You are on page 1of 18

BRITISH STANDARD BS 5978-1:

1989

Safety and performance


of gas-fired hot water
boilers (60 kW to 2 MW
input) —
Part 1: Specification for general
requirements

UDC 697.326 – 62:614.8


BS 5978-1:1989

Committees responsible for this


British Standard

The preparation of this British Standard was entrusted by the Gas Standards
Policy Committee (GSE/-) to Technical Committee GSE/28 upon which the
following bodies were represented:

Associated Offices Technical Committee


Boiler and Radiator Manufacturers’ Association Ltd.
British Combustion Equipment Manufacturers’ Association
British Gas plc
Chartered Institution of Building Services Engineers
Department of Energy (Energy Efficiency Office)
Department of the Environment (PSA)
Health and Safety Executive
Institution of Gas Engineers
Liquefied Petroleum Gas Industry Technical Association (UK)
Loss Prevention Council
Society of British Gas Industries

This British Standard, having


been prepared under the
direction of the Gas Standards
Policy Committee, was
published under the authority
of the Board of BSI and
comes into effect on
31 August 1989

© BSI 06-1999

First published September 1983


New edition
Amendments issued since publication

Amd. No. Date of issue Comments


The following BSI references
relate to the work on this
standard:
Committee reference GSE/28
Drafts for comment 76/75448 DC
85/75811 DC
88/70995 DC

ISBN 0 580 17517 0


BS 5978-1:1989

Contents

Page
Committees responsible Inside front cover
Foreword ii
1 Scope 1
2 Definitions 1
3 Additional requirements for boilers 1
4 Electrical requirements 1
5 General conditions of test 1
6 Design and construction 2
7 Flue system 4
8 Flue dampers 4
9 Combustion air inlet dampers 5
10 Gas soundness of burner train 5
11 Temperature 5
12 Heat input 6
13 Combustion 6
14 Manual gas valves 7
15 Controls 7
16 Electricity supply 8
17 Manufacturer’s instructions 8
18 Identification and marking 9
19 Thermal efficiency 9
Figure 1 — Paint scratch test apparatus 11
Table 1 — Surface temperature rise 5
Table 2 — Permissible temperature rise for windings 6
Publications referred to 12

© BSI 06-1999 i
BS 5978-1:1989

Foreword

This Part of BS 5978 has been prepared under the direction of the Gas Standards
Policy Committee and it replaces BS 5978-1:1983, which is withdrawn.
This edition introduces technical changes to bring the standard up to date, by
including alterations made by Amendment No. 1 to the 1983 edition and further
technical changes to clauses 3, 6, 13 and 19. It does not reflect a full review of the
standard, which will be undertaken in due course.
Account has been taken by the committee of experience and current practice, both
national and international, in the preparation of this Part of BS 5978.
The constructional requirements for the boilers are specified in BS 779, BS 855
and BS 2790 and test methods used for the determination of boiler thermal
performance are described in DD 65-11).
BS 5978 is published in three Parts as follows:
— Part 1: Specification for general requirements;
— Part 2: Specification for additional requirements for boilers with
atmospheric burners;
— Part 3: Specification for additional requirements for boilers with forced or
induced draught burners.
A British Standard does not purport to include all the necessary provisions of a
contract. Users of British Standards are responsible for their correct application.

Compliance with a British Standard does not of itself confer immunity


from legal obligations.

Summary of pages
This document comprises a front cover, an inside front cover, pages i and ii,
pages 1 to 12, an inside back cover and a back cover.
This standard has been updated (see copyright date) and may have had
amendments incorporated. This will be indicated in the amendment table on the
inside front cover.

1) Under revision.

ii © BSI 06-1999
BS 5978-1:1989

1 Scope 2.4
water temperature control
This Part of BS 5978 specifies general
requirements, including performance and safety a temperature-actuated control intended to
requirements and methods of test, for gas-fired hot maintain the temperature of the water within the
water boilers operating at internal pressures up boiler between specified limits
to 4.5 bar2) and having heat inputs from 60 kW up NOTE This is the normal means of boiler water temperature
to 2 MW inclusive, calculated on the gross calorific control and should not be confused with the overheat control
defined in 2.2.
value.
NOTE Electrical requirements are given in BS 5986.
2.5
automatic burner system
This Part of BS 5978 applies to cast iron and steel
boilers constructed in compliance with BS 779, a burner system in which, when starting from the
BS 855 or BS 2790 as appropriate. The completely shut-down condition, the start-gas flame
requirements of this Part of BS 5978, in respect of is established and the main gas valve(s) is/are
safety and performance, also apply to boilers actuated by the control without manual
constructed of other materials and for which there intervention
are no constructional standards. NOTE Automatic burners may have pilots which are either
interrupted or intermittent.
This Part of BS 5978 applies to boilers designed for
use with open flues but does not apply to boilers 2.6 non-automatic burner system
designed for use with room-sealed and balanced flue a burner system which is not automatic within the
systems. meaning of 2.5, i.e. a burner with a permanent pilot
This Part of BS 5978 also applies to boilers designed ignited under manual supervision
for use on normal low-pressure district supplies
of 2nd and 3rd family gases. 3 Additional requirements for boilers
NOTE The titles of the publications referred to in this Part of In addition to complying with this Part of BS 5978,
BS 5978 are listed on the inside back cover. the boiler shall comply with either BS 5978-2 or
BS 5978-3, whichever is appropriate to the boiler
2 Definitions design.
For the purposes of this Part of BS 5978 the
following definitions, together with those given in 4 Electrical requirements
BS 1179 and BS 1179-6, apply. Boilers shall comply with BS 5986.
2.1
lock-out 5 General conditions of test
the safety shut-down condition of a control system 5.1 Test facilities. The test room shall be
such that restart cannot be accomplished without adequately ventilated but free from draughts that
manual reset are likely to affect the performance of the boiler.
2.2 The air in the test room shall not contain more
overheat control (limit control) than 1 000 p.p.m. of carbon dioxide or 10 p.p.m. of
a temperature-actuated device which is preset and carbon monoxide.
sealed, and designed to protect the boiler and its The temperature in the test room shall be
surroundings in the event of failure of the water maintained at 20 ± 50 °C.
temperature control NOTE Appropriate test rigs are described in DD 65-1 and
DD 65-2.
2.3
safety shut-down
the action of shutting off all fuel and ignition energy
by means of a safety control such that restart cannot
be accomplished without either manual reset or an
automatic recycle

2) 1 bar = 105 N/m2 = 100 kPa.

© BSI 06-1999 1
BS 5978-1:1989

5.2 Preparation of boiler for testing NOTE 2 In general, except for tests involving governor
performance, the boiler governor may be put out of action and the
5.2.1 The boiler shall be set up in accordance with specified test pressure obtained by adjustment of the gas
the manufacturer’s instructions as relevant to the pressure at the inlet to the boiler.
test and with particular reference to minimum The heat input to the boiler shall be determined as
declared clearances round the boiler. It shall then be specified in BS 4947.
adjusted in accordance with the manufacturer’s
instructions, using the appropriate reference test 6 Design and construction
gas at an inlet pressure of 17.5 mbar for 2nd family
6.1 Design and construction
gases (NGA), with 28 mbar for butane (LPGA)
and 37 mbar for propane (LPGC) for 3rd family 6.1.1 Boiler design. The boiler manufacturer shall
gases. specify whether or not the boiler is designed to
operate in the condensing mode.
5.2.2 Before any tests are made, the boiler shall be
operated for a period sufficient to dry any insulation Where the boiler is not designed to operate in the
and remove any temporary finish that might condensing mode, the manufacturer shall specify
interfere with observations. the minimum return water temperature for which
the boiler is suitable.
5.2.3 Unless the test method specifically requires
otherwise, boilers with a vertical flue outlet shall be 6.1.2 Boiler construction. A cast iron or steel boiler
fitted with the minimum length of vertical shall comply with BS 779, BS 855 or BS 2790 as
secondary flue specified by the manufacturer and appropriate.
having the same nominal diameter as the flue 6.2 Component location. Parts that are intended
outlet. In the absence of a manufacturer’s to be removable for maintenance or for cleaning
specification a 1 m length of flue shall be used for shall be readily accessible, shall be easy to assemble
these tests. correctly and impossible to assemble incorrectly
Boilers with a horizontal flue outlet shall be fitted in where incorrect assembly would create a hazard for
accordance with the manufacturer’s instructions the user or result in damage to the appliance and its
which shall state the maximum length of horizontal controls.
run and method of adaptation to a vertical flue. The burner(s) shall be positively located and so
Thereafter the vertical flue shall be fitted as above. arranged that misalignment cannot occur.
5.3 Test procedure. The boiler, including the It shall not be possible to loosen complete burner
fuel-carrying parts, shall be examined for soundness assemblies, jets or injectors without the use of tools.
before and after completion of the tests specified in 6.3 Materials in contact with gas
accordance with Parts 2 and 3 of this standard as
appropriate. The test results shall be deemed 6.3.1 Copper tubing. Copper tubing shall not be used
invalid unless the system is sound. where it is likely to be exposed to temperatures
above 100 °C.
During testing the initial adjustment of the boiler
shall not be altered unless specifically required by 6.3.2 Jointing compounds. Jointing compounds
the test method. shall comply with the relevant requirements of
BS 5292.
Precautions shall be taken to prevent thermostats
or other variable controls from acting so as to 6.3.3 Solder. Solder having a melting point
interfere with the fuel flow, except as necessitated below 450 °C after application shall not be used for
by the test. gas-carrying parts.
Unless the test method specifies otherwise, tests 6.4 Insulation. Thermal or acoustic insulation
shall be carried out using the appropriate test gas. shall be non-combustible within the requirements of
BS 476-4, shall be securely located and shall be
For boilers using 3rd family gases, test gases LPGA
protected against mechanical damage, condensate
and LPGB shall be used with the boiler adjusted for
and vermin.
butane, and test gases LPGC and LPGE shall be
used with the boiler adjusted for propane. Gas-carrying parts in contact with, or passing
NOTE 1 Tables indicating the test gases (taken from BS 4947)
through, insulating material shall be adequately
to be used for each of the gas families and, where appropriate, protected against possible corrosive effects of the
their conditions of application, are shown in the relevant clauses insulant.
of BS 5978-2 and BS 5978-3.
6.5 Gas connections. Gas inlet connections shall
Gas test pressures shall be accurate to be suitable for connection to one of the following:
within ± 0.2 mbar and controlled so that the
variation does not exceed ± 0.2 mbar. a) tapered thread installation pipes in accordance
with BS 21;

2 © BSI 06-1999
BS 5978-1:1989

b) flanged pipes and fittings in accordance with 6.13 Materials, fittings and finishes
BS 4504-1 and BS 4504-2 or BS 10. 6.13.1 General. Materials, fittings and finishes, the
6.6 Unions and flanges. Unions in fuel lines shall failure of which might affect the safe operation of
be of the cone or spherical-seated type. Flange joints the boiler, shall comply with the requirements of the
shall include a gasket or “O” ring seal resistant to relevant British Standards and shall be appropriate
the action of components of the gas and suitable for to the conditions arising in the part of the boiler in
the temperature to which it is likely to be exposed. which they are used. The boiler and its associated
6.7 Injectors and jets. Injector and jet orifice areas parts shall be free from swarf, grit or other foreign
shall be non-adjustable. matter.
6.8 Bolts and screws. Drillings for bolts and 6.13.2 Galvanized parts. Galvanized parts shall
screws shall not connect with fuel or water-carrying comply with BS 729, BS 1706, BS 2989, or BS 4921
parts. as appropriate.
The use of self-tapping screws is not recommended 6.13.3 Painted and plastics coated parts. Painted or
but where they are used to secure components plastics coated surfaces shall comply with the
which are moved during servicing, they shall be following requirements.
fitted with spring steel fasteners. a) Resistance to heating. There shall be no
6.9 Viewing ports. Adequate means such as significant change of colour on any part of the
viewing ports shall be provided to allow observation boiler and the finish shall not become tacky or
of pilot, if any, and burner flames. show other signs of deterioration at the end of the
operation referred to in 5.2.2. This requirement
6.10 Servicing. The boiler shall be fitted with
shall not apply to parts that come into direct
access doors or removable panels to facilitate
contact with the flame.
servicing, e.g. of heat exchange surfaces. Means
shall be provided to permit ready removal of the b) Resistance to abrasion. Surfaces subject to
burner assembly for servicing, if necessary. abrasion, e.g. the outer casing(s), shall be tested
6.11 Facility for remote control. The for resistance to scratching as described in the
method below. The hardness shall be such that
manufacturer shall provide information to enable
the protective film is not penetrated. The scratch
the boiler to be controlled remotely, e.g. by means of
shall not have a width greater than 1 mm at any
thermostat(s) and a time control.
point along its length.
6.12 Circulating pumps. Where a circulating
pump forms an integral part of the boiler and is Method. Apply the apparatus (see Figure 1) to
rated up to 2 kW, it shall comply with BS 1394-1 the surface under test and move the ball, after
loading with a force of 10 N, at 30 mm/s
and BS 1394-2 as appropriate. In addition the
to 40 mm/s relative to the surface. If the
following requirements apply.
indicator lamp lights, the surface shall be
a) All information markings on the pump shall be deemed to have been penetrated.
visible without extensive dismantling of the
A metallic paint applied directly to the surface
pump being necessary.
will show a light without penetration and, in this
b) The pump shall be orientated within the limits case, the paint surface should be visually
specified by the pump manufacturer. examined for penetration. Clean the ball after
c) Any emergency freeing device shall be readily each test and inspect it frequently to verify that
accessible. it remains a 1 mm sphere.
d) There shall be union or flange connections on 6.13.4 Plated parts. Electroplated metal parts shall
either side of the pump to facilitate maintenance have a standard of adhesion and resistance to
or exchange and adequate means for locating any corrosion equivalent to the requirements of BS 1224
union washers. for service condition number 2.
e) A stop valve shall be fitted on each side of the 6.13.5 Other finishes. Where finishes other than
pump for complete isolation purposes. those referred to above are employed and where an
appropriate British Standard exists, the finish shall
satisfy its requirements.
6.13.6 Plastics parts. Where any plastics component
is in contact with combustion gases, the failure by
overheating of such components shall cause lockout.
Alternatively, the boiler shall incorporate a device
specifically intended to prevent overheating of the
plastics material.

© BSI 06-1999 3
BS 5978-1:1989

This device shall cause the boiler to go to lockout 6.15 Electric motors. Motors shall comply with
before the plastics material reaches a temperature BS 5000-11 or BS 5000-99 as appropriate.
likely to cause its degradation. The design of the 6.16 Flexible pipes. Flexible pipes shall be metal
device shall be such that, after it has operated, the armoured and have screwed or flanged connections.
attention of a service engineer or other competent They shall withstand at least three times the
person is required before the boiler can be put back working pressure with a minimum of 3.5 bar at both
into service. maximum and minimum service temperatures.
NOTE The use of a tool to gain access to the device is deemed to There shall be electrical continuity across flexible
satisfy this requirement. pipes. A manual isolating valve shall be placed in a
6.14 Formation and disposal of condensate readily accessible position upstream of the inlet of
6.14.1 Condensing boilers. Boilers that are specified any section of flexible pipe.
by the manufacturer to be designed to operate in the
condensing mode shall be provided with means for 7 Flue system
the collection and disposal of condensate. 7.1 The boiler shall be designed so as to prevent the
NOTE Surfaces in contact with condensate, apart from purpose escape of combustion products other than to the
designed sumps, siphons and water traps, should be so designed flue.
as to avoid the retention of condensate.
7.2 Where the flue outlet of the boiler is circular in
The condensate discharge system incorporated in
cross section it shall be suitable for connection to
the boiler shall comply with the following
flue pipes complying with BS 715 or BS 835 as
requirements.
appropriate.
a) It shall be so designed that it cannot transmit
combustion products to the room where the boiler 8 Flue dampers
is installed, or permit the ingress of air.
8.1 General. Where a flue damper is fitted, it shall
b) It shall be capable of being cleaned.
be of the automatic type and shall comply with 8.2
c) It shall be designed so as to inhibit blockage. and 8.3.
d) The size of the discharge pipe shall be Where such an automatic flue damper is fitted on a
appropriate to the boiler rating but shall have a boiler equipped with a permanent pilot the damper
minimum internal diameter of 15 mm. blade shall have a purpose designed opening
With the incorporated condensate discharge system equivalent to at least 5 % of the cross-sectional area
blocked at its outlet and with the boiler operating at of the flue.
its maximum heat input on the appropriate 8.2 Damper blades and spindles. The damper
reference test gas, and with a nominal return water blade shall not be able to move relative to its
temperature of 40 °C, the ratio of carbon monoxide spindle.
to carbon dioxide in the products of combustion shall
not exceed 0.02. 8.3 Provision of interlocks
This requirement shall be deemed to be complied 8.3.1 Where a flue damper is fitted it shall comply
with if the boiler proceeds to safety shut-down with 8.3.2 and 8.3.3 or 8.3.4 as appropriate.
before the CO/CO2 ratio reaches 0.02. 8.3.2 Any flue damper shall be provided with an
During this test there shall be no spillage of interlock to prove that the damper has reached the
condensate from the appliance and condensate shall fully open position before the boiler ignition
only come into contact with parts of the boiler that sequence is initiated.
are protected against corrosion. Failure of the interlock to prove that the damper is
6.14.2 Non-condensing boilers. Boilers that are in the correct position prior to start-up shall prevent
specified by the manufacturer to be designed to start-up.
operate in the non-condensing mode, and which are 8.3.3 Any non-modulating flue damper shall be
suitable for use with return water temperatures provided with an interlock, which may be the same
below 50 °C, shall not give rise to condensation in as that specified in 8.3.2, to prove that the damper
the combustion chamber and associated flueways is fully open throughout the burner operating
when operated at thermal equilibrium at the lowest period.
return water temperature specified in the Failure of the interlock to prove that the damper is
manufacturer’s instructions. fully open during burner operation shall cause
Where a boiler incorporates a condensate discharge safety shut-down.
system, e.g. to dispose of condensate arising at
start-up, 6.14.1 shall be complied with.

4 © BSI 06-1999
BS 5978-1:1989

8.3.4 Any modulating flue damper shall be provided NOTE Care has to be taken to ensure that any means
with an interlock, additional to that specified (e.g. thermal or mechanical) used to maintain the flame
supervision device in the open position is compatible with the
in 8.3.2, to prove that the damper is in at least the normal operation of the device.
minimum open position consistent with the normal
operation of the burner at its lowest rated heat 11 Temperature
input.
11.1 Requirements for surface temperatures.
Failure of the interlock to prove that the damper is When the boiler is operated according to the method
in at least its minimum open position during normal given in 11.2 the temperature rise of the parts listed
operation of the boiler at its lowest rated heat input in Table 1 shall not exceed the values specified.
shall cause safety shut-down.
11.2 Method. Measure the temperatures of
8.4 Safe-start check facility. The interlocks accessible surfaces by means of a surface pyrometer
required by 8.3.2, 8.3.3 and 8.3.4 shall, in addition, (see BS 1041).
be provided with a safe-start check facility to prove
Connect the boiler to an appropriate test rig as
that the interlocks are each in their correct position
described in DD 65-1 or DD 65-2 and operate at the
prior to the damper being opened. The safe-start
maximum rated heat input.
check facility shall prevent opening of the damper if
the interlocks are in an incorrect position. Adjust the test rig to give the manufacturer’s
recommended maximum water flow
9 Combustion air inlet dampers temperature ± 2 °C when the appliance is operated
at the maximum rated heat input. The flow/return
Where a combustion air inlet damper is fitted it temperature difference shall be that specified by the
shall be of the automatic type. manufacturer or, in the absence of a manufacturer’s
specification, 15 ± 2 K.
10 Gas soundness of burner train
Take the temperature measurements when the
10.1 General. All gas-carrying parts of the burner boiler has reached thermal equilibrium.
train shall be sound, and when connected shall form
Table 1 — Surface temperature rise
a complete assembly which is sound. The basic test,
as specified in 10.2, shall be carried out on the Parts of the appliance Temperature
rise
complete assembly.
K
10.2 Complete assembly from gas inlet to
injector. That part of the system between the inlet Handles, knobs, grips and the like
and last shut-off valve(s) shall be sound when tested that, in normal use, are held for short
to 1.5 times the manufacturer’s stated maximum periods only:
inlet pressure, or 50 mbar for 2nd family gases, of metal 35
or 150 mbar for 3rd family gases, whichever is the of porcelain or vitreous material 45
greater. of plastics, rubber or wood 60
Gas-carrying parts downstream of the last shut-off Parts that are likely to be touched
valve(s) shall be tested at the above-mentioned accidentally during normal
pressures and shall be sound. operation:
These requirements shall be deemed to be satisfied of metal 80
if the leakage rate over a period of 1 min does not of vitreous enamelled steel and 95
exceed 85 cm3/h. similar surfaces
10.3 Method. Connect to the appliance inlet an air of plastics, rubber or wood 100
supply maintained constant at the appropriate
pressure and embodying a suitable meter for 11.3 Requirements for component
measuring air flow. Subject all gas-carrying parts of temperatures. When the boiler is operated as
the appliance to this pressure under the following described in 11.2 the temperature of any component
conditions: shall not exceed the maximum allowable
temperature stated by the manufacturer of the
a) with all gas valves in the CLOSED position; component. The temperature of any component
b) with all gas valves in the OPEN position. incorporating a leather diaphragm shall not
The flame supervision device shall be maintained, exceed 60 °C.
by suitable means, in the open position and all
igniters, pilots and injectors capped off.

© BSI 06-1999 5
BS 5978-1:1989

11.4 Motor temperatures Table 2 — Permissible temperature rise for


11.4.1 Motor bearings windings
11.4.1.1 Requirement. The maximum temperature Windings (see note 1) and core Temperature
laminations in contact therewith, if the rise
of motor bearings shall not exceed the maximum winding insulation is:
stated by the motor manufacturer when measured
K
in accordance with 11.4.1.2.
11.4.1.2 Method. Operate the boiler at its maximum of class A material (see notes 2 75
rated heat input with the electricity supply at the and 3)
most unfavourable voltage between 85 % of the of class E material (see notes 2 90
minimum and 110 % of the maximum stated and 3)
operating voltage. Take temperature measurements of class B material (see notes 2 95
when the boiler has reached an equilibrium and 3)
condition and after the boiler has been switched off. of class F material (see note 2) 115
11.4.2 Motor windings. The maximum temperature of class H material (see note 2) 140
rise of the motor windings shall not exceed that
NOTE 1 The value of the temperature rise of a copper winding
given in Table 2, in accordance with BS 3456-101, is calculated from the formula:
and according to the class of insulation when the R2 – R1
appliance is operated at its maximum rated heat %t = ---------------------- (234.5 + t 1 ) – ( t 2 – t 1 )
R
input with the electricity supply at the most 1
unfavourable voltage between 85 % of the minimum where
and 110 % of the maximum stated operating %t is the temperature rise (K);
voltage, and when the appliance is shut-down. R1 is the resistance at the beginning of the test (7);
R2 is the resistance at the end of the test (7);
At the beginning of the test the windings are at t1 is the room temperature at the beginning of the
room temperature. It is recommended that the test (° C);
resistance of the windings at the end of the test be t2 is the room temperature at the end of the test (° C).
determined by taking resistance measurements as NOTE 2 The classification is in accordance with BS 2757.
soon as possible after switching off, and then at NOTE 3 For totally enclosed motors, the permissible
short intervals so that a curve of resistance against temperature rise for class A, class B and class E materials may
time can be plotted for ascertaining the resistance at be increased by 5 K. A totally enclosed motor is one so
constructed that circulation of air between the inside and the
the instant of switching off. outside of the case is prevented, but not necessarily sufficiently
enclosed to be termed airtight.
12 Heat input
12.1 Measurement. The heat input is that which
13 Combustion
would be obtained with a reference gas having a 13.1 Requirements. When tested under the
Wobbe number, under standard conditions of conditions described in clause 5 of BS 5978-2:1989
temperature, pressure and humidity, as specified or in clause 5 of BS 5978-3:1989, the ratio of carbon
for the appropriate gas family as classified in monoxide to carbon dioxide in the products of
BS 4947. combustion shall not exceed 0.02 in the following
The heat input shall be measured with the circumstances:
appliance at thermal equilibrium in its normal a) when the boiler is supplied with the reference
operating condition. gas of the appropriate family under the still air
12.2 Tolerance. Burners operating individually or and adverse flue conditions described in 5.1
in combination shall have a heat input within ± 5 % and 5.2 of BS 5978-2:1989 or in 5.1 of
of that stated by the manufacturer when operated at BS 5978-3:1989;
the manufacturer’s stated setting pressure. b) when the boiler is supplied with the incomplete
combustion test gas NGB, except for boilers
designed to burn 3rd family gases.
NOTE 1 Because the Wobbe numbers of LPGB and LPGE are
lower than those of LPGA and LPGC respectively, tests with the
reference gases according to a) represent the most stringent case
for boilers designed for 3rd family gases.
For boilers intended to operate in the high/low or
modulating mode, the requirements of this
subclause shall apply only in respect of the
maximum heat input declared by the manufacturer.

6 © BSI 06-1999
BS 5978-1:1989

NOTE 2 Requirements to cover the combustion performance of For the purposes of checking compliance with this
high/low and modulating boilers at heat inputs other than the requirement, a component that fails but
declared maximum are under consideration.
nevertheless allows the burner to continue to cycle
13.2 Method. Set up the boiler to the requirements safely and where the fault does not manifest itself to
given in clause 5 and connect to an appropriate test the user, shall not be regarded as having failed and
rig. (Appropriate test rigs are described in DD 65-1 shall be left in this condition during checking of all
and DD 65-2.) other components. Any mode of failure that does not
Adjust the test rig to give the manufacturer’s meet the above criteria shall be considered as a
recommended minimum water flow component failure.
temperature ± 2 °C when the appliance is operated 15.2 Governors. Governors shall comply with
at the manufacturer’s maximum rated heat input. BS 3554-1 or BS 3554-2, or BS 3016, as appropriate.
The flow/return temperature difference shall be
that specified by the manufacturer or, in the The main gas and, except as specified in BS 5978-2,
absence of a manufacturer’s specification, 15 ± 2 K the start gas or pilot supplies shall each be under
for boilers designed to operate at temperatures up the control of a constant pressure governor
to 100 °C. upstream of at least one safety shut-off valve.
For boilers designed to operate at temperatures 15.3 Safety shut-off valves. Safety shut-off valves
above 100 °C the manufacturer shall specify the shall comply with BS 5963 which describes three
flow/return temperature difference to be used. classes of valve.
Collect the products of combustion in such a manner Requirements for the application of safety shut-off
as to ensure a representative sample and determine valves are given in BS 5978-2 and BS 5978-3.
the carbon monoxide and carbon dioxide contents. 15.4 Thermally sensitive flame supervision
NOTE The carbon dioxide and carbon monoxide contents of the devices. Thermally sensitive flame supervision
products of combustion should be determined with respective devices shall comply with BS 6047-1.
accuracies of 0.05 % and 0.001 % of the volume of the sample.
The concentrations of the two gases can be determined
15.5 Multi-functional controls. Multi-functional
conveniently with adequate accuracy by a variety of methods controls shall comply with BS 6067.
(see BS 1756-1 to BS 1756-5).
15.6 Thermostats and control of water
temperature
14 Manual gas valves
15.6.1 General. Thermostats shall comply with
14.1 Manual valves shall be of the 90° turn type. BS 3955 and BS 4201.
14.2 Manual valves shall be so designed or
15.6.2 Control of water temperature
positioned as to prevent inadvertent operation but
shall be easy to operate when required. They shall 15.6.2.1 Normal operating conditions. Means shall
be so designed that, in operation, the “OPEN” and be provided on the boiler for controlling the water
“CLOSED” positions are readily distinguishable. temperature during normal running conditions.
14.3 A manual valve used solely for OPEN/CLOSED When operating with this control device at its
operation shall be provided with positive stops at maximum setting, the boiler water temperature
the “OPEN” and “CLOSED” positions. shall never rise so high as to cause the overheat
control device (see 15.6.2.2) to operate.
15 Controls 15.6.2.2 Overheat control device. An overheat
15.1 General. Electrically operated controls shall control device shall be provided, in addition to the
comply with BS 800 so as to avoid radio and normal water temperature control device
television interference. (see 15.6.2.1), to cause lock-out in the event of an
overheat condition occurring as a result of:
Operation of push-buttons, switches etc., incorrectly
or out of sequence shall not adversely affect the a) failure of the normal means of water
safety of the system. temperature control (see 15.6.2.1);
No single component failure shall lead to the main or
gas safety shut-off system, or any part thereof, being b) cessation of water circulation in the boiler.
permanently energized, nor shall it result in the
occurrence of a hazardous condition.

© BSI 06-1999 7
BS 5978-1:1989

16 Electricity supply The installation instructions shall also include:


16.1 The burner and its associated equipment shall 1) a wiring diagram showing the connections
function normally when the electricity supply between all the controls and the external
voltage is a) reduced to 85 % of the minimum stated connections;
operating voltage and b) increased to 110 % of the 2) a technical data table which shall give the
maximum stated operating voltage and shall either rated heat input(s), heat output(s), rating of
remain safe outside these limits or proceed to safety permanent pilot (where fitted), flue size, physical
shut-down. dimensions, weight, electric motor details and
16.2 Interruption of the electricity supply at any such other technical data as may be necessary.
time during the starting up or operation of the boiler The installation instructions shall recommend:
shall result in shut-down in the case of i) the fitting of a fuel isolation valve, or valves,
non-automatic burners and in safety shut-down in immediately adjacent to the boiler, which, when
the case of automatic burners. closed, allows the burner and control assemblies
16.3 Interruption and subsequent restoration of the to be disconnected for maintenance or repair;
electricity supply shall not override any lock-out ii) the provision of facilities for electrical
condition. isolation.
16.4 Where three-phase supplies are used for some The installation instructions shall state that any
of the power requirements of the appliance and one electrical work carried out during installation of the
phase is used to provide the remaining power appliance shall be in accordance with the IEE
requirements of the appliance, this phase shall be Regulations.
clearly and unambiguously identified.
Any electrical work required during assembly of the
appliance shall be so described as to enable
17 Manufacturer’s instructions compliance with BS 5986.
17.1 General. Installation, commissioning, 17.2.2 Water circulation. The manufacturer shall
servicing and user’s instructions shall be provided state in the installation instructions the pressure
with the boiler by the manufacturer. drop across the boiler over the recommended range
The meaning of names ascribed to parts referred to of flow rates.
in the manufacturer’s instructions shall agree, Where a pump is integral with the boiler, the
where applicable, with the meanings given in available pump head at these flow rates shall be
BS 1179-6. stated. The manufacturer shall also give details of
17.2 Installation instructions any essential design features of the boiler water
17.2.1 General. The installation instructions shall circulation system.
make reference to BS 6644 and shall include 17.3 Servicing instructions. The servicing
information regarding the following items: instructions shall indicate the frequency of servicing
a) the method of assembly; and the scope of the service programme
recommended by the manufacturer.
b) the siting of the boiler;
The servicing instructions shall include a line or
c) flueing; block diagram showing the arrangement of the gas
d) the combustion and ventilation air controls.
requirements; The procedure for removing or gaining access to
e) the fuel, water and electrical supply parts or components to be serviced, together with
connections; the recommended service work and the associated
f) water treatment requirements (if any); procedures, shall be clearly defined.
g) condensate disposal (where necessary); The servicing instructions shall include an electrical
wiring diagram and a short list of parts and part
h) burner supply pressure, injector sizes and
numbers of those items which the manufacturer
number of injectors;
considers may be required for replacement purposes
i) the procedure to be followed for commissioning during the life of the boiler.
the boiler;
The servicing instructions shall include a fault
j) the use of flue materials where necessary finding chart as an aid to servicing. If special tools
(see 6.14), which are resistant to the corrosive or equipment are required for any servicing
effects of condensate; procedure, details of these shall be included in the
k) the minimum clearances around the boiler servicing instructions.
necessary for servicing and cleaning.

8 © BSI 06-1999
BS 5978-1:1989

17.4 User’s instructions. The user’s instructions 18.2.2 Every fuse or circuit breaker shall have on its
shall contain information on the care and operation case or cover, or in an adjacent position, indelible
of the boiler including the lighting procedure. indication of its rated current appropriate to the
The user’s instructions shall include notes on the circuit(s) it protects.
procedure to be followed for shutting the boiler down 18.2.3 All electrical components likely to be
for short periods, e.g. weekends, and for long exchanged during maintenance or servicing shall be
periods, e.g. during the summer. marked with their electrical characteristics.
Where thermo-electric flame safeguards are fitted Such electrical components when supplied for
the user shall be advised not to use the boiler service replacement shall be marked with their
isolation valve in any case other than long-term electrical characteristics.
shutdowns, emergencies, or during servicing. 18.2.4 The electrical supply requirements,
e.g. voltage, frequency, starting and running
18 Identification and marking current, switch ratings and voltage of any external
18.1 Boiler data plate. A plate, or plates, shall be controls shall be clearly marked on the boiler.
securely fitted to the boiler in a readily accessible 18.3 Warning notices. Permanent warning notices
position. shall be provided in a readily visible position on the
The plate(s) shall take account of the identification boiler stating that the boiler is to be electrically
and marking requirements of BS 779, BS 855 or isolated and the fuel turned off before carrying out
BS 2790 as appropriate. any service operations.
The minimum lettering size shall correspond to The warning notice shall be of red lettering on a
Helvetica Medium 10 point (2.5 mm) or any other white background. The minimum lettering size
comparable type face. shall correspond to Helvetica
The plate(s) shall have a matt surface and the Medium 12 point (3.0 mm) or any other comparable
type face.
contrast between lettering and background shall be
as great as possible. The notices shall also draw attention to the need to
replace any protective covers that give direct access
The plate(s) shall include, with indelible marking,
to live components before the electrical supply is
the following information:
restored.
a) the name and address of the manufacturer and
his agent, if the manufacturer is not based in the 18.4 Start-up and shut-down instructions.
Start-up and shut-down instructions shall be
United Kingdom;
permanently fixed to the boiler in an accessible and
b) the country of origin, if other than the United readily visible position. The minimum lettering size
Kingdom; shall correspond to Helvetica
c) the boiler type, name and/or serial number, Medium 10 point (2.5 mm) or any other comparable
with identification of more detailed variations or type face.
modifications, e.g. by suffix or prefix, by serial
number, batch number, date of manufacture, etc.; 19 Thermal efficiency
d) the gas family for which the boiler is suitable 19.1 Efficiency requirement
(the category system of identification shall be
19.1.1 The manufacturer’s claimed efficiency, based
used, e.g. category IN as in BS 4947);
on operation at the following return water
e) the stated range of heat input and heat output temperatures:
in kilowatts;
a) all boilers: 65 °C;
f) the heat input of any continuous pilot in
b) condensing boilers: 40 °C.
kilowatts;
g) the maximum permissible water-side working and expressed on the gross calorific value basis,
pressure in bars; shall be not less than 73 % for boilers with heat
inputs of 60 kW up to and including 1.3 MW and not
h) the maximum permissible flow temperature.
less than 75 % for boilers with heat inputs
18.2 Marking of electrical items above 1.3 MW up to and including 2 MW.
18.2.1 A wiring diagram showing appropriate NOTE In certain circumstances it may be desirable to quote the
internal and external connections shall be marked efficiencies on the net calorific value basis. The gross and net
efficiencies are related as follows:
on or fixed to the boiler in an easily visible position.
i) for NGA, net value = 1.100 × gross value;
Wire coding shall be such that it is easily
identifiable with the wiring diagram. ii) for LPGA, net value = 1.080 × gross value;
iii) for LPGC, net value = 1.085 × gross value.

© BSI 06-1999 9
BS 5978-1:1989

19.1.2 The efficiency determined during type testing 19.3 Test conditions
by the method given in DD 65-1 or DD 65-2, and 19.3.1 Return water temperature. The test rig shall
under the test conditions specified in 19.3, shall be be adjusted to give a return water temperature as
not less than that claimed by the manufacturer follows when the boiler is operated at the maximum
minus two percentage points. rated heat input specified by the boiler
19.1.3 The efficiency determined during any manufacturer:
surveillance or check testing of production samples a) all boilers: 65 ± 0.5 °C;
shall be not less than that claimed by the
manufacturer minus five percentage points. b) condensing boilers: 40 ± 0.5 °C.
19.2 Heat input for efficiency determination. NOTE Additional efficiency determinations at other return
water temperatures may be carried out at the discretion of the
The efficiency shall be determined at the test authority and by agreement with the boiler manufacturer.
manufacturer’s maximum heat input for a fixed 19.3.2 Flow return temperature difference. The
rating boiler and at the maximum and minimum temperature difference between the flow and return
rated heat input for a range rated boiler. water shall be that specified by the manufacturer, or
For a boiler designed to operate on a modulating or in the absence of a manufacturer’s
high/low basis the efficiency shall be determined at specification, 15 ± 2 K for boilers designed to
the maximum rated heat input and at the minimum operate at temperatures up to 100 °C.
heat input specified by the manufacturer. For boilers designed to operate at temperatures
above 100 °C the manufacturer shall specify the
flow return temperature difference to be used,
provided that the specified difference is not greater
than 20 K.

10 © BSI 06-1999
BS 5978-1:1989

Figure 1 — Paint scratch test apparatus

© BSI 06-1999 11
BS 5978-1:1989

Publications referred to

BS 10, Specification for flanges and bolting for pipes, valves and fittings3).
BS 21, Specification for pipe threads for tubes and fittings where pressure-tight joints are made on the
threads (metric dimensions).
BS 476, Fire tests on building materials and structures.
BS 476-4, Non-combustibility test for materials.
BS 715, Specification for metal flue pipes, fittings, terminals and accessories for gas-fired appliances with
a rated input not exceeding 60 kW.
BS 729, Specification for hot dip galvanized coatings on iron and steel articles.
BS 779, Specification for cast iron boilers for central heating and indirect hot water supply (44 kW rating
and above).
BS 800, Specification for radio interference limits and measurements for household appliances, portable
tools and other electrical equipment causing similar types of interference.
BS 835, Specification for asbestos-cement flue pipes and fittings, heavy quality.
BS 855, Specification for welded steel boilers for central heating and indirect hot water supply (rated
output 44 kW to 3 MW).
BS 1041, Code for temperature measurement.
BS 1179:1967, Glossary of terms used in the gas industry.
BS 1179, Glossary of terms used in the gas industry.
BS 1179-6, Combustion and utilization including installation at consumers’ premises.
BS 1224, Specification for electroplated coatings of nickel and chromium.
BS 1394, Stationary circulation pumps for heating and hot water service systems.
BS 1394-1, Specification for safety requirements.
BS 1394-2, Specification for physical and performance requirements.
BS 1706, Specification for electroplated coatings of cadmium and zinc on iron and steel.
BS 1756, Methods for sampling and analysis of flue gases.
BS 1756-1, Methods of sampling.
BS 1756-2, Analysis by the Orsat apparatus.
BS 1756-3, Analysis by the Haldane apparatus.
BS 1756-4, Miscellaneous analyses.
BS 1756-5, Semi-routine analyses.
BS 2757, Method for determining the thermal classification of electrical insulation.
BS 2790, Specification for design and manufacture of shell boilers of welded construction.
BS 2989, Specification for continuously hot-dip zinc coated and iron-zinc alloy coated steel: wide strip,
sheet/plate and slit wide strip.
BS 3016, Specification for pressure regulators and automatic changeover devices for liquefied petroleum
gases.
BS 3456, Specification for safety of household and similar electrical appliances.
BS 3456-101, General requirements.
BS 3554, Specification for gas governors.
BS 3554-1, Independent governors for inlet pressures up to 25 mbar.
BS 3554-2, Independent governors for inlet pressures up to 350 mbar.
BS 3955, Specification for electrical controls for household and similar general purposes.
BS 4201, Specification for thermostats for gas-burning appliances.
BS 4504, Specification for flanges and bolting for pipes, valves and fittings. Metric series.
BS 4504-1, Ferrous.
BS 4504-2, Copper alloy and composite flanges.

3)
Obsolescent.

12 © BSI 06-1999
BS 5978-1:1989

BS 4921, Specification for sherardized coatings on iron or steel.


BS 4947, Specification for test gases for gas appliances.
BS 5000, Specification for rotating electrical machines of particular types or for particular applications.
BS 5000-11, Small-power electric motors and generators.
BS 5000-99, Machines for miscellaneous applications.
BS 5292, Specification for jointing materials and compounds for installations using water, low-pressure
steam or 1st, 2nd and 3rd family gases.
BS 5963, Specification for electrically operated automatic gas shut-off valves.
BS 5978, Safety and performance of gas-fired hot water boilers (60 kW to 2 MW input).
BS 5978-2, Specification for additional requirements for boilers with atmospheric burners.
BS 5978-3, Specification for additional requirements for boilers with forced or induced draught burners.
BS 5986, Specification for electrical safety and performance of gas fired space heating appliances with
inputs 60 kW to 2 MW.
BS 6047, Flame supervision devices for domestic, commercial and catering gas appliances.
BS 6047-1, Specification for heat sensitive types.
BS 6067, Specification for multifunctional gas controls for domestic, commercial and catering appliances.
BS 6644, Specification for installation of gas-fired hot water boilers of rated inputs between 60 kW
and 2 MW (2nd and 3rd family gases).
DD 65, Methods of type testing of heating boilers for thermal performance.
DD 65-1, Direct method4).
DD 65-2, Indirect method.

4)
Under revision.

© BSI 06-1999
BS 5978-1:
1989
BSI — British Standards Institution
BSI is the independent national body responsible for preparing
British Standards. It presents the UK view on standards in Europe and at the
international level. It is incorporated by Royal Charter.

Revisions

British Standards are updated by amendment or revision. Users of


British Standards should make sure that they possess the latest amendments or
editions.

It is the constant aim of BSI to improve the quality of our products and services.
We would be grateful if anyone finding an inaccuracy or ambiguity while using
this British Standard would inform the Secretary of the technical committee
responsible, the identity of which can be found on the inside front cover.
Tel: 020 8996 9000. Fax: 020 8996 7400.

BSI offers members an individual updating service called PLUS which ensures
that subscribers automatically receive the latest editions of standards.

Buying standards

Orders for all BSI, international and foreign standards publications should be
addressed to Customer Services. Tel: 020 8996 9001. Fax: 020 8996 7001.

In response to orders for international standards, it is BSI policy to supply the


BSI implementation of those that have been published as British Standards,
unless otherwise requested.

Information on standards

BSI provides a wide range of information on national, European and


international standards through its Library and its Technical Help to Exporters
Service. Various BSI electronic information services are also available which give
details on all its products and services. Contact the Information Centre.
Tel: 020 8996 7111. Fax: 020 8996 7048.

Subscribing members of BSI are kept up to date with standards developments


and receive substantial discounts on the purchase price of standards. For details
of these and other benefits contact Membership Administration.
Tel: 020 8996 7002. Fax: 020 8996 7001.

Copyright

Copyright subsists in all BSI publications. BSI also holds the copyright, in the
UK, of the publications of the international standardization bodies. Except as
permitted under the Copyright, Designs and Patents Act 1988 no extract may be
reproduced, stored in a retrieval system or transmitted in any form or by any
means – electronic, photocopying, recording or otherwise – without prior written
permission from BSI.

This does not preclude the free use, in the course of implementing the standard,
of necessary details such as symbols, and size, type or grade designations. If these
details are to be used for any other purpose than implementation then the prior
written permission of BSI must be obtained.

If permission is granted, the terms may include royalty payments or a licensing


agreement. Details and advice can be obtained from the Copyright Manager.
BSI Tel: 020 8996 7070.
389 Chiswick High Road
London
W4 4AL

You might also like