Project : D04 Cainta Project

Date : August 19, 2022


Subject : Transfer Pump Calculation

Given:
Vertical Elevation = 26 mts
Horizontal Distance = 54 mts

FITTINGS: FRICTION LOSS OF FITTINGS


# of elbow (4"Ø) = 6 pcs 4"Ø elbow = 10.1 ft
# of elbow (3"Ø) = 5 pcs 3"Ø elbow = 7.7 ft
# of Tee (4"Ø) = 1 pc 4"Ø tee = 16.3 ft
# of Tee (3"Ø) = 1 pc 3"Ø tee = 22.1 ft
# of 2"Ø gate valve = 2 pcs 3"Ø GV = 0.14 ft
# of 3"Ø gate valve = 1 pc 2"Ø GV = 0.15 ft

CALCULATION OF FRICTION LOSS OF FITTINGS PUMP CAPACITY CALCULATION


4"Ø elbow = 60.6 ft Required Pump = (D x Q x H x SG) / 1000
3"Ø elbow = 38.5 ft Where as:
4"Ø tee = 16.3 ft D = Water Density (1000)
3"Ø tee = 22.1 ft Q = Amount of Water
3"Ø GV = 0.14 ft H = Actual Total Head
2"Ø GV = 0.3 ft SG = Specific Gravity (9.87)
TOTAL FRICTION LOSS = 137.94 ft
FRICTION LOSS ft to meter = 50.45 mts HP = 6.5
HP + 15% Safety Factor
TDH = 130.45 mts 7.5 HP
Required GPM = 80 GPM
GPM to cu.m/sec = 0.00505 cu.m/sec