GEO-ENGINEERING & TESTING, INC. ‘Telephone: 671-646-5500
Geotechnical & Material Testing Engineers Facsimile: 671-646-6600
P.O Box 8170 Tamuning, Guam 96931
14 January 2021
921.
Valcon Guam, LLC
P.O Box 25702
Barrigada, Guam 96921
Attention: Mr. Edricson Amurao
Report — Percolation Test
Yigo Guam Temple
Yigo, Guam
We performed one percolation test for the Yigo Guam Temple, under construction,
located in Yigo, Guam. The approximate location of the percolation test is shown on the
attached Percolation Test Location Plan. The percolation test hole was manually
excavated inside an existing trench drain to 2 feet below the existing surface or refusal
to hand digging, using a pinch bar and a post-hole digger, with approximately 12 inches
in diameter.
The percolation test exposed light brown-white coralline limestone in the 2-foot deep
test hole. No free water was encountered in the percolation test hole.
The percolation test hole was first saturated with water prior to conducting the
percolation test. The following percolation test result was obtained together with our
recommended rate:
[ Percolation | Diameter, ‘Overall Rate, Last Rate, Recommended Rate,
Test inches inchesiminute | inches/minute inches/minute
No.
4 2 0.050 0.024 0.024
(Note: Percolation rate may vary within short distances.)
Please contact us if there are any questions.
Respectfully submitted,
GEO-ENGINEERING & TESTING, INC.
Ctt—
Ukrit Siriprusanan
Civil Engineer ~ 360
Attachment: Percolation Test Location Plan