[CCE 6.2.4 Condensate drain connection ‘The condensate drain connection is located inthe middle section, right bottom, ‘The syphon is delivered with the unit and has tobe mounted in he raised floor on site after the A/C unit has been installed. Syphon installation Ensure that there is a sutficiont height difference between the fan pan and the upper bow of the syphon or the highest part of the drain tube, in order to avoid a water column in the drain syphon caused by the pressure in the suction area of the A/C unit, which prevents the draining of the condensate water p=-300 Pa Example: Static pressure in the suction area -300Pa h=p/(p+9) h=-300Pa / (1000kgim® + toms!) h=-3em| If the height h is smaller than 3 cm with a pressure of 300 Pa in the suction area, a water column rests in the drain, the water is not transported and fills the fan pan, ‘This water can be drawn dropwise in the fan or can drop out of the uni ifthe pan is full customer side: funnel | Connect the condensate water drains to the local waste water system. Lo EN /10.2012/29/19