US
Chapter 8 Parameters 73
TCON.FLMID Gravity flow diverter middle position
Range of val- 0 … 100 Level: L Default value: 50
ues:
Unit: %
Value Function
0 A limit switch must be available for the middle position. In this case, the pulse
output is ignored.
> 0 Value for the middle position of the flap. In this case, the position of the flap is
determined by means of the pulse output of the linear cylinder.
Value Function
Value Function
Value Function
Value Function
FC_SLD DFAV standard, feed roller with FC and linear cylinder LINAK.
NORD Not supported yet.
SLIDE Feeder screw 0/4 … 20 mA and linear cylinder.
SCREW Feeder screw 0/4 … 20 mA.
CLIPP Not supported yet.
FC DFAV with manual slide gate, only feed roller with FC.
Bühler AG
MEAG-DFCQ-66802-12-1-1908-en-US
74 Chapter 8 Parameters
TCON.FC_SLD Linear cylinder connection location for feed gap adjustment at throughput
control
Level: L Default value: BASE
Value Function
Value Function
Value Function
1 1 discharge conveyor
2 2 discharge conveyors
Bühler AG
MEAG-DFCQ-66802-12-1-1908-en-US
Chapter 8 Parameters 75
TCON.TRANS Monitor discharge capacity
Range of val- 0 … 150 Level: L Default value: 0
ues:
Unit: %
Value Function
0 Monitoring deactivated.
> 0 Monitoring activated.
Value Function
Value Function
Value Function
Bühler AG
MEAG-DFCQ-66802-12-1-1908-en-US
76 Chapter 8 Parameters
TCON.FMAX Maximum frequency on frequency converter of feed roller
0 … 100
Range of val- Level: L Default value: 70
ues:
Unit: Hz
The control always starts with this slide gate opening. When this value increas-
es, the start becomes faster, but also presents the danger of overshooting.
Value Function
Bühler AG
MEAG-DFCQ-66802-12-1-1908-en-US
Chapter 8 Parameters 77
TCON.TMAX Maximum temperature
50 … 100
Range of val- Level: L Default value: 75
ues:
Unit: °C
Bühler AG
MEAG-DFCQ-66802-12-1-1908-en-US
78 Chapter 8 Parameters
TCON.T2.x Braking time of mill x (0 or 1)
0.1 … 99.9
Range of val- Level: L Default value: 5.0
ues:
Unit: s
If TCON.DFCQ = FCM, the feeder device starts once the release input has
been activated.
If TCON.DFCQ = DFZK, the feeder device starts once the inlet probe DI5.00
signals that it is covered.
If TCON.DFCQ = FCM, the feeder unit stops once the release input has been
deactivated.
If TCON.DFCQ = DFZK, then the feeder unit stops once the inlet probe DI 5.0
signals that it is uncovered.
Bühler AG
MEAG-DFCQ-66802-12-1-1908-en-US
Chapter 8 Parameters 79
TCON.T7 Open heavy particle flap automatically
Range of val- 10 … 9999 Level: L Default value: 0
ues:
Unit: min
Value Function
0 Function deactivated.
Open only with local push-button switch.
> 0 Function activated.
SYS.TYP Application
Level: L Default value: NOAPP
Value Function
NOAPP No application.
No signal from the outputs (e.g. when first switching on after loss of data).
MDDR_T Four-roller mill MDDR.
Eight-roller mill MDDT.
DFCQ Control unit for hammer mill.
DFCI Pellet mill control.
MHSA Huller MHSA.
MDDP_Q Four-roller mill MDDP.
Eight-roller mill MDDQ.
Bühler AG
MEAG-DFCQ-66802-12-1-1908-en-US
80 Chapter 8 Parameters
Value Function
Value Function
SYS.EIN 24 V input “release main motor”, “release feeding” and “mill brakes”
Level: L Default value: OFF
Value Function
Bühler AG
MEAG-DFCQ-66802-12-1-1908-en-US
Chapter 8 Parameters 81
Value Function
Value Function
Value Function
Bühler AG
MEAG-DFCQ-66802-12-1-1908-en-US
82 Chapter 8 Parameters
SYS.SD Standard operating parameters
The data appears by default on the display after 600 seconds if no button is
pressed during this time period. The default time for the change (600 seconds)
can be changed in parameter “SYS.SDT”.
In addition, “SYS.SD” is used to define what is displayed in the
“USER.ACTUAL” parameter.
Value Function
Bühler AG
MEAG-DFCQ-66802-12-1-1908-en-US
Chapter 8 Parameters 83
Value Function
Value Function
0 No automatic change.
>0 If no button is pressed during the set time, the display changes to the standard
operating parameter. See “SYS.SD” parameter.
Value Function
Bühler AG
MEAG-DFCQ-66802-12-1-1908-en-US
84 Chapter 8 Parameters
Value Function
Value Function
Value Function
Value Function
Value Function
Bühler AG
MEAG-DFCQ-66802-12-1-1908-en-US
Chapter 8 Parameters 85
SYS.AI.x Analog inputs
Range of val- 0/4 mA or 5 V Level: L Default value: 0
ues:
Unit: mA
► Select additional analog inputs: Press and hold down and press + .
► Note the adjustment at jumpers X62.
► Select additional analog outputs: Press and hold down and press + .
► Select additional analog inputs: Press and hold down and press + .
The Bühler standard baud rate of 200 and CAN-Open baud rates are supported.
■ 200
■ 10
■ 20
■ 50
■ 125
■ 250
■ 500
■ 800
■ 1000
► If lines are longer than 200 meters: reduce the baud rate.
Bühler AG
MEAG-DFCQ-66802-12-1-1908-en-US
86 Chapter 8 Parameters
SYS.ENET Ethernet interface ProfiNet or Ethernet/IP
Level: L Default value: OFF
Value Function
Value Function
Bühler AG
MEAG-DFCQ-66802-12-1-1908-en-US
Chapter 8 Parameters 87
ADC.MOT 2.2 Nominal current, motor, discharge, mill 2
Range of val- -500.0 … 999.9 Level: L Default value: 100.0
ues:
Unit: A
Bühler AG
MEAG-DFCQ-66802-12-1-1908-en-US
88 Chapter 8 Parameters
ADC.I 2.2 Present current, motor, discharge conveyor, mill 2
1.0 … 999.0
Range of val-
ues:
Unit: A
Bühler AG
MEAG-DFCQ-66802-12-1-1908-en-US
Chapter 8 Parameters 89
8.2.6 ADCT (Analog/Digital Converter Temperature) parameter group
0 or 4 mA = TMIN 20 mA = TMAX
5 V/10 V = 0 V = TMIN 5 V/10 V = TMAX
PT100 or PT1000 = no function.
0 or 4 mA = TMIN 20 mA = TMAX
5 V/10 V = 0 V = TMIN 5 V/10 V = TMAX
PT100 or PT1000 = no function.
Bühler AG
MEAG-DFCQ-66802-12-1-1908-en-US
90 Chapter 8 Parameters
ADCT.UNIT Temperature unit
Default value: °C
Value Function
1317.AI1.x x = 0 … 7 input
Default value: OFF
Value Description
OFF Deactivated – [A]
R General resistance measurement 0.0 [R]
PT100 Temperature measurement PT100 0.0 [R]
PT1000 Temperature measurement PT1000 0.0 [R]
5 V Voltage measurement 0 … 5.000 V [V]
10 V Voltage measurement 0 … 10.000 V [V]
80 mV Voltage measurement difference for DMS ± 80.000 mV [mV]
0/1 2/3 4/5 6/7 (signal +/signal -)
0 mA Current measurement 0 … 20.00 mA [mA]
4 mA Current measurement 4 … 20.00 mA [mA]
Jumper X298/X299:
1317.AIN1.x x = 0 … 7 input
► If options with analog inputs are available, select the desired input: press
and + or .
Bühler AG
MEAG-DFCQ-66802-12-1-1908-en-US
Chapter 8 Parameters 91
1317.AIADJ1.x x = 0 … 7 input
90.0 … 110.0
Range of val- Default value: 100.0
ues:
Unit: %
Alignment of analog inputs. The current value will be changed in percentage in-
crements.
Value Description
0 Current measurement 0 … 20.00
4 Current measurement 4 … 20.00
1317.AOADJ1.x x = 0 / 1 output
Range of val- 90.0 … 110.0 Default value: 100.0
ues:
Unit: %
Bühler AG
MEAG-DFCQ-66802-12-1-1908-en-US
92 Chapter 8 Parameters
Selecting the module
The control has 2 controllers that can be configured independently of each oth-
er. One controller is used for the feed roller, the other one is used for the seg-
ment slide gate.
Value Function
P P controller.
I I controller.
Bühler AG
MEAG-DFCQ-66802-12-1-1908-en-US
Chapter 8 Parameters 93
Value Function
PI PI controller.
PD PD controller.
PID PID controller.
This time does not influence the controller speed but merely serves as a time
basis. After a controller interval, a control action is always executed.
Value Function
The device stops metering if no more communication takes place during the
timeout time.
■ The monitoring is only active when “SYS.REM” = REMP.
Value Function
Bühler AG
MEAG-DFCQ-66802-12-1-1908-en-US
94 Chapter 8 Parameters
PBDP.MPDP Profibus DP operating mode
Level: L Default value: NORM
Value Function
NORM Normal protocol with 24-byte data for sending and receiving. For description,
see operating manual 66499.
SHORT Compact protocol DMS-T. Output byte not consistent (IM308B).
SHORTK Compact protocol DMS-T. Output byte consistent (IM308C).
EXTD_S Short extended protocol. Contains the NORM protocol with additional 32-byte
data.
EXTD_L Long extended protocol. Contains the NORM protocol with additional 48-byte
data.
Value Function
Use analysis filter to select a data set from the Profibus protocol. Its value is
displayed via “PBDP.DAT”.
Value Function
Bühler AG
MEAG-DFCQ-66802-12-1-1908-en-US
Chapter 8 Parameters 95
PBDP.DSNR Data set number analysis filter
Range of val- 0 … 255 Default value: 0
ues:
The counter is increased by 1 each time the dataset defined by the filter is ac-
cessed.
Resetting counter:
► Press key.
Bühler AG
MEAG-DFCQ-66802-12-1-1908-en-US
96 Chapter 8 Parameters
8.2.10 ENET (Ethernet) parameter group
Current address for Profinet communication. The MEAG registers with this ad-
dress.
meag-123 (ENET.ADR = 123)
Only available with ProfiNet - “SYS.ENET” - P-NET.
In addition, the current bus status is shown.
Value Function
Value Function
NORM Normal protocol with 24-byte data for sending and receiving. For description,
see operating manual 66499.
SHORT Compact protocol DMS-T. Output byte not consistent (IM308B).
SHORTK Compact protocol DMS-T. Output byte consistent (IM308C).
EXTD_S Short extended protocol. Contains the NORM protocol with additional 32-byte
data.
EXTD_L Long extended protocol. Contains the NORM protocol with additional 48-byte
data.
ENET.IP IP address
Value Function
Bühler AG
MEAG-DFCQ-66802-12-1-1908-en-US
Chapter 8 Parameters 97
ENET.SUBNET Subnet mask
Bühler AG
MEAG-DFCQ-66802-12-1-1908-en-US
98 Chapter 8 Parameters
ENET.GWSET.x Input new standard gateway. x = 0 … 3
0 … 255
Range of val- Level: L Default value: 0
ues:
The device triggers an alarm if no communication takes place during the time-
out time.
■ The monitoring is only active when “SYS.REM” = REME.
Value Function
Bühler AG
MEAG-DFCQ-66802-12-1-1908-en-US
Chapter 8 Parameters 99
ENET.COM Communication status indicator
Value Function
NORM Normal protocol with 24-byte data for sending and receiving. For a description,
see operating manual 66499.
SHORT Compact protocol DMS-T. Output byte not consistent (IM308B).
SHORTK Compact protocol DMS-T. Output byte consistent (IM308C).
EXTD_S Short advanced protocol. Contains the NORM protocol with additional 32-byte
data.
EXTD_L Long advanced protocol. Contains the NORM protocol with additional 48-byte
data.
Bühler AG
MEAG-DFCQ-66802-12-1-1908-en-US
100 Chapter 8 Parameters
TCP.IP IP address
Value Function
Bühler AG
MEAG-DFCQ-66802-12-1-1908-en-US
Chapter 8 Parameters 101
► Start control system with new IP address: press for 10 seconds.
The device triggers an alarm if no communication has taken place within the
specified time.
■ Monitoring is only active when “SYS.REM” = REMTCP.
Bühler AG
MEAG-DFCQ-66802-12-1-1908-en-US
102 Chapter 8 Parameters
SERV.V_BASE Basic system version
SERV.DATE Date
Range of val- 00.01.01 … 99.12.31 Level: L
ues:
SERV.TIME Time
Range of val- 00.00.00 … 23.59.59 Level: L
ues:
The last alarm is displayed in the form ERR.0 A006. The second to last alarm
is displayed with ERR.–1 etc.
down .
Bühler AG
MEAG-DFCQ-66802-12-1-1908-en-US
Chapter 8 Parameters 103
SERV.SADR System address in the case of a program error
Value Function
Value Function
Value Function
Value Function
Bühler AG
MEAG-DFCQ-66802-12-1-1908-en-US
104 Chapter 8 Parameters
SERV.SIMAZ Simulation mode for training at Bühler AG
Level: L Default value: OFF
Value Function
Also applies to options with digital inputs (e.g. 1.0 ... 1.11).
► Press and keep the key held down and press the + or key.
► Press and keep the key held down and press the + or key.
Selecting input:
► Press and keep the key held down and press the + or key.
Present current.
Bühler AG
MEAG-DFCQ-66802-12-1-1908-en-US
Chapter 8 Parameters 105
Selecting output:
► Press and keep the key held down and press the + or key.
If OFF is displayed, no USB cable is connected. The following elements are dis-
played:
■ Left: Number of data packets received.
■ Right: Current utilization of the data transfer as %.
20 KByte/s = 100 %.
Display options:
Value Function
Bühler AG
MEAG-DFCQ-66802-12-1-1908-en-US
106 Chapter 8 Parameters
Value Function
► Press key.
► Press key.
Bühler AG
MEAG-DFCQ-66802-12-1-1908-en-US
Chapter 8 Parameters 107
9 Alarms and messages
Alarms and messages have the following syntax: The letter A for alarm or W
for warning followed by a three-digit number.
Example: A073.
Example: A073.2
A002 RAM
Cause Correction
The RAM is defective. ► Switch device off and on.
► If the alarm is repeated, replace main circuit board.
A003 RUNTIME
Cause Correction
Runtime error during the program ► Switch device off and on.
execution. Software or hardware ► If the alarm is repeated, note SERV.SADR and contact
problem. Bühler customer service.
► Initialize data or load new program version.
► If the alarm is repeated, replace main circuit board.
A004 WATCHDOG
Cause Correction
Timeout during program cycle. Soft- ► Switch device off and on.
ware or hardware problem. ► If the alarm is repeated, note SERV.SADR and contact
Bühler customer service.
► Initialize data or load new program version.
► If the alarm is repeated, replace main circuit board.
Bühler AG
MEAG-DFCQ-66802-12-1-1908-en-US
108 Chapter 9 Alarms and messages
A005 NO 24V
Cause Correction
The voltage is too low (< 18 V). ► Measure voltage at X1.
► If the voltage is lower than 18 V, locate the cause. The
power supply unit may be defective or overloaded.
► If the voltage exceeds 18 V, replace main circuit board.
A006 DATALOST
Cause Correction
Loss of data in the battery-buf- ► Check that battery base is firmly in place.
fered RAM. The parameters and ► If new software was loaded, acknowledge alarm.
various data are reset to the origi- ► Disconnect the control system from the mains. Wait
nal value. Can occur during soft- 15 minutes. Switch on control system. If the alarm is re-
ware downloads. peated, replace battery.
A012 HOST COM
Cause Correction
Timeout on host interface. The ► Run the host system.
host system no longer communi- ► Check the functionality or wiring of the interface cable.
cates with the device. ► Check jumper X31.
► Increase the timeout value of the HOST.TOUT parame-
ter or set it to 0.
W013 EXTDISP
Cause Correction
Serial communication to remote ► Check the wiring.
control interrupted. Only possible ► Check setting of X80.
with optional remote control. ► Check the value of the SYS.DISP parameter.
A014 PROFI-DP
Cause Correction
Profibus error or communication ► Check the wiring.
has been interrupted (timeout). De- ► Check the address setting in the value of the
vice stopped. Alarm only when PBDP.ADR parameter.
SYS.REM = REMP. ► Check the setting of the operating mode in the value of
the PBDP.MPDP parameter.
► Increase the timeout value of the PBDP.TOUT parame-
ter.
► Check master configuration.
Bühler AG
MEAG-DFCQ-66802-12-1-1908-en-US
Chapter 9 Alarms and messages 109
W017 DISPLAY
Cause Correction
Communication to the primary dis- ► Check setting of X80.
play is interrupted. The display it- ► Set address on the display (see display alarm *No
self can no longer display the error. Comm An*).
► Check the wiring.
A018 BATTERY
Cause Correction
Buffer battery has insufficient volt- ► Check that battery base is firmly in place.
age or clock has stopped. ► Replace battery while device is switched on, then
switch control system off and back on again.
A070 CAN Ctn
Cause Correction
Interrupted communication with a ► Note error display on CAN module. Refer to description
CAN module. t = A (EBD 1317) of CAN expansion modules in appendix.
t = D (EBD 1318/20) ► Check the wiring.
t = L (EBD 1319) n = 1…31 (mod- ► Check address setting on CAN modules.
ule address). If CAN COM is dis- ► Check whether configured CAN modules are present.
played, the whole bus is faulty.
A071 CAN Mtn
Cause Correction
A CAN module transmits an error. ► Note error display on CAN module. Continue in accord-
t = A (EBD 1317) ance with the module description in the Appendix.
t = D (EBD 1318/20) ► Replace CAN module.
t = L (EBD 1319) n = 1…31 (mod-
ule address).
A072 CAN Dtn
Cause Correction
A CAN module has an output er- ► Note error display on CAN module. Continue in accord-
ror. t = D (EBD 1318/20) ance with the module description in the Appendix.
t = L (EBD 1319) n = 1…31 (mod- ► Check wiring of digital outputs.
ule address). ► Check whether alarm stops when output plug connector
is disconnected.
W075 WARNTEMP
Cause Correction
The temperature in the device is ► Check the temperature in the device.
too high. The temperature sensor ► Ensure adequate ventilation.
is located on the display circuit
board.
Bühler AG
MEAG-DFCQ-66802-12-1-1908-en-US
110 Chapter 9 Alarms and messages
A076 HIGHTEMP
Cause Correction
The permissible maximum tempera- ► Check the temperature in the device.
ture in the device is exceeded. ► Ensure adequate ventilation.
The temperature sensor is located
on the display circuit board.
A077 DIGOUT
Cause Correction
One or more of the outputs devi- ► Remove external voltage or overload sources.
ate from expected state.
A020 HOPP
Cause Correction
The discharge probe on the mill is ► Check discharge of the product.
reporting product. ► The probe supplies 24 V if no product is present. DI 1.5
must therefore show 24 V.
A021 INC
Cause Correction
No pulse signals of the segment ► Check whether the LINAK cylinder is moving.
gate are measured. ► Check wiring of the LINAK cylinder.
► Check by means of the LED of DI 5.4 whether pulses
are arriving on the IO module. LED flashes during slide
gate movement.
A022 END P
Cause Correction
The segment slide gate does not ► Check whether the LINAK cylinder is at the limit posi-
reach the limit position “open” or tion. The DI 5.5 or DI 0.9 input must then show 24 V.
“closed”.
A023 CTEMP
Cause Correction
The temperature sensor of the mill ► The mill was operated for too long in idle state. Wait un-
supplies a temperature that is til the temperature is lower than TCON.TMAX.
above the limit TCON.TMAX. ► Configure correct sensor type for 1317.AI1.0.
► Connect sensor correctly. Check wiring PT100 at X210.
At 20 °C, the PT100 must show approx. 108 ohm.
Bühler AG
MEAG-DFCQ-66802-12-1-1908-en-US
Chapter 9 Alarms and messages 111
A024 VIB_W
Cause Correction
The vibration value of the mill has ► Find the mechanical cause for the excessive vibrations,
exceeded the limit value e.g. worn or broken beaters.
TCON.VIB_W within the time ► The machine can continue to be operated. During the
TCON.T VIB. next stop, find the cause.
A025 MSTOP
Cause Correction
The machine stop of the mill was ► —
triggered.
A027 STILL
Cause Correction
The standstill monitoring of the mill ► DI 1.3 must show 24 V when motor is stationary.
is reporting movement from the
motor. The error is only displayed
when attempting to open the cone.
A028 COPEN
Cause Correction
The cone of the mill is not locked ► DI 1.4 must show 24 V when cone is closed.
or the <Move cone> key was
pressed for too long.
A029 MOTOR
Cause Correction
The grinding motor of the mill was ► Once the grinding motors have been started up, a mo-
started and there has been no re- tor current must be measured within 10 seconds. After
sponse. the grinding motors have been stopped, no motor cur-
rent may be measured after a delay of 5 minutes.
Check whether the motor contactor is disconnecting and
whether the actual value input AI0.0 is wired correctly.
A030 S < 4 mA
Cause Correction
No signal on the set point input of ► The AI0.3 input has a current of < 2 mA. If a
the mill 0 … 20 mA signal is used, set SYS.AI.3 to 0 mA. If
there is no analog set point, set SYS.REM ≠ REMA.
Bühler AG
MEAG-DFCQ-66802-12-1-1908-en-US
112 Chapter 9 Alarms and messages
A031 A < 4 mA
Cause Correction
No signal on the actual value input ► The AI0.0 input has a current of < 2 mA. If a
of the mill 0 … 20 mA signal is used, set SYS.AI.0 to 0 mA.
A033 LIMIT
Cause Correction
The limit value TCON.TRANS was ► Check whether the discharge conveyor for the mill is
exceeded for over 5 seconds. The clogged or the drive is blocked.
discharge conveyor is overloaded. ► Check configuration of the discharge motor ADC.MOT
1.2 and ADC.CON 1.2.
A034 V < 4 mA
Cause Correction
No signal on the vibration sensor ► The AI1.1 input has a current of < 2 mA. If a
of the mill. 0 … 20 mA signal is used, set 1317.AI1.2 to 0 mA. If
no vibration sensor is present, set TCON.VIBR = OFF.
A035 TSTART
Cause Correction
The discharge conveyor of the mill ► When the discharge conveyor is started, a response
has not started. The release for must be issued within 10 seconds. If there is no re-
the discharge of the mill is active sponse, the DO 0.7 output must be connected to the
and there has been no response. DI 0.14 input via a jumper wire.
A036 CTIGHT
Cause Correction
The cone for the mill is jammed. ► Make sure that both cylinders are in the same position.
The positions of both cone linear Then reset the difference with the MAN.POSDIF param-
cylinders differ by more than eter.
30 mm from each other. If the posi-
tion difference of both cylinders is
too great, the cone is usually jam-
med. It is also possible that the
pulse signal of a cylinder is not be-
ing measured.
A037 CINC
Cause Correction
No position pulse on the cone of ► Check the pulse signal wiring of the linear cylinder on
the mill the cone.
Bühler AG
MEAG-DFCQ-66802-12-1-1908-en-US
Chapter 9 Alarms and messages 113
A038 VIB_A
Cause Correction
The vibration value of the mill has ► Find the mechanical cause for the excessive vibrations,
exceeded the limit value e.g. worn or broken beaters.
TCON.VIB_A within the time
TCON.T VIB.
A039 MOT_TEMP
Cause Correction
The main motor's PTC has switch- ► Allow motor to cool.
ed. ► Identify and remedy cause for overload.
► If motor has no PTC: TCON.MOT_PTC to OFF.
9.2.2 Mill 2
A040 HOPP
Cause Correction
The discharge probe on the mill is ► Check discharge of the product.
reporting product. ► The probe supplies 24 V if no product is present. DI 2.5
must therefore show 24 V.
A041 INC
Cause Correction
No pulse signals of the segment ► Check whether the LINAK cylinder is moving.
gate are measured. ► Check wiring of the LINAK cylinder.
► Check by means of the LED of DI 6.4, whether pulses
are arriving on the I/O module. LED flashes during slide
gate movement.
A042 END P
Cause Correction
The segment gate does not reach ► Check whether the LINAK cylinder is at the limit posi-
the limit position open or closed. tion. The DI 6.5 or DI 0.21 input must then show 24 V.
A043 CTEMP
Cause Correction
The temperature sensor of the mill ► The mill was operated for too long in idle state. Wait un-
supplies a temperature that is til the temperature is lower than TCON.TMAX.
above the limit TCON.TMAX. ► Configure correct sensor type for 1317.AI2.0.
► Connect sensor correctly. Check wiring PT100 at X210.
At 20 °C, the PT100 must show approx. 108 ohm.
Bühler AG
MEAG-DFCQ-66802-12-1-1908-en-US
114 Chapter 9 Alarms and messages
A044 VIB_W
Cause Correction
The vibration value of the mill has ► Find the mechanical cause for the excessive vibrations,
exceeded the limit value e.g. worn or broken beaters.
TCON.VIB_W within the time ► The machine can continue to be operated. During the
TCON.T VIB. next stop, find the cause.
A045 MSTOP
Cause Correction
The machine stop of the mill was ► —
triggered.
A047 STILL
Cause Correction
The standstill monitoring of the mill ► DI 2.3 must show 24 V when motor is stationary.
is reporting movement from the
motor. The error is only displayed
when attempting to open the cone.
A048 COPEN
Cause Correction
The cone of the mill is not locked ► DI 2.4 must show 24 V when cone is closed.
or the <Move cone> key was
pressed for too long.
A049 MOTOR
Cause Correction
The grinding motor of the mill was ► Once the grinding motors have been started up, a mo-
started and there has been no re- tor current must be measured within 10 seconds. After
sponse. the grinding motors have been stopped, no motor cur-
rent may be measured after a delay of 5 minutes.
Check whether the motor contactor is disconnecting and
whether the actual value input AI0.4 is wired correctly.
A050 S < 4 mA
Cause Correction
No signal on the set point input of ► The AI0.7 input has a current of < 2 mA. If a
the mill 0 … 20 mA signal is used, set SYS.AI.7 to 0 mA. If
there is no analog set point, set SYS.REM ≠ REMA.
Bühler AG
MEAG-DFCQ-66802-12-1-1908-en-US
Chapter 9 Alarms and messages 115
A051 A < 4 mA
Cause Correction
No signal on the actual value input ► The AI0.4 input has a current of < 2 mA. If a
of the mill 0 … 20 mA signal is used, set SYS.AI.4 to 0 mA.
A053 LIMIT
Cause Correction
The limit value TCON.TRANS was ► Check whether the discharge conveyor for the mill is
exceeded for over 5 seconds. The clogged or the drive is blocked.
discharge conveyor is overloaded. ► Check configuration of the discharge motor ADC.MOT
2.2 and ADC.CON 2.2.
A054 V < 4 mA
Cause Correction
No signal on the vibration sensor ► The AI2.1 input has a current of < 2 mA. If a
of the mill. 0 … 20 mA signal is used, set 1317.AI1.3 to 0 mA. If
no vibration sensor is present, set TCON.VIBR = OFF.
A055 TSTART
Cause Correction
The discharge conveyor of the mill ► When the discharge conveyor is started, a response
has not started. The release for must be issued within 10 seconds. If there is no re-
the discharge of the mill is active sponse, the DO 0.11 output must be connected to the
and there has been no response. DI 0.26 input via a jumper wire.
A056 CTIGHT
Cause Correction
The cone for the mill is jammed. ► Make sure that both cylinders are in the same position.
The positions of both cone linear Then reset the difference with the MAN.POSDIF param-
cylinders differ by more than eter.
30 mm from each other. If the posi-
tion difference of both cylinders is
too great, the cone is usually jam-
med. It is also possible that the
pulse signal of a cylinder is not be-
ing measured.
A057 CINC
Cause Correction
No position pulse on the cone of ► Check the pulse signal wiring of the linear cylinder on
the mill the cone.
Bühler AG
MEAG-DFCQ-66802-12-1-1908-en-US
116 Chapter 9 Alarms and messages
A058 VIB_A
Cause Correction
The vibration value of the mill has ► Find the mechanical cause for the excessive vibrations,
exceeded the limit value e.g. worn or broken beaters.
TCON.VIB_A within the time
TCON.T VIB.
A059 MOT_TEMP
Cause Correction
The main motor's PTC has switch- ► Allow motor to cool.
ed. ► Identify and remedy cause for overload.
► If motor has no PTC: TCON.MOT_PTC to OFF.
A060 POWER
Cause Correction
A 24 V miniature circuit breaker ► Check whether the miniature circuit breakers of the con-
has responded. trol have triggered.
► DI 0.23 must show 24 V.
A061 UPSON
Cause Correction
UPS is active. ► Restore the power supply.
► Deselect the UPS. If not present, TCON.UPS = OFF.
A062 ATVCOM
Cause Correction
The communication with the fre- ► Check CAN connection to the converters.
quency converters of the main mo- ► Check address settings on the converter: Mill 1 = ad-
tor is interrupted. dress 1; Mill 2 = address 2.
A063 ATV
Cause Correction
The frequency converter of the ► Read the error cause off the frequency converter dis-
main motor is reporting an error. play. Remedy the error in accordance with the frequen-
cy converter operating instructions.
► Check address settings on the converter: Mill 1 = ad-
dress 1; Mill 2 = address 2.
Bühler AG
MEAG-DFCQ-66802-12-1-1908-en-US
Chapter 9 Alarms and messages 117
A065 FC
Cause Correction
The frequency converter of the ► Read the error number off the frequency converter in
feed roller is reporting an error. the DFCQ. Determine the cause by using the operating
manual of the frequency converter.
► Alarm is active only if “TCON.FEED = FC_SLD”.
A066 DOOR
Cause Correction
Magnetic door is not closed. ► Check whether the magnetic door is closed properly.
DI 5.2 must show 24 V.
A067 FLAT
Cause Correction
Error in the flap control unit. ► Check whether the gravity flow diverter adjustment cylin-
der is moving.
► Use the LED of DI 6.8 to check whether pulses are ar-
riving on the IO module. LED flashes during the flap
movement.
A068 PART
Cause Correction
Defect in the heavy particle separa- ► Check whether the heavy particle cylinder is at the limit
tion. position. DI 5.9 must show 24 V in the limit position.
A090 FAN
Cause Correction
The fan was started and there has ► When the fan is started, a response must be issued
been no response. within 10 seconds. If there is no response, the DO 0.13
output must be connected to the DI 0.12 input via a
jumper. Output DO 0.13 = 24 V → Fan is running. Input
DI 0.12 = 24 V → Fan is running.
A091 PLANT
Cause Correction
The machine stops after an emer- ► Input DI 0.0 = 24 V → no alarm.
gency stop.
A092 SAFES
Cause Correction
The safety switch of the machine ► Input DI 0.7 = 24 V → no alarm.
was actuated.
Bühler AG
MEAG-DFCQ-66802-12-1-1908-en-US
118 Chapter 9 Alarms and messages
9.3 FCM application alarms
A021 INC
Cause Correction
No pulse signals of the segment ► Check whether the LINAK cylinder is moving.
gate are measured. ► Check wiring of the LINAK cylinder.
► Use the LED of DI 5.4 to check whether pulses are ar-
riving on the IO module. LED flashes during segment
gate movement.
A022 END P
Cause Correction
The segment gate does not reach ► Check whether the LINAK cylinder is at the limit posi-
the limit position “open” or “closed”. tion. The DI 5.5 or DI 0.9 input must then show 24 V.
A030 S < 4 mA
Cause Correction
No signal on the setpoint input of ► The AI0.3 input has a current of < 2 mA. If a 0 to
the mill 20 mA signal is used, set SYS.AI.3 to 0 mA. If there is
no analog setpoint, set “SYS.REM” ≠ REMA.
A031 A < 4 mA
Cause Correction
No signal on the actual value input ► The AI0.0 input has a current of < 2 mA. If a 0 to
of the mill 20 mA signal is used, set “SYS.AI.0” to 0 mA.
A041 INC
Cause Correction
No pulse signals of the segment ► Check whether the LINAK cylinder is moving.
gate are measured. ► Check wiring of the LINAK cylinder.
► Check by means of the LED of DI 6.4, whether pulses
are arriving on the I/O module. LED flashes during seg-
ment gate movement.
A042 END P
Cause Correction
The segment gate does not reach ► Check whether the LINAK cylinder is at the limit posi-
the limit position open or closed. tion. The DI 6.5 or DI 0.21 input must then show 24 V.
Bühler AG
MEAG-DFCQ-66802-12-1-1908-en-US
Chapter 9 Alarms and messages 119
A050 S < 4 mA
Cause Correction
No signal on the setpoint input of ► The AI0.7 input has a current of < 2 mA. If a 0 to
the mill 20 mA signal is used, set SYS.AI.7 to 0 mA. If there is
no analog setpoint, set “SYS.REM” ≠ REMA.
A051 A < 4 mA
Cause Correction
No signal on the actual value input ► The AI0.4 input has a current of < 2 mA. If a 0 to
of the mill 20 mA signal is used, set “SYS.AI.4” to 0 mA.
A065 FC
Cause Correction
The frequency converter of the ► Read the error number off the frequency converter in
feed roller is reporting an error. the DFCQ. Determine the cause by using the operating
manual of the frequency converter.
► The alarm is active only if “TCON.FEED” = FC_SLD.
2. Press .
4. Press .
5. Press .
The seven-segment display shows the status and error messages. In the follow-
ing table, the status messages are listed on the seven-segment after the display.
Bühler AG
MEAG-DFCQ-66802-12-1-1908-en-US
120 Chapter 9 Alarms and messages
Display State
– Standard operation.
The middle seg- There are no messages.
ments are dis-
played cyclically
from top to bot-
tom.
L Software is installed and activated after the restart.
If the display is If the device tool is used, press <Activate software>. If the
flashing, the control system is switched to a de-energized state, the new
download has software will also be activated.
not yet been
completed.
U USB connection active.
Device is connected to PC via a USB cable.
P Profibus is attached and connected.
For further information: See page 106, parameter
“SERV.P-DP”.
C New software is copied.
Program 1 is updated. Program 2 is copied. Status mes-
sage is displayed only during the startup phase.
F Program 1 is defective. Program 2 is copied.
Status message is displayed only during the startup phase.
In the following table, the error messages are listed on the seven-segment after
the display. If an “E” flashes alternately with another symbol, an error message
is pending. “E d” means, for example, that “E” und “d” are flashing alternately.
1
Cause Correction
Error in the FLASH EPROM. No ► Switch printed circuit board to de-energized state. Clean
application present. No application with compressed air.
started. ► Restart. If the error occurs again, replace the PCB.
2
Cause Correction
Error in the DRAM memory. No ap- ► Switch printed circuit board to de-energized state. Clean
plication starts. For example, as a with compressed air.
result of a short-circuit on the PCB ► Restart. If the error occurs again, replace the PCB.
due to copper residue.
b
Cause Correction
Error in battery RAM memory. No ► Switch printed circuit board to de-energized state. Clean
application starts. with compressed air.
► Restart. If the error occurs again, replace the PCB.
Bühler AG
MEAG-DFCQ-66802-12-1-1908-en-US
Chapter 9 Alarms and messages 121
E L
Cause Correction
Defective software version instal- ► Reinstall software. If the display does not change, re-
led. Program 1 shows an incorrect quest a new software version.
checksum. ► Switch device to current-free state. Program 2 is used
automatically after restart.
E 3
Cause Correction
► See A003 RUNTIME
E 4
Cause Correction
► See A004 WATCHDOG
E 5
Cause Correction
► See A005 NO 24V
E b
Cause Correction
► See W018 BATTERY
E 6
Cause Correction
► See A006 DATALOST
E C
Cause Correction
► See A070 CAN COM, A071 CAN MOD, A072
CAN DOUT
E d
Cause Correction
► See W017 DISPLAY
Bühler AG
MEAG-DFCQ-66802-12-1-1908-en-US
122 Chapter 9 Alarms and messages
Display State
LOCAL The feeding was manually stopped on the display with the key
STOP S1.
STOP The feeding was stopped because no dosing release is present.
m STOP Dosing release is available, but the mill motor was not started.
c STOP The feeding was stopped because there is no dosing release
via the fieldbus.
STARTING The grinding motor was started. The message is active during
heavy start-up of the drive.
BRAKE The grinding motor was stopped. The reverse current brake is
active.
RUN EMPTY The grinding motor was stopped. Idle time “TCON.T1” is active.
STANDBY All releases are present, but the grinding motor was switched
off after timeout “TCON.T3”.
OPEN The cone of all mills is open.
OPEN1 The cone of mill 1 is open.
OPEN2 The cone of mill 2 is open.
HL INLET The inlet probe is covered.
OVERLOAD The motor current of the grinding motor shows a value > 130%
of the nominal current.
EMPTY The surge hopper is empty
VIBRATION The vibration level has exceeded the programmed limit. If not
remedied, the machine will stop with the alarm A034 or A054.
DISCHARGE Discharge function (or residual discharging) is active (not nor-
mal emptying).
SERVICE The service mode is active, i.e. “SERV.SERM” = “ON” (outputs
can be set).
MANUAL The device is operated manually. No automatic control se-
quence.
SIM ON The simulator mode is activated, i. e. “SERV.SIMM” = “ON”.
HL TRANS- The filling level probe in the discharge conveyor is covered
PORT (see “TCON.TRAPRB”).
Some of the following messages are application-specific, i.e. they do not occur
with every control.
Display State
OK Input has been detected and applied.
Example: When a recipe has been loaded.
LOCK Parameter modification is locked.
See page 84, parameter “SYS.LOCK”.
Bühler AG
MEAG-DFCQ-66802-12-1-1908-en-US
Chapter 9 Alarms and messages 123
Display State
REMOTE The control is in remote operating mode, e.g. via Profi-
bus. Parameters can only be edited in remote operation
mode, e.g: “SYS.REM” = REMP.
See page 81, parameter “SYS.REM”.
PROTECT Recipes are protected from being overwritten. The rec-
ipes cannot be saved.
DATA INIT Initialization is executed. The control is reset to default
values.
See page 87, parameter “SYS.INIT”.
SET ZERO Zero adjustment is executed.
SET CAL Calibration is executed.
SET TARE Taring is executed.
WT INIT Weight values are re-initialized.
Example: If “ADC.DIV” is adjusted.
WAIT The device processes an order and prompts the opera-
tor to wait.
Do not operate the control while WAIT is displayed.
CLEAR Data is being deleted.
ESC Modification has been aborted.
Bühler AG
MEAG-DFCQ-66802-12-1-1908-en-US
124 Chapter 9 Alarms and messages
10 Spare parts
10.1 Spare parts in stock
Stocks of spare parts and parts subject to wear are an important requirement
for the permanent operational readiness of the control system.
Bühler spare parts often fulfil special manufacturing and delivery specifications.
Bühler sells spare parts in accordance with state-of-the-art technology.
Only spare parts delivered by Bühler are inspected and approved. Spare parts
from other sources might negatively change the prescribed constructional quali-
ties of the control system and/or impair safety.
We would recommend keeping the following parts in stock for the correspond-
ing design version:
The remaining available spare parts are summarized in the following table:
Bühler AG
MEAG-DFCQ-66802-12-1-1908-en-US
Chapter 10 Spare parts 125
Designation Part no.
Set of cables (strands) numbered for CAN expansion or
display circuit board:
200 mm WEWS-95011-810
500 mm WEWS-95012-810
1000 mm WEWS-95013-810
1400 mm WEWS-95014-810
Bühler AG
MEAG-DFCQ-66802-12-1-1908-en-US
126 Chapter 10 Spare parts
11 Appendix
11.1 CAN expansion modules
11.1.1 Types
11.1.2 Connection
Bühler AG
MEAG-DFCQ-66802-12-1-1908-en-US
Chapter 11 Appendix 127
11.1.3 LED display
Each CAN expansion module contains a 1-digit LED display; EBD 1320 has a
2-digit display. It indicates the hardware status.
Set address:
E 1
Cause Correction
Software error ► Switch module off and back on
again. If the message is displayed
again, replace module.
E 2
Cause Correction
EEPROM data loss ► Switch module off and back on
again. If the message is displayed
again, replace module.
► Check whether the correct address is
displayed.
E 3
Cause Correction
No connection to CAN interface ► Press button and check address.
► Check settings of the parameters on
the MEAG.
E 4
Cause Correction
A/D converter error ► Switch module off and back on
again. If the message is displayed
again, replace module.
Bühler AG
MEAG-DFCQ-66802-12-1-1908-en-US
128 Chapter 11 Appendix
E 5
Cause Correction
Digital outputs ► One or more of the outputs deviates
from expected behavior. (External
voltage, short circuit, overload).
E 6
Cause Correction
No external 24 V for EBD 1320 ► Check external 24 V at X105:1 plug.
LED 24 V EXT lights up when there
is voltage.
E b
Cause Correction
Automatic baud rate search (no ► Press button and check address.
connection to CAN interface). (For setting see address.)
► Check settings of the parameters on
the MEAG.
235
206
101 101
127
113
99
Fig. 11.1
Technical data
Bühler AG
MEAG-DFCQ-66802-12-1-1908-en-US
Chapter 11 Appendix 129
Depth 40 mm
Power supply +24 V DC from the device control system
6 bores 6 mm in diameter
Cable cross section max. 2.5 mm2
Front panel section 99 x 206 mm
Fig. 11.2
Technical data
Bühler AG
MEAG-DFCQ-66802-12-1-1908-en-US
130 Chapter 11 Appendix
11.2.3 Connect to MDDR main circuit board SIO_0
MDDR MEAG
Main circuit board Display circuit board
EBD 1311 EBD 1316
SIO_0 X50
X30
1
2 1 +24 V Line 1
1
3 2 0 V Line 2 2
4 3 RXD_TXD + 3 3
X80
SIO_0
1 6 X30 4 RXD_TXD - 4 4
2 5 X51
3 4 SIO_0
X50
Fig. 11.3
If the local display unit is removed from the control and assembled elsewhere,
it is to be connected as a remote control. Address 1 is still used, however, and
the value of the parameter SYS.DISP will remain on OFF.
► Press 5 times.
► Press .
► Press .
► Press .
2. Activate interface.
► Select SYS.DISP parameter.
Bühler AG
MEAG-DFCQ-66802-12-1-1908-en-US
Chapter 11 Appendix 131
Parameter list
Production plant:
Name:
Date:
Bühler AG
MEAG-DFCQ-66802-12-1-1908-en-US
132 Chapter 11 Parameter list
Parameter Default value Unit Customer value
TCON.MOTCAN OFF
TCON.MOT_F1.x 50 Hz
TCON.MOT_F2.x 50 Hz
TCON.MODE REG
TCON.FLAP OFF
TCON.FLMID 50 %
TCON.VIBR OFF
TCON.UPS OFF
TCON.TEMP OFF
TCON.FEED FC_SLD
TCON.FC_SLD BASE
TCON.AOUT ACTV
TCON.N TRANS 2
TCON.TRANS 0 %
TCON.TRAPRB OFF
TCON.REG_M2 OFF
TCON.CSYNC ON
TCON.FMAX 70 Hz
TCON.FMIN 30 Hz
TCON.SMAX 100 %
TCON.SMIN 5 %
TCON.SINI 0 %
TCON.DIFF 10 %
TCON.TMAX 75 °C
TCON.VIB_W 10.0 mm/s
TCON.VIB_A 20.0 mm/s
TCON.T VIB 10 s
TCON.T1 30 s
TCON.T2.x 5.0 s
TCON.T3 15 min
TCON.T4 1.0 s
TCON.T5 1.0 s
TCON.T6 15 s
TCON.T7 0 min
TCON.LOGMSTP 60 s
TCON.LOGMRUN 10 s
TCON.ASSIST
SYS.TYP NOAPP
SYS.REM LOC
Bühler AG
MEAG-DFCQ-66802-12-1-1908-en-US
Chapter 11 Parameter list 133
Parameter Default value Unit Customer value
SYS.EIN OFF
SYS.DISP OFF
SYS.PSAV STOP
SYS.SD
SYS.SDT 600 s
SYS.LOCK OFF
SYS.MSG ALL
SYS.ACLR OFF
SYS.AINV ON
SYS.ASCROL ON
SYS.AO.x 0 mA
SYS.AI.x 0 mA
SYS.AOADJ.x 100.0 %
SYS.AIADJ.x 100.0 %
SYS.CANBR 50 kBaud
SYS.ENET OFF
SYS.TCP OFF
SYS.INIT
ADC.MOT 1.1 100.0 A
ADC.MOT 1.2 100.0 A
ADC.MOT 2.1 100.0 A
ADC.MOT 2.2 100.0 A
ADC.CON 1.1 200.0 A
ADC.CON 1.2 200.0 A
ADC.CON 2.1 200.0 A
ADC.CON 2.2 200.0 A
ADC.I 1.1 A
ADC.I 1.2 A
ADC.I 2.1 A
ADC.I 2.2 A
ADC.I0 1.1 1.0 A
ADC.I0 1.2 1.0 A
ADC.I0 2.1 1.0 A
ADC.I0 2.2 1.0 A
ADC.AOMAX 150 %
ADCT.T.n °C
ADCT.OFFSET.n 0.0 °C
ADCT.TMIN.n –40 °C
ADCT.TMAX.n 300.0 °C
Bühler AG
MEAG-DFCQ-66802-12-1-1908-en-US
134 Chapter 11 Parameter list
Parameter Default value Unit Customer value
ADCT.UNIT °C
1317.AI1.x OFF
1317.AIN1.x
1317.AIADJ1.x 100.0 %
1317.AO1.x 0 mA
1317.AOUT1.x mA
1317.AOADJ1.x 100.0 %
1317.MODT.x °C
CTRL.TN.x See table
CTRL.TV.x See table
CTRL.KR.x See table
CTRL.REG.x See table
CTRL.TIME.x 1000 ms
PBDP.ADR 0
PBDP.TOUT 1.0 s
PBDP.WFOR FIX
PBDP.MPDP NORM
PBDP.COMP OFF
PBDP.CTRLB
PBDP.STATB
PBDP.DSDIR RXD
PBDP.DSNR 0
PBDP.DSIDX 0
PBDP.DSBYTE 8
PBDP.DSTYPE 1 BYTE
PBDP.DAT
PBDP.DSCNT
ENET.ADR 0
ENET.MPDP EXTD_L
ENET.IP
ENET.SUBNET
ENET.STDGW
ENET.IPSET.x 0
ENET.SNSET.x 0
ENET.GWSET.x 0
ENET.TOUT 1.0 s
ENET.STATUS
ENET.COM
ENET.NAMEOS ON
Bühler AG
MEAG-DFCQ-66802-12-1-1908-en-US
Chapter 11 Parameter list 135
Parameter Default value Unit Customer value
TCP.MPDP EXTD_L
TCP.IP
TCP.SUBNET
TCP.STDGW
TCP.IPSET.x 0
TCP.SNSET.x 0
TCP.GWSET.x 0
TCP.TOUT 1.0 s
TCP.COM
SERV.ID
SERV.V_PROG
SERV.V_APPL
SERV.V_BASE
SERV.V_BOOT
SERV.DATE
SERV.TIME
SERV.ERR.x
SERV.EVT.x
SERV.ALLEVT.x
SERV.CPU
SERV.SADR
SERV.PCNT
SERV.ELOG ON
SERV.CLOG OFF
SERV.SIMM OFF
SERV.SERM OFF
SERV.SIMAZ OFF
SERV.DIN
SERV.DOUT
SERV.DISPIN
SERV.AIN.x V / mA
SERV.AOUT.x mA
SERV.TINT °C
SERV.SIO1
SERV.SIO2
SERV.USB
SERV.P-DP
SERV.PUPDAT
Bühler AG
MEAG-DFCQ-66802-12-1-1908-en-US
136 Chapter 11 Parameter list
Parameter Default value Unit Customer value
SERV.PDWDAT
SERV.TEST
Bühler AG
MEAG-DFCQ-66802-12-1-1908-en-US
Chapter 11 Parameter list 137
Bühler Group
www.buhlergroup.com