You are on page 1of 1

Page 1

abb VFD SIZING CALCULATION

Project : SAISIDHA SUGAR PVT LTD - METEC ETIHOPIA


Application: VFD system for 5500 KW for FIBERISER

A. Supply side data


Network voltage 11000 V
Supply voltage tolerance +6/-9 %
Supply frequency 50 Hz
Supply frequency tolerance +3/-6 %
Maximum short circuit power 500 MVA
Minimum short circuit power 350 MVA

B. Ambient conditions
Altitude of installation < 1000 m a.s.l.
Maximum ambient operating temerature 45 °C
Relative humidity < 95 %

C. Motor and load data


Application Fiberiser
Load characteristic Constant torque
Motor voltage 6600 V
Motor rated current (As per Datasheet) 560 A
Motor rated frequency 50 Hz
Motor pole number 6
Motor rated shaft power 5500 kW
Efficiency at rated load 97 %
Power factor at rated load 0.88
Rated speed 1000 rpm
Starting torque 100 %
Overload 110 % for 60 s every 600 s

D. Converter selection
Selected Converter ACS 5066-A2E-M5, kindly refer attached catalogue page no.16
Continuous load:
Derating factor for ambient temperature of appx 0.5% per deg C over 40 deg C 0.98

Rated continuous output current of selected converter at 40°C 585 A

Derated countinuous output current of selected converter at 45°C 570 A


(As per the ACS5000 cataloque)

As derated continuous output current of selected converter at 45 deg C (i.e. 570 A) is


greater than load (i.e. 560 A), the selected converter is suitable for rated load at 45 Deg C

110% of motor full load current (1.1 x Motor Rated Current) 616 A
Rated Overload output current of selected converter at 40°C 643.5 A
(1.1 x Converter Rated Current of 585 A)

The overload current of the selected converter at 40 deg C (i.e. 643.5 A) is


greater thab load(i.e.616A), hence the selected converter is suitable for overload condition.

Issued: Rajesh More Document: YN3A251318-5500-VSC


Check/rel.: Samir Kumar ABB Limited, India 7/15/2013 Rev. 0
Resp. dept.: DM-DM