K td × I scc ( external fault )

A. Kscc’(relay1) ¿
CT primary rating
1×3670
Kscc’ ¿ 300 = 12 ; K td = 1 for cable feeder
As per SIP 2006 catalogue if Kscc’ < 20 , then Kscc’ should be at least 20
Hence
Kscc’ >= 20

B. Kscc’(reqd) >= 20
K scc ×(Rct + Rb )
C. Kscc’(eff) = (Rct + Rb )
20×(6 +15)
Kscc’(effective) = (6+ 0.156) = 68.226

D. As Kscc’ (required) is < Kscc’ (effective) CT Size OK


E. CT Primary rating should be at least, 1.1*Maximum feeder continuous
current)
300 < 1.2 x 262
CT Size OK