Battery Care the new Battery Charger Philosophy

Battery Charger and Battery Tester

Charge & Testing

Integrated Electronic Solutions


Connect Multimediality
The new ADELSystem platform communication ADELVIEW SYSTEM
ADELBus allows the connection of all Comprehensive suite for remote monitoring and
components in a simple but very powerful management of Adel System devices connected
way. A single communication protocol based in an ADELBus network.
on MODbus-RTU or CANbus technology • ADELView System is a PC-based software
developed to monitor in real time every important
depending on the application field. It allows
parameter of the Battery Chargers. A simple
to communicate with all devices provided by
and intuitive user’s interface allows monitoring
ADELSystem and to develop an independent
of battery parameters, load output, temperature
system for electrical continuity. Monitoring and sensor, mains presence and all alarm and
control of all parameters in the system, even diagnostic flags. All features are displayed on a
from the other side of the world, by means of single screen.
application tools and Cloud. • ADELView app, application for tablet, you can
ADELSystem allows you to implement very visualize in real time data stored on your own
simple but sophisticated monitoring and control device.
for your energy system and opens your mind to • ADELView Cloud, a suite available to all
new ways to approach your applications. customers. Main function as Data Logger for all
parameters coming from the connected devices.
• ADELView Config: interface that allows
Everything and more!
application engineers to configure the system,
• More efficiency for the battery thanks to customize battery charging curve, set alarm
continuous control over time. thresholds, configure parameters, Demo for
• More monitoring features in the main customers.
connection nodes: input , output load, battery. Everything is available in free download on the
• Event logging: number of battery charging Web page.
cycles, charge cycles completed, aborted
charge cycles, Ah charged, charging time, ADELVIEW GRAPHIC
total number of transitions stand-by /back-up The Device is a robust multifunction display. It
allows to monitor, configur and manage the Adel
etc...
System’s devices connected in an ADELBus
• Event Management: checking the load output,
network. It has a high-brightness and wide
shutdown management of PCs (UPS function),
viewing-angle 3.5’’ TFT-LCD screen which
RESET management of a generic equipment. guarantees an optimum visibility in any operating
• Flexibility of use: customization of the entire condition. The user interface is clear, intuitive and
battery charging curve, battery type setting, allows configuring and managing the connected
setting boost voltage, absorption, float, etc... devices in a quick and straightforward way.
configuration as Batteries Charger, Enabling Moreover, using the on-board Ethernet interface
power supply function. it is possible to remotely manages the ADELBus
network through Internet with a PC or a mobile
device. At the same time, the Device can act as a
gateway that implements standard protocols such
as Modbus TCP/IP and SNMP.
From the Display you can manages all the
connected devices allowing:
• Monitoring
• Configuration
• Alarms management
• Events program, i.e. programmed actions that
are coordinated among the devices
ADEL VIEW
SYSTEM CONTROLLER

BATTERY ETHERNET

ADEL VIEW
GRAPHIC

DPY353

TEMPERATURE
SENSOR

110/240 VAC

CONTROLLER BATTERY TEMPERATURE DPY353


You can connect the Device directly By installing the battery temperature “DPY353” is a circular LED display
to the GenSet Controller by protocol probe “RJ Temp”, the charging device for panel mount. Simple and
Can J1939. voltage is automatically adapted to sturdy, it displays the current charge
battery temperatures. mode, state of charge and system
ADELBUS When battery temperature is low, diagnostics at a glance.
ADELSystem network, interconnect the charging voltage increases.
all Devices in Canbus and Modbus. Conversely, when battery
temperature is high, charge voltage
BATTERY is decreased. Over charging and
You can recharge and Test all Battery gassing are thus prevented.
types: Open Lead Acid, Sealed Lead This will extend battery life, it is a
Acid, AGM Sealed Lead Acid, Gel, Ni/ part of Battery Care Philosophy.
Cd. Any Size is taken in Care.

Battery Care Catalogue ADELSystem Srl 3


Charging & Testing
CHARGING
One device for all battery types Multi-Stage charging Recovery charging
All devices are suitable to charge Four charging modes Automatic multi-stage operation
most battery types thank to user Automatic multi-stage operation optimizes and adapt to battery status,
selectable charging curves. They and real time diagnostic allow fast even when the battery voltage is very
can charge open lead acid, sealed recharge and recovery of deeply low. CB can recharge batteries even
lead acid, Gel, Ni-Cd, Ni-MH, Li Ion discharged batteries, adding value when their voltage is close to zero. It
batteries. It is possible to change or and reliability to the system hosting allows recharge and complete recov-
add other charging curves connecting the Battery Charger device. The type ery of flat batteries.
the device to a portable PC. Charging of charging is Voltages stabilized and
mode is then completely automatic. Current stabilized IUoU.
Battery Charger feature four charging
modes, identified by a flashing code
JUMPER POSITIONS / VPC:
on a LED.
Open Lead Acid:
Float 2.23V Boost 2.40V • Recovery (5 Blinks / sec) able to
(factory preset)
recharge batteries even when their
Sealed Lead Acid (1): voltage is close to zero
Typical charging curve for
Float 2.25 Boost 2.40V • Boost - Bulk (2 Blinks / sec)
recovery of batteries with voltage
• Absorption (1 Blinks / sec) close to zero.
AGM Sealed Lead Acid (2): • Float (1 Blink / 2 sec)
Float 2.27 Boost 2.40V

Gel: Float 2.30V Boost Recovery Float


2.40V (blink 5/sec.) (blink 1/sec.)
Adjustable charging current
Ni/Cd
LI-Ion The maximum battery charging cur-
rent can be set from 10% to 100% of
the device rated value.

Boost - Bulk
(blink 2/sec.)
Diagnosis

Jumper for
Battery Type
Selection

4 Battery Care Catalogue ADELSystem Srl


TESTING
Battery and Device Diagnosis Battery Life Test Diagnostic checks “during
All CB devices support the user For battery reliability during time. operation”
during installation and operation. A The device detects each two hours
LED flashing sequence code allows to the internal Battery impedance, to
discriminate among various possible avoid any possible risk of damages ACCIDENTAL DISCONNECTION
CABLES
faults. and grant a permanent and reliable
Detect accidental disconnection
battery connection on the device. and immediately switches off
The device, through inside battery output power.
ERROR CONDITIONS, LED FAULT detection circuit recognizes sulphated
ON AND LED DIAGNOSIS FLASHING batteries or batteries with a short- BATTERY NOT CONNECTED
WITH SEQUENCE OF: If the battery is not connected the
1 flash = Reverse polarity, wrong circuited or open cell.
battery output is disabled.
battery voltage
2 flashes= Disconnected battery TEST OF WIRE CONNECTION
3 flashes = Battery element in IMPEDANCE
short circuit During Float charge the resistance
4 flashes = Overload on the battery connection is
5 flashes = Battery to be replaced checked every 20 sec. This to
(Internal impedance Bad or Bad detect if the cable connection has
battery wire connection) been properly made.
Diagnosis
BATTERY IN OPEN CIRCUIT OR
SULPHATED
Every Two hours detect the internal
impedance, while in Float charging
mode.

REVERSE POLARITY CHECK


Diagnosis
Temperature Compensation If the battery is connected with
inverted polarity, the device is
In special application like Fire automatically protected.
prevention System, you can recharge
the battery also with temperature TEST OF BATTERY VOLTAGE
CONNECTIONS
compensation charging function, for
Appropriate voltage check, to
the best condition of your battery in prevent connection of wrong
high temperature environment. battery types.

END OF CHARGE CHECK


When the battery is completely full,
the device automatically switches
to Float charging mode.

CHECK FOR BATTERY CELLS IN


SHORT CIRCUIT
Thanks to specific testing
algorithms, the CB recognize
batteries with cells in internal short
circuit.

Battery Care Catalogue ADELSystem Srl 5


General Data Input - Output
Maximum safety and protection
Wide input voltage range
All Battery Charger ADELSystem are designed to
provide safe operation and long power supply and Flexibility is given also by the wide range input voltage.
All devices accept input voltage 115 / 230 / 277 Vac.
battery life. The following protections are standard
features:
• Outputs protected against short circuit and 230 Vac
overload
• Outputs in conformity to SELV and PELV

ac

27
5V

7V
conditions

11

ac
• High insulation between primary and secondary
INPUT
• Protection against deep battery discharge FLEXIBILITY
• Protection against reverse polarity connection
• Detection of batteries with wrong rated voltage
All protections have automatic reset. No thermal
fuse to be replaced.

Technology One device for Output 12 or 24 Vdc


The Battery Charger range is based on two You can select the voltage between 12 or 24 Vdc just
strategic know-how elements before installing the device in your panel (available on
SWITCHING TECHNOLOGY some products in the ADELSystem range).
ADELSYSTEM has a 25 year experience in design
of advanced stabilized switching technology power
c
supplies. A power supply/battery charger unit Vd
24
based on this technology is much more efficient.
BATTERY CARE
Unlike most other state-of-the-art battery chargers,
the Battery Charger ADELSystem are equipped
with complex algorithms which controls the
c
charging process and enable several monitoring Vd
12
functions. The firmware implements the extended
Adel battery care know-how, result of many years
of experience in this field

Robust construction and easy


installation Power Supply Function
All the units in the range have aluminium casing, On some devices it is possible to enable the power
DIN rail fastening clip and are light and compact. supply function, to provide power also when the
IP20 protection degree. battery is disconnected from output battery output.
Enabling by Jumper:
Norms
In Conformity to: Safety EN IEC 62368-1, Emission:
IEC 61000-6-4, Immunity: IEC 61000-6-2; EN60950
/ UL1950; Electrical Safety EN54-4 Fire Detection
and Fire Alarm Systems; EMC Directive; DIN41773
(Charging Cycle); UL1236; Directive, 2014/35/UE
(Low Voltage); CE. CONTROLLER
- +
Vac

Diagnosis & BATTERY


State of battery

BATTERY FAULT
IF DISCONNECTED
Connections & Monitoring

Monitor Signals Driver Comand Accessories


Clear definition of each system Remote link for selection of Float/ Temperature sensor Probe, for
operation, via LED indications and Boost charging via RTCONN remote ambient temperature compensation
Relay contacts: connections cable, it is possible to charging.
drive the devices from Boost to Float
charge.
CONTACT PORT SIGNALS, It is also possible to permanently put
GALVANIC INSULATED a jumper for Boost Charging.
Mains or back-up conditions
Battery or system fault
Flat battery

Auxiliary Output
“Aux 2 and Aux 3”
ADELBus network in Can J1939 or
Boost flat charge ModBus, for the connection to net
ADELsystem devices and connection
to external Controller ex. GenSet.

DISPLAY SIGNALS BY LED


Input: Mains or Back Up
Battery or system Fault C
Low battery (capacity less than AUX 2
A
30%) N
Type of Charging mode J
Autodiagnosis true through 1
9
“blinking code” AUX 3
3
9

Battery Care Catalogue ADELSystem Srl 7


Battery Care 12-24 Vdc
115 - 230 - 277 Vac
12 Vdc
115 - 230 - 277 Vac

Model CB12245A CB122410A CB123A CB6012A


12 Vdc - 6A 12 Vdc - 15A
Output 12 Vdc - 3A 12 Vdc - 3A
24 Vdc - 5A 24 Vdc - 10A
INPUT Nominal Input Voltage 115 - 230 - 277 115 - 230 - 277 115 - 230 - 277 115 - 230 - 277
DATA
Frequency (Hz) 47- 63 Hz ± 6% 47- 63 Hz ± 6% 47- 63 Hz ± 6% 47- 63 Hz ± 6%
OUTPUT 12 Vdc - 6A
DATA 12 Vdc - 15A
Output Vdc / IN 24 Vdc - 5A (230 Vac) 12 Vdc - 3A 12 Vdc - 3A
24 Vdc - 10A
24 Vdc - 4A (120 Vac)
Efficiency (50% of IN) >90% >91% >81% >81%
Over Load and Short-circuit protection ✔ ✔ ✔ ✔
Overheating Thermal Protection ✔ ✔ ✔ ✔
Reverse polarity protection ✔ ✔ ✔ ✔
Power Supply Function ✔ ✔ ✘ ✘
BATTERY 14.4 Vdc (12 Vdc) 14.4 Vdc (12 Vdc)
CHARGER Boost - Bulk charge (Typ. at IN) 14.4 Vdc 14.4 Vdc
28.8 Vdc (24 Vdc) 28.8 Vdc (24 Vdc)
OUTPUT
Max. Time Boost-Bulk charge (Typ. at IN) 15 hr 15 hr 15 hr 15 hr
Min. Time Boost-Bulk charge (Typ. at IN) 4 min. 1 min. 70 min. 70 min.
13.75 Vdc (12 Vdc) 13.8 Vdc (12 Vdc)
Float charge (Typ. at IN) 13.75 Vdc 13.75 Vdc
27.50 Vdc (24 Vdc) 27.6 Vdc (24 Vdc)
3-8 Vdc (12 Vdc) 2-10 Vdc (12 Vdc)
Recovery Charge 2 - 7 Vdc 2 - 7 Vdc
6-18 Vdc (24 Vdc) 2-20 Vdc (24 Vdc)
Charging current Limiting IN (Iadj) 20 ÷ 100% / Ibatt 20 ÷ 100% / Ibatt 20 ÷ 100% / Ibatt 20 ÷ 100% / Ibatt
Boost Charge Enabling ✔ ✔ ✘ ✘
Output Voltage Selection 12 / 24 12 / 24
Charging Curve
SIGNAL
Mains or Backup Power ✔ ✔ ✔ ✘
OUTPUT
(RELAY)
Low Battery and Fault Battery ✔ ✔ ✔ ✔
CONNECTION Temp. Compensation Charging probe ✘ ✔ ✘ ✘
& MONITO-
RING
Adel Bus CB12245AJ: Can J1939 Modbus ✘ ✘
CLIMATIC Ambient Temperature (operation) -25 - +70 °C -25 - +70 °C -25 - +70 °C -25-+70°C
DATA
Derating Tª > (In) >40°C 2.5% >50°C 2.5% >50°C 2.5% >50°C 2.5%
Automatic Derating ✔ ✔ ✘ ✘
Ambient Temperature Storage -40 - +85 °C -40 - +85 °C -40 - +85 °C -40-+85 °C
Humidity at 25 °C, no condensation 95% at 25°C 95% at 25°C 95% at 25°C 95% at 25°C
GENERAL Insulation Voltage (IN / OUT) 3000 Vac 3000 Vac 3000 Vac 3000 Vac
DATA
Insulation Voltage (IN / PE) 1605 Vac 1605 Vac 1605 Vac 1605 Vac
Insulation Voltage (OUT / PE) 500 Vac 500 Vac 500 Vac 500 Vac
Protection Class (EN / IEC 60529) IP 20 IP 20 IP 20 IP 20
Reliability: MTBF IEC 61709 > 300 000 hr > 300 000 hr > 300 000 hr > 300 000 hr
Environment Pollution Degree 2 2 2 2
6 mm (30-10 AWG)
Terminal Blocks Connection Screw Type 2,5 mm 2,5 mm 2,5 mm
2,5 mm (24-14 SWG)
Dimensions (w-h-d) mm 45x110x105 115x115x135 45x110x105 45x100x100
1
Safety Standard Approval CE CE CE CE
OPTIONAL ADELView Graphic ✔ ✔ ✘ ✘
ADELView System ✔ ✘ ✘
ADELBus ✔ ✔ ✘ ✘
(1) UL 1236
(2) UL 60950

8 Battery Care Catalogue ADELSystem Srl


24 Vdc
115 - 230 - 277 Vac

CB1210A CB1235A CB243A CB6024A CB2410AC CB2420A


12 Vdc - 10 A 12 Vdc - 35 A 24 Vdc - 3A 24 Vdc - 3A 24 Vdc - 10A 24 Vdc - 20A

115 - 230 - 277 115 - 230 - 277 115 - 230 - 277 115 - 230 - 277 115 - 230 - 277 115 - 230 - 277
47- 63 Hz ± 6% 47- 63 Hz ± 6% 47- 63 Hz ± 6% 47- 63 Hz ± 6% 47- 63 Hz ± 6% 47- 63 Hz ± 6%

12 Vdc - 10A 12 Vdc - 35A 24 Vdc - 3A 24 Vdc - 2A 24 Vdc - 10A 24 Vdc - 20A

>89% >91% >81% >81% >88% >91%

✔ ✔ ✔ ✔ ✔ ✔

✔ ✔ ✔ ✔ ✔ ✔

✔ ✔ ✔ ✔ ✔ ✔

✘ ✘ ✘ ✘ ✘ ✘

14.4 Vdc 14.4 Vdc 28.8 Vdc 28.8 Vdc 28.8 Vdc 28.8 Vdc

15 hr 15 hr 15 hr 15 hr 15 hr 15 hr
1 min. 1 min. 1 min. 1 min. 1 min. 1 min.

13.75 Vdc 13.75 Vdc 27.5 Vdc 27.5 Vdc 27.5 Vdc 27.5 Vdc

2 - 9 Vdc 2 - 9 Vdc 2 - 16 Vdc 2 - 16 Vdc 2 - 18 Vdc 2 - 7 Vdc

20 ÷ 100% / Ibatt 10 ÷ 100% / Ibatt 20 ÷ 100% / Ibatt 20 ÷ 100% / Ibatt 20 ÷ 100% / Ibatt 10 ÷ 100% / Ibatt

✔ ✔ ✘ ✘ ✔ ✔

IUoUo, Automatic, 3 stage

✔ ✔ ✔ ✘ ✔ ✔

✔ ✔ ✔ ✔ ✔ ✔

✔ ✔ ✘ ✘ ✔ ✔

✘ ModBus ✘ ✘ ✘ ModBus
-25 - +70 °C -25 - +70 °C -25 - +70 °C -25 - +70 °C -25 - +70 °C -25 - +70 °C
>40°C 2.5% >50°C 2.5% >50°C 2.5% >50°C 2.5% >50°C 2.5% >50°C 2.5%
>40 °C ✔ ✘ ✘ ✘ ✔
-40 - +85 °C -40 - +85 °C -40 - +85 °C -40 - +85 °C -40 - +85 °C -40 - +85 °C
95% at 25°C 95% at 25°C 95% at 25°C 95% at 25°C 95% at 25°C 95% at 25°C
3000 Vac 3000 Vac 3000 Vac 3000 Vac 3000 Vac 3000 Vac
1605 Vac 1605 Vac 1605 Vac 1605 Vac 1605 Vac 1605 Vac
500 Vac 500 Vac 500 Vac 500 Vac 500 Vac 500 Vac
IP 20 IP 20 IP 20 IP 20 IP 20 IP 20
> 300 000 hr > 300 000 hr > 300 000 hr > 300 000 hr > 300 000 hr > 300 000 hr
2 2 2 2 2 2

2,5 mm 4 mm 2,5 mm 2,5 mm 2,5 mm 4 mm

65x115x135 150x115x135 45x110x105 45x110x105 100x115x135 150x115x135


2 2 2 2
CE CE CE CE CE CE

✘ ✔ ✘ ✘ ✘ ✔

✘ ✘ ✘ ✘ ✘ ✘

✘ ✔ ✘ ✘ ✘ ✔

Battery Care Catalogue ADELSystem Srl 9


Battery Care 12 Vdc
48 Vdc
30 Vdc
115 - 230 - 277 Vac
36 Vdc
115 - 230 - 277 Vac

Model CB123A/48 CB304A CB363A


Output 12 Vdc - 3A 30 Vdc - 3A 36 Vdc - 3A
INPUT Nominal Input Voltage 35 - 72 115 - 230 - 277 115 - 230 - 277
DATA

Frequency 47- 63 Hz ± 6% 47- 63 Hz ± 6%


OUTPUT Output Vdc / IN 12 Vdc - 3A 30 Vdc - 3A 36 Vdc - 3A
DATA

Efficiency (50% of IN) >81% >81% >81%

Over Load and Short-circuit protection ✔ ✔ ✔

Overheating Thermal Protection ✔ ✔ ✔

Reverse polarity protection ✔ ✔ ✔

Power Supply Function ✘ ✘ ✘


BATTERY Boost - Bulk charge (Typ. at IN) 14.4 Vdc 36 Vdc 43.2 Vdc
CHARGER
OUTPUT
Max. Time Boost-Bulk charge (Typ. at IN) 15 hr 15 hr 15 hr

Min. Time Boost-Bulk charge (Typ. at IN) 70 min. 1 min. 1 min.

Float charge (Typ. at IN) 13.75 Vdc 33.45 Vdc 40.14 Vdc

Recovery Charge 2 - 7 Vdc 2 - 29 Vdc 2 - 29 Vdc

Charging current Limiting IN (Iadj) 20 ÷ 100% / Ibatt 20 ÷ 100% / Ibatt 20 ÷ 100% / Ibatt

Boost Charge Enabling ✘ ✘ ✘

Output Voltage Selection ✘ ✘ ✘

Charging Curve IUoUo, Automatic, 3 stage


SIGNAL Main or Backup Power ✔ ✔ ✔
OUTPUT
(RELAY)
Low Battery and Fault Battery ✔ ✔ ✔
CONNECTION Temp. Compensation Charging probe ✘ ✘ ✘
& MONITO-
RING
Adel Bus ✘ ✘ ✘
CLIMATIC Ambient Temperature (operation) -25 - +70 °C -25 - +70 °C -25 - +70 °C
DATA

Derating Tª > (In) >50°C 2.5% >50°C 2.5% >50°C 2.5%

Automatic Derating ✘ >40 °C >40 °C

Ambient Temperature Storage -40 - +85 °C -40 - +85 °C -40 - +85 °C

Humidity at 25 °C, no condensation 95% at 25°C 95% at 25°C 95% at 25°C


GENERAL Insulation Voltage (IN / OUT) 3000 Vac 3000 Vac 3000 Vac
DATA

Insulation Voltage (IN / PE) 1605 Vac 1605 Vac 1605 Vac

Insulation Voltage (OUT / PE) 500 Vac 500 Vac 500 Vac

Protection Class (EN / IEC 60529) IP 20 IP 20 IP 20

Reliability: MTBF IEC 61709 > 300 000 hr > 300 000 hr > 300 000 hr

Environment Pollution Degree 2 2 2

Terminal Blocks Connection Screw Type 2,5 mm 2,5 mm 2,5 mm

Dimensions (w-h-d) mm 45x110x105 45x110x105 45x110x105

Safety Standard Approval CE CE CE


OPTIONAL ADELView Graphic ✘ ✘ ✘

ADELView System ✘ ✘ ✘

ADELBus ✘ ✘ ✘

10 Battery Care Catalogue ADELSystem Srl


Adel View Graphic

110/240 VAC

POWER

ETHERNET

BATTERY
DISPLAY
TEMPERATURE
SENSOR

CONTROLLER

The DPY351 is a robust and What does it do? Alarms and Recorder
versatile multifunction display that
From ADELBus network (ADELSystem management
allows monitoring, configuring and • Setting Alarm threshold
network) manages all the connected
managing the ADELSystem devices • Receive Message from other
devices allowing:
connected in an ADELBus network. devices
It is equipped with a high-brightness • Event Record
Monitoring
and wide viewing-angle 3.5’’ TFT
• Event logging: number of battery
screen which guarantees an optimum
charging cycles, charge cycles Events program, i.e.
visibility in any operating condition.
completed, aborted charge cycles, programmed actions
The user interface is clear, intuitive • Coordinated action among devices
Ah charged, charging time, total
and allows configuring and managing • Program Event to other device to
number of transitions stand-by /
the connected devices in a quick and change the type of charging curve
back-up etc.
straightforward way. Moreover, using • Checking the load output, shutdown
• Status of Charging Battery
the on-board Ethernet interface it management Reset.
is possible to remotely manage the
Configuration
ADELBus network through Internet
• Charging curve,
with a PC or a mobile device. At the
• Battery type,
same time, the DPY351 can act as a
• Limitation charging Current
gateway that implements standard
• Enabling power supply function
protocols such as Modbus TCP/IP and
• Timer…
SNMP.

Battery Care Catalogue ADELSystem Srl 11


PRODUCT RANGE

G R A PH I C D ES I G N: DAV I D E PLO I A
DC UPS “ALL IN ONE” FLEX D-FLEX CB
DC UPS “All In One”DC Power DIN rail Switching Power High efficiency Power Supply The Best generation of Battery
Back Up units. Multi-function Supplies. Very compact in size, in Mini Size Dimension, for all Charger with 4 level of charge,
devices: power supply, battery 150% power boost, wide input kind of small power request in a Auto Diagnosis system inside.
charger and back-up module in voltage range 110 - 230 - 400 flat control panel. For Domotic, One product for all battery types.
the same casing together with - 500 Vac. Selectable output Domestic and Industrial field.
Adel Battery Care software. protection mode.

POWER SUPPLY DC/DC CONVERTER INTERFACES BATTERY BANK


LOW INPUT VOLTAGE Dc / Dc Converter, step Up Wide range of passive interfaces Power Storage Devices, for
Switching power suppy for and Step down. Input - Output units for Input and Output connection to DC Ups Products.
direct connection to secondary isolated, low voltage. With or connections, for PLC and CNC Battery size: 1.2; 3; 7,2; 12 Ah,
transformer. In 24 Vac. Out 12 - 24 without DIN Rail. machine. 24 Vdc.
- 48 Vdc Watt: 25 - 460.

AUXILIARY MODULE SFP SAFETY POWER POWER VIEW GRAPHIC ADEL VIEW SYSTEM
Decoupling Modules for Power continuity solutions for Robust Display wide viewing- Suite for remote monitoring and
redundancy applications. alarm systems and fire alarms. angle 3.5’’ TFT. ADELBus management devices connected
Electronic Fuses for Over Load Available as a fully enclosed device network. Gateway for Ethernet in in an ADELBus network. Features:
output control, up to 4 cannel. conforming with EN54.4 or as a Modbus TCP and SNMP. PC software; iOS and Android;
component to be integrated in Cloud latform; Advanced features
other instrumentation. for installation and demonstration
purposes.

I N N O V AT I O N A N D M U LT I M E D I A L I T Y
ADELSystem continues to implement oped comes with ADELBus inside. The view in the search of innovation.
its offering of innovative and functional Power Continuity products ADELSystem ADELBus, the ADELViewsystem and the
products as a company specializing in the are enhanced by Multimedia devices like ADELViewgraphic are the connecting
electrical continuity for the DIN Rail field. Display and Software APPlications for the elements to DC Ups, Power Supply and
The wide range of available products new way towards Industry 4.0. Battery Charger for catching all of the
is now involved in the Interconnection These, are innovative solutions has been parameters inside the device.
field through the ADELBus protocol developed by the ADELSystem R&D team All of this, to involve you into a new
implemented in the main devices of our for the expert electrical designer and the evolution of Actions both for today and
products range. Every new device devel- user who need to change their point of next-future life.

Adel System srl


Via Luigi Barchi 9/B · 42124 Reggio Emilia · Italy
tel. +39 0522 345518 · info@adelsystem.it
www.adelsystem.com

© ADELSystem srl. The copying, distribution and utilization of this document as well as the communication of its contents
to others without expressed authorization is prohibited. All data in this publication are subject to change without information.