The outer diameter of 28AWG, 32AWG cable Category 6A 28AWG, 32AWG Patch Cords in
is about 3.5mm, 2.6mm respectively. It is much LS Cable & System has not only small outer
smaller than our USS(Ultra Super Slim, 26AWG, diameter as fiber patch cord (about 3.5mm),
5.8mm) Cable, which supports world best but also ‘Turn-Boot’ with LS Cable & System
capacity in installation. This benefit offers you patent. To pull out the plug from jack, what
a big efficiency in high-density data center, you should do is just turn the boot. It can be
which has numerous patch panels and patch a best solution in high-density data center.
cords.
* MDA (Main Distribution Area) HDA (Horizontal Distribution Area) EDA (Equipment Distribution Area)
28AWG 32AWG
Characteristic
P/C P/C
Insertion Loss
1.1 1.6
de-rating factor
Resistance
0.43 1.17
de-rating factor
Patching process in data center getting more
difficult as high-density integration grows. For
this problem, ‘Turn-Boot’ offers convenience to
installers and managers.
Formula of Max. Patch Cord length according to Permanent Link – 1dB, 1Ω margin
( Resistance is a major factor in USS Cat.6A Perm. Link + 32AWG Patch Cords Channel,
and insertion loss is a major factor for all channel except upper case )
- Insertion loss margin of 3rd Cat.6A Perm. Link (90m) : about 11.6dB
11.6 + {0.40 * (90 – Perm. Link length)} – (1.1 * 28AWG Patch Cords length) > 1
11.6 + {0.40 * (90 – Perm. Link length)} – (1.6 * 32AWG Patch Cords length) > 1
- Insertion loss margin of USS Cat.6A Perm. Link (60m) : about 16.4dB
16.4 + {0.57 * (60 – Perm. Link length)} – (1.1 * 28AWG Patch Cords length) > 1
- Resistance margin of USS Cat.6A Perm. Link (60m) : about 16.72Ω
16.72 – {0.29 * (60 – Perm. Link length)} + (1.17 * 32AWG Patch Cords length) < 24
28AWG 32AWG
Case
P/C P/C
Max. Patch Cords length with LS Cable & System 3rd Cat.6A Perm. Link Table
(1dB margin Recommend)
(meter)
Max. 28AWG Max. 32AWG
Perm. Link Channel Channel
Patch Cords Patch Cords
90 10.0 100.0 7.2 97.2
89 10.3 99.3 7.4 96.4
88 10.7 98.7 7.7 95.7
87 11.0 98.0 7.9 94.9
86 11.4 97.4 8.2 94.2
85 11.8 96.8 8.4 93.4
84 12.1 96.1 8.7 92.7
83 12.5 95.5 8.9 91.9
82 12.8 94.8 9.2 91.2
81 13.2 94.2 9.4 90.4
80 13.6 93.6 9.7 89.7
79 13.9 92.9 9.9 88.9
78 14.3 92.3 10.2 88.2
77 14.6 91.6 10.4 87.4
76 15.0 91.0 10.7 86.7
75 15.4 90.4 10.9 85.9
* Below 10m of Patch Cords Recommended in channel
Max. Patch Cords length with LS Cable & System USS Cat.6A Perm. Link Table
(1dB margin Recommend)
(meter)
Max. 28AWG Max. 32AWG
Perm. Link Channel Channel
Patch Cords Patch Cords
60 13.9 73.9 6 66
59 14.4 73.4 6.3 65.3
58 14.9 72.9 6.5 64.5
57 15.4 72.4 6.8 63.8
56 15.9 71.9 7 63
55 16.5 71.5 7.3 62.3
54 17 71 7.5 61.5
53 17.5 70.5 7.8 60.8
52 18 70 8 60
51 18.5 69.5 8.3 59.3
50 19.1 69.1 8.5 58.5
49 19.6 68.6 8.8 57.8
48 20.1 68.1 9 57
47 20.6 67.6 9.3 56.3
46 21.1 67.1 9.5 55.5
45 21.7 66.7 9.8 54.8
44 22.2 66.2 10 54
43 22.7 65.7 10.3 53.3
42 23.2 65.2 10.5 52.5
41 23.7 64.7 10.8 51.8
40 24.3 64.3 11 51
* Below 10m of Patch Cords Recommended in channel