PERFECT ENGINEERING AND TRADING COMPANY

19/3-Temple Road, Ground Floor, Behind Farid Tower, Lahore.


Phone: 0345-9225313, Cell: 0300-6734529, E-mail: Perfectengg@hotmail.com

M/S: Scandic Green Energy Dated: 29-07-2022


C/O Unilever
Rahim Yar Khan.

Attn: MR. Tanveer Ahmed (Boiler Engineer)

Water Testing Report of Biomass Boiler


Parameters Boiler Drum Water Status Limits for
Feed Water Drum Water
TDS mg/l 390* 2900 *High 3000

pH 8.0 10.0 Low 10.5 to 11.5

Iron (mg/l) 0.02 0.05 OK <0.1

Color of Water Clear L.Redish OK Light Reddish

Total Hardness mg/l 195* 625* *High 0 to 5

Phosphate mg/l Nil 10 Low 40 to 60

Sulphite mg/l Nil 30 OK 30 to 50

M-Alkalinity (HCO3) mg/l 140 200 Low 300 to 600

P-Alkalinity (CO3) mg/l 0 20 Low 200 to 300

Observation & Recommendations:


Feed and drum water hardness is still out of limits. This could be very dangerous for boiler. Total
hardness must not be greater than 5 mg/l. This is strongly recommended that use only RO or
softner treated water of zero hardness for boiler feed. To maintain pH and Alkalinity of drum water
dose some caustic (NaOH)in boiler feed tank. Morover ensure regular dosing of all chemicals
according to the said schedule and quantity.


Done By:
Muhammad Ahmed
(Service Engineer)