REGISTER LIST
ALARMS
Table B– 1: Register Listing—Setup and Status
Scale Factor V
4106 1 Integer RO N - - - Power of 10
(voltage)
Scale Factor W
4107 1 Integer RO N - - - Power of 10
(power)
Scale Factor E
4108 1 Integer RO N - - - Power of 10
(energy)
PT Ratio - Scale (0 =
4123 1 Integer R/W Y - - 0, 1, 10, 100
No PT)
RO = Read Only
R/W = Read/Write
NV = Nonvolatile.
Always return a 0.
4126 Reset Commands 1 Integer R/W N - - N/A A list of commands is shown in
Table B– 5.
10,11,12,30,31,
4127 System Type 1 Integer R/W Y - -
32,40,42,44
0 = IEC Units
4128 Display Mode 1 Integer R/W Y - - 0,1
1 = IEEE Units
RO = Read Only
R/W = Read/Write
NV = Nonvolatile.
The PM710 includes registers in two different formats: integer and floating
point. For example, Real Power A is included in Register 1066 and 1067
(floating point) and register 4036 (integer).
Table B– 2: Register Listing—Metered Data
Metered Data
Apparent Energy,
1002 2 Float RO Y - kVAh -
Total
Reactive Energy,
1004 2 Float RO Y - kVARh - Absolute
Total
Voltage, L-L, 3P
1014 2 Float RO N - Volt -
Average
Voltage, L-N, 3P
1016 2 Float RO N - Volt -
Average
RO = Read Only
R/W = Read/Write
NV = Nonvolatile.
Metered Data
RO = Read Only
R/W = Read/Write
NV = Nonvolatile.
Metered Data
0-
4000 Real Energy, Total 2 Long RO Y E kWh/Scale Absolute
0xFFFFFFFF
Apparent Energy, 0-
4002 2 Long RO Y E kVAh/Scale
Total 0xFFFFFFFF
Reactive Energy, 0-
4004 2 Long RO Y E kVARh/Scale Absolute
Total 0xFFFFFFFF
Voltage, L-L, 3P
4010 1 Integer RO N V Volt/Scale 0-32767
Average
Voltage, L-N, 3P
4011 1 Integer RO N V Volt/Scale 0-32767
Average
RO = Read Only
R/W = Read/Write
NV = Nonvolatile.
Metered Data
RO = Read Only
R/W = Read/Write
NV = Nonvolatile.
Demand Values
Current, B, Demand
1044 2 Float RO N - Amp -
Present
Current, C, Demand
1046 2 Float RO N - Amp -
Present
Current, A, Demand
1048 2 Float RO Y - Amp -
Peak
Current, B, Demand
1050 2 Float RO Y - Amp -
Peak
Current, C, Demand
1052 2 Float RO Y - Amp -
Peak
Real Power, Total
4014 Demand 1 Integer RO N W kW/Scale 0-32767 Absolute
Present
Apparent Power, Total
4015 Demand 1 Integer RO N W kVA/Scale 0-32767
Present
Reactive Power, Total
4016 Demand 1 Integer RO N W kVAR/Scale 0-32767 Absolute
Present
Real Power, Total
4017 Demand 1 Integer RO Y W kW/Scale 0-32767 Absolute
Peak
Apparent Power, Total
4018 Demand 1 Integer RO Y W kVA/Scale 0-32767
Peak
Reactive Power, Total
4019 Demand 1 Integer RO Y W kVAR/Scale 0-32767 Absolute
Peak
Current, A, Demand
4024 1 Integer RO N I Amp/Scale 0-32767
Present
Current, B, Demand
4025 1 Integer RO N I Amp/Scale 0-32767
Present
Current, C, Demand
4026 1 Integer RO N I Amp/Scale 0-32767
Present
RO = Read Only
R/W = Read/Write
NV = Nonvolatile.
Demand Values
Current, B, Demand
4028 1 Integer RO Y I Amp/Scale 0-32767
Peak
Current, C, Demand
4029 1 Integer RO Y I Amp/Scale 0-32767
Peak
RO = Read Only
R/W = Read/Write
NV = Nonvolatile.
Frequency
1112 2 Float RO Y - Hz 45.0-65.0
Minimum
Current, A,
1114 2 Float RO Y - Amp -
Minimum
Current, B,
1116 2 Float RO Y - Amp -
Minimum
Current, C,
1118 2 Float RO Y - Amp -
Minimum
Voltage, A-N,
1122 2 Float RO Y - Volt -
Minimum
Voltage, B-N,
1124 2 Float RO Y - Volt -
Minimum
Voltage, C-N,
1126 2 Float RO Y - Volt -
Minimum
Voltage, A-B,
1128 2 Float RO Y - Volt -
Minimum
Voltage, B-C,
1130 2 Float RO Y - Volt -
Minimum
Voltage, C-A,
1132 2 Float RO Y - Volt -
Minimum
Current, A, THD
1134 2 Float RO Y - % 0.0-1000.0
Minimum
Current, B, THD
1136 2 Float RO Y - % 0.0-1000.0
Minimum
Current, C, THD
1138 2 Float RO Y - % 0.0-1000.0
Minimum
RO = Read Only
R/W = Read/Write
NV = Nonvolatile.
Frequency
1162 2 Float RO Y - Hz 45.0-65.0
Maximum
Current, A,
1164 2 Float RO Y - Amp -
Maximum
Current, B,
1166 2 Float RO Y - Amp -
Maximum
Current, C,
1168 2 Float RO Y - Amp -
Maximum
Voltage, A-N,
1172 2 Float RO Y - Volt -
Maximum
Voltage, B-N,
1174 2 Float RO Y - Volt -
Maximum
Voltage, C-N,
1176 2 Float RO Y - Volt -
Maximum
Voltage, A-B,
1178 2 Float RO Y - Volt -
Maximum
Voltage, B-C,
1180 2 Float RO Y - Volt -
Maximum
Voltage, C-A,
1182 2 Float RO Y - Volt -
Maximum
Current, A, THD
1184 2 Float RO Y - % 0.0-1000.0
Maximum
Current, B, THD
1186 2 Float RO Y - % 0.0-1000.0
Maximum
Current, C, THD
1188 2 Float RO Y - % 0.0-1000.0
Maximum
Frequency
4059 1 Integer RO Y 0.01 Hz 4500-6500
Minimum
Current, A,
4060 1 Integer RO Y I Amp 0-32767
Minimum
Current, B,
4061 1 Integer RO Y I Amp 0-32767
Minimum
Current, C,
4062 1 Integer RO Y I Amp 0-32767
Minimum
Voltage, A-N,
4064 1 Integer RO Y V Volt 0-32767
Minimum
Voltage, B-N,
4065 1 Integer RO Y V Volt 0-32767
Minimum
Voltage, C-N,
4066 1 Integer RO Y V Volt 0-32767
Minimum
Voltage, A-B,
4067 1 Integer RO Y V Volt 0-32767
Minimum
Voltage, B-C,
4068 1 Integer RO Y V Volt 0-32767
Minimum
Voltage, C-A,
4069 1 Integer RO Y V Volt 0-32767
Minimum
Current, A, THD
4070 1 Integer RO Y 0.1 % 0-10000
Minimum
Current, B, THD
4071 1 Integer RO Y 0.1 % 0-10000
Minimum
Current, C, THD
4072 1 Integer RO Y 0.1 % 0-10000
Minimum
Frequency
4084 1 Integer RO Y 0.01 Hz 4500-6500
Maximum
Current, A,
4085 1 Integer RO Y I Amp 0-32767
Maximum
Current, B,
4086 1 Integer RO Y I Amp 0-32767
Maximum
Current, C,
4087 1 Integer RO Y I Amp 0-32767
Maximum
Voltage, A-N,
4089 1 Integer RO Y V Volt 0-32767
Maximum
Voltage, B-N,
4090 1 Integer RO Y V Volt 0-32767
Maximum
Voltage, C-N,
4091 1 Integer RO Y V Volt 0-32767
Maximum
Voltage, A-B,
4092 1 Integer RO Y V Volt 0-32767
Maximum
Voltage, B-C,
4093 1 Integer RO Y V Volt 0-32767
Maximum
Voltage, C-A,
4094 1 Integer RO Y V Volt 0-32767
Maximum
Current, A, THD
4095 1 Integer RO Y 0.1 % 0-10000
Maximum
Current, B, THD
4096 1 Integer RO Y 0.1 % 0-10000
Maximum
Current, C, THD
4097 1 Integer RO Y 0.1 % 0-10000
Maximum
Command Description
0x03 Read holding registers
0x04 Read input registers
0x06 Preset single registers
0x10 Preset multiple registers
Report ID
Return String
byte 1: 0x11
0x11 byte 2: number of bytes following without crc
byte 3: ID byte = 250
byte 4: status = 0xFF
bytes 5+: ID string = PM710 Power Meter
last 2 bytes: CRC
Read device identification, BASIC implementation (0x00, 0x01, 0x02 data),
conformity level 1,
Object Values
0x01: If register 4128 is 0, then “Merlin Gerin. If register 4128 is 1, then
0x2B “Square D”
0x02: “PM710”
0x03: “Vxx.yyy” where xx.yyy is the OS version number. This is the
reformatted version of register 7001. If the value for register 7001 is 12345,
then the 0x03 data would be “V12.345”