6.2.4 Condensate drain connection
‘The condensate drain connection is located
inthe middle section, right bottom,
‘The syphon is delivered with the unit and
has tobe mounted in he raised floor on site
after the A/C unit has been installed.
Syphon installation
Ensure that there is a sutficiont height difference between the fan pan and the upper bow of the syphon or the highest
part of the drain tube, in order to avoid a water column in the drain syphon caused by the pressure in the suction
area of the A/C unit, which prevents the draining of the condensate water
p=-300 Pa
Example: Static pressure in the suction area
-300Pa
h=p/(p+9)
h=-300Pa / (1000kgim® + toms!)
h=-3em|
If the height h is smaller than 3 cm with a pressure of
300 Pa in the suction area, a water column rests in the
drain, the water is not transported and fills the fan pan,
‘This water can be drawn dropwise in the fan or can drop
out of the uni ifthe pan is full
customer side: funnel |
Connect the condensate water drains to the local waste water system.
Lo
EN /10.2012/29/19