You are on page 1of 1

04/07/2022 pág.

1
AJUTE DE RELE Elaborado por:
Omar Matos
ING-A1097-AR-INF-01_Rev.0

A.1 CELDA PDC20A – H260-TCG-101: RELE REF543

DESCRIPCION VALOR -
FASES 150/5A -
CT
TIERRA 150/5A -

FUNCION DESCRIPCION VALOR RANGO


Operation Mode Extremely Inv.
Start current 1.2 xIn (0.10 … 5.00)
51-1 Operate time n/a (0.05 … 300.00)
Time multiplier 0.49 (0.05 … 1.00)
IEEE time dial n/a (0.5 … 15.0)

FUNCION DESCRIPCION VALOR RANGO


Operation Mode Definite time
52-2 Start current 18.28 xIn (0.10 … 40.00)
Operate time 0.15 s (0.05 … 300.00)

FUNCION DESCRIPCION VALOR RANGO


Operation Mode Definite time
Start current 6 %In (1.0 … 500.0)
51N-1 Operate time 0.30 s (0.05 … 300.00)
Time multiplier n/a (0.05 … 1.00)
IEEE time dial n/a (0.5 … 15.0)