(1.2orS phases) Projectva Earth No
(PEN or tne in
ean | Fyn
“ese fff Gen
i
\
‘esto i
‘Submain Novi —
Protective Earth Moutral PEN)
coparate MEW inetalsion |
Netra ar
: i
Eartha sae) |
7 Potovive carting conductor (PE)
foigntng pert
3 Prctectve eastning
eauibmen 2)5.1.3 MEN earthing system
The protective earthing arrangements required in this Standard apply to
electrical installations connected to the multiple earthed neutral (MEN)
distribution system that forms the standard distribution system used in
Australia and New Zealand
Under the MEN system, the neutral conductor (PEN) of the distribution
system is earthed at the source of supply at regular intervals throughout the
system and at each electrical installation connected to the system. Within
the electrical installation, the earthing system is separated from the neutral
conductor and is arranged for the connection of the exposed conductive
parts of equipment.
ASINZS 3000:2018 288
NOTES:
1. The MEN system as installed in Australia and New Zealand differs from the
IEC system. Both systems are identical in principle but vary in detail. For
further details refer to AS/NZS 61439 and AS/NZS 3007.
2 The MEN system and its various parts are illustrated in Figures 5.1 and 5.2.
Figure 5.1. shows a general arrangement and Figure 5.2 an alternative
artangement in an owner of user operated supply substation installation
IEC 60364 series describes the MEN system as a TN-C-S system with the
letters signifying—
T the distribution system is directly connected to earth—at the neutral
Point of the supply transformer:
N_ the exposed conductive parts are connected to the earthed point of the
distribution system—at the MEN connection;
C_ the neutral and protective conductor functions are combined in a single
conductor (the neutral conductor of the distribution system);
S the protective conductor function is separated from the neutral—
separate conductors within the installation.5.3.3. Earthing conductor size (cross-sectional area)
5.3.3.1 Protective earthing conductors
5.3.3.1.1 General
The cross-sectional area of a protective earthing conductor shall
ensure—
(a)
(b)
(c)
(d)
adequate current-carrying capacity for prospective fault currents
for a time at least equal to the operating time of the associated
overcurrent protective device;
appropriate earth fault-loop impedance (see Clause 5.7);
adequate mechanical strength and resistance to external
influences; and
for parts of the protective earthing conductor that do not consist
of cables, or parts of cables, that there is an allowance for the
subsequent deterioration in conductivity that may reasonably be
expected.
5.3.3.1.2 Selection
The cross-sectional area of any copper protective earthing conductor
required for the protection of any portion of an electrical installation shall be
determined either—
(a)
from Table 5.1 in relation to the cross-sectional area of the largest
active conductor supplying the portion of the electrical installation to
be protected; orTABLE 5.1
MINIMUM COPPER EARTHING CONDUCTOR SIZE
Nominal size of copper earthing conductor,
Nominal size of mm?
active conductor ———__—_—_——
mm? With copper active | With aluminium active
conductors conductors
1 °
15 1.5*
25 25
4 25
6 2.5
10 4
16 6 4
25 6 6
35 10 6
50 16 10
70 25 10
95 25 16
120 35 25
150 50 25
185 70 35
240 95 50
300 120 70
400 2120t 298t
500 >120t >95t
630 2120+ >120t
>630 225% of active sizet 225% of active sizet
5.3.3.2 Main earthing conductor
Where the main earthing conductor connects the main earth terminal to an
electrode (arrangement depicted in Figure 5.1), the conductor shall be
determined from Table 5.1 in relation to the cross-sectional area of the
largest active conductor of the consumer mains,
The cross-sectional area of such a copper main earthing conductor shall be
not less than 4 mm? and need not be greater than 120 mm?,5.3.4 Main earthing terminal/connection or bar
(a) Protective earthing conductors.
(b) Main earthing conductor.
(c) MEN connection.
(4) Equipotential bonding conductors.
(e) Functional earthing conductors, if required.
NOTE: A main earthing terminal/connection may be a soldered connection.
5.3.5 MEN connection
5.3.5.1 General
5.3.5.2 Size
The MEN connection shall be a conductor complying with Clause 5.3.2 and
have a cross-sectional area capable of carrying the maximum current that it
May be required to carry under short-circuit conditions.
The minimum size shall be—
(a) not less than the current-carrying capacity of the main neutral
conductor; or
5.3.6 Earth electrodes
5.3.6.1 General
NOTE: No specific value of resistance to earth is required by this Standard for
(thelearthvelectrode at an electrical installation connected to a MEN system.
guidance on methods of measurement of resistance to earth and earth fault-
loop impedance.5.3.6.2 Types
Materials and dimensions of earth electrodes shall be selected to withstand
corrosion and to have adequate mechanical strength.
NOTE: Consideration should be given to the nature of the soil and
environmental conditions.
Earth electrodes shall be of a type and shall be installed in accordance with
Table 5.2.
TABLE 5.2
ACCEPTABLE EARTH ELECTRODES
Minimum:
Material | Surface treatment Minimum Surface
imensions treatment
thickness
Vertical electrodes
Stool Copper clad 212 mm circular rod 250 um
Copper plated (212 mm circular rod 250 jum
Stainless (including 12 mm circular rod 500 um
clad with stainless)
Hot dipped (216 mm circular rod 63 um
galvanized
Hot dipped Section with minimum cross 63 um
galvanized sectional area of 200 mm? and
with no part less than 3 mm thick
Non-ferrous Solid 12mm NA
(excluding
aluminium)
Horizontal (strip) electrodes
Copper tod Solid @7 mm circular NA
Copper strip Solid 25 mm » 1.6 mm NA
Copper pipe Bare 215 mm circular x 2.45 mm wall NA
thickness
Copper cable Bare 25 mm? NIA
Steel pipe Hot dipped ‘20 mm circular x 3 mm wall 63 um
galvanized thickness
Steel strip Hot dipped 40 mm x 3 mm 63 um
galvanized5.3.6.3 Installation
‘Vertical-type earth electrodes shall be driven to a minimum depth of— __
(a)_ in Australia, 1.2 m; and
(b)_ in New Zealand, 1.8 m.
() Gevustratiagsim) and
(ii) in New Zealand, 7.5 m.
Earth electrodes shall be installed in a location that satisfies the following
conditions:
(a) The electrode maintains effective contact with moist soil that is not
subject to excessive drying out.
NOTE: This condition is deemed to be satisfied by locating the electrode—
(a) external to the building in ground that is exposed to the weather; or
(b) in other locations where the ground remains moist because of soil
conditions or covers that reduce loss of moisture.
NZ|
>
NZ|
(b)
5.5.1.4 ResistanceMain neutral
Jeanductor (PEN)
MEN
lconnection stain earth bar
9 terminal/connection
aint
Neutral bar _ switchboard |
Subcircults
supplied
irom main
switchboars
B 2 Active conductors for
DB2 supplied from DB
*5.5.2.110)
Subciroulte
supplied
from DB2
‘Subeireuits
Eartn supplied
slectrose from 08
"5.3.6 and
“5.5.1.2 and
ae LeGeno:
Clause number
Protective earthing conductor (PE)
Earthing connection at equipment
‘or exposed conductive part
= Distaibution board
Switchboard earth bar
‘or terminal’ connection
FIGURE 5.3 EXAMPLES OF EARTHING ARRANGEMENTSASINZS 3000:2018 300
Conductive ewitehboard enclosure
To installation main
Energy metering | switch or switches
arrangement
Main Neutral tink
Main Neutral
Concuctor
main Earin bar
‘Service
Neutral earthing
jeenductor
Service
protective
‘devies Main earthing
‘conductor
Double Insulation
shall be fully
maintained to the
service protection
dovioe
Double insulates consumers
maine in'a wirng encloure
ASINZS 60079.14:2017 45
6.3.2 TN type of system earthing
Ia type of system earthing TN is used, it shall be type TN-S (with separate
> size of the main
earthing conductor.
Clause 8.5.35)
NOTE 1
neutral N and
protective conductor PE) in the hazardous area, i.e. the neutral and the protective conductor
Shall not be connected together, or combined in a single conductor, in the hazardous area. At
any point of transition from TN-C to TN-S, the protective conductor shall be connected to the
equipotential bonding system in the non-hazardous area6.4 Potential equalization
6.4.1 General
TT and IT
systems,
The bonding system may include protective conductors, metal conduits,
metal cable sheaths, steel wire armouring and metallic parts of structures, but shall not
include neutral conductors. Connections shall be secure against self loosening and shall
minimise the risk of corrosion which may reduce the effectiveness of connection.
|
Exposed conductive parts need not be separately connected to the equipotential bonding
system if they are firmly secured to and are in conductive contact with structural parts or
piping which are connected to the equipotential bonding system. Extraneous conductive parts
which are not part of the structure or of the electrical installation, for example frames of doors
or windows, need not be connected to the equipotential bonding system, if there is no danger
of voltage displacement,
Installations with cathodic protection shall not be connected to the equipotential bonding
system unless the system is specifically designed for this purpose.65.1 General
The requirements of 6.5.1 apply to external non-metallic materials used for construction or
protecting purposes that are not part of certified equipment (e.g. plastic covered cable tray,
plastic mounting plates, plastic weather protection and enclosures).
NOTE 1 Non-n
provide addit
alic paints, fims, fos, and plates are typically atachod to external surfaces of metallic parts to
‘environmental protection. Their ably ta Store an electrostatic charge is addressed by 6.5.
NOTE 2 itis generally acknowledged that glass is not susceptible to storing an electrostatic charge.
NOTE 3 Further information can be found in IEC TS 60079-22-1 and IEC 60079-22-2 (under consideration)
6.5.2 Avoidance of a build-up of electrostatic charge on construction and protecting
parts for locations requiring EPL “Ga", “Gb” and “Gc”
Construction and protecting parts shall be so designed that under normal conditions of use,
maintenance and cleaning, danger of ignition due to electrostatic charges is avoided. This
requirement shall be satisfied by one of the following:
a) By suitable selection of the material so that maximum surface resistance complies with
either of the limits given below when measured in accordance with IEC 60079-0
= 1090 measured at (50 + 5) % relative humidity; or
- 10" measured at (304 5) % relative humidity.
)_ By limitation of the surface area of non-metallic parts as shown in Table 6
The surface area is defined as follows:
— for sheet materials, the area shall be the exposed (chargeable) area,
— for curved objects, the area shall be the projection of the object giving the maximum
area;
— for individual non-metallic parts, the area shall be evaluated independently if they are
separated by conductive earthed frames.
The values for surface area can be increased by a factor of four if the exposed area of
non-metallic material is surrounded by and in contact with conductive earthed frames9)
d)
Alternatively, for long parts with non-metallic surfaces, such as tubes, bars, of ropes. the
surface area need not be considered, but the diameters or widths shall not exceed the
values shown in Table 8. Cables for connection of external circuits are not considered to
fall under this requirement.
By limitation of a non-metallic layer bonded to a conductive surface. The thickness of the
non-metallic layer shall not exceed the values shown in Table 7 oF the breakdown voltage
shall be < 4 kV (measured across the thickness of the insulating material according to the
method described in IEC 60243-1).
Where the construction and protecting parts are used in the installation in such a way that
the risk from electrostatic discharge is minimized, these parts shall be marked with the
following warning label’
WARNING ~ POTENTIAL ELECTROSTATIC CHARGING HAZARD
Table 5 — Limitation of surface areas
‘Construction and protecting parts (mm)
Equipment Group A Group 1B Group uc
protection lovel
required
EPL Ga 5.000 2500 200
EPL Gb 10 000) 70000 2000
EPL Go 10 000 70.000 2000
Table 6 — Maximum diameter or width
Construction and protecting parts (mm)
Group A Group I Group llc
required
EPL Ga 3 3 1
EPL Gb 30 30 20
EPL Ge 30 30) 20
Table 7 - Limitation of thickness of non-metallic layor
‘Construction and protecting parts. (mm)
Equipment Group nA Group ue, Group WC
protection level
fequired
EPL Ga 2 2 02
EPL Gb 2 2 02
EPL Ge 2 2 02
These thickness limitations do not apply to non-metallic layers that have a surface
resistance of less than 10° Q or 10" G.as applicable. See IEC 60079.
‘One of main reasons for the thickness limitation is that the maximum thicknese of non-
metalic layer is intended to permit dissipation of charge through the insulation to earth
By this means the static charge Is not able to build up to incendive levels,66
jghtning protection