Photovoltaic components
and combiner boxes
The evolution of product technology, production costs and the regulatory framework
in photovoltaic generation has led to a strong development of small and medium-
sized self-consumption facilities. The SOLARTEC range of modular combiner boxes has
been designed for maximum ease of use by both the installer and the end user.
Functions
Photovoltaic combiner boxes Combiner boxes can typically also
perform the connection and include overload protection,
protection functions of the short-circuit protection and devices to
photovoltaic arrays and subarrays protect against overvoltages of
on the direct current side of a solar atmospheric origin.
generation installation. The new international standard
IEC60364-7-712:2017 includes signifi-
The combiner boxes include the cant revisions taking into account expe-
functions of switching and rience gained in the construction and
disconnecting the electrical circuits operation of PV installation including
in order to isolate the inverter updated related to developments made
direct current input and comply in PV technology.
with the regulatory requirements According to standards
aimed at guaranteeing safety of
persons. • IEC 60364-7-712:2017
• IEC 60947-3
• EN 50539-11:2013
• EN 61439-1/-2
2
Modular PV combiner boxes
REFERENCE SYSTEM
STM 3 10 40 P 12 / 2
Nr. of strings Fuse protection
Rating
3 Fuse 10 A (standard)
4 25 25 A Surge 12 Fuse 12 A
6 40 40 A
80 80 A
protectors 15 Fuse 15 A
Fuse selection
To select the fuse rating according to 431.102, we must use the Isc
max of the string, apply a coefficient x1.1 and select the fuse of
nominal current In immediately higher than the result. This
coefficient is a safety margin for untimely operation of the
protection devices taking into account normal stress conditions. In
value can never be higher than Imod_max_ocpr
www.gave.com 3
Photovoltaic components
and combiner boxes
GENERAL CHARACTERISTICS
Box Material
Gray RAL7035
polycarbonate suitable
for outdoor use with high
impact resistance (IK08)
Enclosure safety
Double insulation
class II according to
61439-1
4
Modular PV combiner boxes
++ -
+ - 10,3x38
211PV 1000Vdc
DO NOT OPERATE
10,3x38
211PV 1000Vdc
DO NOT OPERATE
ON | 10,3x38
211PV 1000Vdc
DO NOT OPERATE
UNDER LOAD
10,3x38
211PV 1000Vdc
DO NOT OPERATE
UNDER LOAD
10,3x38
211PV 1000Vdc
ON | 10,3x38
211PV 1000Vdc
UNDER LOAD UNDER LOAD
rojo/red: replace rojo/red: replace rojo/red: replace
rojo/red: replace rojo/red: replace rojo/red: replace
DO NOT OPERATE DO NOT OPERATE
UNDER LOAD UNDER LOAD
rojo/red: replace rojo/red: replace rojo/red: replace
PV-40/1000
PV-40/500 PV-40/1000 PV-40/1000
PV-40/1000
PV-40/500 PV-40/1000 PV-40/1000
OFF 0
PV Ucpv
PV Ucpv 1060 Vdc PV Ucpv 1060 Vdc PV Ucpv 1060 Vdc
530 Vdc
PV-40/1000
PV-40/500 PV-40/1000 PV-40/1000 PVPVUcpv In1060 Vdc
530 20 kA PV
Vdc PVUcpv kA PV
T2 In 106020Vdc PV Ucpv 20Vdc
T2 In 1060 kA
PV T2
T2 In 20 kA
OFF 0
+ in- + - - in + in- + - - in
modules out out modules modules out out modules
www.gave.com 5
Photovoltaic components
and combiner boxes
OFF 0
PV Ucpv 1060 Vdc PV Ucpv 1060 Vdc PV Ucpv 1060 Vdc
PV T2 In 20 kA PV T2 In 20 kA PV T2 In 20 kA
T2 Imax 40 kA T2 Imax 40 kA T2 Imax 40 kA
Up(+/- PE) 3.6 kV Up(+/- PE) 3.6 kV Up(+/- PE) 3.6 kV
+ in - + - - in
modules out out modules + in - + - - in
modules out out modules
6
Modular PV combiner boxes
+ -
10,3x38 10,3x38 ON | 10,3x38 10,3x38 10,3x38 10,3x38
211PV 1000Vdc 211PV 1000Vdc
10,3x38
211PV 1000Vdc
10,3x38
211PV 1000Vdc 211PV 1000Vdc 211PV 1000Vdc 211PV 1000Vdc 211PV 1000Vdc 10,3x38
211PV 1000Vdc
10,3x38
211PV 1000Vdc
10,3x38
211PV 1000Vdc
10,3x38
211PV 1000Vdc ON | 10,3x38
211PV 1000Vdc
10,3x38
211PV 1000Vdc
10,3x38
211PV 1000Vdc
10,3x38
211PV 1000Vdc 10,3x38
211PV 1000Vdc
10,3x38
211PV 1000Vdc
10,3x38
211PV 1000Vdc
10,3x38
211PV 1000Vdc
10,3x38
211PV 1000Vdc
10,3x38
211PV 1000Vdc
10,3x38
211PV 1000Vdc
10,3x38
211PV 1000Vdc
DO NOT OPERATE
UNDER LOAD
DO NOT OPERATE
UNDER LOAD
DO NOT OPERATE
UNDER LOAD
DO NOT OPERATE
UNDER LOAD
DO NOT OPERATE
UNDER LOAD
DO NOT OPERATE
UNDER LOAD
DO NOT OPERATE
UNDER LOAD
DO NOT OPERATE
UNDER LOAD
DO NOT OPERATE
UNDER LOAD
DO NOT OPERATE
UNDER LOAD
DO NOT OPERATE
UNDER LOAD
DO NOT OPERATE
UNDER LOAD
DO NOT OPERATE
UNDER LOAD
DO NOT OPERATE
UNDER LOAD
DO NOT OPERATE
UNDER LOAD
DO NOT OPERATE
UNDER LOAD
DO NOT OPERATE DO NOT OPERATE DO NOT OPERATE DO NOT OPERATE ON | DO NOT OPERATE DO NOT OPERATE DO NOT OPERATE DO NOT OPERATE
UNDER LOAD UNDER LOAD UNDER LOAD UNDER LOAD UNDER LOAD UNDER LOAD UNDER LOAD UNDER LOAD
rojo/red: replace rojo/red: replace rojo/red: replace
OFF 0
OFF 0
PV Ucpv 1060 Vdc PV Ucpv 1060 Vdc PV Ucpv 1060 Vdc
PV T2 In 20 kA PV T2 In 20 kA PV T2 In 20 kA
T2 Imax 40 kA T2 Imax 40 kA T2 Imax 40 kA
Up(+/- PE) 3.6 kV Up(+/- PE) 3.6 kV Up(+/- PE) 3.6 kV
+ in - + - - in + in - + - - in
+ - modules out out modules modules out out modules
+ in - - in
modules out out modules
4 4 4
1 1 1
1000 V 1000 V 1000 V
40 A 40 A 80 A
Yes - gPV Curve Yes - gPV Curve Yes - gPV Curve
No PST31PV No
- 1060 VDC -
- 20 kA -
- 40 kA -
- 3.6 kV -
www.gave.com 7
Photovoltaic components
and combiner boxes
Reference STM41080P12
STM41080P15
Connection diagram
+ -
ON |
rojo/red: replace rojo/red: replace rojo/red: replace
OFF 0
PV Ucpv 1060 Vdc PV Ucpv 1060 Vdc PV Ucpv 1060 Vdc
PV T2 In 20 kA PV T2 In 20 kA PV T2 In 20 kA
T2 Imax 40 kA T2 Imax 40 kA T2 Imax 40 kA
Up(+/- PE) 3.6 kV Up(+/- PE) 3.6 kV Up(+/- PE) 3.6 kV
+ in - in
modules modules
+ -
out out
8
Modular PV combiner boxes
STM61080 STM61080P
STM61080-12 STM61080P-12
STM61080-15 STM61080P-15
ON | + -
ON |
rojo/red: replace rojo/red: replace rojo/red: replace
OFF 0
OFF 0
PV Ucpv 1060 Vdc PV Ucpv 1060 Vdc PV Ucpv 1060 Vdc
PV T2 In 20 kA PV T2 In 20 kA PV T2 In 20 kA
T2 Imax 40 kA T2 Imax 40 kA T2 Imax 40 kA
Up(+/- PE) 3.6 kV Up(+/- PE) 3.6 kV Up(+/- PE) 3.6 kV
10,3x38 10,3x38 10,3x38 10,3x38 10,3x38 10,3x38 10,3x38 10,3x38 10,3x38 10,3x38 10,3x38 10,3x38
10,3x38
211PV 1000Vdc
10,3x38 10,3x38 10,3x38 10,3x38 10,3x38 10,3x38 10,3x38 10,3x38 10,3x38 10,3x38 10,3x38 211PV 1000Vdc 211PV 1000Vdc 211PV 1000Vdc 211PV 1000Vdc 211PV 1000Vdc 211PV 1000Vdc 211PV 1000Vdc 211PV 1000Vdc 211PV 1000Vdc 211PV 1000Vdc 211PV 1000Vdc 211PV 1000Vdc
211PV 1000Vdc 211PV 1000Vdc 211PV 1000Vdc 211PV 1000Vdc 211PV 1000Vdc 211PV 1000Vdc 211PV 1000Vdc 211PV 1000Vdc 211PV 1000Vdc 211PV 1000Vdc 211PV 1000Vdc DO NOT OPERATE DO NOT OPERATE DO NOT OPERATE DO NOT OPERATE DO NOT OPERATE DO NOT OPERATE DO NOT OPERATE DO NOT OPERATE
DO NOT OPERATE DO NOT OPERATE DO NOT OPERATE DO NOT OPERATE
DO NOT OPERATE DO NOT OPERATE DO NOT OPERATE DO NOT OPERATE DO NOT OPERATE DO NOT OPERATE DO NOT OPERATE DO NOT OPERATE DO NOT OPERATE DO NOT OPERATE DO NOT OPERATE DO NOT OPERATE UNDER LOAD UNDER LOAD UNDER LOAD UNDER LOAD UNDER LOAD UNDER LOAD UNDER LOAD UNDER LOAD UNDER LOAD UNDER LOAD UNDER LOAD UNDER LOAD
UNDER LOAD UNDER LOAD UNDER LOAD UNDER LOAD UNDER LOAD UNDER LOAD UNDER LOAD UNDER LOAD UNDER LOAD UNDER LOAD UNDER LOAD UNDER LOAD
+ in - in + in - in
modules modules modules modules
+ -
+ - out out
out out
6 6
1 1
1000 V 1000 V
80 A 80 A
Yes - gPV Curve Yes - gPV Curve
No PST31PV
- 1060 VDC
- 20 kA
- 40 kA
- 3.6 kV
Class II Class II
IP65 IP65
IK08 IK08
YES YES
436 x 418 x 148 436 x 418 x 148
PC PC
750ºC 750ºC
www.gave.com 9
Photovoltaic components
and combiner boxes
+ -
10,3x38
211PV 1000Vdc
10,3x38
211PV 1000Vdc ON | 10,3x38
211PV 1000Vdc
10,3x38
211PV 1000Vdc
DO NOT OPERATE DO NOT OPERATE DO NOT OPERATE DO NOT OPERATE
UNDER LOAD UNDER LOAD rojo/red: replace rojo/red: replace rojo/red: replace UNDER LOAD UNDER LOAD
PV-40/1000
PV-40/500 PV-40/1000 PV-40/1000
PV Ucpv 1060 Vdc PV Ucpv 1060 Vdc PV Ucpv 1060 Vdc
OFF 0
530 Vdc
PV T2 In 20 kA PV T2 In 20 kA PV T2 In 20 kA
T2 Imax 40 kA T2 Imax 40 kA T2 Imax 40 kA
Up(+/- PE) 3.6
1.8 kV Up(+/- PE) 3.6 kV Up(+/- PE) 3.6 kV
+ - + -
10,3x38 ON | 10,3x38 10,3x38 ON | 10,3x38
211PV 1000Vdc
211PV 1000Vdc 211PV 1000Vdc 211PV 1000Vdc
DO NOT OPERATE DO NOT OPERATE DO NOT OPERATE DO NOT OPERATE
UNDER LOAD rojo/red: replace rojo/red: replace rojo/red: replace UNDER LOAD UNDER LOAD rojo/red: replace rojo/red: replace rojo/red: replace UNDER LOAD
PV-40/500 PV-40/500
PV-40/1000 PV-40/1000 PV-40/1000
+ in + - - in
modules
PV-40/1000 PV-40/1000 PV-40/1000
modules
OFF 0
OFF 0
out out
PV PV
PV Ucpv 530 Vdc
PV Ucpv 530 Vdc
Ucpv 1060 Vdc PV Ucpv 1060 Vdc PV Ucpv 1060 Vdc Ucpv 1060 Vdc PV Ucpv 1060 Vdc PV Ucpv 1060 Vdc
PV PV T2 In
PV T2 20 kA
20
T2 In
PV T2 In 20 kA
20 kA PV T2 In 20 kA PV T2 In 20 kA In kA PV T2 In 20 kA PV T2 In 20 kA
T2 Imax
T2 Imax 40 kA
40 kA T2 Imax 40 kA T2 Imax 40 kA T2 Imax
T2 Imax 40 kA
40 kA T2 Imax 40 kA T2 Imax 40 kA
Up(+/- PE)
Up(+/- 3.6 kV
PE) 1.8 kV Up(+/- PE) 3.6 kV Up(+/- PE) 3.6 kV Up(+/- PE)
Up(+/- 3.6 kV
PE) 1.8 kV Up(+/- PE) 3.6 kV Up(+/- PE) 3.6 kV
+ -
2 8 2 8 10,3x38
211PV 1000Vdc
10,3x38
211PV 1000Vdc ON | 10,3x38
211PV 1000Vdc
10,3x38
211PV 1000Vdc
DO NOT OPERATE DO NOT OPERATE DO NOT OPERATE DO NOT OPERATE
UNDER LOAD UNDER LOAD rojo/red: replace rojo/red: replace rojo/red: replace UNDER LOAD UNDER LOAD
PV-40/1000
PV-40/500 PV-40/1000 PV-40/1000
PV Ucpv 1060 Vdc PV Ucpv 1060 Vdc PV Ucpv 1060 Vdc
OFF 0
530 Vdc
+ - + -
PV T2 In 20 kA PV T2 In 20 kA PV T2 In 20 kA
++ in + in - in
T2 Imax 40 kA T2 Imax 40 kA T2 Imax 40 kA
- in
Up(+/- PE) 3.6
1.8 kV Up(+/- PE) 3.6 kV Up(+/- PE) 3.6 kV
+ in + - - in
modules out out modules
10
Modular PV combiner boxes
Maintenance safety
The switching and disconnection devices guarantee
maintenance in safety conditions without the need to
fully stop solar generation.
+ -
10,3x38 10,3x38 10,3x38
ON | 10,3x38 10,3x38 10,3x38
211PV
10,3x38
211PV 1000Vdc
DO NOT OPERATE
10,3x38
211PV 1000Vdc
DO NOT OPERATE
10,3x38
211PV 1000Vdc
DO NOT OPERATE
ON | 10,3x38
211PV 1000Vdc
DO NOT OPERATE
10,3x38
211PV 1000Vdc
DO NOT OPERATE
10,3x38
211PV 1000Vdc
DO NOT OPERATE
211PV 1000Vdc
211PV
DO NOT OPERATE
UNDER LOAD
211PV 1000Vdc
DO NOT OPERATE
UNDER LOAD
211PV 1000Vdc
DO NOT OPERATE
UNDER LOAD rojo/red: replace rojo/red: replace rojo/red: replace
211PV 1000Vdc
DO NOT OPERATE
UNDER LOAD
211PV 1000Vdc
DO NOT OPERATE
UNDER LOAD
211PV 1000Vdc
DO NOT OPERATE
UNDER LOAD
+ - + - + - + -
UNDER LOAD UNDER LOAD UNDER LOAD UNDER LOAD UNDER LOAD UNDER LOAD
ON | 10,3x38 10,3x38 ON | 10,3x38 10,3x38 ON | 10,3x38 10,3x38 ON | 10,3x38
211PV 1000Vdc
10,3x38
211PV 1000Vdc 211PV 1000Vdc 211PV 1000Vdc 211PV 1000Vdc 211PV 1000Vdc 211PV 1000Vdc 211PV 1000Vdc
DO NOT OPERATE DO NOT OPERATE DO NOT OPERATE DO NOT OPERATE DO NOT OPERATE DO NOT OPERATE DO NOT OPERATE
DO NOT OPERATE rojo/red: replace rojo/red: replace rojo/red: replace rojo/red: replace rojo/red: replace rojo/red: replace UNDER LOAD
PV-40/1000
PV-40/500 PV-40/1000 PV-40/1000 UNDER LOAD rojo/red: replace rojo/red: replace rojo/red: replace UNDER LOAD UNDER LOAD rojo/red: replace rojo/red: replace rojo/red: replace UNDER LOAD UNDER LOAD UNDER LOAD UNDER LOAD
530 Vdc
PV T2 In 20 kA PV T2 In 20 kA PV T2 In 20 kA PV-40/500 PV-40/500 PV-40/500
OFF 0
PV-40/500 PV-40/1000 PV-40/1000 PV-40/1000 PV-40/1000 PV-40/1000 PV-40/1000 PV-40/1000 PV-40/1000 PV-40/1000
PV-40/1000 PV-40/1000 PV-40/1000
OFF 0
40 kA T2 Imax 40 kA T2 Imax 40 kA
OFF 0
T2 Imax
OFF 0
OFF 0
PV PV
PV Ucpv 530 Vdc
PV
PV Ucpv 530 Vdc
Ucpv 1060 Vdc PV Ucpv 1060 Vdc PV Ucpv 1060 Vdc
PV
PV Ucpv 530 Vdc
Ucpv 1060 Vdc PV Ucpv 1060 Vdc PV Ucpv 1060 Vdc PV Ucpv 530 Vdc
Ucpv 1060 Vdc PV Ucpv 1060 Vdc PV Ucpv 1060 Vdc Ucpv 1060 Vdc PV Ucpv 1060 Vdc PV Ucpv 1060 Vdc
Up(+/- PE) 3.6
1.8 kV Up(+/- PE) 3.6 kV Up(+/- PE) 3.6 kV PV PV T2 In
PV T2 20 kA
20 PV T2 In
PV T2 20 kA
20 PV T2 In
PV T2 In 20 kA
20 kA PV T2 In 20 kA PV T2 In 20 kA
T2 In
PV T2 In 20 kA
20 kA PV T2 In 20 kA PV T2 In 20 kA In kA PV T2 In 20 kA PV T2 In 20 kA In kA PV T2 In 20 kA PV T2 In 20 kA
T2 Imax
T2 Imax 40 kA
40 kA T2 Imax 40 kA T2 Imax
T2 Imax 40 kA
40 kA T2 Imax 40 kA T2 Imax 40 kA T2 Imax
T2 Imax 40 kA
40 kA T2 Imax 40 kA T2 Imax 40 kA T2 Imax
T2 Imax 40 kA
40 kA T2 Imax 40 kA T2 Imax 40 kA
T2 Imax 40 kA
Up(+/- Up(+/- PE)
Up(+/- 3.6 kV
PE) 1.8 Up(+/- PE)
Up(+/- 3.6 kV
PE) 1.8
Up(+/- PE)
Up(+/- 3.6 kV
PE) 1.8 kV Up(+/- PE) 3.6 kV Up(+/- PE) 3.6 kV Up(+/- PE) 3.6 kV
PE) 1.8 kV Up(+/- PE) 3.6 kV Up(+/- PE) 3.6 kV kV Up(+/- PE) 3.6 kV Up(+/- PE) 3.6 kV kV Up(+/- PE) 3.6 kV Up(+/- PE) 3.6 kV
2 8 2 8 2 8 2 8
+
+ in + - + in + - - in +
+ in + - - in + in + - - in
out out - in out out out out out out
modules modules modules modules modules modules modules modules
+ in - in + in + - - in
+ - modules modules
modules out out modules out out
+ - + - + -
10,3x38
211PV 1000Vdc
211PV
10,3x38
211PV 1000Vdc
10,3x38
211PV 1000Vdc ON | 10,3x38
211PV 1000Vdc
10,3x38
211PV 1000Vdc
10,3x38
211PV 1000Vdc ON |
+ -
ON | 10,3x38 10,3x38
ON |
10,3x38 10,3x38
10,3x38 10,3x38 10,3x38 10,3x38 10,3x38 10,3x38 211PV 1000Vdc 211PV 1000Vdc 211PV 1000Vdc 211PV 1000Vdc
211PV 1000Vdc
211PV 211PV 1000Vdc 211PV 1000Vdc 211PV 1000Vdc 211PV 1000Vdc 211PV 1000Vdc DO NOT OPERATE
UNDER LOAD
DO NOT OPERATE
UNDER LOAD
DO NOT OPERATE
UNDER LOAD rojo/red: replace rojo/red: replace rojo/red: replace
DO NOT OPERATE
UNDER LOAD
DO NOT OPERATE
UNDER LOAD
DO NOT OPERATE
UNDER LOAD DO NOT OPERATE DO NOT OPERATE DO NOT OPERATE
rojo/red: replace rojo/red: replace rojo/red: replace
DO NOT OPERATE
UNDER LOAD rojo/red: replace rojo/red: replace rojo/red: replace UNDER LOAD UNDER LOAD UNDER LOAD
DO NOT OPERATE DO NOT OPERATE DO NOT OPERATE DO NOT OPERATE DO NOT OPERATE DO NOT OPERATE
UNDER LOAD UNDER LOAD UNDER LOAD UNDER LOAD UNDER LOAD UNDER LOAD 10,3x38 ON | 10,3x38
211PV 1000Vdc
211PV 1000Vdc
DO NOT OPERATE DO NOT OPERATE PV-40/500 PV-40/500
PV-40/1000 PV-40/1000 PV-40/1000 rojo/red: replace rojo/red: replace rojo/red: replace PV-40/1000 PV-40/1000 PV-40/1000 PV-40/1000 PV-40/1000 PV-40/1000
PV-40/500 UNDER LOAD UNDER LOAD
OFF 0
OFF 0
PV PV
PV Ucpv 530 Vdc
PV Ucpv 530 Vdc
Ucpv 1060 Vdc PV Ucpv 1060 Vdc PV Ucpv 1060 Vdc Ucpv 1060 Vdc PV Ucpv 1060 Vdc PV Ucpv 1060 Vdc
PV Ucpv 1060 Vdc PV Ucpv 1060 Vdc PV Ucpv 1060 Vdc PV PV T2 In
PV T2 20 kA
20
OFF 0
530 Vdc T2 In
PV T2 In 20 kA
20 kA PV T2 In 20 kA PV T2 In 20 kA In kA PV T2 In 20 kA PV T2 In 20 kA
PV T2 In 20 kA PV T2 In 20 kA PV T2 In 20 kA T2 Imax
T2 Imax 40 kA
40 kA T2 Imax 40 kA T2 Imax 40 kA T2 Imax
T2 Imax 40 kA
40 kA T2 Imax 40 kA T2 Imax 40 kA
PV-40/500
OFF 0
PV
PV Ucpv 530 Vdc
Ucpv 1060 Vdc PV Ucpv 1060 Vdc PV Ucpv 1060 Vdc
Up(+/- PE) 3.6
1.8 kV Up(+/- PE) 3.6 kV Up(+/- PE) 3.6 kV PV T2 In
PV T2 In 20 kA
20 kA PV T2 In 20 kA PV T2 In 20 kA
T2 Imax
T2 Imax 40 kA
40 kA T2 Imax 40 kA T2 Imax 40 kA
Up(+/- PE)
Up(+/- 3.6 kV
PE) 1.8 kV Up(+/- PE) 3.6 kV Up(+/- PE) 3.6 kV
2 8 2 8
2 8
+
+ in + - - in + in + - - in
+ - modules out out modules out out modules
+
+ in - in modules
modules out out modules
+ in - in + in + - - in
+ - modules out out modules
modules out out modules
3 3 1 1
2 2 3 4
1000 V 1000 V 1000 V 1000 V
2 x 40 A 2 x 40 A 3 x 40 A 4 x 40 A
Yes - gPV Curve Yes - gPV Curve Yes - gPV Curve Yes - gPV Curve
No Yes Yes Yes
- 1060 VDC 1060 VDC 1060 VDC
- 20 kA 20 kA 20 kA
- 40 kA 40 kA 40 kA
- 3.6 kV 3.6 kV 3.6 kV
www.gave.com 11
Photovoltaic components
and combiner boxes
+ - + -
10,3x38
211PV 1000Vdc
ON | 10,3x38
211PV 1000Vdc
10,3x38
211PV 1000Vdc
ON | 10,3x38
211PV 1000Vdc
+ - + -
DO NOT OPERATE
DO NOT OPERATE
UNDER LOAD rojo/red: replace rojo/red: replace rojo/red: replace
DO NOT OPERATE
UNDER LOAD
DO NOT OPERATE
UNDER LOAD rojo/red: replace rojo/red: replace rojo/red: replace UNDER LOAD 10,3x38 ON | 10,3x38 10,3x38 ON | 10,3x38
211PV 1000Vdc
211PV 1000Vdc 211PV 1000Vdc 211PV 1000Vdc
DO NOT OPERATE DO NOT OPERATE DO NOT OPERATE DO NOT OPERATE
UNDER LOAD rojo/red: replace rojo/red: replace rojo/red: replace UNDER LOAD UNDER LOAD rojo/red: replace rojo/red: replace rojo/red: replace UNDER LOAD
PV-40/500 PV-40/500
PV-40/1000 PV-40/1000 PV-40/1000 PV-40/1000 PV-40/1000 PV-40/1000
OFF 0
OFF 0
PV PV
PV Ucpv 530 Vdc
PV Ucpv 530 Vdc
Ucpv 1060 Vdc PV Ucpv 1060 Vdc PV Ucpv 1060 Vdc Ucpv 1060 Vdc PV Ucpv 1060 Vdc PV Ucpv 1060 Vdc
PV PV-40/500 PV-40/500
PV T2 In
PV T2 In 20 kA
20 kA PV T2 In 20 kA PV T2 In 20 kA T2 In
PV T2 In 20 kA
20 kA PV T2 In 20 kA PV T2 In 20 kA PV-40/1000 PV-40/1000 PV-40/1000 PV-40/1000 PV-40/1000 PV-40/1000
OFF 0
T2 Imax
T2 40 kA
40
OFF 0
T2 Imax
T2 Imax 40 kA
40 kA T2 Imax 40 kA T2 Imax 40 kA Imax kA T2 Imax 40 kA T2 Imax 40 kA PV
PV Ucpv 530 Vdc
Ucpv 1060 Vdc PV Ucpv 1060 Vdc
PV
PV Ucpv 530 Vdc
Ucpv 1060 Vdc PV Ucpv 1060 Vdc PV Ucpv 1060 Vdc
Up(+/- PV Ucpv 1060 Vdc
Up(+/- PE)
Up(+/- 3.6 kV
PE) 1.8 Up(+/- PE) 3.6 kV
PE) 1.8 kV Up(+/- PE) 3.6 kV Up(+/- PE) 3.6 kV PV
kV Up(+/- PE) 3.6 kV Up(+/- PE) 3.6 kV PV T2 In
PV T2 In 20 kA
20 kA PV T2 In 20 kA PV T2 In 20 kA T2 In
PV T2 In 20 kA
20 kA PV T2 In 20 kA PV T2 In 20 kA
T2 Imax
T2 Imax 40 kA
40 kA T2 Imax 40 kA T2 Imax 40 kA T2 Imax
T2 Imax 40 kA
40 kA T2 Imax 40 kA T2 Imax 40 kA
Up(+/- PE)
Up(+/- 3.6 kV
PE) 1.8 kV Up(+/- PE) 3.6 kV Up(+/- PE) 3.6 kV Up(+/- PE)
Up(+/- 3.6 kV
PE) 1.8 kV Up(+/- PE) 3.6 kV Up(+/- PE) 3.6 kV
2 8 2 8
2 8 2 8
++ in + - - in + in + - - in
out out out out ++ in + - - in + in + - - in
modules modules modules modules out out out out
modules modules modules modules
+ - + -
10,3x38
211PV 1000Vdc
ON | 10,3x38
211PV 1000Vdc
10,3x38
211PV 1000Vdc
ON | 10,3x38
211PV 1000Vdc
+ - + -
DO NOT OPERATE
DO NOT OPERATE
UNDER LOAD rojo/red: replace rojo/red: replace rojo/red: replace
DO NOT OPERATE
UNDER LOAD
DO NOT OPERATE
UNDER LOAD rojo/red: replace rojo/red: replace rojo/red: replace UNDER LOAD 10,3x38 ON | 10,3x38 10,3x38 ON | 10,3x38
211PV 1000Vdc
211PV 1000Vdc 211PV 1000Vdc 211PV 1000Vdc
DO NOT OPERATE DO NOT OPERATE DO NOT OPERATE DO NOT OPERATE
UNDER LOAD rojo/red: replace rojo/red: replace rojo/red: replace UNDER LOAD UNDER LOAD rojo/red: replace rojo/red: replace rojo/red: replace UNDER LOAD
PV-40/500 PV-40/500
PV-40/1000 PV-40/1000 PV-40/1000 PV-40/1000 PV-40/1000 PV-40/1000
OFF 0
OFF 0
PV PV
PV Ucpv 530 Vdc
PV Ucpv 530 Vdc
Ucpv 1060 Vdc PV Ucpv 1060 Vdc PV Ucpv 1060 Vdc Ucpv 1060 Vdc PV Ucpv 1060 Vdc PV Ucpv 1060 Vdc
PV PV-40/500 PV-40/500
PV T2 In
PV T2 In 20 kA
20 kA PV T2 In 20 kA PV T2 In 20 kA T2 In
PV T2 In 20 kA
20 kA PV T2 In 20 kA PV T2 In 20 kA PV-40/1000 PV-40/1000 PV-40/1000 PV-40/1000 PV-40/1000 PV-40/1000
OFF 0
T2 Imax
T2 40 kA
40
OFF 0
T2 Imax
T2 Imax 40 kA
40 kA T2 Imax 40 kA T2 Imax 40 kA Imax kA T2 Imax 40 kA T2 Imax 40 kA PV
PV Ucpv 530 Vdc
Ucpv 1060 Vdc PV Ucpv 1060 Vdc
PV
PV Ucpv 530 Vdc
Ucpv 1060 Vdc PV Ucpv 1060 Vdc PV Ucpv 1060 Vdc
Up(+/- PV Ucpv 1060 Vdc
Up(+/- PE)
Up(+/- 3.6 kV
PE) 1.8 Up(+/- PE) 3.6 kV
PE) 1.8 kV Up(+/- PE) 3.6 kV Up(+/- PE) 3.6 kV PV
kV Up(+/- PE) 3.6 kV Up(+/- PE) 3.6 kV PV T2 In
PV T2 In 20 kA
20 kA PV T2 In 20 kA PV T2 In 20 kA T2 In
PV T2 In 20 kA
20 kA PV T2 In 20 kA PV T2 In 20 kA
T2 Imax
T2 Imax 40 kA
40 kA T2 Imax 40 kA T2 Imax 40 kA T2 Imax
T2 Imax 40 kA
40 kA T2 Imax 40 kA T2 Imax 40 kA
Up(+/- PE)
Up(+/- 3.6 kV
PE) 1.8 kV Up(+/- PE) 3.6 kV Up(+/- PE) 3.6 kV Up(+/- PE)
Up(+/- 3.6 kV
PE) 1.8 kV Up(+/- PE) 3.6 kV Up(+/- PE) 3.6 kV
2 8 2 8
2 8 2 8
++ in + - - in + in + - - in
out out out out ++ in + - - in + in + - - in
modules modules modules modules out out out out
modules modules modules modules
+ -
10,3x38
211PV 1000Vdc
ON | 10,3x38
211PV 1000Vdc
+ - + -
DO NOT OPERATE DO NOT OPERATE
UNDER LOAD rojo/red: replace rojo/red: replace rojo/red: replace UNDER LOAD
10,3x38 ON | 10,3x38 10,3x38 ON | 10,3x38
211PV 1000Vdc
211PV 1000Vdc 211PV 1000Vdc 211PV 1000Vdc
DO NOT OPERATE DO NOT OPERATE DO NOT OPERATE DO NOT OPERATE
UNDER LOAD rojo/red: replace rojo/red: replace rojo/red: replace UNDER LOAD UNDER LOAD rojo/red: replace rojo/red: replace rojo/red: replace UNDER LOAD
PV-40/500
PV-40/1000 PV-40/1000 PV-40/1000
OFF 0
PV
PV Ucpv 530 Vdc
Ucpv 1060 Vdc PV Ucpv 1060 Vdc PV Ucpv 1060 Vdc
PV T2 In
PV T2 20 kA
20 PV-40/500 PV-40/500
In kA PV T2 In 20 kA PV T2 In 20 kA PV-40/1000 PV-40/1000 PV-40/1000 PV-40/1000 PV-40/1000 PV-40/1000
OFF 0
T2 Imax
T2 40 kA
40
OFF 0
Imax kA T2 Imax 40 kA T2 Imax 40 kA PV
PV
PV Ucpv 530 Vdc
Ucpv 1060 Vdc PV Ucpv 1060 Vdc PV Ucpv 1060 Vdc PV Ucpv 530 Vdc
Ucpv 1060 Vdc PV Ucpv 1060 Vdc PV Ucpv 1060 Vdc
Up(+/- PE)
Up(+/- 3.6 kV
PE) 1.8 kV Up(+/- PE) 3.6 kV Up(+/- PE) 3.6 kV PV PV T2 In
PV T2 20 kA
20
T2 In
PV T2 In 20 kA
20 kA PV T2 In 20 kA PV T2 In 20 kA In kA PV T2 In 20 kA PV T2 In 20 kA
T2 Imax
T2 Imax 40 kA
40 kA T2 Imax 40 kA T2 Imax 40 kA T2 Imax
T2 Imax 40 kA
40 kA T2 Imax 40 kA T2 Imax 40 kA
Up(+/- PE)
Up(+/- 3.6 kV
PE) 1.8 kV Up(+/- PE) 3.6 kV Up(+/- PE) 3.6 kV Up(+/- PE)
Up(+/- 3.6 kV
PE) 1.8 kV Up(+/- PE) 3.6 kV Up(+/- PE) 3.6 kV
2 8
2 8 2 8
++ in + - - in
out out ++ in + - - in + in + - - in
modules modules out out out out
modules modules modules modules
12
Modular PV combiner boxes
12 A PST31PV STM110MCP12
15 A PST31PV STM110MCP15
+ -
10,3x38 10,3x38
211PV 1000Vdc 211PV 1000Vdc
DO NOT OPERATE DO NOT OPERATE
UNDER LOAD UNDER LOAD
PV-40/1000
PV-40/500 PV-40/1000 PV-40/1000
PV Ucpv 1060
530 Vdc PV Ucpv 1060 Vdc PV Ucpv 1060 Vdc
PV T2 In 20 kA PV T2 In 20 kA PV T2 In 20 kA
T2 Imax 40 kA T2 Imax 40 kA T2 Imax 40 kA
Up(+/- PE) 3.6
1.8 kV Up(+/- PE) 3.6 kV Up(+/- PE) 3.6 kV
In 20 kA
Imax 40kA
231
Up 3.6 kV
+ - 118 238
12 A 2xPST31PV STM110MCP12/2
15 A 2xPST31PV STM110MCP15/2
+ - + -
10,3x38 10,3x38 10,3x38 10,3x38
211PV 1000Vdc 211PV 1000Vdc 211PV 1000Vdc 211PV 1000Vdc
DO NOT OPERATE DO NOT OPERATE DO NOT OPERATE DO NOT OPERATE
UNDER LOAD rojo/red: replace rojo/red: replace rojo/red: replace UNDER LOAD UNDER LOAD rojo/red: replace rojo/red: replace rojo/red: replace UNDER LOAD
PV-40/1000
T2 Imax
PV-40/500
PV Ucpv 1060
PV T2 In
40 kA T2 Imax
PV-40/1000
Vdc PV Ucpv 1060 Vdc PV Ucpv 1060 Vdc
530 Vdc
20 kA PV T2 In 20 kA PV T2 In
40 kA T2 Imax
20 kA
40 kA
1.8 kV Up(+/- PE) 3.6 kV Up(+/- PE) 3.6 kV
Up(+/- PE) 3.6
PV-40/1000 PV-40/1000
PV-40/500
PV Ucpv 1060
PV T2 In
T2 Imax
20 kA PV T2 In
40 kA T2 Imax
PV-40/1000
Vdc PV Ucpv 1060 Vdc PV Ucpv 1060 Vdc
530 Vdc
20 kA PV T2 In
40 kA T2 Imax
20 kA
40 kA
1.8 kV Up(+/- PE) 3.6 kV Up(+/- PE) 3.6 kV
Up(+/- PE) 3.6
PV-40/1000
12 A 3xPST31PV STM110MCP12/3
15 A 3xPST31PV STM110MCP15/3
+ - + - + -
10,3x38 10,3x38 10,3x38
10,3x38 10,3x38
211PV 1000Vdc
10,3x38
211PV 1000Vdc 211PV 1000Vdc 211PV 1000Vdc 211PV 1000Vdc
211PV 1000Vdc DO NOT OPERATE DO NOT OPERATE
DO NOT OPERATE DO NOT OPERATE DO NOT OPERATE
DO NOT OPERATE UNDER LOAD rojo/red: replace rojo/red: replace rojo/red: replace UNDER LOAD
UNDER LOAD rojo/red: replace rojo/red: replace rojo/red: replace UNDER LOAD UNDER LOAD rojo/red: replace rojo/red: replace rojo/red: replace UNDER LOAD
PV-40/1000
PV-40/500 PV-40/1000 PV-40/1000 PV-40/1000
PV-40/500 PV-40/1000 PV-40/1000
PV-40/1000
PV-40/500 PV-40/1000 PV-40/1000
In 20 kA
Imax 40kA
286
Up 3.6 kV
+ - + - + - 148 418
12 A 4xPST31PV STM110MCP12/4
+ - + -
15 A 4xPST31PV STM110MCP15/4
10,3x38 10,3x38 10,3x38
10,3x38
211PV 1000Vdc 211PV 1000Vdc 211PV 1000Vdc 211PV 1000Vdc
DO NOT OPERATE DO NOT OPERATE DO NOT OPERATE DO NOT OPERATE
UNDER LOAD rojo/red: replace rojo/red: replace rojo/red: replace UNDER LOAD UNDER LOAD rojo/red: replace rojo/red: replace rojo/red: replace UNDER LOAD
PV-40/1000
PV-40/500 PV-40/1000 PV-40/1000 PV-40/1000
PV-40/500 PV-40/1000 PV-40/1000
PV Ucpv 1060 Vdc PV Ucpv 1060 Vdc PV Ucpv 1060 Vdc
530 Vdc PV Ucpv 1060 Vdc PV Ucpv 1060 Vdc PV Ucpv 1060 Vdc
530 Vdc
PV T2 In 20 kA PV T2 In 20 kA PV T2 In 20 kA PV T2 In 20 kA PV T2 In 20 kA PV T2 In 20 kA
T2 Imax 40 kA T2 Imax 40 kA T2 Imax 40 kA T2 Imax 40 kA T2 Imax 40 kA T2 Imax 40 kA
1.8 kV Up(+/- PE) 3.6 kV Up(+/- PE) 3.6 kV
Up(+/- PE) 3.6 1.8 kV Up(+/- PE) 3.6 kV Up(+/- PE) 3.6 kV
Up(+/- PE) 3.6
Up 3.6 kV
T2 Imax 40 kA T2 Imax 40 kA T2 Imax 40 kA T2 Imax 40 kA T2 Imax 40 kA T2 Imax 40 kA
1.8 kV Up(+/- PE) 3.6 kV Up(+/- PE) 3.6 kV
Up(+/- PE) 3.6 1.8 kV Up(+/- PE) 3.6 kV Up(+/- PE) 3.6 kV
Up(+/- PE) 3.6
148 310
+ + - - + + - -
www.gave.com 13
Photovoltaic components
and combiner boxes
Surge protection
Battery chargers and controllers are characterised by operating at very low voltages and being
extremely sensitive to transient overvoltages that may occur. It is essential to design a combiner
box whose protection level Up is compatible with the maximum voltage of the battery controller/
charger. A mistaken selection of the associated protector can be the origin of
surges that reach the inverter causing irreparable damage.
12 A PST140-110D STM30140P12
15 A PST140-110D STM30140P15
10,3x38
211PV 1000Vdc
DO NOT OPERATE
UNDER LOAD
10,3x38
211PV 1000Vdc
DO NOT OPERATE
UNDER LOAD
10,3x38
211PV 1000Vdc
DO NOT OPERATE
UNDER LOAD
ON |
+ -
rojo/red: replace
10,3x38
211PV 1000Vdc
DO NOT OPERATE
UNDER LOAD
10,3x38
211PV 1000Vdc
DO NOT OPERATE
UNDER LOAD
10,3x38
211PV 1000Vdc
DO NOT OPERATE
UNDER LOAD
Ucpv 150V DC
In 20 kA
PV-40/110
PV-40/500
OFF 0
Un Ucpv 530
PV 150 Vdc
Uc T2 In 11020Vdc
PV kA
In Imax
T2 40 kA
20 kA
T2 Imax
Up(+/- 40 kA
PE) 1.8 kV
Up 500 V
246
Imax 40kA
148 310 Up 390 V
+ in - + - - in
modules out out modules
12 A PST140-110D STM60180P12
15 A PST140-110D STM60180P15
+ -
ON |
rojo/red: replace
Ucpv 150V DC
PV-40/110
PV-40/500
OFF 0
UnUcpv 15O
PV 530 Vdc
UcT2 In 110
PV 20Vdc
kA
In Imax
T2 20 kA
40
T2 Imax
Up(+/- 40 kV
PE) 1.8 kA
Up 500 V
In 20 kA
436
Imax 40kA
148 310 Up 390 V
10,3x38 10,3x38 10,3x38 10,3x38 10,3x38 10,3x38 10,3x38 10,3x38 10,3x38 10,3x38 10,3x38 10,3x38
211PV 1000Vdc 211PV 1000Vdc 211PV 1000Vdc 211PV 1000Vdc 211PV 1000Vdc 211PV 1000Vdc 211PV 1000Vdc 211PV 1000Vdc 211PV 1000Vdc 211PV 1000Vdc 211PV 1000Vdc 211PV 1000Vdc
DO NOT OPERATE DO NOT OPERATE DO NOT OPERATE DO NOT OPERATE DO NOT OPERATE DO NOT OPERATE DO NOT OPERATE DO NOT OPERATE DO NOT OPERATE DO NOT OPERATE DO NOT OPERATE DO NOT OPERATE
UNDER LOAD UNDER LOAD UNDER LOAD UNDER LOAD UNDER LOAD UNDER LOAD UNDER LOAD UNDER LOAD UNDER LOAD UNDER LOAD UNDER LOAD UNDER LOAD
+ in - in
modules modules
+ -
out out
14
Modular PV combiner boxes
www.gave.com 15