Model SMG5 Description For your safety...

MEGOHMMETER The SMG5 Megohmmeter is for fast, easy, and WARNING 1. Connect the E terminal to ground using
safe testing of insulation resistance. It provides Do not measure when compressor the alligator clip (included).
1000V voltage source, monitors current, and motor is in a vacuum. 2. Use one hand to conduct test.
HOLD
displays the resistance between the test points. 3. Make sure to turn meter OFF to avoid
Maximum current output is <1.5mA. To extend accidentally pressing MEAS and creating a
battery life, it automatically turns itself off in 15 WARNING 1000V voltage source. If the switch is ON
seconds. To avoid electrical shock remove test and MEAS is depressed, 1000V will appear
Applications leads before opening case or battery cover. on the terminals.
The SMG5 can be used to determine the Do not operate with battery cover open.
condition of insulation from winding to ground in
a motor, compressor, or transformer. Disconnect
the windings and measure the resistance between WARNING
the windings and ground through the insulation. Remove power from circuit under test.
Determine what a "good" reading is by comparing
your reading to values supplied by the
manufacturer of the equipment or from your own WARNING
experience. Make sure that all measurements are Do not touch test lead tips, test points,
compared to readings at the same temperature. or terminals when pressing MEAS.
Insulation resistance can vary dramatically with
temperature.
Megohm readings can work best when the
same equipment is measured over time.
Decreasing insulation resistance levels can
OPERATOR'S MANUAL forecast failure before catastrophic failure.

Specifications Dimensions:
Display: 170mm(H) x 44mm(W) x 40mm(D).
3 1/2 digit liquid crystal display (LCD) Weight: 160g including batteries. Insulation Resistance
with maximum reading of 1999. Measurement Terminal
Overrange: (OL) or (-OL) is displayed. ELECTRICAL Voltage
Low battery indication: The " " is Range: 20ΜΩ,2000ΜΩ.
displayed when the battery voltage Resolution: 10KΩ on 20ΜΩ range.
drops below the operating level. 1ΜΩ on 2000ΜΩ range.
Measurement rate: 2.5 times per Accuracy:
second, nominal. 20ΜΩ range: ±(2%rdg + 2dgts)
Operating Environment: 0°C to 40°C at 2000ΜΩ range: <500ΜΩ ±(4%rdg + 2dgts)
< 70% relative humidity. >500ΜΩ ±(5%rdg + 2dgts)
Terminal voltage(V)

Storage Temperature: -20°C to 60°C, 0 Rated voltage: DC-DC converter to


to 80% R.H. with battery removed from 1000VDC
meter. Accuracy temperature: 23°C ± 5°C less
Auto power off: 15 seconds approx. than 70%RH
Standby consume current: <10μA Temperature Coefficient: 0.1X (specified
Battery: accuracy)/°C (<18°C or >28°C)
4 pcs 1.5V (AAA size) UM-4 R03.
Battery Life: DANGEROUS SEE EXPLANATION
VOLTAGE IN MANUAL
4 hours (continuity) typical with alkaline
AC-ALTERNATING DOUBLE INSULATION
battery (@20ΜΩ range test 10ΜΩ CURRENT (Protection ClassII)
resistor). DC-DIRECT GROUND Ω )
Rx(Ω
CURRENT

International Electrical Symbols


How to use Battery test Refrigeration and A/C systems Guidelines
1. Disconnect all wires from the winding to 1. Slide the middle switch to power on. A megger can be particularly effective with The following are general guidelines. The
be tested. Test each winding in three-phase 2. Press the MEAS button. compressors. Contaminants (moisture, numbers recommended by the equipment
system separately. 3. If the " " in the display lights, the microscopic metal filings, and acids) can get in manufacturer may be different, depending on
2. Connect the E terminal to ground and batteries are near the end of their life and should the refrigerant and destroy the insulation in the the equipment tested and conditions. Results
insert probe tip in L. be replaced immediately. windings of the compressor. With a megger, you can vary significantly as the temperature
3. Select ON (middle slide switch). The low battery indicator can see the degradation over time and may be varies.
4. Touch test point, and press MEAS, and The low battery indicator " " is displayed able to replace the compressor before it
hold until you get a stable reading. when measuring very low values of resistance catastrophically fails and spews contaminants
5. Release MEAS. The reading will remain into the refrigeration system, possibly requiring a R ead i n g Co n d itio n Ac t i o n
(below 500KΩ). This is due to the large amount
on the display for approximately in 15 of current power consumed when measuring such much more expensive repair.
seconds. small resistances. Replace the batteries if To insure consistent measurements, the system >100Mo hm Exce lle nt No ne
6. Select OFF. subsequent resistance measurements of high should be run for at least an hour and shut off.
Range select values result in the display " " appearing. Take the megohmmeter reading immediately. This
way temperatures and the exact condition of the 50-100Mo hm So me Chang e filte r d rie r
If the meter is on the 20MΩ setting and Temperature effects mo isture
reads OL during the test, select the 2000MΩ refrigerant will be the same from test to test.
For accurate measurements, when comparing p re se nt
setting and try again. If the meter is on the readings over time or when comparing readings
2000MΩ setting and the display reads 19 or 20-50Mo hm Co ntaminatio n/ Chang e filte r d rie r
to other similar equipment or to the mo isture se ve ral time s
less, select 20MΩ for better resolution. The recommended values, the temperatures must be p re se nt Chang e o il if acid
range selected will be displayed on the bottom the same. Insulation resistance can change by a p re se nt
of the LCD. factor of two with a change in temperature from
Display back-light switch ( ) 70 deg F to 100 deg F. 0-20Mo hm Se ve re Full syste m cle an-up
Equipment manufacturers publish acceptable co ntaminatio n and re -e valuatio n.
Select to turn on backlight. Backlight
will remain on only when the LCD is on. limits that vary with temperature.

How does it relate to a


Why a DMM often won’t work ANY IMPLIED WARRANTIES ARISING Service
milliohmmeter? OUT OF THE SALE OF A FIELDPIECE
A megger such as the Fieldpiece SMG5 To test resistance, a DMM supplies low Return any defective SMG5 to Fieldpiece
voltage (<1V) to the test points and is capable of INSTRUMENT’S PRODUCT, INCLUDING for warranty service along with proof of
measures the insulation resistance between BUT NOT LIMITED TO IMPLIED
the coil and ground by supplying a very high delivering only a few milliamps. It's not a high purchase. Contact Fieldpiece for out of
enough voltage to detect high resistance WARRANTIES OF MERCHANTABILITY AND warranty repair charges.
voltage to break down the insulation and FITNESS FOR A PARTICULAR PURPOSE,
measuring the very low resultant current. The problems that might indicate moisture and other
contaminants and it's not enough current to ARE LIMITED TO THE ABOVE. FIELDPIECE
resistance measured is very high. Fifty million SHALL NOT BE LIABLE FOR LOSS OF USE
ohms is typical. A milliohmmeter such as the measure real low values of resistance.
OF THE INSTRUMENT OR OTHER
Fieldpiece AMR1 supplies a higher current Cleaning INCIDENTAL OR CONSEQUENTIAL
(50mA) but at a very low voltage. The Periodically wipe the case with a damp cloth DAMAGES, EXPENSES, OR ECONOMIC
resistance measured is very low (thousandths and detergent. Do not use abrasives or solvents. LOSS, OR FOR ANY CLAIM FOR SUCH
of an ohm). Limited warranty DAMAGE, EXPENSES, OR ECONOMIC
You may be able to determine insulation LOSS.
This meter is warranted against defects in
problems with either a megger or a milliohm State laws vary. The above limitations or
material or workmanship for one year from date
meter. The megger will tell you the condition exclusions may not apply to you. This warranty
of purchase. Fieldpiece will replace or repair the
of the insulation between the winding and gives you specific legal rights, and you may also
defective unit, at its option, subject to verification
ground by forcing a small current though it have other rights which vary from state to state.
of the defect.
with a high voltage. The milliohm meter will
This warranty does not apply to defects
determine if the test current supplied between
resulting from abuse, neglect, accident, Fieldpiece Instruments, Inc.
the ends of the windings takes a "shortcut" at
unauthorized repair, alteration, or unreasonable California,U.S.A.
a point where the insulation has failed.
use of the instrument. www.fieldpiece.com
Both measurements can be used to
v10
determine the health of the insulation, but in
different ways.