(PWPS 16) OFFICES BUILDING - DDC-02 - CABLE SCHEDULE

CORE & CABLE


S.No DDC CONTROL PANEL Description CABLE SIZE REMARKS
SIZE

TERMINAL - BLOCK

TERMINAL -TB-X0

Aa Per Site
● TB-X0(1,2,3) MAIN INCOMING POWER TO 6A BREAKER 2CX2.5mm² 2.5mm²
Condition

TERMINAL -TB-X1

● TB-X1(1 ,2) Connection from FACP 2CX1.5mm² 1.5mm² Unshielded

TERMINAL -TB-X2 PACU-16-02

● TB-X2(1,2) SUPPLY AIR FLOW SWITCH 2CX1.5mm² 1.5mm² Unshielded

● TB-X2(3,4) BAG FILTER DPS 2CX1.5mm² 1.5mm² Unshielded

● TB-X2(5,6,7,8) SUPPLY AIR DUCT SMOKE DETECTOR 4CX1.5mm² 1.5mm² Unshielded

● TB-X2(9,10,11,12) RETURN AIR DUCT SMOKE DETECTOR 4CX1.5mm² 1.5mm² Unshielded

● TB-X2(13,14,15,16) SUPPLY FAN & COMP-1,2 START STOP 4CX1.5mm² 1.5mm² Unshielded

● TB-X2(17,18) SUPPLY FAN RUN STATUS 2CX1.5mm² 1.5mm² Unshielded

● TB-X2(19,20) SUPPLY FAN TRIP STATUS 2CX1.5mm² 1.5mm² Unshielded

● TB-X2(21,22,23) COMP-1 RUN/TRIP STATUS 3CX1.5mm² 1.5mm² Unshielded

● TB-X2(24,25,26) COMP-2 RUN/TRIP STATUS 3CX1.5mm² 1.5mm² Unshielded


Shielded
● TB-X2(27,28,29,30) ROOM TEMP/HUMIDITY SENSOR 4CX1.5mm² 1.5mm²
Cable
Shielded
● TB-X2(31,32,33) ROOM DIFFERENTIAL PRESSURE SENSOR 3CX1.5mm² 1.5mm²
Cable
Shielded
● TB-X2(34,35) SUPPLY AIR DUCT TEMPERATURE 2CX1.5mm² 1.5mm²
Cable

-------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------

1
(PWPS 16) OFFICES BUILDING - DDC-02 - CABLE SCHEDULE

CORE & CABLE


S.No DDC CONTROL PANEL Description CABLE SIZE REMARKS
SIZE

TERMINAL - BLOCK

TERMINAL -TB-X3 EF-16-01

● TB-X3(1 ,2) START/STOP 2CX1.5mm² 1.5mm² Unshielded

● TB-X3(3 ,4) RUN STATUS 2CX1.5mm² 1.5mm² Unshielded

● TB-X3(5 ,6) TRIP STATUS 2CX1.5mm² 1.5mm² Unshielded

● TB-X3(7 ,8) AIRFLOW STATUS 2CX1.5mm² 1.5mm² Unshielded

TERMINAL -TB-X3 SP-16-01

● TB-X3(1 ,2) START/STOP 2CX1.5mm² 1.5mm² Unshielded

● TB-X3(3 ,4) RUN STATUS 2CX1.5mm² 1.5mm² Unshielded

● TB-X3(5 ,6) TRIP STATUS 2CX1.5mm² 1.5mm² Unshielded

TERMINAL -TB-X3 SP-16-02

● TB-X3(1 ,2) START/STOP 2CX1.5mm² 1.5mm² Unshielded

● TB-X3(3 ,4) RUN STATUS 2CX1.5mm² 1.5mm² Unshielded

● TB-X3(5 ,6) TRIP STATUS 2CX1.5mm² 1.5mm² Unshielded


Shielded
● TB-X2(7,8,9,10) ROOM TEMP/HUMIDITY SENSOR 4CX1.5mm² 1.5mm²
Cable
END OF CABLE SCHEDULE

-------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------