ESIE 17-02

Technical Info
Technical Services Division – Daikin Europe NV

Parameter and Error list


Zanotti GM-Uniblock
Zanotti GS-Split

GM GS

1
Technical Info
Technical Services Division – Daikin Europe NV

SUBJECT: Parameter and Error list Zanotti GM-Uniblock & GS-Split

Attached, please find the Zanotti GM-Uniblock & GS-Split Parameter and Error list. This document
explains how to work with the units controller, gives an overview of all the parameter settings and
gives an thoroughly explanation about the error codes.

Before performing design, construction, or maintenance, thoroughly read the "Installation Manual" that
come with this product.

1. Table of contents

1. Table of contents ........................................................................................................... 2


2. Version log ..................................................................................................................... 2
1. PCB: Technical data ...................................................................................................... 3
2. Keyboard Technical Data ............................................................................................... 4
3. How to program the parameters ..................................................................................... 6
4. Entering ‘Machine Status’ Menu ..................................................................................... 8
5. Alarm signalling.............................................................................................................. 9
5.1 MAX/MIN Temperature alarms.............................................................................. 11
5.2 Duty-Cycle ............................................................................................................ 11
6. Parameters .................................................................................................................. 12

2. Version log

Month/Year Revised contents


09/2017 -

2
Technical Info
Technical Services Division – Daikin Europe NV
1. PCB: Technical data

Casing: Open board


Dimensions: 160x117 mm (Lxh)
Mounting: Can be adapted to container sizes that comply with DIN specifications (installed on
DIN rail)
Terminals: Screw type for 2.5mm² section cables and faston
Temperature: Operating: –5…55 °C - storage: –30…85 °C
Ambient humidity: Operating / storage: 10…90 % RH (non-condensing)
Power supply: SMPS 100-240 V~ ±10% 50/60 Hz
Power consumption: 7.5W max
Range: –50...110°C
Accuracy: Better than 0.5% full scale + 1 digit
Resolution: 1 or 0.1 °C
Buzzer: NO
Analogue inputs: 3 NTC inputs (Pb1, Pb2* and Pb3*)
*NOTE: probe Pb2 is present if H42 = y and probe Pb3 is present if H43 ≠ n
Digital inputs: 3 voltage-free digital inputs (clean) configurable via parameters H11, H12 and H13
Serial Outputs:  TTL (5-way connector): for connection to Copy Card or Supervisor
(connection to Televis).
• 'Voltage' serial (terminals 1-2-3) for power module-keyboard connection
(long distance)
• 'RS485' serial (terminals 19 ... 24) for Supervision (connection to Televis).
Digital outputs: The device has 5 relay outputs:
 Output RL1 = Relay 12(12)A (2Hp) 250V~ SPST (Compressor)
 Output RL2 = Relay 8(4)A 250V~ SPST (Fans)
 Output RL3 = Relay 16A 250V~ SPDT (Defrost)
 Output RL4 = Relay 16A 250V~ SPST (Light)
 Output RL5 = Relay 8(4)A 250V~ SPST (Alarm)
The device is  In terms of construction, as an independently mounted automatic
classified: electronic control device.
 In terms of automatic operating characteristics, as a type 1B controller.
 In terms of software class and structure, as a Class A controller.
 As a device with class 2 pollution rating (standard).
 As a device with class D fire resistance.
 In terms of the over voltage category, as a grade II device.
 As a device made with class IIIa material.

Terminals
1/2/3 ‘Voltage’ serial (power module-keyboard RL1 Compressor relay output
connection)
4-5 Digital input D.I.1 (general pressure switch) RL2 Fans relay output
6-7 Digital input D.I.2 (external alarm) RL3 Defrost relay output
8-9 Digital input D.I.3 (door switch) RL4 Lights relay output
12 - 13 Probe Pb1 input (cold room) RL5 Alarm relay output
14 - 15 Probe Pb2 input (evaporator) L-N 230Va board power supply
16 - 17 Probe Pb3 input (condenser alarm) GND Ground
TTL TTL / Copy Card input from 19 to 24 RS485 for Supervision
(connection to Televis)

3
Technical Info
Technical Services Division – Daikin Europe NV

2. Keyboard Technical Data

For split For Mono-blocks


Casing: Open board with polyester front cover
Dimensions: Front panel 66x130 mm, panel thickness Front panel 83x310 mm, panel
0.5 mm thickness 0.5 mm
Mounting: Panel-mounting (via double-sided adhesive) can be set for a distance of up to 100
m
Terminals: Screw terminals for cables with a cross-section of 2.5mm2
Temperature: Operating: –5…55 °C - storage: –30…85 °C
Ambient humidity: Operating/storage: 10…90 % RH (non-condensing)
Power supply: 12Vc ±10% from power board (IWP750 Zanotti series)
Display range: –50...110°C
Accuracy: Better than 0.5% integral scale + 1 digit
Resolution: 1 or 0.1 °C
Buzzer: No
Display: Display with 4 white colour digits
Icons: 14 Colour icons (7 red - 3 yellow - 4 green)
Keys: Colour icons (7 red - 3 yellow – 4 green) 5 Capacitive touch keys + 2 touch
knob
The device is classified: The classification of the instrument is:
• According to its construction, as an independently mounted automatic
electronic control device.
• In terms of automatic operating characteristics, as a type 1B controller.
• in terms of software class and structure, as a Class A controller.
• As a device with class 2 pollution rating (standard).
• As a device with class D fire resistance.
• According to the overvoltage category, as a class II device.
• As a device made with class IIIa material.

4
Technical Info
Technical Services Division – Daikin Europe NV

5
Technical Info
Technical Services Division – Daikin Europe NV
3. How to program the parameters
Level 1 parameters:

1. Touch PRG key for 5 seconds.


It will display the label CP (compressor) indicating that you have access to the programming menu.

2. Act on the wheel to display the desired folder.

3. Touch the PRG key to access the parameters of the selected folder.

4. Act on the wheel to select the parameter you want to modify.

5. Touch the PRG key to display the parameter value.

6. act on the wheel to change it.

7. Touch the PRG key to store the value and return to display the parameter label.

8. To return to the folder briefly touch the ON / OFF key.

Level 2 parameters:

1. Touch PRG key for 5 seconds.

2. Act on the wheel and scroll to the CnF-folder.

3. Touch the PRG key to access the folder.

4. Act on the wheel and scroll to the PA2-label.

5. Touch the PRG key to access the folder.

6. Give in the password “100” by using the scroll wheel.

7. Touch the PRG key.

8. Scroll through the level 2 parameters.

9. Touch the PRG key to access a folder.

Level 2 parameters should not be changed, they are unit related and
critical for the unit operation.

6
Technical Info
Technical Services Division – Daikin Europe NV

7
Technical Info
Technical Services Division – Daikin Europe NV
4. Entering ‘Machine Status’ Menu
Press and release the PRG key to open the ‘Machine Status’ menu. The following parameters will
appear:
• ALr: alarms folder (if present; probe errors/faults excluded)
• SP: setpoint configuration folder
• Pb1: probe 1 value folder
• Pb2: probe 2 value folder (if present; H42 = y)
• Pb3: probe 3 value folder (if present; H43 ≠ n)
 FnC: Functions folder. The functions are :

Function Function label ACTIVE Function label NOT Alarm signalling


ACTIVE
Manual defrost dEF + blinking icon dEF Blinking Defrost icon
Alarm acknowledgement tAL tAL Blinking Alarm icon
Reset pressure switch alarms rAP rAP Alarm ON icon
NOTES:
• To change the status of a given function, press the ‘SET’ or ‘PRG’ key
• If the instrument is switched off, the function labels will return to the default status.

8
Technical Info
Technical Services Division – Daikin Europe NV
5. Alarm signalling

Label Description Cause Effects Remedy


E1 Probe Pb1 error • Measured values • Label E1 displayed. • Check the probe
(cold room) are outside • Alarm icon type (NTC).
operating range. permanently on. • Check the probe
• Probe faulty/short- • Max and min alarm wiring.
circuited/open. regulator disabled. • Replace probe.
• Compressor function
based on parameters
Ont and Oft.
E2 Probe Pb2 error • Measured values • Label E2 displayed. • Check the probe
(defrost) are outside. • Alarm icon type (NTC).
operating range. permanently on. • Check the probe
• Probe faulty/short- • The defrost cycle will wiring.
circuited/open. end due to Time out • Replace probe.
(dEt).
E3 Probe Pb3 error • Measured values • Label E3 displayed. • Check the probe
(condenser) are outside • Alarm icon type (NTC).
operating range. permanently on. • Check the probe
• Probe faulty/short- wiring.
circuited/open. • Replace probe.

AH1 Pb1 HIGH Value read by Pb1 > HAL • Label AH1 recorded Wait until value read by
temperature alarm after time of tAO. in folder ALr. the probe Pb1 returns
(see ‘MAX/MIN • No effect on below HAL−AFd.
TEMPERATURE regulation.
ALARMS’).
AL1 Pb1 LOW Value read by Pb1 < LAL • Label AL1 recorded Wait until value read by
temperature alarm after time of tAO. in folder ALr. the probe Pb1 returns
(see ‘MAX/MIN • No effect on above LAL+AFd.
TEMPERATURE regulation.
ALARMS’).
AH3 Pb3 HIGH Value read by Pb3 > SA3 • Label AH3 recorded Wait until value read by
temperature alarm after time of tAO (if dA3 < in folder ALr. the probe Pb3 returns
0). • No effect on below SA3−dA3.
(see ‘MAX/MIN regulation.
TEMPERATURE
ALARMS’).
AL3 Pb3 LOW Value read by Pb3 > SA3 • Label AL3 recorded Wait until value read by
temperature alarm after time of tAO (se dA3 ≥ in folder ALr. the probe Pb3 returns
0) • No effect on below SA3+dA3.
(see ‘MAX/MIN regulation.
TEMPERATURE
ALARMS’).
EA External Alarm Activation of a digital input. • Label EA recorded in Check and remove
(H1x = ±5) folder ALr external cause of alarm on
• Alarm icon D.I.
permanently on.
• Regulation blocked.

9
Technical Info
Technical Services Division – Daikin Europe NV
Label Description Cause Effects Remedy
OPd Door Open Alarm Activation of a digital input • Label Opd recorded
for a time greater than tdO in folder ALr. • Close the door.
(H1x = ±4). • Alarm icon • Delay function
permanently on. defined by OAO.
• Regulation blocked if
dOd = y.
Ad2 End of Defrost for End of defrost cycle due to • Label Ad2 recorded Wait for the next defrost
time-out timeout rather than due to in folder ALr if cycle for automatic reset.
defrost end temperature parameter dAt=1; not
being read by probe Pb2. shown if dAt=0.
• Alarm icon
permanently on.
nPA General pressure Activation of pressure If the number of pressure Check and remove the
switch alarm switch alarm by general switch activations is: cause that triggered the
pressure switch. n < PEn alarm on the digital input
(Auto reset).
• Folder nPA recorded
in folder ALr with the
number of pressure
switch activations.
• Regulation blocked .
LPA Minimum pressure Activation of pressure If the number of pressure Check and remove the
switch alarm switch alarm by low switch activations is: cause that triggered the
pressure switch regulator. n < PEn alarm on the digital input
• Folder LPA recorded (Auto reset).
in folder ALr with the
number of pressure
switch activations.
• Regulation blocked.
HPA Maximum pressure Activation of pressure If the number of pressure Check and remove the
switch alarm switch alarm by high switch activations is: cause that triggered the
pressure switch regulator. n < PEn alarm on the digital input
• Folder HPA recorded (Auto reset).
in folder ALr with the
number of pressure
switch activations.
• Regulation blocked .
PA General pressure Activation of pressure If the number of pressure
switch alarm switch alarm by general switch activations is: • Switch the device
pressure switch. n = PEn off and back on
• Label PA displayed. again.
• Label PA recorded in • Reset alarms by
folder ALr. entering the FnC
• Alarm LED on. folder and
• Relay activated (if selecting the rAP
configured). function (Manual
• Regulation blocked. Reset).
E7 No link between Communication fault • Label E7 displayed. During configuration,
power board and between Power board and • No effect on switch off all devices then
keyboard Keyboard regulation. switch them back on
again.

10
Technical Info
Technical Services Division – Daikin Europe NV
5.1 MAX/MIN Temperature alarms

Temperature value in relation to setpoint Temperature value Absolute


(Att=1) (Att=0)

Minimum Temp. ≤ Set + LAL* Temp. ≤ LAL (LAL with sign)


temperature
alarm
Maximum Temp. ≥ Set + HAL** Temp. ≥ HAL (HAL with sign)
temperature
alarm
Returning from Temp. ≥ Set + LAL + AFd or Temp. ≥ LAL + AFd
minimum ≥ Set + │LAL│ + AFd (LAL<0)
temperature
alarm
Returning from Temp. ≤ Set + HAL . AFd (HAL>0) Temp. ≤ HAL - AFd
maximum
temperature
alarm
*If LAL is negative, Set + LAL < Set
**If HAL is negative, Set + HAL < Set

5.2 Duty-Cycle

A probe Pb1 (cold room) error Parameters Ont and OFt programmed
causes the following actions: for duty-cycle

 Code E1 is shown on Ont OFt Compressor output


the display
0 0 OFF
 The regulator is 0 >0 OFF
activated as indicated >0 0 ON
by parameters Ont >0 >0 DUTY-CYCLE
and OFt if set for
dutycycle.

11
Technical Info
Technical Services Division – Daikin Europe NV

6. Parameters

Label Name Medium Low Medium Low Unit Range Level Description
hot gas hot gas electric electric
CP Compressor parameters
diF Differential 2 2 2 2 °/1 0,1…30 1&2 Compressor relay activation differential:
The compressor stops when reaching the Setpoint value (as
indicated by the regulation probe) and restarts at a temperature
value equal to the Setpoint plus the value of the differential.
Note: diF ≠ 0.
HSE Max. temp. 10 -15 10 -15 °/1 LSE…302 1&2 Higher SEt. Maximum value that can be assigned to the
Allowed setpoint Setpoint.
Note: The two Setpoints are interdependent: HSE cannot be
less than LSE and vice-versa.
LSE Min. temp. -5 -25 -5 -25 °/1 -58,0…HSE 1&2 Lower SEt. Minimum value that can be assigned to the
Allowed setpoint Setpoint.
Note: The two Setpoints are interdependent: HSE cannot be
less than LSE and vice-versa.
Ont ON time if faulty 10 10 10 10 min 0…250 1&2 Compressor start time in the event of faulty probe.
room sensor If Ont = 1 and OFt = 0, the compressor stays on permanently
(ON),
If Ont > 0 and OFt > 0, it will run in duty cycle mode (See Duty
Cycle diagram).
Oft OFF time if faulty 20 20 20 20 min 0…250 1&2 Compressor switch off time in the event of faulty probe.
room sensor If OFt = 1 and Ont = 0, the compressor will always stay off
(OFF).
If Ont > 0 and OFt > 0, it will run in duty cycle mode (See Duty
Cycle diagram).

12
Technical Info
Technical Services Division – Daikin Europe NV
Label Name Medium Low Medium Low Unit Range Level Description
hot gas hot gas electric electric
dOF Time between 2 2 2 2 min 0…250 1&2 Delay time after switch off: the delay time indicated must elapse
comp. OFF and between deactivation of the compressor relay and the next
next start switch-on.
dbi Time between 2 2 2 2 2 min 0…250 1&2 Delay time between switch-ons: the delay time indicated must
compressor elapse between two consecutive compressor switch-ons.
starts
DEF Defrost Parameters
dtY Defrost operating 1 1 0 0 num 0/1/2 1&2 Type of defrost.
mode: 1=gas 0 = electric defrost - compressor OFF during defrost cycl
0=electric 1 = cycle inversion defrost (hot gas) - compressor ON during
defrost cycle
2 = ‘Free’: defrost independent of compressor
dit Time interval 3 3 3 3 hours 0…250 1&2 Interval between the start of two consecutive defrost cycles.
between 2 0 = function disabled (defrosting NEVER performed)
defrosts
dt1 Unit of measure 0 0 0 0 flag 0/1/2 2 Defrost time 1. Unit of measure for defrost interval (parameter
for defrost dit).
interval 0 = dit in hours.
1 = dit in minutes.
2 = dit in seconds.
dCt Defrost interval 0 0 0 0 Num 0/1/2/3 Selects the count mode for the defrost interval.
time count mode 0 = compressor running hours (DIGIFROST® method); Defrost
active ONLY when the compressor is on.
Note: compressor running hours are counted separately from
the evaporator probe (count active also when evaporator probe
missing or faulty).
1 = appliance running hours; the defrost count is always active
when the machine is on and starts at each power-on
2 = compressor stop. Every time the compressor stops, a
defrost cycle is performed based on parameter
3 = not used

13
Technical Info
Technical Services Division – Daikin Europe NV
Label Name Medium Low Medium Low Unit Range Level Description
hot gas hot gas electric electric

dEt Defrost time 20 20 30 30 min 1…250 1&2 Defrost time-out; determines the maximum defrost duration.
override
dSt Defrost 15 15 8 8 °/1 -50,0…150 1&2 Defrost end temperature (determined by the evaporator probe).
Termination
Temperature
Fan Fans parameters
FSt Fans stop 50 50 50 50 °/1 -50,0…150 1&2 Fans lockout temperature; if the value read by evaporator probe
temperature is greater than FSt, the fans will be stopped. The value is either
positive or negative and, depending on parameter FPt, can be
either the absolute temperature or the temperature relative to
the setpoint.
Fdt Fans ON delay 3 3 3 3 min 0…250 1&2 Fans activation delay after a defrost cycle.
dt Drain Down Time 2 2 2 2 min 0…250 1&2 Drainage time. Dripping time.
dFd Fans OFF during Y Y Y Y flag n/y 1&2 Operating mode of evaporator fans during defrost.
defrost 0=n = no
1=y = yes.
FCO Fans ON during n n n n flag n/y/dc 1&2 Fan Compressor OFF. Selects or deselects fan deactivation at
compressor OFF compressor OFF.
0=n = fans off
1=y = fans on (with thermostat; depending on the value read by
the defrosting probe, see FSt)
2=dc = duty cycle (via parameters ‘Fon’ and ‘FoF’)

Fod Fans OFF during n n n n flag n/y 1&2 Allows fan block to be selected when the door is open and fan
door open restart when the door is shut (if they were running).
0=n = fans blocked
1=y = fans unaltered.

14
Technical Info
Technical Services Division – Daikin Europe NV
Label Name Medium Low Medium Low Unit Range Level Description
hot gas hot gas electric electric
AL Alarms parameters
Afd Alarm differential 2 2 2 2 °/1 1,0…50,0 1&2 Alarms cut-in differential.

HAL High temperature 5 5 5 5 °/1 LAL…150 1&2 Maximum temperature alarm. Temperature value (intended
alarm setpoint either as distance from Setpoint or as an absolute value based
on Att) which, if exceeded in an upward direction, triggers the
activation of the alarm signal. See ‘Max/Min temperature
alarms.
LAL Low temperature -5 -5 -5 -5 °/1 -50,0…HAL 1&2 Minimum temperature alarm. Temperature value (intended as
alarm setpoint distance from the set point or as an absolute value based on
Att) which, when exceeded downwards, triggers the activation
of the alarm signal. See ‘Max/Min temperature alarms’.
PAO Alarm delay after 3 6 3 6 hours 0…10 1&2 Alarm override time after device is switched on following a
start-up power failure. This parameter refers to high/low temperature
alarms only.
dAo Alarm delay after 60 60 60 60 min 0…999 1&2 Temperature alarm exclusion time after defrost.
defrost
OAO Alarm delay after 1 1 1 1 hours 0…10 1&2 Alarm signal delay (low and high temperature) after the
door opening deactivation of the digital input (port closed).
SA3 High temperature 55 55 55 55 °/1 -50,0…150 1&2 Alarm Setpoint for probe Pb3.
alarm setpoint
dA3 Differential 2 2 2 2 °/1 -30,0…30 1&2 Probe Pb3 alarm activation differential.
PrE Pressure alarms parameters
Pen Number of 10 10 10 10 Num 0…15 1&2 Number of errors allowed per maximum/minimum pressure
pressure trips switch input.
0 = disabled.
PEI Time period for 60 60 60 60 min 1…99 1&2 Minimum/maximum pressure switch error count interval.
pressure trips

15
Technical Info
Technical Services Division – Daikin Europe NV
Label Name Medium Low Medium Low Unit Range Level Description
hot gas hot gas electric electric
diS Display parameters
CA1 Calibration room 0 0 0 0 °C -12,0…12,0 1&2 Calibration 1. Positive or negative temperature value added to
sensor the value read by Pb1. This sum is used both for the
temperature displayed and for regulation.

dro Selection 0 0 0 0 flag 0/1 1&2 Selection of °C or °F to display the temperature read by the
Celsius/Farenheit probe.
0 = °C
1 = °F.
NOTE: switching between °C and °F or vice versa DOES NOT
modify the setpoint, differential, etc. (e.g. setpoint=10°C
becomes 10°F).
ddL Display during 0 0 0 0 flag 0/1/2 1&2 Selects type of value to display.
the defrost 0=normal read
1=read block
2=display deF
CnF Configuration parameters
PA2 password setting x x x x flag 2
according
second level
H41 Presence control y y y y flag n/y 2 Presence of probe 1 (Pb1).
probe n (0) = not present
y (1) = present.
H42 Presence y y y y flag n/y 2 Presence of probe 2 (Pb2).
evaporator probe 0=n= not present
1= Y = present.

16