SCADA - I/O Summary Annexure

Sr. Function AI DI AO DO
No.
A Electrical System
I Main Power Panel HT, Main LT
1 Vaccum Circuit Breaker On/Off and Status 20 15 Volt Free Contact fro
2 Vaccum Circuit Breaker TRIP Status 20 Volt Free Contact fro
II LT Panels
1 Air Circuit Breaker and MCCB On/Off/TRIP Status 48 48 Volt Free Contact fro

2 ACB/ MCCB TRIP Status 48 Volt Free Contact fro


III PAHU , PAHU fan,lightning, emergency BMS
lighting panels
1 MCCB On/Off/ and status 10 Volt Free Contact fro
2 MCCB TRIP Status 8 BMSFree Contact fro
Volt
DG Breaker 1 & 2 20 BMS
HT breaker 1 ,2 ,3 ,4, 5 22
Transformer 1 and 2 12

Total 0 198 0 73
Spare @20% 0 40 0 15
Total hardware points 0 238 0 88
B Integration
2 DG 1 & 2
Load Manager
6 Integration of EA on MODBUS RTU on RS485 60 EA supplied by E
(120 points)
8 Integration with addressable Existing Fire alarm Software level Seam
system with BMS (100 poin

Total Software points


Spare of 20%
Total software points
Total Hardware Points
Total Software Points
Total Hardware & Software Points
y Annexure
Through Plant manager

Volt Free Contact from ACB to BMS


Volt Free Contact from ACB to BMS

Volt Free Contact from ACB to BMS

Volt Free Contact from MCCB to


BMS

Volt Free Contact from MCCB to


BMS
Volt Free Contact from MCCB to
BMS

Software Points
60
80
60 EA supplied by Electrical vendor 120
(120 points)
Software level Seamless integration 100
with BMS (100 points)

360
72.0
432
325
432
757