Professional Documents
Culture Documents
Function;
A scaled dial and mechanical indicator continuously monitor the flow rate at
any given time whilst electrical switches can be specified to signal when a
particular level has been reached during increasing or decreasing flow rates.
Minimum Scale (3/4" to 21/2") 0-40 LPM
Maximum Scale (3/4" to 11/2") 0-400 LPM
(11/2" to 2") 0-500 LPM
(21/2") 0-800 LPM
Style;
Through its unique modular design it allows for easy field installation and Flanged Unit
service. It does not require any straight pipe runs before or after the monitor
thus minimizing the installation footprint. The versatile design of the vane DIMENSIONS
monitor allows for orientation to be mounted in any position. Vane style Standard Enclosure Box
monitor operates when flow is introduced through the inlet connection
making direct contact with the vane that is mechanically linked to the
indicator shaft. The fluid forces the vane to move through a contoured
opening creating a variable orifice, the greater the flow the larger the orifice
becomes for flow to pass. The vane style monitor is spring loaded and allows
the vane to return on decreasing flows.
Switches;
Are field adjustable, suitable for batching, trending, totalising or recording
where required. All Flow-Mon units can be supplied with a 0-10v or 4-20mA
output.
Aluminium Enclosure Box
Sizes;
All sizes are manufactured to the same simple design concept, the main
characteristic of which ensures that the pressure drops are confined to an
absolute minimum (see “pressure drop” charts) across the vane orifice at full
flow, with viscosities as high as 600cS. Sizes are defined by pipe size and/or
maximum flow capacity, and every flow switch is individually calibrated so that
full scale deflection is used in each application i.e. the maximum scale reading
coincides with the maximum requirements of system as specified by the customer.
Calibration may be in any units with Single or Dual scale to specification.
Comparison;
Comparable to similar style devices Medium Series
5.0
in the industry, “flow 4.5
Pressure Drop (psi)
CODE: AIR
This system offers an alternative safety arrangement for operation in explosive Air & Gas Applications
atmospheres. Compressed air can be used to transmit an on / off signal from the Flow switches can be used to measure gas flows in
danger area, or to operate a klaxon inside the danger area.
exactly the same way as liquid flows. When enquiring for such
CODE: POT an application the following information will be required:
Remote read-out option (0-10V). Rating to customer’s specification, e.g. 1K, 2K etc. Specific gravity of the gas
CODE: OUT Maximum flow volume
A transducer can be connected to the potentiometer to give the required 4-20 Operating temperature
mAmp readout. Data Loggers or Recorders can be added to the system. Operating pressure
The 3 and 6 wire switches described above are available in ATEX approved
explosion proof versions, with the appropriate enclosure box. When two or more
switches are assembled in one unit, they remain independently adjustable.
Re-adjustments may be carried out in the field.
Medium Series Installation and Maintenance Instructions
Installation Instructions; Switch Setting;
• The flow indicators are in-line devices. To install, connect your piping The cam which operates the microswitch is situated on the spindle behind
into the flanged ports, with the flow going into the port marked “IN”. the pointer and can be adjusted to give an alarm anywhere between zero
Mounting can be in any position, and no straight length of pipe is and max, flow. To alter the setting, lift the cam and rotate the cam in the
required before or after the unit. direction required until switch point is located, then gently lower cam in
• Under the Pressure Equipment Directive (PED) these products are that position.
Pressure Accessories, and are not approved for use as safety Accessories,
as defined by the PED. If used for safety purposes, it is the responsibility Enclosure box rotation instructions-change of
of the user/installer to assess the suitability of the product in the pressure flow direction
equipment or system in which it is used. Tools required:
Screw driver
It is the responsibility of the user/installer of this equipment Allen wrench set
to ensure;- 5/16 nut driver
1. The product is installed and used by suitably trained personnel in
accordance with all relevant Local and National regulations and codes. 1.) Remove 4 screws from nameplate. -5/16 Nut Driver
2. Safe working practices for the media & processes concerned are 2.) Remove Name Plate and Window
followed during installation & maintenance. 3.) Remove Calibrated Scale.
3. The materials of construction are suitable for the application. 4.) Remove Electrical Switch -Screw Driver (if monitor does not have
4. The product is protected from fire. switch(es) go to #5.)
5. The product is protected from impact/vibration. 5.) Remove all 4 Allen Screws (5/32 or 4mm Allen Wrench) at base of
6. The instrument is only cleaned by washing with detergent, do not use enclosure and rotate enclosure box to the desired position
abrasive cleaners or solvents. 6.) Place 4 Allen Screws back into required tapped and tighten control
7. For outdoor use in exposed positions the instrument must be box to meter body.
additionally protected/shielded from heavy rainfall. 7.) Loosen Indicator Pointer
8. Regular inspection for corrosion/erosion and wear are carried out. NOTE: if monitor does not have switch(es) skip to #11)
Essential Safety Requirements; 8.) "Slightly" Loosen Cam Set Screw just enough to move cam on dial.
1. The instrument must be installed in accordance with the instructions (DO NOT LOOSEN DIAL SET SCREW LOCATED BELOW THE CAM). This
provided. will make easier to tighten once switch contact point is set.) -1/8
2. Prior to installation ensure pipelines are flushed/drained to ensure they (3.175mm)Allen Wrench
are free from any solid particles or pressure. 9.) Place Switch back into enclosure box and tighten until snug -DO NOT
3. Care must be taken to avoid introducing torsional stress on the OVER TIGHTEN
instrument when installing into the pipeline. Tighten sufficiently to avoid NOTE: Switch should be wired prior to re-installation
leaks & check at regular intervals during maintenance.
4. Ensure pipelines are fully primed before commencing normal use. 10.) Rotate Cam to desired Set Point and tighten Allen Screw until snug.
5. Valves must be opened or closed gradually to avoid shock/vibration. Cam will press against switch roller arm to actuate switch.
6. Do not exceed maximum working pressure as stated on the label. 11.) Place Calibrate Scale and tighten back in position. - DO NOT OVER
7. Only use with the fluid/gas stated on the label. TIGHTEN
8. Do not exceed minimum/maximum working temperature as stated. 12.) Move Pointer to zero position on calibrated scale and tighten
9. Do Not Use instrument if any part of the cable appears to be damaged. 13.) Place Window then nameplate back on enclosure box and tighten
10. Isolate instrument before removing cover. Allen Screws.
Item Description
27. Spring Cover
28. Spring Housing
29. Stud & Nuts
30. O-Ring
S1, S2, S3, S4
31. Bowl Screwed/Flanged
AL, B, CI, CIK, S, SS, PVC
32. Centre Housing
AL, B, CI, CIK, S, SS, PVC
33. Mounting Disc
34. Enclosure Box
35. Switch
3EE, 3EEG, 4EE, 6EE, 3EE(ATEX3), 3EE(ATEX2),
6EE(ATEX2), AIR, POT, OUT, DIG, TOT
36. Screw
37. Pointer
38. Window
39. Screw
40. (a) Rear O-Ring
(b) Front O-Ring
41. Spring
42. Bearing
Spares Kit
43. O-Ring
Item Qty
S1, S2, S3, S4
30 4-off
44. Valve Plate
35 1-off
45. Grub Screw
36 2-off
46. Spindle
38 1-off
47. Indicator Dial
40 1-off
48. Screw
43 2-off
49. Cam
52 3-off
50. Dial Plate
51. Face Plate
52. Screw