Professional Documents
Culture Documents
B. Ambient conditions
Altitude of installation < 1000 m a.s.l.
Maximum ambient operating temerature 45 °C
Relative humidity < 95 %
D. Converter selection
Selected Converter ACS 5066-A2E-M5, kindly refer attached catalogue page no.16
Continuous load:
Derating factor for ambient temperature of appx 0.5% per deg C over 40 deg C 0.98
110% of motor full load current (1.1 x Motor Rated Current) 616 A
Rated Overload output current of selected converter at 40°C 643.5 A
(1.1 x Converter Rated Current of 585 A)