Professional Documents
Culture Documents
PAC Max Connections EN
PAC Max Connections EN
https://support.industry.siemens.com/cs/ww/en/view/61630471
QUESTION:
How many simultaneous TCP communication connections are supported via the integrated Ethernet interface of SENTRON
PAC, Powercenter or 3VA COM?
ANSWER:
The multifunctional measuring devices provide an integrated Ethernet interface for network communication as standard. For
this maximum simultaneous TCP communication are possible:
PAC3200:
Firmware < V2.4.5: 1 Connection (Modbus TCP)
Firmware ≥ V2.4.5: 3 Connections (Modbus TCP)
PAC4200:
Firmware < V2.2.4: 3 Connections (Modbus TCP) *3
Firmware ≥ V2.2.4: 12 Connections (Modbus TCP) *1, *2, *3
V2 (7KM9300-0AE01-0AA0):
Firmware < V2.1.4: 2 Connections (Profinet and Modbus TCP)
Firmware ≥ V2.1.4: 3 Connections (Profinet and Modbus TCP)
Supported devices: PAC3200, PAC4200, COM100 and COM800
Powercenter:
POC1000: 3 Connections (Modbus TCP)
POC3000: 128 Connections (Modbus TCP & Webserver).
Remarks
*1) Webserver available on device. Connections on webserver are additional to available communication connections. Limit
depends to the actual workload of device.
*2) Webserver is only available via the integrated Ethernet interface of device. Access via expansion modules is not
possible.
Page 1 / 1
04.10.2021