Company: PT PUTRAGAYA WAHANA Page: 1
Address: Project Thamrin Nine Specifier: Prasetyo Junianto
Phone I Fax: +62 878-7810-7966 | E-Mail: prasetyo.junianto@thamrinnine.com
Design: WF300 - Balok 600x1000 Date: 9/19/2022
Fastening point: WF300 - Balok 600x1000
Specifier's comments:
1 Input data
Anchor type and diameter: HIT-RE 500 V3 + HAS-U 8.8 M16
Item number: not available
Effective embedment depth: hef,act = 125.0 mm (hef,limit = - mm)
Material: 8.8
Evaluation Service Report: ESR-3814
Issued I Valid: 3/1/2021 | 1/1/2023
Proof: Design Method ACI 318-14 / Chem
Stand-off installation: eb = 0.0 mm (no stand-off); t = 18.0 mm
Anchor plate :
R lx x ly x t = 180.0 mm x 300.0 mm x 18.0 mm; (Recommended plate thickness: not calculated)
R
- The anchor calculation is based on a rigid anchor plate assumption.
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2022 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
1
Hilti PROFIS Engineering 3.0.80
www.hilti.group/content/hilti/CP/XX/en/non-transactional/light-pages/Indonesia.html
Company: PT PUTRAGAYA WAHANA Page: 2
Address: Project Thamrin Nine Specifier: Prasetyo Junianto
Phone I Fax: +62 878-7810-7966 | E-Mail: prasetyo.junianto@thamrinnine.com
Design: WF300 - Balok 600x1000 Date: 9/19/2022
Fastening point: WF300 - Balok 600x1000
Anchor forces are calculated based on the assumption of a rigid anchor plate.
3 Tension load
Load Nua [kN] Capacity f Nn [kN] Utilization bN = Nua/f Nn Status
Steel Strength* N/A N/A N/A N/A
Bond Strength** N/A N/A N/A N/A
Sustained Tension Load Bond Strength* N/A N/A N/A N/A
Concrete Breakout Failure** N/A N/A N/A N/A
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2022 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
2
Hilti PROFIS Engineering 3.0.80
www.hilti.group/content/hilti/CP/XX/en/non-transactional/light-pages/Indonesia.html
Company: PT PUTRAGAYA WAHANA Page: 3
Address: Project Thamrin Nine Specifier: Prasetyo Junianto
Phone I Fax: +62 878-7810-7966 | E-Mail: prasetyo.junianto@thamrinnine.com
Design: WF300 - Balok 600x1000 Date: 9/19/2022
Fastening point: WF300 - Balok 600x1000
4 Shear load
Load Vua [kN] Capacity f Vn [kN] Utilization bV = Vua/f Vn Status
Steel Strength* 18.277 45.300 41 OK
Steel failure (with lever arm)* N/A N/A N/A N/A
Pryout Strength (Bond Strength 73.110 144.499 51 OK
controls)**
Concrete edge failure in direction y-** 73.110 140.060 53 OK
Variables
2 2
Ase,V [mm ] futa [N/mm ]
157 800.00
Calculations
Vsa [kN]
75.500
Results
Vsa [kN] f steel f Vsa [kN] Vua [kN]
75.500 0.600 45.300 18.277
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2022 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
3
Hilti PROFIS Engineering 3.0.80
www.hilti.group/content/hilti/CP/XX/en/non-transactional/light-pages/Indonesia.html
Company: PT PUTRAGAYA WAHANA Page: 4
Address: Project Thamrin Nine Specifier: Prasetyo Junianto
Phone I Fax: +62 878-7810-7966 | E-Mail: prasetyo.junianto@thamrinnine.com
Design: WF300 - Balok 600x1000 Date: 9/19/2022
Fastening point: WF300 - Balok 600x1000
Na0
ec1,Na y ec2,Na y ed,Na y cp,Na Nba ] ACI 318-14 Eq. (17.5.3.1b)
f Vcpg ³ Vua ACI 318-14 Table 17.3.1.1
ANa see ACI 318-14, Section 17.4.5.1, Fig. R 17.4.5.1(b)
2
ANa0 = (2 cNa) ACI 318-14 Eq. (17.4.5.1c)
t uncr
cNa = 10 da √ 1100
ACI 318-14 Eq. (17.4.5.1d)
( )
1
'
y ec,Na = eN £ 1.0 ACI 318-14 Eq. (17.4.5.3)
1+
cNa
Na
ACI 318-14 Eq. (17.4.5.4b)
= MAX(
c ) £
c c a,min Na
y cp,Na , 1.0 ACI 318-14 Eq. (17.4.5.5b)
c ac ac
Nba = l a · t k,c · p · da · hef ACI 318-14 Eq. (17.4.5.2)
Variables
kcp aoverhead t k,c,uncr [N/mm ]
2
da [mm] hef [mm] ca,min [mm]
2
t k,c [N/mm ]
2 1.000 18.14 16.0 125.0 410.0 9.68
Calculations
cNa [mm] ANa [mm ]
2
ANa0 [mm ]
2
y ed,Na
246.4 412,192 242,775 1.000
Results
Vcpg [kN] f concrete f Vcpg [kN] Vua [kN]
206.427 0.700 144.499 73.110
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2022 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
4
Hilti PROFIS Engineering 3.0.80
www.hilti.group/content/hilti/CP/XX/en/non-transactional/light-pages/Indonesia.html
Company: PT PUTRAGAYA WAHANA Page: 5
Address: Project Thamrin Nine Specifier: Prasetyo Junianto
Phone I Fax: +62 878-7810-7966 | E-Mail: prasetyo.junianto@thamrinnine.com
Design: WF300 - Balok 600x1000 Date: 9/19/2022
Fastening point: WF300 - Balok 600x1000
Vcbg = (AA ) y
Vc
Vc0
ec,V y ed,V y c,V y h,V y parallel,V Vb ACI 318-14 Eq. (17.5.2.1b)
f Vcbg ³ Vua ACI 318-14 Table 17.3.1.1
AVc see ACI 318-14, Section 17.5.2.1, Fig. R 17.5.2.1(b)
2
AVc0 = 4.5 ca1 ACI 318-14 Eq. (17.5.2.1c)
( )
1
'
y ec,V = 2ev £ 1.0 ACI 318-14 Eq. (17.5.2.5)
1+
3ca1
a1
ACI 318-14 Eq. (17.5.2.6b)
= (7 ( ) √ d ) l
0.2
l
Vb e
a a √f'c c1.5
a1 ACI 318-14 Eq. (17.5.2.2a)
d a
Variables
ca1 [mm] ca2 [mm] ecV [mm] y c,V ha [mm]
410.0 - 0.0 1.000 600.0
'
le [mm] la da [mm] fc [psi] y parallel,V
125.0 1.000 16.0 5,076 1.000
Calculations
AVc [mm ]
2
AVc0 [mm ]
2
y ec,V y ed,V y h,V Vb [kN]
810,000 756,450 1.000 1.000 1.012 172.260
Results
Vcbg [kN] f concrete f Vcbg [kN] Vua [kN]
186.746 0.750 140.060 73.110
5 Warnings
• The anchor design methods in PROFIS Engineering require rigid anchor plates per current regulations (AS 5216:2021, ETAG 001/Annex C,
EOTA TR029 etc.). This means load re-distribution on the anchors due to elastic deformations of the anchor plate are not considered - the
anchor plate is assumed to be sufficiently stiff, in order not to be deformed when subjected to the design loading. PROFIS Engineering
calculates the minimum required anchor plate thickness with CBFEM to limit the stress of the anchor plate based on the assumptions
explained above. The proof if the rigid anchor plate assumption is valid is not carried out by PROFIS Engineering. Input data and results
must be checked for agreement with the existing conditions and for plausibility!
• Condition A applies where the potential concrete failure surfaces are crossed by supplementary reinforcement proportioned to tie the
potential concrete failure prism into the structural member. Condition B applies where such supplementary reinforcement is not provided, or
where pullout or pryout strength governs.
• Design Strengths of adhesive anchor systems are influenced by the cleaning method. Refer to the INSTRUCTIONS FOR USE given in the
Evaluation Service Report for cleaning and installation instructions.
• For additional information about ACI 318 strength design provisions, please go to
https://submittals.us.hilti.com/PROFISAnchorDesignGuide/
• Installation of Hilti adhesive anchor systems shall be performed by personnel trained to install Hilti adhesive anchors. Reference ACI 318-14,
Section 17.8.1.
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2022 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
5
Hilti PROFIS Engineering 3.0.80
www.hilti.group/content/hilti/CP/XX/en/non-transactional/light-pages/Indonesia.html
Company: PT PUTRAGAYA WAHANA Page: 6
Address: Project Thamrin Nine Specifier: Prasetyo Junianto
Phone I Fax: +62 878-7810-7966 | E-Mail: prasetyo.junianto@thamrinnine.com
Design: WF300 - Balok 600x1000 Date: 9/19/2022
Fastening point: WF300 - Balok 600x1000
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2022 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
6
Hilti PROFIS Engineering 3.0.80
www.hilti.group/content/hilti/CP/XX/en/non-transactional/light-pages/Indonesia.html
Company: PT PUTRAGAYA WAHANA Page: 7
Address: Project Thamrin Nine Specifier: Prasetyo Junianto
Phone I Fax: +62 878-7810-7966 | E-Mail: prasetyo.junianto@thamrinnine.com
Design: WF300 - Balok 600x1000 Date: 9/19/2022
Fastening point: WF300 - Balok 600x1000
6 Installation data
Anchor type and diameter: HIT-RE 500 V3 + HAS-U 8.8
M16
Profile: W shape (AISC), ; (L x W x T x FT) = 300.0 mm x 150.0 mm x 6.5 mm Item number: not available
x 9.0 mm
Hole diameter in the fixture: df = 18.0 mm Maximum installation torque: 80 Nm
Plate thickness (input): 18.0 mm Hole diameter in the base material: 18.0 mm
Recommended plate thickness: not calculated Hole depth in the base material: 125.0 mm
Drilling method: Hammer drilled Minimum thickness of the base material: 161.0 mm
Cleaning: Compressed air cleaning of the drilled hole according to instructions
for use is required
Hilti HAS-U threaded rod with HIT-RE 500 V3 injection mortar with 125 mm embedment h_ef, M16, Steel galvanized, Hammer drilled
installation per ESR-3814
y
90.0 90.0
60.0
3 4
150.0
180.0
x
150.0
1 2
60.0
Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2022 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
7
Hilti PROFIS Engineering 3.0.80
www.hilti.group/content/hilti/CP/XX/en/non-transactional/light-pages/Indonesia.html
Company: PT PUTRAGAYA WAHANA Page: 8
Address: Project Thamrin Nine Specifier: Prasetyo Junianto
Phone I Fax: +62 878-7810-7966 | E-Mail: prasetyo.junianto@thamrinnine.com
Design: WF300 - Balok 600x1000 Date: 9/19/2022
Fastening point: WF300 - Balok 600x1000
Input data and results must be checked for conformity with the existing conditions and for plausibility!