.8 .9 1 2 3 4 5 6 7 8 9 10 20 30 40 50 60 70 80 90 .8 .9 1 2 3 4 5 6 7 8 9 10 20 30 40 50 60 70 80 90
1000 1000
900 900
800 800
700 700
600 Maximum GF Pickup 600
500 (X of Sensor Rating) 500
400
1200A Maximum 400
Switch Sensor
300 Maximum (X) Frame (A) Rating (A) 300
1.00 800 800
200 0.75 1200 1600 200
0.75 1600 1600
0.60 2000 2000
0.48 2500 2500
100 0.40 3000 3000 100
90 90
80 0.30 4000 4000 80
70 70
60 Adjustable in increments of 60
0.01X the Sensor Rating
TIME IN SECONDS
TIME IN SECONDS
50 50
40 40
30 30
20 20
10 10
9 9
8 8
7 7
6 6
5 5
4 4
2 2
Maximum
1
.9 14 .9
1
.8 13 .8
.7 12 .7
.6 11 .6
DES-121
DES-121
10 16mS additional at minimum possible
.5 .5
GF Pickup, (20% Sensor)
.4
9
.4
8
TGF delay band additional time may
.3 .3
be calculated via the following formula;
7 Additional t = 21.25 –18x% Sensor
.2 6 Minimum 1000 .2
5 Up to 119% Sensor
1 (I2t slope) 4
3
.1 .1
.09 .09
.08 2 2 .08
.07 0mS additional at 119% Sensor .07
.06 .06
.05 .05
.04 .04
.03 .03
.02 .02
.01 .01
.8 .9 1 2 3 4 5 6 7 8 9 10 20 30 40 50 60 70 8090 .8 .9 1 2 3 4 5 6 7 8 9 10 20 30 40 50 60 70 8090
100
100
MULTIPLE OF SENSOR
GE
Industrial Solutions
Fusible Switches DES-121
Frames 800-4000A HPC* Switches
New Generation EntelliGuard* Control Unit for Pickup Range
HPC* Switches, New Generation Minimum 0.2X Sensor
(SHP Type) Maximum 1.0X-0.3X Sensor,
not to exceed 1200A
UL977/cUL977
All Voltages: 600 Vac and below Fused Power Circuit Devices
Ground Fault
Curves apply at 60 Hertz
and from -20°C to 55°C switch ambient temperature.