A. Introduction
IEC 60870-5 provides a communication method to send basic telecontrol messages between two
systems. The IEC Technical Committee 57 have developed a protocol standard for Telecontrol,
Teleprotection, and associated telecommunications for electric power systems.
IEC 60870-5-101/-104 are applied to tele-control equipment and systems with coded bit serial data
transmission for monitoring and controlling geographically widespread processes.
IEC 60870-5-101 protocol uses the standard of asynchronous serial tele-control channel interface
between DTE (Data Terminal Equipment) and DCE (Data Communication Equipment). The
standard is suitable for multiple configurations like point-to-point and multipoint.
IEC 60870-5-104 protocol is an extension of IEC 60870-5-101 protocol with the changes in terms
of transport, network, link & physical layer services for the complete network access. The standard
uses an open TCP/IP interface to network to have connectivity to the LAN(Local Area Network)
and routers with different facility(ISDN, X.25, Frame relay etc) can be used to connect to the WAN
(Wide Area Network). Application layer of IEC 60870-5-104 is preserved same as that of IEC
60870-5-101 with some of the data types and facilities not used. There are two separate link layers
defined in the standard and suitable for data transfer over Ethernet & serial line (PPP - Point-to-
Point Protocol).
ENHANCED TECHNOLOGY 1
IEC 60870-5-101/104 PROTOCOL http://www.entecene.co.kr
2 ENHANCED TECHNOLOGY
IEC 60870-5-101/104 PROTOCOL http://www.entecene.co.kr
Function
Select whether to use IEC60870-5-101 Protocol.
Use Port
Set physical port to use IEC60870-5-101 communication.
Link Address
Enter the slave address for IEC60870-5-101 communication.
ASDU Address
Enter the Application Service Data Unit Address.
Cyclic Period
Enter the Cyclic Period. It is to set interval time between Point set for Cyclic.
Event Period
Enter the delay time before events are sent. Single event or several events occur and then if new
event is not generated during the delay time, the event(s) already generated is(are) sent to a Master.
Retries
Enter the Data retires number.
Conf. Timeout
Enter the wait time till receive the Data Confirm (ACK) of master after transfer the Data. If there isn’t
the Confirm during this setting time and Data retries is available, Entec’s Recloser Control transfers
the Data again.
Link Confirm
Enter the Link layer confirm mode.
ENHANCED TECHNOLOGY 3
IEC 60870-5-101/104 PROTOCOL http://www.entecene.co.kr
Rx Frame Size
Enter the maximum size of received frame.
Rx Frame TO
Enter the maximum amount of time to wait for a complete frame after receiving the frame sync.
Tx Frame Size
Enter the maximum size of transmitted frame.
COT Size
Enter the size of cause of transmission.
IOA Size
Enter the size of information object address.
One Ch Response
This allows to send one character response instead of a fixed length NACK when no response data
available.
Frame Repet’ TO
Enter the time out for repetition of frames(or incremental application layer timeout).
Select Timeout
Enter the period after a previously received select will timeout.
CMD Termination
Select whether to send Activation Termination upon completion of commands other than set point
commands.
CSE Termination
Select whether to send Activation Termination upon completion of set point commands.
4 ENHANCED TECHNOLOGY
IEC 60870-5-101/104 PROTOCOL http://www.entecene.co.kr
MSP Time-Tag
Select whether a time tag format for single-point.
MIT Time-Tag
Select whether a time tag format for integrated totals.
MME Time-Tag
Select whether a time tag format for measured value and normalized value for general event except
for fault current event.
Flt Time-Tag
Select whether a time tag format for measured value and normalized value for fault current event.
ENHANCED TECHNOLOGY 5
IEC 60870-5-101/104 PROTOCOL http://www.entecene.co.kr
Function
Select whether to use IEC60870-5-104 Protocol.
COM Port
Enter a port for IEC60870-5-104 communication. It is fixed in PORT4.
ASDU Address
Enter the Application Service Data Unit Address.
6 ENHANCED TECHNOLOGY
IEC 60870-5-101/104 PROTOCOL http://www.entecene.co.kr
Cyclic Period
Enter the Cyclic Period. It is to set interval time between Point set for Cyclic.
Timeout(t0)
Select the Timeout for connection establishment.
Timeout(t1)
Select the Timeout for send or test APDUs.
Timeout(t2)
Select the Timeout for acknowledgements in case of no data message ( t2<t1).
Timeout(t3)
Select the Timeout for sending test frame in case of a long idle state.
Event Period
Select the delay time before events are sent. Single event or several events occur and then if new
event is not generated during the delay time, the event(s) already generated is(are) sent to a Master.
TCP Port
Set the TCP Port of Entec’s Recloser Control for IEC60870-5-104 Protocol communication.
Rx Frame Size
Enter the maximum size of received frame.
Tx Frame Size
Enter the maximum size of transmitted frame.
Select Timeout
Enter the period after a previously received select will timeout.
CMD Termination
Select whether to send Activation Termination upon completion of commands other than set point
commands.
CSE Termination
Select whether to send Activation Termination upon completion of set point commands.
ENHANCED TECHNOLOGY 7
IEC 60870-5-101/104 PROTOCOL http://www.entecene.co.kr
MSP Time-Tag
Select whether a time tag format for single-point.
MIT Time-Tag
Select whether a time tag format for integrated totals.
MME Time-Tag
Select whether a time tag format for measured value and normalized value for general event except
for fault current event.
Flt Time-Tag
Select whether a time tag format for measured value and normalized value for fault current event.
8 ENHANCED TECHNOLOGY
IEC 60870-5-101/104 PROTOCOL http://www.entecene.co.kr
MMEND Start Measured value, normalized value without quality descriptor 1 6000
PMENC Start Parameter of measured value, short floating point value 1 14000
ENHANCED TECHNOLOGY 9
IEC 60870-5-101/104 PROTOCOL http://www.entecene.co.kr
NOTE )
“Threshold” used in IEC60870-5-101/104 protocol is described as “Deadband” in the settings
and manuals of all ENTEC’s products.
In order to change the Threshold Configuration for IEC 60870-5-101/104 protocol
communication, change settings such as Limit Low, Limit High, Dead Band or Smoothing
Factor in the “DB MAP CONFIGURATION” setting on the application program.
“Threshold” is described as “Deadband” in the explanation below.
A maximum or minimum value of an analog input can be configured to set the desired range for
analog event reporting. Deadband value is set to generate the event when the analog input’s
value difference between the last value and the current value exceeds the deadband value. The
time period of data updating is 1sec.
10 ENHANCED TECHNOLOGY
IEC 60870-5-101/104 PROTOCOL http://www.entecene.co.kr
input’s value difference between the last value and the current value is over the
deadband value configured by a user. For example, in Figure 1, if the value
difference between the analog input’s values at t1 and t2 exceeds the deadband
value, the event occurs. If the measured value at t4 is below the “Limit Low”
value, the value difference between t3 and t4 is considered as the difference
between the analog input value at t3 and t4 and so the variation between t3 and t4
generates event if it is over the deadband value.
However, after the measured value crosses down the “Limit Low” value once like
the value at t4 and if the subsequent measured values after the time t4 keep
changing below the “Limit Low” value, those variations below the “Limit Low”
value do not generate event even though the variations below the “Limit Low”
value exceeds the deadband value. If the measured value comes in the range
between the “Limit High” and the “Limit Low” values again and the variation at
that time exceeds the deadband value, the event for the variation is generated. In
the same way, an event is generated for the value crossing over or down the
“Limit High” value.
ENHANCED TECHNOLOGY 11
IEC 60870-5-101/104 PROTOCOL http://www.entecene.co.kr
D. Interoperability Document
if>1200 bits/s:
□ 600bits/sec. ▣ 19200bits/sec.
▣ 1200bits/sec. ▣ 38400bits/sec.
▣ 56000bits/sec.
□ 64000bits/sec
12 ENHANCED TECHNOLOGY
IEC 60870-5-101/104 PROTOCOL http://www.entecene.co.kr
if>1200 bits/s:
□ 600bits/sec. ▣ 19200bits/sec.
▣ 1200bits/sec. ▣ 38400bits/sec.
▣ 56000bits/sec.
□ 64000bits/sec
□ Structured
▣ Unstructured
*. NOTE ) The above item marked with * are supported from Ver. 2.05 of
CPU firmware.
Frame Length :
When using an unbalanced link layer, the following ADSU types are returned in class 2 messages (low
priority) with the indicated causes of transmission:
9 <1>
※ Note) In response to a class 2 poll, a controller station may respond with class 1 data when there is no
ENHANCED TECHNOLOGY 13
IEC 60870-5-101/104 PROTOCOL http://www.entecene.co.kr
*. NOTE ) The above item marked with * are supported from Ver. 2.05 of CPU firmware.
*. NOTE ) The above item marked with * are supported from Ver. 2.05 of CPU firmware.
Cause of Transmission:
▣ One Octet
▣ Two Octets (with originator address). Originator address is set to zero if not used. (*)
*. NOTE ) The above item marked with * are supported from Ver. 2.05 of CPU firmware.
▣– used in standard direction; □ – not used; ■ – cannot be selected in IEC 60870-5-104 standard.
14 ENHANCED TECHNOLOGY
IEC 60870-5-101/104 PROTOCOL http://www.entecene.co.kr
■ <14> := Measured value, short floating point value with time tag M_NE_TC_1
■ <18> := Packed start events of protection equipment with time tag M_EP_TB_1
■ <19> := Packed output circuit information of protection equipment with time tag M_EP_TC_1
▣ <34> := Measured value, normalized value with time tag CP56Time2a (*) M_ME_TD_1
□ <35> := Measured value, scaled value with time tag CP56Time2a M_ME_TE_1
□ <36> := Measured value, short floating point value with time tag CP56Time2a M_ME_TF_1
□ <39> := Packed start events of protection equipment with time tag CP56Time2a M_EP_TE_1
Either the ASDUs of the set <2>, <4>, <6>, <8>, <10>, <12>, <14>, <16>, <17>, <18>, and <19> or of the
*. NOTE ) 1. The above item marked with * are supported from Ver. 2.05 of CPU firmware.
2. The above item marked with * are supported from Ver. 2.10 of CPU firmware.
ENHANCED TECHNOLOGY 15
IEC 60870-5-101/104 PROTOCOL http://www.entecene.co.kr
File transfer
□ <120> := File Ready F_FR_NA_1
□ <122> := Call directory, select file, call file, call section F_SC_NA_1
□ <123> := Last section, last segment F_LS_NA_1
16 ENHANCED TECHNOLOGY
IEC 60870-5-101/104 PROTOCOL http://www.entecene.co.kr
IDENTIFICATION
PERIODIC, CYCLIC
BACKGROUND SCAN
SPONTANEOUS
INITIALIZED
REQUEST OR REQUESTED
ACTIVATION
ACTIVATION CONFIRMATION
DEACTIVATION
DEACTIVATION CONFIRMATION
ACTIVATION TERMINATION
FILE TRANSFER
<1> M_SP_NA_1 X X X
<2> M_SP_TA_1** X X X
<3> M_DP_NA_1
<4> M_DP_TA_1
<5> M_ST_NA_1
<6> M_ST_TA_1
<7> M_BO_NA_1
<8> M_BO_TA_1
<9> M_ME_NA_1 X X X X
<10> M_ME_TA_1** X
<11> M_ME_NB_1
<12> M_ME_TB_1
<13> M_ME_NC_1
<14> M_ME_TC_1
<15> M_IT_NA_1 X X
<16> M_IT_TA_1** X
<17> M_EP_TA_1
<18> M_EP_TB_1
<19> M_EP_TC_1
<20> M_PS_NA_1
<21> M_ME_ND_1 X X
<30> M_SP_TB_1 X X X
<31> M_DP_TB_1
<32> M_ST_TB_1
ENHANCED TECHNOLOGY 17
IEC 60870-5-101/104 PROTOCOL http://www.entecene.co.kr
PERIODIC, CYCLIC
BACKGROUND SCAN
SPONTANEOUS
INITIALIZED
REQUEST OR REQUESTED
ACTIVATION
ACTIVATION CONFIRMATION
DEACTIVATION
DEACTIVATION CONFIRMATION
ACTIVATION TERMINATION
FILE TRANSFER
<33> M_BO_TB_1
<34> M_ME_TD_1* X
<35> M_ME_TE_1
<36> M_ME_TF_1
<37> M_IT_TB_1* X
<38> M_EP_TD_1
<39> M_EP_TE_1
<40> M_EP_TF_1
<45> C_SC_NA_1 X X X X X
<46> C_DC_NA_1
<47> C_RC_NA_1
<48> C_SE_NA_1 X X X X X
<49> C_SE_NB_1
<50> C_SE_NC_1
<51> C_BO_NA_1
<70> M_EI_NA_1* X
<100> C_IC_NA_1 X X X X X
<101> C_CI_NA_1 X X X
<102> C_RD_NA_1 X
<103> C_CS_NA_1 X X X
<104> C_TS_NA_1
<105> C_RP_NA_1 X X
<106> C_CD_NA_1
18 ENHANCED TECHNOLOGY
IEC 60870-5-101/104 PROTOCOL http://www.entecene.co.kr
PERIODIC, CYCLIC
BACKGROUND SCAN
SPONTANEOUS
INITIALIZED
REQUEST OR REQUESTED
ACTIVATION
ACTIVATION CONFIRMATION
DEACTIVATION
DEACTIVATION CONFIRMATION
ACTIVATION TERMINATION
FILE TRANSFER
<110> P_ME_NA_1 X X X
<111> P_ME_NB_1
<112> P_ME_NC_1
<113> P_AC_NA_1
<120> F_FR_NA_1
<121> F_SR_NA_1
<122> F_SC_NA_1
<123> F_LS_NA_1
<124> F_AF_NA_1
<125> F_SG_NA_1
<126> F_DR_TA_1*
- Blank or X only
*. NOTE ) 1. The above item marked with * are supported from Ver. 2.05 of CPU firmware.
2. The above item marked with * are supported from Ver. 2.10 of CPU firmware.
ENHANCED TECHNOLOGY 19
IEC 60870-5-101/104 PROTOCOL http://www.entecene.co.kr
Read Procedure:
▣ Read procedure
Spontaneous Transmission:
▣ Spontaneous transmission
an information object. The particular information object addresses for which double transmission is
enabled are defined in a project-specific list.
□ Bitstring of 32 bits: M_BO_NA_1, M_BO_TA_1, and M_BO_TB_1 (if defined for a specific project)
□ Measured value, short floating point number: M_ME_NC_1, M_ME_TC_1, and M_ME_TF_1
Station interrogation:
▣ Global
20 ENHANCED TECHNOLOGY
IEC 60870-5-101/104 PROTOCOL http://www.entecene.co.kr
Clock synchronization:
▣ Clock synchronization (optional)
Command transmission:
▣ Direct command transmission
□ No additional definition
□ Persistent output
▣ Counter read
*. NOTE ) The above item marked with ** are supported from Ver. 2.10 of CPU firmware.
ENHANCED TECHNOLOGY 21
IEC 60870-5-101/104 PROTOCOL http://www.entecene.co.kr
Parameter loading:
▣ Threshold value
□ Smoothing factor
Parameter activation:
□ Activation/deactivation of persistent cyclic or periodic transmission of the addressed object
Test procedure:
□ Test procedure
File transfer:
File transfer in monitor direction:
□ Transparent file
□ Transparent file
Background scan:
□ Background scan
22 ENHANCED TECHNOLOGY
IEC 60870-5-101/104 PROTOCOL http://www.entecene.co.kr
if>1200 bits/s:
■ 600bits/sec. ■ 19200bits/sec.
■ 1200bits/sec. ■ 38400bits/sec.
■ 56000bits/sec.
■ 64000bits/sec.
ENHANCED TECHNOLOGY 23
IEC 60870-5-101/104 PROTOCOL http://www.entecene.co.kr
if>1200 bits/s:
■ 600bits/sec. ■ 19200bits/sec.
■ 1200bits/sec. ■ 38400bits/sec.
■ 56000bits/sec.
■ 64000bits/sec.
■ Two Octets
■ Structured
■ Unstructured
Frame Length (maximum length, number of octets): Not selectable in companion IEC 60870-5-104 standard
When using an unbalanced link layer, the following ADSU types are returned in class 2 messages (low
priority) with the indicated causes of transmission:
24 ENHANCED TECHNOLOGY
IEC 60870-5-101/104 PROTOCOL http://www.entecene.co.kr
▣ Three Octets
Cause of Transmission:
■ One Octet
▣ Two Octets (with originator address). Originator address is set to zero if not used.
Maximum Length of APDU: 253 (the maximum length may be reduced by the system.)
▣– used in standard direction; □ – not used; ■ – cannot be selected in IEC 60870-5-104 standard.
■ <14> := Measured value, short floating point value with time tag M_NE_TC_1
■ <18> := Packed start events of protection equipment with time tag M_EP_TB_1
■ <19> := Packed output circuit information of protection equipment with time tag M_EP_TC_1
ENHANCED TECHNOLOGY 25
IEC 60870-5-101/104 PROTOCOL http://www.entecene.co.kr
▣ <34> := Measured value, normalized value with time tag CP56Time2a (*) M_ME_TD_1
▣ <35> := Measured value, scaled value with time tag CP56Time2a M_ME_TE_1
□ <36> := Measured value, short floating point value with time tag CP56Time2a M_ME_TF_1
□ <39> := Packed start events of protection equipment with time tag CP56Time2a M_EP_TE_1
Either the ASDUs of the set <2>, <4>, <6>, <8>, <10>, <12>, <14>, <16>, <17>, <18>, and <19> or of the
*. NOTE ) 1. The above item marked with * are supported from Ver. 2.05 of CPU firmware.
2. The above item marked with * are supported from Ver. 2.10 of CPU firmware.
□ <61> := Set point command, normalized value with time tag CP56Time2a C_SE_TA_1
□ <62> := Set point command, scaled value with time tag CP56Time2a C_SE_TB_1
□ <63> := Set point command, short floating point value with time tag CP56Time2a C_SE_TC_1
Either the ASDUs of the set <45> to <51> or of the set <58> to <64> are used.
26 ENHANCED TECHNOLOGY
IEC 60870-5-101/104 PROTOCOL http://www.entecene.co.kr
File transfer
□ <120> := File Ready F_FR_NA_1
□ <122> := Call directory, select file, call file, call section F_SC_NA_1
ENHANCED TECHNOLOGY 27
IEC 60870-5-101/104 PROTOCOL http://www.entecene.co.kr
PERIODIC, CYCLIC
BACKGROUND SCAN
SPONTANEOUS
INITIALIZED
REQUEST OR REQUESTED
ACTIVATION
ACTIVATION CONFIRMATION
DEACTIVATION
DEACTIVATION CONFIRMATION
ACTIVATION TERMINATION
FILE TRANSFER
<1> M_SP_NA_1 X X X
<2> M_SP_TA_1** X X X
<3> M_DP_NA_1
<4> M_DP_TA_1
<5> M_ST_NA_1
<6> M_ST_TA_1
<7> M_BO_NA_1
<8> M_BO_TA_1
<9> M_ME_NA_1 X X X X
<10> M_ME_TA_1** X
<11> M_ME_NB_1
<12> M_ME_TB_1
<13> M_ME_NC_1
<14> M_ME_TC_1
<15> M_IT_NA_1 X X
<16> M_IT_TA_1** X
<17> M_EP_TA_1
<18> M_EP_TB_1
<19> M_EP_TC_1
<20> M_PS_NA_1
<21> M_ME_ND_1 X X
<30> M_SP_TB_1 X X X
<31> M_DP_TB_1
28 ENHANCED TECHNOLOGY
IEC 60870-5-101/104 PROTOCOL http://www.entecene.co.kr
PERIODIC, CYCLIC
BACKGROUND SCAN
SPONTANEOUS
INITIALIZED
REQUEST OR REQUESTED
ACTIVATION
ACTIVATION CONFIRMATION
DEACTIVATION
DEACTIVATION CONFIRMATION
ACTIVATION TERMINATION
FILE TRANSFER
<32> M_ST_TB_1
<33> M_BO_TB_1
<34> M_ME_TD_1* X
<35> M_ME_TE_1
<36> M_ME_TF_1
<37> M_IT_TB_1* X
<38> M_EP_TD_1
<39> M_EP_TE_1
<40> M_EP_TF_1
<45> C_SC_NA_1 X X X X X
<46> C_DC_NA_1
<47> C_RC_NA_1
<48> C_SE_NA_1 X X X X X
<49> C_SE_NB_1
<50> C_SE_NC_1
<51> C_BO_NA_1
<58> C_SC_TA_1 X X X X X
<59> C_DC_TA_1
<60> C_RC_TA_1
<61> C_SE_TA_1 X X X X X
<62> C_SE_TB_1
<63> C_SE_TC_1
<64> C_BO_TA_1
ENHANCED TECHNOLOGY 29
IEC 60870-5-101/104 PROTOCOL http://www.entecene.co.kr
PERIODIC, CYCLIC
BACKGROUND SCAN
SPONTANEOUS
INITIALIZED
REQUEST OR REQUESTED
ACTIVATION
ACTIVATION CONFIRMATION
DEACTIVATION
DEACTIVATION CONFIRMATION
ACTIVATION TERMINATION
FILE TRANSFER
<70> M_EI_NA_1* X
<100> C_IC_NA_1 X X X X X
<101> C_CI_NA_1 X X X
<102> C_RD_NA_1 X
<103> C_CS_NA_1 X X X
<104> C_TS_NA_1
<105> C_RP_NA_1 X X
<106> C_CD_NA_1
<107> C_TS_TA_1 X X
<110> P_ME_NA_1 X X X
<111> P_ME_NB_1
<112> P_ME_NC_1
<113> P_AC_NA_1
<120> F_FR_NA_1
<121> F_SR_NA_1
<122> F_SC_NA_1
<123> F_LS_NA_1
<124> F_AF_NA_1
<125> F_SG_NA_1
<126> F_DR_TA_1*
- Blank or X only
*. NOTE ) 1. The above item marked with * are supported from Ver. 2.05 of CPU firmware.
2. The above item marked with * are supported from Ver. 2.10 of CPU firmware.
30 ENHANCED TECHNOLOGY
IEC 60870-5-101/104 PROTOCOL http://www.entecene.co.kr
Read Procedure:
▣ Read procedure
Spontaneous Transmission:
▣ Spontaneous transmission
an information object. The particular information object addresses for which double transmission is
enabled are defined in a project-specific list.
□ Bitstring of 32 bits: M_BO_NA_1, M_BO_TA_1, and M_BO_TB_1 (if defined for a specific project)
□ Measured value, short floating point number: M_ME_NC_1, M_ME_TC_1, and M_ME_TF_1
Station interrogation:
▣ Global
ENHANCED TECHNOLOGY 31
IEC 60870-5-101/104 PROTOCOL http://www.entecene.co.kr
Clock synchronization:
▣ Clock synchronization (optional)
Command transmission:
▣ Direct command transmission
□ No additional definition
□ Persistent output
▣ Supervision of maximum delay in command direction of commands and set point commands
▣ Counter read
▣ Counter reset
Parameter loading:
▣ Threshold value
□ Smoothing factor
32 ENHANCED TECHNOLOGY
IEC 60870-5-101/104 PROTOCOL http://www.entecene.co.kr
Parameter activation:
□ Activation/deactivation of persistent cyclic or periodic transmission of the addressed object
Test procedure:
□ Test procedure
File transfer:
File transfer in monitor direction:
□ Transparent file
□ Transparent file
Background scan:
□ Background scan
VALUE VALUE
ENHANCED TECHNOLOGY 33
IEC 60870-5-101/104 PROTOCOL http://www.entecene.co.kr
VALUE VALUE
Port number:
the Internet as determined by the Internet Architecture Board (IAB). It offers a broad spectrum of actual
standards used in the Internet. The suitable selection of documents from RFC 2200 defined in this
standard for given projects has to be chosen by the user of this standard.
▣ Ethernet 802.3
34 ENHANCED TECHNOLOGY
IEC 60870-5-101/104 PROTOCOL http://www.entecene.co.kr
ENHANCED TECHNOLOGY 35
IEC 60870-5-101/104 PROTOCOL http://www.entecene.co.kr
36 ENHANCED TECHNOLOGY
IEC 60870-5-101/104 PROTOCOL http://www.entecene.co.kr
ENHANCED TECHNOLOGY 37
IEC 60870-5-101/104 PROTOCOL http://www.entecene.co.kr
38 ENHANCED TECHNOLOGY
IEC 60870-5-101/104 PROTOCOL http://www.entecene.co.kr
ENHANCED TECHNOLOGY 39
IEC 60870-5-101/104 PROTOCOL http://www.entecene.co.kr
NOTE
*. All Single Points can change assigned Point Property, Group Number and Object Address on ETIMS Interface Software.
Please refer to “ETIMS Interface Software User’s Manual” for more detail information.
*. By the use of the "Base Number" specified to each point above, the detailed description for the corresponding point
can be confirmed on "Table 1. BASE DATA POINTS - BINARY INPUT" of the "Recloser Control ETR300-R
40 ENHANCED TECHNOLOGY
IEC 60870-5-101/104 PROTOCOL http://www.entecene.co.kr
NOTE
*. Block Condition Description
- CTR Lock(Control Lock) : CONTROL function is locked status in panel
- Mec’ Lock(Mechanism Lock) : Recloser(Tank) is locked status
- Seq’ Running : Currently Sequence is conducting(79 CYCLE).
- Synchro : Synchronism check element is detected.
- AC Fail : External AC Power is not supplied.
*. All “Single Command” points can change assigned Object Address and the value(ON/OFF) of single command can be
inverted on ETIMS Interface Software. Please refer to “ETIMS Interface Software User’s Manual” for more detail
information.
ENHANCED TECHNOLOGY 41
IEC 60870-5-101/104 PROTOCOL http://www.entecene.co.kr
NOTE
*. 16 bit rollover Counter.
*. All “Integrated Totals” Points can change assigned Point Property, Group Number and Object Address on ETIMS
Interface Software. Please refer to “ETIMS Interface Software User’s Manual” for more detail information.
42 ENHANCED TECHNOLOGY
IEC 60870-5-101/104 PROTOCOL http://www.entecene.co.kr
ENHANCED TECHNOLOGY 43
IEC 60870-5-101/104 PROTOCOL http://www.entecene.co.kr
Following tables shows IOA, Value, Flags( Threshold, Low Limit, High Limit) at address 2002.
10008 50 0х01(Threshold)
*. All “Normalized Measurands” Points can change assigned Point Property, Group Number and Object Address on
ETIMS Interface Software. Please refer to “ETIMS Interface Software User’s Manual” for more detail information.
*. By the use of the "Base Map Number" specified to each point above, the detailed description for the corresponding
point can be confirmed on "Table 4. BASE DATA POINTS - ANALOG INPUT" of the " Recloser Control ETR300-
44 ENHANCED TECHNOLOGY