1 User instructions .............................................................................................................. 4
1.1 Target group .................................................................................................................. 4
1.2 Symbols .......................................................................................................................... 4
1.3 Guarantee and Liability ............................................................................................... 5
2 Safety ..................................................................................................................................... 6
2.1 Designated application ............................................................................................... 6
2.2 When gas can be smelled ......................................................................................... 6
2.3 Safety measures ........................................................................................................... 6
2.3.1 Personal protective equipment (PPE) .............................................................. 6
2.3.2 Normal operation ................................................................................................... 6
2.3.3 Electrical work ........................................................................................................ 7
2.3.4 Gas supply .............................................................................................................. 7
2.4 Alterations to the construction of the equipment ................................................. 7
2.5 Noise emission ............................................................................................................. 7
2.6 Disposal ......................................................................................................................... 7
7 Commissioning .............................................................................................................. 27
7.1 Prerequisite ................................................................................................................. 27
8 Shutdown .......................................................................................................................... 47
9 Servicing ............................................................................................................................ 48
9.1 Notes on servicing ..................................................................................................... 48
9.2 Service plan ................................................................................................................. 50
9.3 Removing and refitting mixing head ....................................................................... 51
9.4 Set mixing head .......................................................................................................... 52
9.5 Set ionisation and ignition electrodes ................................................................... 53
9.6 Service position .......................................................................................................... 53
9.7 Removing and refitting fan wheel ........................................................................... 54
9.8 Remove burner motor ............................................................................................... 54
9.9 Removing and refitting air regulator ....................................................................... 55
9.10 Replacing coil on multifunction assembly .......................................................... 56
9.11 Replacing the fuse .................................................................................................. 57
13 Spares ................................................................................................................................. 72
1 User instructions
This manual forms part of the equipment and must be kept on site.
Translation of original Carefully read the manual prior to working on the unit.
operating instructions
1.2 Symbols
Immediate danger with high risk.
Non observance can lead to serious injury or death.
DANGER
Danger with medium risk.
Non observance can lead to environmental damage,
serious injury or death.
WARNING
Danger with low risk.
Non observance can cause damage to the equip-
ment and injury to personnel.
CAUTION
Important information
2 Safety
2.6 Disposal
Dispose of all materials and components in a safe and environmentally friendly way
at an authorised location. Observe local regulations.
3 Product description
1 Name plate
Ser.No.
3.3 Function
Air damper
The air damper regulates the air quantity required for combustion. The air damper
position is set using a setting screw on the air damper or the actuator (optional).
At burner shutdown the the actuator (optional) automatically closes the air damper.
At burner shutdown the air dampers close automatically.
Fan wheel
The fan wheel supplies the air from the air intake housing to the combustion head.
Diffuser
The air gap between flame tube and diffuser is adjusted by positioning the diffuser.
This adjusts the mixing pressure and the air quantity required for combustion.
Multifunction assembly 8
The multifunction assembly contains:
Gas filter 2 The gas filter protects the gas valve train from for-
eign particles.
Double gas valve 4 The double gas valve opens and shuts off the gas
supply.
Pressure regulator 3 The pressure regulator reduces the connection
pressure and ensures a constant setting pressure.
Using setting screws, the gas quantity for ignition
gas (A) and full load (B) can be set separately.
3 4 2 1
A V2 V1
P P
6 8 7 5
Combustion Manager
The combustion manager W-FM is the control unit of the burner.
It controls the sequence of operation and monitors the flame.
Burner motor
The burner motor drives the fan wheel.
Ignition unit
The electronic ignition unit creates a spark at the electrode, which ignites the fuel/
air mixture.
Ionisation electrode
The combustion manager monitors the flame signal via the ionisation electrode.
If the flame signal becomes too weak, the combustion manager carries out a con-
trolled shutdown.
Ignition
Pre-ignition time (TVZ) starts before the end of the pre-purge time (TV).
Ignition starts.
Fuel release
Following pre-ignition time (TVZ) the double gas valve (K32) opens and releases the
fuel.
Safety time
With fuel release, safety time (TS) and post-ignition time (TNZ) start.
The flame signal must be present within the safety time (TS).
Operation
The combustion manager monitors the flame signal via the ionisation electrode.
Post-purge
If there is no longer a heat demand, the double gas valve (K32) closes and stops
the fuel supply.
Post-purge time (TN) begins.
Following the post-purge time (TN) the burner motor switches off.
W-FM 05
L N T1 T2 6 12 2 3 11 4 5 13 B4
P P P P
F2 B15 B31 S2 B10
B1
M M
1
K33 M20 M1 T1 K32 P11
L N
TI
(1
TV
TVZ
TNZ TS
TN
3.4.4 Fuels
Natural Gas E/LL
Liquid Petroleum Gas B/P
3.4.5 Emissions
Flue gas
To EN 676 the burner complies with emission class 3.
The NOx values are influenced by:
combustion chamber dimensions
flue gas system
fuel
combustion air (temperature and humidity)
medium temperature
Combustion chamber dimensions, see Weishaupt Partner Portal / Documents and
Applications / Online Applications / NOX calculation for burners.
Sound levels
Dual number noise emission values
Measured sound power level LWA (re 1 pW) 63 dB(A)(1
Uncertainty value KWA 4 dB(A)
Measured sound pressure level LpA (re 20 μPa) 58 dB(A)(2
Uncertainty value KpA 4 dB(A)
(1
Determined to ISO 9614-2.
(2
Determined at 1 metre distance from the front of the burner.
The measured noise levels plus uncertainty values form the upper limit value, which
could occur when measuring.
3.4.6 Rating
Capacity graph
Capacity graph to EN 676.
The capacity data given relates to an installation elevation of 0 m above sea level.
For installation elevations above 0 m a capacity reduction of
approx. 1 % per 100 m applies.
A limited capacity graph is valid for ducted air intake.
1.2
1.0
0.8
0.6
0.4
0.2
0
-0.2
-0.4
-0.6
-0.8
0 5 10 15 20 25 30 35 40 45 50 55 60
3.4.7 Dimensions
Burner
Rp½
–weishaupt–
154 mm
90 mm
292 mm
292 mm
216 mm
30 mm 286 mm
103 mm
308 mm 1
143 mm
30 mm
~5
0m 2
m
~5 4
0m
m
Isolating With thermal shut off device Without thermal shut off device
valve
1 Rp½ approx. 310 mm approx. 300 mm
2 Rp½ approx. 280 mm approx. 270 mm
3 Rp½ approx. 510 mm approx. 500 mm
4 Rp½ approx. 480 mm approx. 470 mm
3.4.8 Weight
approx. 12 kg
4 Installation
Installation location
Prior to installation ensure that:
sufficient space is available for normal and service position [ch. 3.4.7],
sufficient combustion air is available, if necessary install ducted air intake,
M8
60°
45°
120 mm
1
90 mm
110 mm
3 130 ... 150 mm
1 Flange gasket
2 135 mm
3 Refractory
4 Aperture
The burner in its standard version is designed for valve train connection from the
right. For gas valve train connection from the left the burner has to be installed ro-
tated by 180°. This does not require conversion measures.
3 2
5 Installation
Only an approved gas installer may carry out the gas side connection. Observe
local regulations.
The following should be obtained from the gas supply company:
Type of gas
Gas connection pressure.
Maximum CO2 content in the flue gas.
Calorific value in normal condition [kWh/m3].
Observe maximum permissible pressure of all components of the gas valve train.
Close all fuel shut off devices prior to commencing work and protect from acci-
dental re-opening.
Installation position
Multifunction assembly and pressure regulator (optional) can be installed with the
axis standing vertical to lying horizontal.
A B
A B
Accessories
5.1.2 Carry out soundness test of gas supply line and vent
Only the gas supply company or a contract installation company may carry out a
soundness test and vent the gas line.
The electrical connection must only be carried out by qualified electricians. Ob-
serve local regulations.
Observe wiring diagram [ch. 11.1].
Plug in plug for gas pressure switch 2 and double gas valve 3 and secure with
screws.
Check polarity and wiring of 7 pole connection plug 1.
Plug in connection plug 1.
With remote reset, install connection line separately. Do not exceed maximum cable
length of 10 metres.
6 Operation
The illuminated push button on the combustion manager has the following func-
tions:
display operating condition [ch. 6.2],
display fault codes [ch. 10.1.2],
reset burner lockout [ch. 10.1.2].
6.2 Display
Illuminated push button Operating condition
orange Start phase
Flashing orange Ignition and pre-purge phase
Green Operation
red Fault [ch. 10]
Additional flashing signals can be read off as fault code [ch. 10].
7 Commissioning
7.1 Prerequisite
Commissioning must only be carried out by qualified personnel.
Only correctly carried out commissioning ensures the operational safety.
Add the combustion chamber pressure in mbar to the minimum connection pres-
sure. The connection pressure should not fall below 15 mbar.
A B
1 1
A B 1
1
2
2
Use only leak detecting foam solutions, which do not cause corrosion, see DVGW-
TRGI, worksheet G 600.
Check all components, intersections and test points of the gas valve train
between multifunction assembly and burner.
Document result of the soundness test on the engineers report.
Test points
Determine setting pressure and dimension 1 and 3 from table and note down.
The details given for calorific value Hi relate to 0 °C and 1013 mbar.
The table values have been calculated under ideal conditions. The values are there-
fore guide values for basic settings.
Full load Setting pres- Full load setting Ignition load setting
[kW] sure Dimension 1 [mm] Dimension 3 [mm]
[mbar]
Connection pressure(1
20 mbar 50 mbar
Natural Gas E: Hi = 10.35 kWh/m3, d = 0.606
12.5 3.0 13.0 16.0 14.0
15.0 3.2 14.0 16.0 15.0
17.5 3.4 14.5 17.0 15.5
20.0 3.6 15.0 17.0 16.0
22.5 4.0 16.0 17.5 16.5
25.0 4.2 18.0 18.0 16.5
27.5 5.0 18.0 18.5 17.0
30.0 5.5 18.0 18.5 17.0
32.5 6.3 18.0 18.5 17.0
35.0 6.6 22.0 19.0 18.0
37.5 7.2 22.0 19.0 18.0
40.0 7.9 22.0 19.0 18.0
42.5 8.5 22.0 19.0 18.0
45.0 9.3 22.0 19.0 18.0
47.5 10.2 22.0 19.0 18.0
50.0 11.1 22.0 19.0 18.0
(1
With connection pressures between 20 and 50 mbar, the value of dimension 3
must be interpolated.
Full load Setting pres- Full load setting Ignition load setting
[kW] sure Dimension 1 [mm] Dimension 3 [mm]
[mbar]
Connection pressure(1
20 mbar 50 mbar
Natural Gas LL: Hi = 8.83 kWh/m3, d = 0.641
12.5 3.4 13.5 17.5 16.5
15.0 3.6 14.0 17.5 16.5
17.5 4.0 14.5 18.0 17.0
20.0 4.4 15.0 18.0 17.0
22.5 4.8 16.0 18.5 17.5
25.0 5.0 18.0 19.0 17.5
27.5 6.0 18.0 19.5 17.5
30.0 6.9 18.0 19.5 17.5
32.5 7.9 18.0 19.5 17.5
35.0 8.3 22.0 20.0 18.0
37.5 9.2 22.0 20.0 18.0
40.0 10.3 22.0 20.0 18.0
42.5 11.3 22.0 20.0 18.0
45.0 12.5 22.0 20.0 18.0
47.5 13.6 22.0 20.0 18.0
50.0 14.6 22.0 20.0 18.0
3
Liquid Petroleum Gas: Hi = 25.89 kWh/m , d = 1.555
The selection is calculated for Propane, it can however, also be used
for Butane.
12.5 3.0 12.5 16.0 13.5
15.0 3.2 12.8 16.0 14.0
17.5 3.4 13.0 16.0 14.0
20.0 3.6 13.5 16.5 14.5
22.5 3.8 14.0 16.5 15.0
25.0 4.2 14.5 17.0 15.5
27.5 4.5 15.0 17.0 15.5
30.0 4.7 16.0 17.0 16.0
32.5 5.0 16.0 17.0 16.0
35.0 5.2 22.0 17.5 16.5
37.5 5.6 22.0 17.5 16.5
40.0 6.0 22.0 17.5 16.5
42.5 6.5 22.0 17.5 16.5
45.0 7.1 22.0 17.5 16.5
47.5 7.7 22.0 17.5 16.5
50.0 8.1 22.0 17.5 16.5
(1
With connection pressures between 20 and 50 mbar, the value of dimension 3
must be interpolated.
¾ 2 x 1 x
Determine the diffuser setting (dimension X) and air damper setting required
from the diagram and note down.
Example Burner capacity required 40 kW
Diffuser setting (dimension X) 6.5 mm
Air damper setting 6.2
10
9
8
7
6
5
4
3
2 2
1
10 15 20 25 30 35 40 45 50
9
8
7
6
5
4
3
2
2 1
0
10 15 20 25 30 35 40 45 50
Set diffuser
With dimension X = 0mm the indicating bolt is flush with nozzle assembly cover.
Turn screw 1, until dimension X equals the value determined.
1
X
A B 1
1
A Manual adjustment
B Actuator (optional)
5.0
4.5
4.0
3.5
3.0
2.5
2.0
1.5
2 1.0
0.5
10 15 20 25 30 35 40 45 50
3. Adjust combustion
When adjusting, the ratings data given by the boiler manufacturer and the capacity
graph of the burner should be observed [ch. 3.4.6].
Check CO content of combustion and if necessary adjust combustion values via
air damper and/or diffuser. Observe mixing pressure while doing so.
Calculate gas throughput (operating volume VB) required [ch. 7.6].
Optimise setting pressure until gas throughput (VB) is achieved.
Check combustion values
Determine combustion limit and set excess air via air damper and/or diffuser
[ch. 7.5].
Determine gas throughput once more and adjust if necessary.
Re-set excess air.
1
2
20
30
150
50
130
70
11
0
90
A2
qA = (tA - tL ) ( + B)
21- O2
QN 50 kW
VN = VN = = 5.25 m³/h
η Hi 0,92 10.35 kW/m³
VN 5.25 m³/h
VB = VB = = 5.63 m³/h
f 0.933
8 Shutdown
For breaks in operation:
Switch off burner.
Close fuel shut off devices.
9 Servicing
Servicing must only be carried out by qualified personnel. The combustion plant
should be serviced annually. Depending on site conditions more frequent checks
may be required.
Components, which show increased wear and tear or whose design lifespan is or
will be exceeded prior to the next service should be replaced as a precaution.
The design lifespan of the components is listed in the service plan [ch. 9.2].
The following components must only be replaced and must not be repaired:
combustion manager
flame sensor
actuator
multifunction assembly
pressure regulator
pressure switch
Following servicing
Removing
Unplug ionisation cable 3.
Unplug ignition cable 2.
Remove screws 4.
Remove screw 5 and remove nozzle assembly cover 6.
Push mixing head 1 to the side and remove.
Refitting
Refit mixing head in reverse order ensuring correct alignment of O ring 7.
6
5
4
3 2
Lx S1 = 10 mm
2 m
X 5 8m
=2
Lx
1
3
1.5 ... 2 mm
mm
2
...
1.5
5 mm
4 2
3
Removing
Place housing cover into service position [ch. 9.6].
Remove grub screw 1 and remove fan wheel.
Refitting
Refit fan wheel in reverse order and
ensure correct alignment on the motor shaft 2,
screw in new grub screw 1,
turn fan wheel to ensure it moves freely.
2 1
2
3
11
Removing
Remove bolts 1.
Remove burner from heat exchanger [ch. 4.2].
If necessary unplug actuator plug.
Remove bolts 2.
Remove intake housing 5.
Remove bolts 4.
Remove air regulator 3.
1 2
Refitting
Refit air regulator in reverse order.
Carry out soundness test [ch. 7.1.3].
Ensure correct voltage and solenoid number when replacing the solenoid coil.
Loosen cover 1.
Remove circuit board 2 and if necessary replace.
Replace solenoid coil 3.
10 Troubleshooting
Resetting
11 Technical documentation
K1 W-FM 05
K2
K3
F7
F7
M1 M
M
~
~ P
M20 C1 B10
F2 B15
P P
P11
S1 P6 N L1 PE L2
X8 1 2 3
F1
P
L PE N B31
X6 C1 Motor capacitor
F7
F1 External fuse (max 16 AB)
F2 Temperature or pressure limiter
X3:
F7 Internal unit fuse (T6.3H, IEC 127-2/5)
5
B10 Air pressure switch
4
B31 Low gas pressure switch
6
B15 Temperature or pressure regulator
3
2 P6 Control lamp lockout (optional)
12 P11 Control lamp operation (optional)
11 M1 Burner motor
13 M20 Air damper actuator (optional)
W-FM 05 S1 Operating switch
1 Bridge for air regulator with manual adjustment
K3 K2
X8
T1 B1 P11.1
N PE L1 L2
S3
X9 1 PE 2 3
K32 K33 2
B1 Flame sensor
P11.1 Hours counter (optional)
S3 Remote reset (optional)
T1 Ignition unit
K32 Double gas valve
K33 External valve LPG
2 Bus interface (optional)
12 Project planning
13 Spares
1.20
1.01
1.16
0.00
1.06 1.18
1.15
1.19
1.03 1.18
1.02
1.17 1.05
1.04
1.08 1.17
1.11
1.12
1.07
1.09
1.12 1.10
1.14 1.13
2.11
2.09
2.08
2.12
2.10
2.05
2.06 2.01
2.13
2.07
2.04
2.02
2.03
3.01
3.02
3.04
3.03
3.07
3.15 3.08 3.05
3.15
3.24 3.06
3.23
3.08
3.22 3.13 3.09
3.22
3.19 3.18 3.14 3.11
3.17
3.10
3.16
3.21
3.12
3.20
4.04
4.05
4.03 4.05
4.02
4.01
5.03 5.01
5.02 5.09
5.03
5.08
5.07
5.05
5.04
5.06
5.11 5.13
5.06
5.12
5.10
5.03
5.15 5.14
5.16
14 Notes
A Electrode............................................................................... 53
Air damper ........................................................ 9, 36, 37, 55 Electrostatic discharge........................................................ 7
Air damper setting .............................................................. 36 Emission................................................................................ 15
Air number ............................................................................ 45 Emission class ..................................................................... 15
Air pressure .......................................................................... 46 Error code............................................................................. 59
Air pressure switch........................................................ 9, 43 Error codes................................................................... 60, 62
Air regulator.......................................................................... 55 Errors ..................................................................................... 60
Ambient conditions............................................................. 14 ESD protection measures................................................... 7
Ammeter................................................................................ 28 Excess air.............................................................................. 45
Aperture ........................................................................ 19, 20
Appliance category............................................................. 67 F
Approval data....................................................................... 14 Fabrication number............................................................... 8
Fan motor.............................................................................. 54
B Fan pressure ................................................................ 28, 38
Bar .......................................................................................... 66 Fan wheel......................................................................... 9, 54
Basic setting ........................................................................ 52 Fault ............................................................................... 58, 63
Basic settings ...................................................................... 36 Fault history .......................................................................... 59
Boiler room ............................................................................. 6 Faults ..................................................................................... 62
Booming................................................................................ 63 Filter ....................................................................................... 10
Breaks in operation............................................................. 47 Flame signal ................................................................. 11, 28
Burner motor ................................................................ 11, 54 Flame tube............................................................................ 19
Flashing codes ............................................................ 60, 62
Flue gas losses.................................................................... 45
C
Flue gas measurement....................................................... 45
Calorific value ...................................................................... 32 Flue gas temperature ......................................................... 45
Capacity ................................................................................ 16 FRS ........................................................................................ 10
Capacity graph .................................................................... 16 Fuel......................................................................................... 14
Circuit board ........................................................................ 56 Fuel release .......................................................................... 12
CO content .......................................................................... 45 Fuse ....................................................................................... 57
Coil ......................................................................................... 56 Fusing .................................................................................... 14
Combustion air ...................................................................... 6
Combustion chamber pressure ....................................... 16 G
Combustion control............................................................ 45
Combustion head ............................................................... 16 Gas connection pressure.......................................... 21, 29
Combustion head extension............................................. 19 Gas family ............................................................................. 67
Combustion heat rating ............................................. 16, 36 Gas filter................................................................................ 10
Combustion Manager ................................................ 11, 26 Gas isolating valve...................................................... 10, 18
Commissioning.................................................................... 27 Gas pressure switch .................................................. 23, 42
Condensate............................................................................ 7 Gas supply ........................................................................... 21
Connection pressure ........................... 21, 22, 29, 32, 33 Gas temperature ................................................................. 46
Consumption........................................................................ 14 Gas throughput ................................................................... 46
Conversion factor ............................................................... 46 Gas valve train ....................................... 18, 20, 21, 22, 32
Conversion table ................................................................. 66 Guarantee............................................................................... 5
Current measuring device................................................. 28
H
D Heat exchanger ................................................................... 19
Default settings ................................................................... 36 High gas pressure switch ......................................... 10, 42
Design lifespan ............................................................... 6, 48 Hours counter...................................................................... 65
Diffuser ...................................................................... 9, 36, 37 Housing cover...................................................................... 53
Diffuser setting .................................................................... 36 Humidity ................................................................................ 14
Dimensions........................................................................... 17
Display ................................................................................... 26 I
Disposal .................................................................................. 7 Ignition ................................................................................... 12
Double gas valve......................................................... 10, 21 Ignition electrode ................................................................ 53
Drilling diagram.................................................................... 19 Ignition unit ........................................................................... 11
Ducted air intake ............................................................ 6, 16 Illuminated push button ...................................... 26, 58, 59
Indicating bolt ...................................................................... 37
E Initialisation time .................................................................. 13
Electrical connection.......................................................... 25 Installation..................................................................... 19, 20
Electrical data ...................................................................... 14 Installation elevation ................................................... 14, 16
O T
Operating hours counter................................................... 65 Temperature ......................................................................... 14
Operating problems ........................................................... 63 Test points............................................................................ 31
Operating volume ............................................................... 46 Test pressure ....................................................................... 30
Transport............................................................................... 14
P Troubleshooting .................................................................. 63
Type key .................................................................................. 8
Pa............................................................................................ 66
Type of gas................................................................... 14, 67
Pascal .................................................................................... 66
Personal protective equipment .......................................... 6
Plug assignment.................................................................. 64 U
Post-purge............................................................................ 12 Unit ......................................................................................... 66
Post-purge time................................................................... 13 Unit fuse ................................................................................ 57
PPE .......................................................................................... 6 Unit of pressure................................................................... 66
Pre-ignition time .................................................................. 13
Pre-purge.............................................................................. 12 V
Pre-purge time..................................................................... 13
Valve train ............................................................................. 22
Pressure measuring device .............................................. 28
Voltage supply ..................................................................... 14
Pressure regulator ...................................................... 10, 21
Pressure switch....................................................... 9, 42, 43
Pressure switches .............................................................. 39 W
Program sequence ............................................................. 12 Weight................................................................................... 18
Protective equipment ........................................................... 6 Wiring diagram .................................................................... 64
Pulsating ............................................................................... 63
R
Refractory ............................................................................. 19
Remote reset........................................................................ 25
Reset...................................................................................... 59
These legendary industrial burners are durable The floor-standing condensing boilers
and versatile. WTC-GB (up to 300 kW) and WTC-OB
Numerous variations of oil, gas and dual fuel (up to 45 kW) are efficient, low in pollutants
burners meet a wide range of applications and and versatile in use.
capacity requirements. Even the largest capacities can be covered by
cascading up to four gas condensing boilers.
The WKmono 80 burners are the most The stylish flat-plate collectors are the ideal
powerful monoblock burners from Weishaupt. complement for any Weishaupt heating
They are available as oil, gas or dual fuel system. They are suitable for solar water
burners and are designed for tough industrial heating and for combined heating support.
application. With versions for on-roof, in-roof and flat roof
installations, solar energy can be utilised on
almost any roof.
These industrial burners of modular The diverse program of potable water and
construction are adaptable, robust and energy storage for various heat sources
powerful. includes storage volumes of 70 to 3,000 litres.
Even on the toughest industrial applications In order to minimize storage losses, potable
these oil, gas and dual fuel burners operate water cylinders from 140 to 500 litres are
reliably. available with highly efficient insulation using
vacuum insulation panels.
Weishaupt customers can be assured that With its daughter company, BauGrund Süd,
specialist knowledge and tools are available Weishaupt also offers geothermal probe and
whenever they are needed. Our service well drilling. With the experience of more than
engineers are fully qualified and have 10,000 systems and more than 2 million meters
extensive product knowledge, be it for burners, of drilling, BauGrund Süd offers a
heat pumps, condensing boilers or solar comprehensive service program.
collectors.
83051202 1/2020-01 La