Professional Documents
Culture Documents
Coolpack: Cooling Demand For A Liquid Cooler
Coolpack: Cooling Demand For A Liquid Cooler
HEATING OF LIQUID
Calculate
Liquid: Propylene glycol [%] : 70 Cooling load [kW] 50 QLIQUID : 50.00 [kW]
Save inputs
Inlet temperature [°C] : 7.0 Outlet temperature [°C] : 12.0
Load inputs 3 3
Mass flow : 2.407 [kg/s] ~ 8666 [kg/h] Volume flow : 0.002403 [m /s] ~ 8.649 [m /h]
Help 3
Specific heat capacity : 4.154 [kJ/(kg·K)] Density : 1002 [kg/m ]
Print HEAT INGRESS AND PRESSURE LOSSES IN PIPES
Total pipe length [m] : 20 Pipe diameter (inner) [mm] : 45 QSUPPLY : 0.09 [kW]