CUADRO DE CARGA PARA CASA DE ESTRA
TOMAS POTENCIA P (W)
NORMAL GFCI ESPECIALES REGULADOS
A B C TOTAL
171 171
202 202
264 264
346 346
5 855 855
1 1350 1350
5 3 1368 1368
1 1425 1425
1 1350 1350
1 171 171
1 1350 1350
2 342 342
1 1800 1800
11 5 1 1 5915 5915
0 0 0 0 0
0 0 0 0 0

24 8 5 9747 3306 3685 16738

CUADRO DE CARGA- PLANTA(2)


TOMAS POTENCIA P (W)
NORMAL GFCI ESPECIALES REGULADO
A B C TOTAL
171 171
140 140
204 204
60 60
4 684 684
1 1350 1350
2 342 342
5 5 1710 1710
1 1425 1425
0 0 0 0 0
0 0 0 0 0

11 5 1 2534 2979 402 5915


RA CASA DE ESTRATO 6 PLUS
PROTECCION CONDUCTO
FP S(VA) V(V) I(A) I*1,15
POLOS CAPASIDAD I*1,25

0.9 224 208 1.07906 1.240918803419 3 20 1.348824786325


0.9 293 208 1.41026 1.621794871795 3 20 1.762820512821
0.9 384 208 1.84829 2.125534188034 3 20 2.310363247863
0.95 900 208 4.32692 4.975961538462 3 20 5.408653846154
0.9 1500 208 7.21154 8.293269230769 3 20 9.014423076923
0.9 1520 208 7.30769 8.403846153846 3 20 9.134615384615
0.95 1500 208 7.21154 8.293269230769 3 20 9.014423076923
0.9 1500 208 7.21154 8.293269230769 3 20 9.014423076923
0.95 180 208 0.86538 0.995192307692 3 20 1.081730769231
0.9 1500 208 7.21154 8.293269230769 3 20 9.014423076923
0.95 360 208 1.73077 1.990384615385 3 20 2.163461538462
0.9 2000 208 9.61538 11.05769230769 3 20 12.01923076923
0.9 6329 208 30.4274 34.99145299145 3 2X20 38.03418803419

0.9201 18191.11111 208 87.4573 100.5758547009 3 75 109.3215811966

CARGA- PLANTA(2)
PROTECCION CONDUCTO
FP S(VA) V(V) I(A) I*1,15
POLOS CAPASIDAD I*1,25

0.9 156 208 0.74786 0.860042735043 3 20 0.934829059829


0.9 227 208 1.08974 1.253205128205 3 20 1.362179487179
0.9 67 208 0.32051 0.36858974359 3 20 0.400641025641
0.95 720 208 3.46154 3.980769230769 3 20 4.326923076923
0.9 1500 208 7.21154 8.293269230769 3 20 9.014423076923
0.95 360 208 1.73077 1.990384615385 3 20 2.163461538462
0.95 1800 208 8.65385 9.951923076923 3 20 10.81730769231
0.95 1500 208 7.21154 8.293269230769 3 20 9.014423076923

0.9346 6328.888889 208 30.4274 34.99145299145 3 60 38.03418803419


CONDUCTOR
OBCERVACIONES
CALIBRE TIPO

12 Cu THHN AWG LUCES


12 Cu THHN AWG LUCES
12 Cu THHN AWG LUCES
12 Cu THHN AWG TOMAS
12 Cu THHN AWG LAV-AFEC
12 Cu THHN AWG TOMAS
12 Cu THHN AWG TOMA.REGULADO
12 Cu THHN AWG P.ART(NEV-LIC)
12 Cu THHN AWG TOMAS
12 Cu THHN AWG PLANCHA
12 Cu THHN AWG TOMAS
12 Cu THHN AWG AIRE-ACON
8 Cu THHN AWG PISO 2

Cu THHN AWG (ANTI


4 FRAUDE- ACOMETIDA
CONSENTRICO)
CONDUCTOR
OBCERVACIONES
CALIBRE TIPO

12 Cu THHN HWG LUCES


12 Cu THHN HWG LUCES
12 Cu THHN HWG LUCES
12 Cu THHN HWG TOMA
12 Cu THHN HWG LAV-AFEC
12 Cu THHN HWG TOMAS
12 Cu THHN HWG TOMAS
12 Cu THHN HWG TOMA.REGULADO

Cu THHN HWG (ANTI


4 FRAUDE- ACOMETIDA
CONSENTRICO)
CALCULO DE CARGA
ESSA NTC2050
PISO 2 6329 6329
PEQ ART 1500 1500
LAV+AFE 1500 1500
ESP(AIRE AA) 2000 2000
VA/M 2
32 32
AREA 195 195
TOTAL 11556 11556
FAC-DDM 0.3 0.35
DEM-MAX 7897.1 8158.45
CORRIENTE 37.96682692 39.22331731
I*1,25 47.45853365 49.02914663
CONDUCTOR 8 8
PROTECCION 50 50
CALCULO DE CARGA
ESSA NTC2050
PEQ ART(LAV-AFEC) 1500 1500
VA/M 2
32 32
AREA 195 195
TOTAL 1727 1727
FAC-DDM 0.3 3.5
DEM.MAX 1568.1 2294.5
CORRIENTE 7.538942308 11.03125
I*1,25 9.423677885 13.7890625
CONDUCTOR 8 8
PROTECCION 40 40