Job Name:

SUBMITTAL PC-GH-2203-358 KukaHome Parque Industrial-R1


Job Site: PROVEEDORA DE CLIMAS SA DE CV
BONIFACIO SALINAS 700
COL RINCON DE LA PURISIMA
GUADALUPE, 67129
Mexico
Engineer: THELMA K. RIVERA HERNANDEZ
Contractor: GIASA CONSTRUCCIONES
Elevation: (ft) 1,690
Date: 6/07/2022
Submitted By: Uriel Quiroz Jr.
PROVEEDORA DE CLIMAS SA DE CV
BONIFACIO SALINAS 700
COL RINCON DE LA PURISIMA
GUADALUPE, NL 67129
MX
Phone: 528183591770
Fax: 1528183731144
Email Address: uriel.quiroz@proveedora.mx

P.O. Box 410 Schofield, WI 54476 (715) 359-6171 FAX (715) 355-2399 www.greenheck.com

C:\Users\uriel.quiroz\Grupo 4HG\PDC Aplicaciones - Sist. De Ventilacion - Sist. De Ventilacion\GREENHECK\Jobs\PC-GH-2203-358 KukaHome Parque Industrial-R1.gfcj
CAPS 4.38.1089 Generated by: uriel.quiroz@proveedora.mx Page 1 of 106
Printed Date: 06/07/2022
Job: PC-GH-2203-358 KukaHome Parque Industrial-R1
Mark: BF 01-11
Model: DS-6-20-170HV

Model: DS-6-20-170HV 42.0


High Volume, Low Speed Ceiling Fan
3.0

Dimensional
Impeller Diameter (ft) 20
Impeller Diameter (in.) 240
Quantity 11
Weight w/o Acc's (lb) 119
Weight w/ Acc's (lb) 235

Installation Clearances
Minimum Fan Spacing (ft) 60
Clearance to Wall (ft) 30
Blade Tip Clearance (ft) 3
Vertical Blade Clearance (ft) 3
Standby Blade Deflection (in.) 1.7

Performance Per Fan


*Tested Direction of Operation Forward
Actual Volume (CFM) 196,200
Coverage Area (ft2) 21,600
Max Coverage Area (ft2) 21,600
Avg. Air Speed (ft/min) 477
Max Avg. Air Speed (ft/min) 477
Fan RPM 78
Max Fan RPM 78
**CFEI at 40% Speed 2.72
**CFEI at 100% Speed 1.44
**Integrated Efficiency
-
(CFM/W)
Total Sound Pressure (dBA) 52

Fan Operation
Direction of Operation
Forward or Reverse
Capability
Communication Protocol Modbus RTU

Motor
Size (W) 1,100 Notes:
All dimensions shown are in units of in. (unless specified
Voltage/Cycle/Phase 460/60/3
otherwise)
Enclosure IP54 Dimensions shown may vary with fan speed. Consult
installation manual for clearance requirements.
Max Motor RPM 78 dBA – A weighted sound pressure level measured 5 ft off
the ground at 20 ft from the center of the fan – dBA levels
***System FLA (Amps) 3.5 are not licensed by AMCA International
*Cataloged performance data tested using forward
**Standby Power (W) 11 direction of operation per 10 CFR Part 430.
**Input Power (W) 1,398 **Based on 208/60/3 testing per 10 CFR 430
***FLA is based on worst case system voltage and phase
combination

C:\Users\uriel.quiroz\Grupo 4HG\PDC Aplicaciones - Sist. De Ventilacion - Sist. De Ventilacion\GREENHECK\Jobs\PC-GH-2203-358 KukaHome Parque Industrial-R1.gfcj
CAPS 4.38.1089 Generated by: uriel.quiroz@proveedora.mx Page 2 of 106
Printed Date: 06/07/2022
Job: PC-GH-2203-358 KukaHome Parque Industrial-R1
Mark: BF 01-11
Model: DS-6-20-170HV
Model: DS-6-20-170HV
High Volume, Low Speed Ceiling Fan
Tags: BF 01 BF 02 BF 03 BF 04 BF 05 BF 06 BF 07 BF 08 BF 09 BF 10 BF 11
Standard Construction Features:
Heavy duty frame with protective finish - Extruded aluminum airfoils - High
efficiency direct drive motor designed for either forward or reverse operation -
Factory mounted and wired variable frequency drive - Factory installed plug and
play wiring - Universal ceiling mount - Heavy duty safety restraint cable - Airfoil
and fan hub retaining systems - AMCA certified for Circulating Fan Performance
Selected Options & Accessories:
6 Blade, Extruded Aluminum Airfoil Kit
Mill Finish, No Color
Aluminum Winglet; Hi-Pro Polyester Finish, Flat Black (044) Color
I-Beam Mounting Kit; Hi-Pro Polyester Finish, Flat Black (044) Color
3.5 ft Drop Length; Hi-Pro Polyester Finish, Flat Black (044) Color
Hub Plate and Impeller Hub; Hi-Pro Polyester Finish, Flat Black (044) Color
Hub Plate Decal with Greenheck Logo
Power Wiring Pigtail, Internal, General, 3 ft of Flexible Power Cord from Unit,
Unstripped Wire
Plug-and-Play Network Communication Wiring Pigtail, Internal, Terminated with
Shielded CAT-5e Splitter (RJ45 Ports)
100 ft of Shielded, Twisted Pair (STP) CAT-5e Control Cable
Fire Alarm Wiring Pigtail, Internal, 2.5 ft from Unit, Terminated with Crimp
Connector
Low-Voltage (24VDC/VAC or 115VAC), Normally Closed Electromechanical Fire
Alarm Relay
Braided Galvanized Steel Safety Cable, 16 ft from Unit
Braided Galvanized Steel Guy Wires, 20 ft from Unit
Cable Clamp Hardware for Safety Cable and Guy Wires
Electrical Warranty: 1 Yr (Standard)
Mechanical Warranty: 10 Yrs (Standard)

C:\Users\uriel.quiroz\Grupo 4HG\PDC Aplicaciones - Sist. De Ventilacion - Sist. De Ventilacion\GREENHECK\Jobs\PC-GH-2203-358 KukaHome Parque Industrial-R1.gfcj
CAPS 4.38.1089 Generated by: uriel.quiroz@proveedora.mx Page 3 of 106
Printed Date: 06/07/2022
Job: PC-GH-2203-358 KukaHome Parque Industrial-R1
Mark: BF 01-11
Model: DS-6-20-170HV

Model: DS-6-20-170HV
High Volume, Low Speed Ceiling Fan

Fan Coverage Data

Zone 1 Zone 2 Zone 3 Zone 4


375+ 230+ 105+ <105
Fan Recommended
FPM Air FPM Air FPM Air FPM Air
Speed Coverage Radius
Speed Speed Speed Speed
(RPM) Per Fan (ft)
Radius Radius Radius Radius
(ft) (ft) (ft) (ft)
Selected 78 38 58 75 90 83
Maximum 78 38 58 75 90 83

C:\Users\uriel.quiroz\Grupo 4HG\PDC Aplicaciones - Sist. De Ventilacion - Sist. De Ventilacion\GREENHECK\Jobs\PC-GH-2203-358 KukaHome Parque Industrial-R1.gfcj
CAPS 4.38.1089 Generated by: uriel.quiroz@proveedora.mx Page 4 of 106
Printed Date: 06/07/2022
Job: PC-GH-2203-358 KukaHome Parque Industrial-R1
Mark: BF 01-11
Model: DS-6-20-170HV

Model: DS-6-20-170HV
High Volume, Low Speed Ceiling Fan

Fan Spacing & Clearances

A - Clearance to Wall (ft) B - Fan Spacing (ft) C - Clearance to Floor (ft)


Minimum 30 60 10

Additional Requirements

1. For NFPA 13 compliance in buildings equipped with sprinklers:


-Fan must be centered approximately between four adjacent sprinklers
-Vertical clearance from fan to sprinkler deflector must be a minimum of 3 ft (36 in.)
-Fan must be interlocked to shut down immediately upon a waterflow alarm from the building's fire alarm system
-Interlock with building's fire alarm system shall be in accordance with the requirements of NFPA 72
2. Avoid installing fan directly below a light source to prevent a strobing effect that can be caused by fan rotation

C:\Users\uriel.quiroz\Grupo 4HG\PDC Aplicaciones - Sist. De Ventilacion - Sist. De Ventilacion\GREENHECK\Jobs\PC-GH-2203-358 KukaHome Parque Industrial-R1.gfcj
CAPS 4.38.1089 Generated by: uriel.quiroz@proveedora.mx Page 5 of 106
Printed Date: 06/07/2022
Job: PC-GH-2203-358 KukaHome Parque Industrial-R1
Mark: BF 01-11
Model: DS-6-20-170HV

Perceived Cooling Effect

Feels 12°F
Cooler

Perceived Cooling Effect Based on ASHRAE 55-2017


Perceived
Coverage Area Operative Relative Metabolic Avg. Air Speed
Clothing Level Cooling
Per Fan (ft2) Temp. (F) Humidity (%) Rate (ft/min)
Effect (F)
0.57 Pants, Short
21,600 77 60 1.7 Walking 477 12
Sleeves

C:\Users\uriel.quiroz\Grupo 4HG\PDC Aplicaciones - Sist. De Ventilacion - Sist. De Ventilacion\GREENHECK\Jobs\PC-GH-2203-358 KukaHome Parque Industrial-R1.gfcj
CAPS 4.38.1089 Generated by: uriel.quiroz@proveedora.mx Page 6 of 106
Printed Date: 06/07/2022
Job: PC-GH-2203-358 KukaHome Parque Industrial-R1
Mark: BF 01-11
Model: DS-6-20-170HV

Payback Analysis

Payback Inputs
Electric Cost (USD/ Heating Cost (USD/
Operating Time Heat Source
KwH) therm)
24 hours/day, 7
0.08 Gas 0.80
days/week

Winter Destratification Energy Savings


Estimated Heating Load Annual Energy Cost HVLS Energy Cost Net Energy Cost
Without HVLS With HVLS Savings (USD) (USD) Savings (USD)
0.0 0.0 0 0 0

Summer Cooling Energy Savings


Estimated Cooling Load Annual Energy Cost HVLS Energy Cost Net Energy Cost
Without HVLS With HVLS Savings (USD) (USD) Savings (USD)
0.0 0.0 0 0 0

Equipment Cost
Estimated HVLS Avoided A/C
Equipment First Cost Equipment Cost Net First Cost (USD)
(USD) (USD)
80,080 0 80,080

Payback
Net Operating
Payback Period
Savings Per Year
(Years)
(USD)
0 0.0

C:\Users\uriel.quiroz\Grupo 4HG\PDC Aplicaciones - Sist. De Ventilacion - Sist. De Ventilacion\GREENHECK\Jobs\PC-GH-2203-358 KukaHome Parque Industrial-R1.gfcj
CAPS 4.38.1089 Generated by: uriel.quiroz@proveedora.mx Page 7 of 106
Printed Date: 06/07/2022
Job: PC-GH-2203-358 KukaHome Parque Industrial-R1
Mark: BF 01-11
Model: DS-6-20-170HV

Model: DS-6-20-170HV
Finish Selection

Selected Frame Finish


Finish Type Hi-Pro Polyester
Mount Finish Color Flat Black (044)
Downtube Finish Color Flat Black (044)
Hub/Hub Plate Finish Color Flat Black (044)
Winglet Finish Color Flat Black (044)

Selected Airfoil Finish


Finish Type Mill
Finish Color None

Available Finish Options (Additional Charges May Apply):

C:\Users\uriel.quiroz\Grupo 4HG\PDC Aplicaciones - Sist. De Ventilacion - Sist. De Ventilacion\GREENHECK\Jobs\PC-GH-2203-358 KukaHome Parque Industrial-R1.gfcj
CAPS 4.38.1089 Generated by: uriel.quiroz@proveedora.mx Page 8 of 106
Printed Date: 06/07/2022
Job: PC-GH-2203-358 KukaHome Parque Industrial-R1
Mark: BF 01-11
Model: DS-6-20-170HV

Model: DS-6-20-170HV
High Volume, Low Speed Ceiling Fan

Mechanical Installation Requirements


Selected Mounting Kit: I-Beam

IMPORTANT: HVLS fans must be mounted to building structure as shown in one


of the mounting details on this page. Other mounting methods are not acceptable
unless approved by Structural Engineer of Record (SEOR). For complete installation
instructions, refer to the installation, operation and maintenance manual (IOM).

IMPORTANT: Failure to install the fan's safety retention cable and guy wires
(if provided) will result in voiding of the fan warranty.

Available Mounting Kits (Additional Charges May Apply):

C:\Users\uriel.quiroz\Grupo 4HG\PDC Aplicaciones - Sist. De Ventilacion - Sist. De Ventilacion\GREENHECK\Jobs\PC-GH-2203-358 KukaHome Parque Industrial-R1.gfcj
CAPS 4.38.1089 Generated by: uriel.quiroz@proveedora.mx Page 9 of 106
Printed Date: 06/07/2022
Job: PC-GH-2203-358 KukaHome Parque Industrial-R1
Mark: BF 01-11
Model: DS-6-20-170HV

Model: DS-6-20-170HV
High Volume, Low Speed Ceiling Fan

Electrical Installation Requirements


IMPORTANT: HVLS fans must be installed with the supplied CAT-5e communication cable or
shielded, twisted pair (STP) CAT-5e (by others) that complies with the following specifications. Cable
must be twisted pair, shielded 26 ga. CAT-5e cable with a drain wire and must be compliant with ISO
11801. Cable must use shielded RJ45 connectors with a soldered drain and wiring configuration must
follow EIA/TIA T568B wiring pinout. Individual CAT-5e cable lengths must not exceed 200 ft. in order
to prevent network communication issues.

POWER WIRING
SHIELDED TWISTED PAIR CAT-5e CONNECTION

TO NEXT FAN POWER SOURCE


(IF APPLICABLE) RED
L3
BLACK
TO CONTROL L2
WHITE
L1
GREEN GROUND

FIRE SYSTEM WIRING (IF APPLICABLE)


DIP SWITCH BANK 3
ON

SUPPLIED FIRE RELAY FIRE ALARM


1 2 3 4 5 6 7 8 CONTROL PANEL

BLACK
YELLOW (NC) RED (+) RED
RED
BLUE (COMMON) WHITE (-) WHITE
DIP SWITCH BANK 2
ON

1 2 3

3 HALL CONNECTION
NOTE:
HALL CABLE PLUG HAS
BUILT-IN ALIGNMENT TAB.
MOTOR CABLE CONNECTION DO NOT FORCE THIS PLUG

POWER 1
GROUND 2
POWER 1
GROUND 2

3 HALL CONNECTION

NOTE: If networking multiple HVLS fans to run using a single control source, additional
wiring and network modification may be required. Please refer to the fans's installation,
operation and maintenance manual (IOM)

C:\Users\uriel.quiroz\Grupo 4HG\PDC Aplicaciones - Sist. De Ventilacion - Sist. De Ventilacion\GREENHECK\Jobs\PC-GH-2203-358 KukaHome Parque Industrial-R1.gfcj
CAPS 4.38.1089 Generated by: uriel.quiroz@proveedora.mx Page 10 of 106
Printed Date: 06/07/2022
Job: PC-GH-2203-358 KukaHome Parque Industrial-R1
Mark: BF 01-11
Model: DS-6-20-170HV

Model: DS-6-20-170HV
High Volume, Low Speed Ceiling Fan

HVLS Fan Compliance


Department of Energy (DOE) 10 CFR Part 430 Compliance
DOE Min. CFEI at Calculated CFEI at DOE Min. CFEI at Calculated CFEI at DOE Min. Efficiency Calculated Efficiency
Compliance
40% Speed 40% Speed 100% Speed 100% Speed (CFM/W) (CFM/W)
1.31 2.72 1.00 1.44 - - Yes

ASHRAE 55-2017 Compliance


Perceived Acceptable Calculated
Operative Relative Metabolic Avg. Air Speed Thermal
Clothing Level Cooling Effect Predicted Mean Predicted Mean Compliance
Temp. (F) Humidity (%) Rate (ft/min) Sensation
(F) Vote (PMV) Vote (PMV)
0.57 Pants, -0.5 ≤ PMV ≤
77 60 1.7 Walking 477 12 -0.44 Neutral Yes
Short Sleeves 0.5

C:\Users\uriel.quiroz\Grupo 4HG\PDC Aplicaciones - Sist. De Ventilacion - Sist. De Ventilacion\GREENHECK\Jobs\PC-GH-2203-358 KukaHome Parque Industrial-R1.gfcj
CAPS 4.38.1089 Generated by: uriel.quiroz@proveedora.mx Page 11 of 106
Printed Date: 06/07/2022
Job: PC-GH-2203-358 KukaHome Parque Industrial-R1
Mark: BF 01-11
Model: DS-6-20-170HV
Assembly Drawing
Type: High Volume, Low Speed Ceiling Fan

42.0

3.0

SIDE VIEW

240

BOTTOM VIEW

Notes: All dimensions shown are in units of in..

C:\Users\uriel.quiroz\Grupo 4HG\PDC Aplicaciones - Sist. De Ventilacion - Sist. De Ventilacion\GREENHECK\Jobs\PC-GH-2203-358 KukaHome Parque Industrial-R1.gfcj
CAPS 4.38.1089 Generated by: uriel.quiroz@proveedora.mx Page 12 of 106
Printed Date: 06/07/2022
Job: PC-GH-2203-358 KukaHome Parque Industrial-R1
Mark: BF 01-11
Model: DS-6-20-170HV
Mechanical Warranty
10 Yrs (Standard)

WARRANTY AND LIABILITY: SELLER warrants to Buyer that the mechanical components of HVLS products manufactured are
free from defects in material and workmanship for a period of 10 Yrs (Standard) from the date of shipment. SELLER's
obligations and liabilities under this warranty are limited to furnishing FOB factory or warehouse at SELLER's designated
shipping point, freight allowed to Buyer's city, (or point of export for shipments outside the conterminous United States)
replacement equipment (or at the option of SELLER parts therefore) for all Seller's products not conforming to this warranty and
which have been returned to the manufacturer. No liability whatever shall attach to SELLER until said products have been paid
for and such liability shall be strictly limited to the purchase price of the equipment shown to be defective. SELLER will not be
responsible for any labor, removal, or installation costs. Electrical components are warranted separately as described in the
product's electrical warranty statement. The legal remedies described in this Warranty are the sole exclusive remedy of Buyer.
SELLER MAKES NO OTHER WARRANTY, EITHER EXPRESS OR IMPLIED, REGARDING ITS PRODUCTS, OR ITS
SELECTION AND APPLICATION, INCLUDING, BUT NOT LIMITED TO, COMPLIANCE WITH BUILDING CODES, SAFETY
CODES, LAWS, MERCHANTABILITY OR FITNESS OR A PARTICULAR PURPOSE. This warranty is extended solely to the
Buyer. It is nontransferable and non-assignable, and the Buyer shall not permit or authorize its employees, agents,
representatives or customers to claim, represent or imply that this limited warranty extends or is available to anyone other than
the Buyer. This warranty only applies to the first installation location of the product and terminates if the product is moved or
reinstalled in a new location. ANY MISUSE, NEGLECT, FAILURE TO FOLLOW INSTRUCTIONS OR MANUALS OF
INSTALLATION OF MAINTENANCE REPAIR, SERVICE, RELOCATION OR ALTERATION TO OR OF, OR OTHER
TAMPERING WITH, THE PRODUCTS PERFORMED BY ANY PERSON OR ENTITY OTHER THAN SELLER WITHOUT
SELLER'S PRIOR WRITTEN APPROVAL OR ANY USE OF REPLACEMENT PARTS NOT SUPPLIED BY SELLER, SHALL
IMMEDIATELY VOID AND CANCEL ALL WARRANTIES WITH RESPECT TO THE AFFECTED PRODUCTS. SELLER
RESERVES THE RIGHT TO MAKE FINAL DETERMINATION ON WARRANTY CLAIMS, BASED ON ITS OWN EVALUATION,
AS TO WHETHER THE PROBLEM IN QUESTION IS THE RESULT OF A DEFECT AND NOT A RESULT OF ERROR,
MISUSE, AN ACT OF GOD, OR ABUSE ON THE PART OF THE CUSTOMER WHICH WOULD MAKE THE WARRANTY
VOID. CONDITIONS THAT WOULD MAKE THE WARRANTY VOID INCLUDE BUT ARE NOT LIMITED TO: NOISE HEARD
DURING OPERATION THAT IS WITHIN NORMAL OPERATING LEVELS, IMPROPER APPLICATION, IMPROPER
INSTALLATION, OR ADVERSE SITE CONDITIONS (INCLUDING, BUT NOT LIMITED TO, EXCESSIVE DUST, HEAT,
HUMIDITY, UNSTABLE ELECTRICAL SERVICE, OR ANY OTHER UNKNOWN OR UNFORESEEN CONDITION THAT
AFFECTS THE PROPER OPERATION OF THE PRODUCT). THE WARRANTY AND LIABILITY SET FORTH HEREIN ARE IN
LIEU OF ALL OTHER WARRANTIES AND LIABILITIES WHETHER IN CONTRACT OR IN NEGLIGENCE, EXPRESSED OR
IMPLIED, IN LAW OR IN FACT, INCLUDING IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A
PARTICULAR USE. SELLER PROVIDES NO INDEPENDENT WARRANTY FOR THIRD PARTY PRODUCTS OR
COMPONENTS SOLD TOGETHER OR INCORPORATED WITH SELLER'S PRODUCT(S). THE SELLER HAS THE RIGHT
TO SETTLE ANY AND ALL DISPUTES REGARDING THE WARRANTY.

C:\Users\uriel.quiroz\Grupo 4HG\PDC Aplicaciones - Sist. De Ventilacion - Sist. De Ventilacion\GREENHECK\Jobs\PC-GH-2203-358 KukaHome Parque Industrial-R1.gfcj
CAPS 4.38.1089 Generated by: uriel.quiroz@proveedora.mx Page 13 of 106
Printed Date: 06/07/2022
Job: PC-GH-2203-358 KukaHome Parque Industrial-R1
Mark: BF 01-11
Model: DS-6-20-170HV
Electrical Warranty
1 Yr (Standard)

WARRANTY AND LIABILITY: SELLER warrants to Buyer that the electrical components (including motors, variable frequency
drives, and factory-supplied wiring; excluding UV-C lightbulbs and ballasts) of HVLS products manufactured are free from
defects in material and workmanship for a period of 1 Yr (Standard) from the date of shipment. SELLER's obligations and
liabilities under this warranty are limited to furnishing FOB factory or warehouse at SELLER's designated shipping point, freight
allowed to Buyer's city, (or point of export for shipments outside the conterminous United States) replacement equipment (or at
the option of SELLER parts therefore) for all Seller's products not conforming to this warranty and which have been returned to
the manufacturer. No liability whatever shall attach to SELLER until said products have been paid for and such liability shall be
strictly limited to the purchase price of the equipment shown to be defective. SELLER will not be responsible for any labor,
removal, or installation costs. Mechanical components are warranted separately as described in the product's mechanical
warranty statement. To the extent that SELLER is entitled to pass through a warranty of the original equipment manufacturer of
the electrical goods sold, SELLER will pass through such warranty to Buyer. The legal remedies described in this Warranty are
the sole exclusive remedy of Buyer. SELLER MAKES NO OTHER WARRANTY, EITHER EXPRESS OR IMPLIED,
REGARDING ITS PRODUCTS, OR ITS SELECTION AND APPLICATION, INCLUDING, BUT NOT LIMITED TO,
COMPLIANCE WITH BUILDING CODES, SAFETY CODES, LAWS, MERCHANTABILITY OR FITNESS OR A PARTICULAR
PURPOSE. This warranty is extended solely to the Buyer. It is nontransferable and non-assignable, and the Buyer shall not
permit or authorize its employees, agents, representatives or customers to claim, represent or imply that this limited warranty
extends or is available to anyone other than the Buyer. This warranty only applies to the first installation location of the product
and terminates if the product is moved or reinstalled in a new location. ANY MISUSE, NEGLECT, FAILURE TO FOLLOW
INSTRUCTIONS OR MANUALS OF INSTALLATION OF MAINTENANCE REPAIR, SERVICE, RELOCATION OR ALTERATION
TO OR OF, OR OTHER TAMPERING WITH, THE PRODUCTS PERFORMED BY ANY PERSON OR ENTITY OTHER THAN
SELLER WITHOUT SELLER'S PRIOR WRITTEN APPROVAL OR ANY USE OF REPLACEMENT PARTS NOT SUPPLIED BY
SELLER, SHALL IMMEDIATELY VOID AND CANCEL ALL WARRANTIES WITH RESPECT TO THE AFFECTED PRODUCTS.
SELLER RESERVES THE RIGHT TO MAKE FINAL DETERMINATION ON WARRANTY CLAIMS, BASED ON ITS OWN
EVALUATION, AS TO WHETHER THE PROBLEM IN QUESTION IS THE RESULT OF A DEFECT AND NOT A RESULT OF
ERROR, MISUSE, AN ACT OF GOD, OR ABUSE ON THE PART OF THE CUSTOMER WHICH WOULD MAKE THE
WARRANTY VOID. CONDITIONS THAT WOULD MAKE THE WARRANTY VOID INCLUDE BUT ARE NOT LIMITED TO:
NOISE HEARD DURING OPERATION THAT IS WITHIN NORMAL OPERATING LEVELS, IMPROPER APPLICATION,
IMPROPER INSTALLATION, OR ADVERSE SITE CONDITIONS (INCLUDING, BUT NOT LIMITED TO, EXCESSIVE DUST,
HEAT, HUMIDITY, UNSTABLE ELECTRICAL SERVICE, OR ANY OTHER UNKNOWN OR UNFORESEEN CONDITION THAT
AFFECTS THE PROPER OPERATION OF THE PRODUCT). THE WARRANTY AND LIABILITY SET FORTH HEREIN ARE IN
LIEU OF ALL OTHER WARRANTIES AND LIABILITIES WHETHER IN CONTRACT OR IN NEGLIGENCE, EXPRESSED OR
IMPLIED, IN LAW OR IN FACT, INCLUDING IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A
PARTICULAR USE. SELLER PROVIDES NO INDEPENDENT WARRANTY FOR THIRD PARTY PRODUCTS OR
COMPONENTS SOLD TOGETHER OR INCORPORATED WITH SELLER'S PRODUCT(S). THE SELLER HAS THE RIGHT
TO SETTLE ANY AND ALL DISPUTES REGARDING THE WARRANTY.

C:\Users\uriel.quiroz\Grupo 4HG\PDC Aplicaciones - Sist. De Ventilacion - Sist. De Ventilacion\GREENHECK\Jobs\PC-GH-2203-358 KukaHome Parque Industrial-R1.gfcj
CAPS 4.38.1089 Generated by: uriel.quiroz@proveedora.mx Page 14 of 106
Printed Date: 06/07/2022
Job: PC-GH-2203-358 KukaHome Parque Industrial-R1
Mark: BF 01-11
Model: DS-6-20-170HV

AMCA

Greenheck Fan Corporation certifies that the model shown herein is licensed to bear the AMCA Seal. The ratings
shown are based on tests and procedures performed in accordance with AMCA Publication 211 and comply with the
requirements of the AMCA Certified Ratings Program. The AMCA Certified Ratings Seal applies to air performance
ratings only. The AMCA Certified Ratings Seal applies at free delivery only. Performance ratings do not include the
effects of appurtenances (accessories).

C:\Users\uriel.quiroz\Grupo 4HG\PDC Aplicaciones - Sist. De Ventilacion - Sist. De Ventilacion\GREENHECK\Jobs\PC-GH-2203-358 KukaHome Parque Industrial-R1.gfcj
CAPS 4.38.1089 Generated by: uriel.quiroz@proveedora.mx Page 15 of 106
Printed Date: 06/07/2022
Job: PC-GH-2203-358 KukaHome Parque Industrial-R1
Mark: BF 12-59
Model: DS-6-20-170HV

Model: DS-6-20-170HV 42.0


High Volume, Low Speed Ceiling Fan
3.0

Dimensional
Impeller Diameter (ft) 20
Impeller Diameter (in.) 240
Quantity 48
Weight w/o Acc's (lb) 119
Weight w/ Acc's (lb) 235

Installation Clearances
Minimum Fan Spacing (ft) 60
Clearance to Wall (ft) 30
Blade Tip Clearance (ft) 3
Vertical Blade Clearance (ft) 3
Standby Blade Deflection (in.) 1.7

Performance Per Fan


*Tested Direction of Operation Forward
Actual Volume (CFM) 196,200
Coverage Area (ft2) 21,600
Max Coverage Area (ft2) 21,600
Avg. Air Speed (ft/min) 477
Max Avg. Air Speed (ft/min) 477
Fan RPM 78
Max Fan RPM 78
**CFEI at 40% Speed 2.72
**CFEI at 100% Speed 1.44
**Integrated Efficiency
-
(CFM/W)
Total Sound Pressure (dBA) 52

Fan Operation
Direction of Operation
Forward or Reverse
Capability
Communication Protocol Modbus RTU

Motor
Size (W) 1,100 Notes:
All dimensions shown are in units of in. (unless specified
Voltage/Cycle/Phase 460/60/3
otherwise)
Enclosure IP54 Dimensions shown may vary with fan speed. Consult
installation manual for clearance requirements.
Max Motor RPM 78 dBA – A weighted sound pressure level measured 5 ft off
the ground at 20 ft from the center of the fan – dBA levels
***System FLA (Amps) 3.5 are not licensed by AMCA International
*Cataloged performance data tested using forward
**Standby Power (W) 11 direction of operation per 10 CFR Part 430.
**Input Power (W) 1,398 **Based on 208/60/3 testing per 10 CFR 430
***FLA is based on worst case system voltage and phase
combination

C:\Users\uriel.quiroz\Grupo 4HG\PDC Aplicaciones - Sist. De Ventilacion - Sist. De Ventilacion\GREENHECK\Jobs\PC-GH-2203-358 KukaHome Parque Industrial-R1.gfcj
CAPS 4.38.1089 Generated by: uriel.quiroz@proveedora.mx Page 16 of 106
Printed Date: 06/07/2022
Job: PC-GH-2203-358 KukaHome Parque Industrial-R1
Mark: BF 12-59
Model: DS-6-20-170HV
Model: DS-6-20-170HV
High Volume, Low Speed Ceiling Fan
Tags: BF 12 BF 13 BF 14 BF 15 BF 16 BF 17 BF 18 BF 19 BF 20 BF 21 BF 22
BF 23 BF 24 BF 25 BF 26 BF 27 BF 28 BF 29 BF 30 BF 31 BF 32 BF 33 BF 34
BF 35 BF 36 BF 37 BF 38 BF 39 BF 40 BF 41 BF 42 BF 43 BF 44 BF 45 BF 46
BF 47 BF 48 BF 49 BF 50 BF 51 BF 52 BF 53 BF 54 BF 55 BF 56 BF 57 BF 58
BF 59
Standard Construction Features:
Heavy duty frame with protective finish - Extruded aluminum airfoils - High
efficiency direct drive motor designed for either forward or reverse operation -
Factory mounted and wired variable frequency drive - Factory installed plug and
play wiring - Universal ceiling mount - Heavy duty safety restraint cable - Airfoil
and fan hub retaining systems - AMCA certified for Circulating Fan Performance
Selected Options & Accessories:
6 Blade, Extruded Aluminum Airfoil Kit
Mill Finish, No Color
Aluminum Winglet; Hi-Pro Polyester Finish, Flat Black (044) Color
I-Beam Mounting Kit; Hi-Pro Polyester Finish, Flat Black (044) Color
3.5 ft Drop Length; Hi-Pro Polyester Finish, Flat Black (044) Color
Hub Plate and Impeller Hub; Hi-Pro Polyester Finish, Flat Black (044) Color
Hub Plate Decal with Greenheck Logo
Power Wiring Pigtail, Internal, General, 3 ft of Flexible Power Cord from Unit,
Unstripped Wire
Plug-and-Play Network Communication Wiring Pigtail, Internal, Terminated with
Shielded CAT-5e Splitter (RJ45 Ports)
100 ft of Shielded, Twisted Pair (STP) CAT-5e Control Cable
Fire Alarm Wiring Pigtail, Internal, 2.5 ft from Unit, Terminated with Crimp
Connector
Low-Voltage (24VDC/VAC or 115VAC), Normally Closed Electromechanical Fire
Alarm Relay
Braided Galvanized Steel Safety Cable, 16 ft from Unit
Braided Galvanized Steel Guy Wires, 20 ft from Unit
Cable Clamp Hardware for Safety Cable and Guy Wires
Electrical Warranty: 1 Yr (Standard)
Mechanical Warranty: 10 Yrs (Standard)

C:\Users\uriel.quiroz\Grupo 4HG\PDC Aplicaciones - Sist. De Ventilacion - Sist. De Ventilacion\GREENHECK\Jobs\PC-GH-2203-358 KukaHome Parque Industrial-R1.gfcj
CAPS 4.38.1089 Generated by: uriel.quiroz@proveedora.mx Page 17 of 106
Printed Date: 06/07/2022
Job: PC-GH-2203-358 KukaHome Parque Industrial-R1
Mark: BF 12-59
Model: DS-6-20-170HV

Model: DS-6-20-170HV
High Volume, Low Speed Ceiling Fan

Fan Coverage Data

Zone 1 Zone 2 Zone 3 Zone 4


375+ 230+ 105+ <105
Fan Recommended
FPM Air FPM Air FPM Air FPM Air
Speed Coverage Radius
Speed Speed Speed Speed
(RPM) Per Fan (ft)
Radius Radius Radius Radius
(ft) (ft) (ft) (ft)
Selected 78 38 58 75 90 83
Maximum 78 38 58 75 90 83

C:\Users\uriel.quiroz\Grupo 4HG\PDC Aplicaciones - Sist. De Ventilacion - Sist. De Ventilacion\GREENHECK\Jobs\PC-GH-2203-358 KukaHome Parque Industrial-R1.gfcj
CAPS 4.38.1089 Generated by: uriel.quiroz@proveedora.mx Page 18 of 106
Printed Date: 06/07/2022
Job: PC-GH-2203-358 KukaHome Parque Industrial-R1
Mark: BF 12-59
Model: DS-6-20-170HV

Model: DS-6-20-170HV
High Volume, Low Speed Ceiling Fan

Fan Spacing & Clearances

A - Clearance to Wall (ft) B - Fan Spacing (ft) C - Clearance to Floor (ft)


Minimum 30 60 10

Additional Requirements

1. For NFPA 13 compliance in buildings equipped with sprinklers:


-Fan must be centered approximately between four adjacent sprinklers
-Vertical clearance from fan to sprinkler deflector must be a minimum of 3 ft (36 in.)
-Fan must be interlocked to shut down immediately upon a waterflow alarm from the building's fire alarm system
-Interlock with building's fire alarm system shall be in accordance with the requirements of NFPA 72
2. Avoid installing fan directly below a light source to prevent a strobing effect that can be caused by fan rotation

C:\Users\uriel.quiroz\Grupo 4HG\PDC Aplicaciones - Sist. De Ventilacion - Sist. De Ventilacion\GREENHECK\Jobs\PC-GH-2203-358 KukaHome Parque Industrial-R1.gfcj
CAPS 4.38.1089 Generated by: uriel.quiroz@proveedora.mx Page 19 of 106
Printed Date: 06/07/2022
Job: PC-GH-2203-358 KukaHome Parque Industrial-R1
Mark: BF 12-59
Model: DS-6-20-170HV

Perceived Cooling Effect

Feels 12°F
Cooler

Perceived Cooling Effect Based on ASHRAE 55-2017


Perceived
Coverage Area Operative Relative Metabolic Avg. Air Speed
Clothing Level Cooling
Per Fan (ft2) Temp. (F) Humidity (%) Rate (ft/min)
Effect (F)
0.57 Pants, Short
21,600 77 60 1.7 Walking 477 12
Sleeves

C:\Users\uriel.quiroz\Grupo 4HG\PDC Aplicaciones - Sist. De Ventilacion - Sist. De Ventilacion\GREENHECK\Jobs\PC-GH-2203-358 KukaHome Parque Industrial-R1.gfcj
CAPS 4.38.1089 Generated by: uriel.quiroz@proveedora.mx Page 20 of 106
Printed Date: 06/07/2022
Job: PC-GH-2203-358 KukaHome Parque Industrial-R1
Mark: BF 12-59
Model: DS-6-20-170HV

Payback Analysis

Payback Inputs
Electric Cost (USD/ Heating Cost (USD/
Operating Time Heat Source
KwH) therm)
24 hours/day, 7
0.08 Gas 0.80
days/week

Winter Destratification Energy Savings


Estimated Heating Load Annual Energy Cost HVLS Energy Cost Net Energy Cost
Without HVLS With HVLS Savings (USD) (USD) Savings (USD)
0.0 0.0 0 0 0

Summer Cooling Energy Savings


Estimated Cooling Load Annual Energy Cost HVLS Energy Cost Net Energy Cost
Without HVLS With HVLS Savings (USD) (USD) Savings (USD)
0.0 0.0 0 0 0

Equipment Cost
Estimated HVLS Avoided A/C
Equipment First Cost Equipment Cost Net First Cost (USD)
(USD) (USD)
349,440 0 349,440

Payback
Net Operating
Payback Period
Savings Per Year
(Years)
(USD)
0 0.0

C:\Users\uriel.quiroz\Grupo 4HG\PDC Aplicaciones - Sist. De Ventilacion - Sist. De Ventilacion\GREENHECK\Jobs\PC-GH-2203-358 KukaHome Parque Industrial-R1.gfcj
CAPS 4.38.1089 Generated by: uriel.quiroz@proveedora.mx Page 21 of 106
Printed Date: 06/07/2022
Job: PC-GH-2203-358 KukaHome Parque Industrial-R1
Mark: BF 12-59
Model: DS-6-20-170HV

Model: DS-6-20-170HV
Finish Selection

Selected Frame Finish


Finish Type Hi-Pro Polyester
Mount Finish Color Flat Black (044)
Downtube Finish Color Flat Black (044)
Hub/Hub Plate Finish Color Flat Black (044)
Winglet Finish Color Flat Black (044)

Selected Airfoil Finish


Finish Type Mill
Finish Color None

Available Finish Options (Additional Charges May Apply):

C:\Users\uriel.quiroz\Grupo 4HG\PDC Aplicaciones - Sist. De Ventilacion - Sist. De Ventilacion\GREENHECK\Jobs\PC-GH-2203-358 KukaHome Parque Industrial-R1.gfcj
CAPS 4.38.1089 Generated by: uriel.quiroz@proveedora.mx Page 22 of 106
Printed Date: 06/07/2022
Job: PC-GH-2203-358 KukaHome Parque Industrial-R1
Mark: BF 12-59
Model: DS-6-20-170HV

Model: DS-6-20-170HV
High Volume, Low Speed Ceiling Fan

Mechanical Installation Requirements


Selected Mounting Kit: I-Beam

IMPORTANT: HVLS fans must be mounted to building structure as shown in one


of the mounting details on this page. Other mounting methods are not acceptable
unless approved by Structural Engineer of Record (SEOR). For complete installation
instructions, refer to the installation, operation and maintenance manual (IOM).

IMPORTANT: Failure to install the fan's safety retention cable and guy wires
(if provided) will result in voiding of the fan warranty.

Available Mounting Kits (Additional Charges May Apply):

C:\Users\uriel.quiroz\Grupo 4HG\PDC Aplicaciones - Sist. De Ventilacion - Sist. De Ventilacion\GREENHECK\Jobs\PC-GH-2203-358 KukaHome Parque Industrial-R1.gfcj
CAPS 4.38.1089 Generated by: uriel.quiroz@proveedora.mx Page 23 of 106
Printed Date: 06/07/2022
Job: PC-GH-2203-358 KukaHome Parque Industrial-R1
Mark: BF 12-59
Model: DS-6-20-170HV

Model: DS-6-20-170HV
High Volume, Low Speed Ceiling Fan

Electrical Installation Requirements


IMPORTANT: HVLS fans must be installed with the supplied CAT-5e communication cable or
shielded, twisted pair (STP) CAT-5e (by others) that complies with the following specifications. Cable
must be twisted pair, shielded 26 ga. CAT-5e cable with a drain wire and must be compliant with ISO
11801. Cable must use shielded RJ45 connectors with a soldered drain and wiring configuration must
follow EIA/TIA T568B wiring pinout. Individual CAT-5e cable lengths must not exceed 200 ft. in order
to prevent network communication issues.

POWER WIRING
SHIELDED TWISTED PAIR CAT-5e CONNECTION

TO NEXT FAN POWER SOURCE


(IF APPLICABLE) RED
L3
BLACK
TO CONTROL L2
WHITE
L1
GREEN GROUND

FIRE SYSTEM WIRING (IF APPLICABLE)


DIP SWITCH BANK 3
ON

SUPPLIED FIRE RELAY FIRE ALARM


1 2 3 4 5 6 7 8 CONTROL PANEL

BLACK
YELLOW (NC) RED (+) RED
RED
BLUE (COMMON) WHITE (-) WHITE
DIP SWITCH BANK 2
ON

1 2 3

3 HALL CONNECTION
NOTE:
HALL CABLE PLUG HAS
BUILT-IN ALIGNMENT TAB.
MOTOR CABLE CONNECTION DO NOT FORCE THIS PLUG

POWER 1
GROUND 2
POWER 1
GROUND 2

3 HALL CONNECTION

NOTE: If networking multiple HVLS fans to run using a single control source, additional
wiring and network modification may be required. Please refer to the fans's installation,
operation and maintenance manual (IOM)

C:\Users\uriel.quiroz\Grupo 4HG\PDC Aplicaciones - Sist. De Ventilacion - Sist. De Ventilacion\GREENHECK\Jobs\PC-GH-2203-358 KukaHome Parque Industrial-R1.gfcj
CAPS 4.38.1089 Generated by: uriel.quiroz@proveedora.mx Page 24 of 106
Printed Date: 06/07/2022
Job: PC-GH-2203-358 KukaHome Parque Industrial-R1
Mark: BF 12-59
Model: DS-6-20-170HV

Model: DS-6-20-170HV
High Volume, Low Speed Ceiling Fan

HVLS Fan Compliance


Department of Energy (DOE) 10 CFR Part 430 Compliance
DOE Min. CFEI at Calculated CFEI at DOE Min. CFEI at Calculated CFEI at DOE Min. Efficiency Calculated Efficiency
Compliance
40% Speed 40% Speed 100% Speed 100% Speed (CFM/W) (CFM/W)
1.31 2.72 1.00 1.44 - - Yes

ASHRAE 55-2017 Compliance


Perceived Acceptable Calculated
Operative Relative Metabolic Avg. Air Speed Thermal
Clothing Level Cooling Effect Predicted Mean Predicted Mean Compliance
Temp. (F) Humidity (%) Rate (ft/min) Sensation
(F) Vote (PMV) Vote (PMV)
0.57 Pants, -0.5 ≤ PMV ≤
77 60 1.7 Walking 477 12 -0.44 Neutral Yes
Short Sleeves 0.5

C:\Users\uriel.quiroz\Grupo 4HG\PDC Aplicaciones - Sist. De Ventilacion - Sist. De Ventilacion\GREENHECK\Jobs\PC-GH-2203-358 KukaHome Parque Industrial-R1.gfcj
CAPS 4.38.1089 Generated by: uriel.quiroz@proveedora.mx Page 25 of 106
Printed Date: 06/07/2022
Job: PC-GH-2203-358 KukaHome Parque Industrial-R1
Mark: BF 12-59
Model: DS-6-20-170HV
Assembly Drawing
Type: High Volume, Low Speed Ceiling Fan

42.0

3.0

SIDE VIEW

240

BOTTOM VIEW

Notes: All dimensions shown are in units of in..

C:\Users\uriel.quiroz\Grupo 4HG\PDC Aplicaciones - Sist. De Ventilacion - Sist. De Ventilacion\GREENHECK\Jobs\PC-GH-2203-358 KukaHome Parque Industrial-R1.gfcj
CAPS 4.38.1089 Generated by: uriel.quiroz@proveedora.mx Page 26 of 106
Printed Date: 06/07/2022
Job: PC-GH-2203-358 KukaHome Parque Industrial-R1
Mark: BF 12-59
Model: DS-6-20-170HV
Mechanical Warranty
10 Yrs (Standard)

WARRANTY AND LIABILITY: SELLER warrants to Buyer that the mechanical components of HVLS products manufactured are
free from defects in material and workmanship for a period of 10 Yrs (Standard) from the date of shipment. SELLER's
obligations and liabilities under this warranty are limited to furnishing FOB factory or warehouse at SELLER's designated
shipping point, freight allowed to Buyer's city, (or point of export for shipments outside the conterminous United States)
replacement equipment (or at the option of SELLER parts therefore) for all Seller's products not conforming to this warranty and
which have been returned to the manufacturer. No liability whatever shall attach to SELLER until said products have been paid
for and such liability shall be strictly limited to the purchase price of the equipment shown to be defective. SELLER will not be
responsible for any labor, removal, or installation costs. Electrical components are warranted separately as described in the
product's electrical warranty statement. The legal remedies described in this Warranty are the sole exclusive remedy of Buyer.
SELLER MAKES NO OTHER WARRANTY, EITHER EXPRESS OR IMPLIED, REGARDING ITS PRODUCTS, OR ITS
SELECTION AND APPLICATION, INCLUDING, BUT NOT LIMITED TO, COMPLIANCE WITH BUILDING CODES, SAFETY
CODES, LAWS, MERCHANTABILITY OR FITNESS OR A PARTICULAR PURPOSE. This warranty is extended solely to the
Buyer. It is nontransferable and non-assignable, and the Buyer shall not permit or authorize its employees, agents,
representatives or customers to claim, represent or imply that this limited warranty extends or is available to anyone other than
the Buyer. This warranty only applies to the first installation location of the product and terminates if the product is moved or
reinstalled in a new location. ANY MISUSE, NEGLECT, FAILURE TO FOLLOW INSTRUCTIONS OR MANUALS OF
INSTALLATION OF MAINTENANCE REPAIR, SERVICE, RELOCATION OR ALTERATION TO OR OF, OR OTHER
TAMPERING WITH, THE PRODUCTS PERFORMED BY ANY PERSON OR ENTITY OTHER THAN SELLER WITHOUT
SELLER'S PRIOR WRITTEN APPROVAL OR ANY USE OF REPLACEMENT PARTS NOT SUPPLIED BY SELLER, SHALL
IMMEDIATELY VOID AND CANCEL ALL WARRANTIES WITH RESPECT TO THE AFFECTED PRODUCTS. SELLER
RESERVES THE RIGHT TO MAKE FINAL DETERMINATION ON WARRANTY CLAIMS, BASED ON ITS OWN EVALUATION,
AS TO WHETHER THE PROBLEM IN QUESTION IS THE RESULT OF A DEFECT AND NOT A RESULT OF ERROR,
MISUSE, AN ACT OF GOD, OR ABUSE ON THE PART OF THE CUSTOMER WHICH WOULD MAKE THE WARRANTY
VOID. CONDITIONS THAT WOULD MAKE THE WARRANTY VOID INCLUDE BUT ARE NOT LIMITED TO: NOISE HEARD
DURING OPERATION THAT IS WITHIN NORMAL OPERATING LEVELS, IMPROPER APPLICATION, IMPROPER
INSTALLATION, OR ADVERSE SITE CONDITIONS (INCLUDING, BUT NOT LIMITED TO, EXCESSIVE DUST, HEAT,
HUMIDITY, UNSTABLE ELECTRICAL SERVICE, OR ANY OTHER UNKNOWN OR UNFORESEEN CONDITION THAT
AFFECTS THE PROPER OPERATION OF THE PRODUCT). THE WARRANTY AND LIABILITY SET FORTH HEREIN ARE IN
LIEU OF ALL OTHER WARRANTIES AND LIABILITIES WHETHER IN CONTRACT OR IN NEGLIGENCE, EXPRESSED OR
IMPLIED, IN LAW OR IN FACT, INCLUDING IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A
PARTICULAR USE. SELLER PROVIDES NO INDEPENDENT WARRANTY FOR THIRD PARTY PRODUCTS OR
COMPONENTS SOLD TOGETHER OR INCORPORATED WITH SELLER'S PRODUCT(S). THE SELLER HAS THE RIGHT
TO SETTLE ANY AND ALL DISPUTES REGARDING THE WARRANTY.

C:\Users\uriel.quiroz\Grupo 4HG\PDC Aplicaciones - Sist. De Ventilacion - Sist. De Ventilacion\GREENHECK\Jobs\PC-GH-2203-358 KukaHome Parque Industrial-R1.gfcj
CAPS 4.38.1089 Generated by: uriel.quiroz@proveedora.mx Page 27 of 106
Printed Date: 06/07/2022
Job: PC-GH-2203-358 KukaHome Parque Industrial-R1
Mark: BF 12-59
Model: DS-6-20-170HV
Electrical Warranty
1 Yr (Standard)

WARRANTY AND LIABILITY: SELLER warrants to Buyer that the electrical components (including motors, variable frequency
drives, and factory-supplied wiring; excluding UV-C lightbulbs and ballasts) of HVLS products manufactured are free from
defects in material and workmanship for a period of 1 Yr (Standard) from the date of shipment. SELLER's obligations and
liabilities under this warranty are limited to furnishing FOB factory or warehouse at SELLER's designated shipping point, freight
allowed to Buyer's city, (or point of export for shipments outside the conterminous United States) replacement equipment (or at
the option of SELLER parts therefore) for all Seller's products not conforming to this warranty and which have been returned to
the manufacturer. No liability whatever shall attach to SELLER until said products have been paid for and such liability shall be
strictly limited to the purchase price of the equipment shown to be defective. SELLER will not be responsible for any labor,
removal, or installation costs. Mechanical components are warranted separately as described in the product's mechanical
warranty statement. To the extent that SELLER is entitled to pass through a warranty of the original equipment manufacturer of
the electrical goods sold, SELLER will pass through such warranty to Buyer. The legal remedies described in this Warranty are
the sole exclusive remedy of Buyer. SELLER MAKES NO OTHER WARRANTY, EITHER EXPRESS OR IMPLIED,
REGARDING ITS PRODUCTS, OR ITS SELECTION AND APPLICATION, INCLUDING, BUT NOT LIMITED TO,
COMPLIANCE WITH BUILDING CODES, SAFETY CODES, LAWS, MERCHANTABILITY OR FITNESS OR A PARTICULAR
PURPOSE. This warranty is extended solely to the Buyer. It is nontransferable and non-assignable, and the Buyer shall not
permit or authorize its employees, agents, representatives or customers to claim, represent or imply that this limited warranty
extends or is available to anyone other than the Buyer. This warranty only applies to the first installation location of the product
and terminates if the product is moved or reinstalled in a new location. ANY MISUSE, NEGLECT, FAILURE TO FOLLOW
INSTRUCTIONS OR MANUALS OF INSTALLATION OF MAINTENANCE REPAIR, SERVICE, RELOCATION OR ALTERATION
TO OR OF, OR OTHER TAMPERING WITH, THE PRODUCTS PERFORMED BY ANY PERSON OR ENTITY OTHER THAN
SELLER WITHOUT SELLER'S PRIOR WRITTEN APPROVAL OR ANY USE OF REPLACEMENT PARTS NOT SUPPLIED BY
SELLER, SHALL IMMEDIATELY VOID AND CANCEL ALL WARRANTIES WITH RESPECT TO THE AFFECTED PRODUCTS.
SELLER RESERVES THE RIGHT TO MAKE FINAL DETERMINATION ON WARRANTY CLAIMS, BASED ON ITS OWN
EVALUATION, AS TO WHETHER THE PROBLEM IN QUESTION IS THE RESULT OF A DEFECT AND NOT A RESULT OF
ERROR, MISUSE, AN ACT OF GOD, OR ABUSE ON THE PART OF THE CUSTOMER WHICH WOULD MAKE THE
WARRANTY VOID. CONDITIONS THAT WOULD MAKE THE WARRANTY VOID INCLUDE BUT ARE NOT LIMITED TO:
NOISE HEARD DURING OPERATION THAT IS WITHIN NORMAL OPERATING LEVELS, IMPROPER APPLICATION,
IMPROPER INSTALLATION, OR ADVERSE SITE CONDITIONS (INCLUDING, BUT NOT LIMITED TO, EXCESSIVE DUST,
HEAT, HUMIDITY, UNSTABLE ELECTRICAL SERVICE, OR ANY OTHER UNKNOWN OR UNFORESEEN CONDITION THAT
AFFECTS THE PROPER OPERATION OF THE PRODUCT). THE WARRANTY AND LIABILITY SET FORTH HEREIN ARE IN
LIEU OF ALL OTHER WARRANTIES AND LIABILITIES WHETHER IN CONTRACT OR IN NEGLIGENCE, EXPRESSED OR
IMPLIED, IN LAW OR IN FACT, INCLUDING IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A
PARTICULAR USE. SELLER PROVIDES NO INDEPENDENT WARRANTY FOR THIRD PARTY PRODUCTS OR
COMPONENTS SOLD TOGETHER OR INCORPORATED WITH SELLER'S PRODUCT(S). THE SELLER HAS THE RIGHT
TO SETTLE ANY AND ALL DISPUTES REGARDING THE WARRANTY.

C:\Users\uriel.quiroz\Grupo 4HG\PDC Aplicaciones - Sist. De Ventilacion - Sist. De Ventilacion\GREENHECK\Jobs\PC-GH-2203-358 KukaHome Parque Industrial-R1.gfcj
CAPS 4.38.1089 Generated by: uriel.quiroz@proveedora.mx Page 28 of 106
Printed Date: 06/07/2022
Job: PC-GH-2203-358 KukaHome Parque Industrial-R1
Mark: BF 12-59
Model: DS-6-20-170HV

AMCA

Greenheck Fan Corporation certifies that the model shown herein is licensed to bear the AMCA Seal. The ratings
shown are based on tests and procedures performed in accordance with AMCA Publication 211 and comply with the
requirements of the AMCA Certified Ratings Program. The AMCA Certified Ratings Seal applies to air performance
ratings only. The AMCA Certified Ratings Seal applies at free delivery only. Performance ratings do not include the
effects of appurtenances (accessories).

C:\Users\uriel.quiroz\Grupo 4HG\PDC Aplicaciones - Sist. De Ventilacion - Sist. De Ventilacion\GREENHECK\Jobs\PC-GH-2203-358 KukaHome Parque Industrial-R1.gfcj
CAPS 4.38.1089 Generated by: uriel.quiroz@proveedora.mx Page 29 of 106
Printed Date: 06/07/2022
Job: PC-GH-2203-358 KukaHome Parque Industrial-R1
Mark: Controls
Model: HVLS-Controls

HVLS Fan Controls


Standard Construction Features:

HVLS fan controls are designed for use with Greenheck's high volume, low speed (HVLS) ceiling fan products. Each control is
configured for communication with one or multiple HVLS fans via the included RJ45 connector.

Control Type: Std. Touchscreen


Control Quantity: 17
Fans Per Control: 10
Installation Kit: N/A
Control Enclosure: Touchscreen interface with IP40 Front enclosure
Power Supply: Requires 24V power from fan via shielded, twisted pair (STP) CAT-5e cable
Communications: Configured for Modbus RTU Communication with HVLS Fan(s)
Fan Operation: Capable of Operating Up to 10 HVLS Fans with Any Combination of Models and Sizes
Fans Operate Individually with Unique Speed Settings and Directions of Rotation

TOP/BOTTOM

2.75

1.08

FRONT SIDE BACK

2.75 1.08 2.75

4.50 2.21 4.50 4.50 3.29

1.64 NOTE:
CONTROL HOLE MOUNTING PATTERN
FITS A STANDARD 2X4 JUNCTION BOX

Notes: All dimensions shown are in units of in.

C:\Users\uriel.quiroz\Grupo 4HG\PDC Aplicaciones - Sist. De Ventilacion - Sist. De Ventilacion\GREENHECK\Jobs\PC-GH-2203-358 KukaHome Parque Industrial-R1.gfcj
CAPS 4.38.1089 Generated by: uriel.quiroz@proveedora.mx Page 30 of 106
Printed Date: 06/07/2022
Job: PC-GH-2203-358 KukaHome Parque Industrial-R1
Mark: AWU 01-22
Model: MSX-130-H38

MSX-130-H38
Unit Performance
Design Conditions
Summer
Elevation (ft) Winter (°F) Supply (CFM) Outdoor Air (CFM)
DB (°F) WB (°F)
1,690 100.7 80.1 39.8 25,242 25,242

Unit Specifications
Qty Weight (lb) Cooling Type Heating Type Unit Installation Unit ETL Listing
22 3,396 (+/- 5%) Direct Evaporative None Outdoor/Indoor UL / cUL 1995

Configuration
Unit Orientation Unit Configuration Outdoor Air Intake Return Air Intake Supply Air Discharge
Constant Volume 100%
Horizontal End - End
OA

Cooling Specifications
Media Required Performance (DB/WB)
Type Cooling Media
Depth (in.) Flow (GPM) EAT (°F) LAT (°F)
Direct Evaporative CELdek 12 1.8 100.7 / 80.1 82.1 / 80.1

Air Performance
Total Fan
External SP Total SP Operating
Type Volume RPM
(in. wg) (in. wg) Power (hp) Qty Type Size (in.) Drive-Type
(CFM)
Supply 25,242 1.5 1.831 495 16.22 1 Forward Curve 30.2 Belt-Drive

Motor Specifications
Motor Qty Size (HP) Enclosure Efficiency RPM
Supply Fan Motor 1 20 ODP NEMA Premium 1725

Electrical Specifications
Power Supply Rating (V/C/P) MCA (A) MOP (A) SCCR
Unit 460/60/3 34 60 5kA

C:\Users\uriel.quiroz\Grupo 4HG\PDC Aplicaciones - Sist. De Ventilacion - Sist. De Ventilacion\GREENHECK\Jobs\PC-GH-2203-358 KukaHome Parque Industrial-R1.gfcj
CAPS 4.38.1089 Generated by: uriel.quiroz@proveedora.mx Page 31 of 106
Printed Date: 06/07/2022
Job: PC-GH-2203-358 KukaHome Parque Industrial-R1
Mark: AWU 01-22
Model: MSX-130-H38

CONSTRUCTION FEATURES AND ACCESSORIES


Unit Accessories
Unit Installation - Outdoor Std Factory Installed, Lockable, NEMA 3R Disconnect Std
Unit Construction - Single Wall X Weatherhood - Louvered with aluminum mesh filters X
Wall Insulation Supply Air Filters
Base Insulation - 1in. fiberglass - entire unit base pan Std Outdoor Air Inlet Damper
Paneled Bottom - Sheet metal liner for base insulation Supply Air Outlet Damper
Corrosion Resistant Fasteners Std Return Air Damper
Access and Connections - Right side when facing intake X Diffuser
Service Access - Hinged access doors X Roof Curb
Unit Finish - G90 Galvanized X Combination Curb
Finish Color Electrofin Coil Coating
Supply Fan - Belt-drive, forward-curved X Fan Bearing Extended Lube Lines
Supply Fan and Motor Vibration isolation - Neoprene X Inlet Damper Module
Controls Spare Belts
Unit Controls - Terminal strip X Spare Filters
Remote Panel Motor with Shaft Grounding
BMS Communication Service Outlet
BMS Protocol Service Lights
Temperature Control Evaporative Cooling Accessories
Supply Fan Control Evap Controls - Recirculating Pump X
Unoccupied Mode (Night Setback) Evap Valves (Ship loose)
Control Accessories Louvered intake provided with 2" aluminum mesh filters X
Remote display Warranty Options
Heating Inlet Air Sensor Unit Warranty - 1 Year X
Cooling Inlet Air Sensor X 5 Year Compressor Warranty
Dirty Filter Switch
Fire Stat Type III (Ships loose)
120V/24V Smoke Detector (Ships loose) Standard Option Std
Inlet Damper End Switch Not Included
External Cooling Lockout Relay Included X
Freeze Protection (Supply Air Low Limit)
Auxiliary Supply Starter Contacts
Auxiliary Exhaust Starter Contacts
Heating Coil Freeze Protection
Airflow Proving Monitoring Contact

Notes
Evap cooler pump requires a separate field provided 115V power connection
Evaporative cooler section ships separate and requires field installation.

C:\Users\uriel.quiroz\Grupo 4HG\PDC Aplicaciones - Sist. De Ventilacion - Sist. De Ventilacion\GREENHECK\Jobs\PC-GH-2203-358 KukaHome Parque Industrial-R1.gfcj
CAPS 4.38.1089 Generated by: uriel.quiroz@proveedora.mx Page 32 of 106
Printed Date: 06/07/2022
Job: PC-GH-2203-358 KukaHome Parque Industrial-R1
Mark: AWU 01-22
Model: MSX-130-H38

Fan Charts And Performance


Supply Fan Performance
Motor Fan
Total Volume External SP Total SP Operating
RPM Size
(CFM) (in. wg) (in. wg) Power (hp) Qty Qty Type Drive-Type
(HP)
25,242 1.5 1.831 495 16.22 1 20 1 Forward Curve Belt

Pressure Drop (in. wg)


Diffuser Weatherhood Filter Damper Cooling Heating External Total
- - - - 0.331 - 1.5 1.831

Sound Performance in Accordance with AMCA


Sound Power by Octave Band
Lwa dBA Sones
62.5 125 250 500 1000 2000 4000 8000
92 95 95 86 84 84 78 73 92 81 39

Supply Fan

C:\Users\uriel.quiroz\Grupo 4HG\PDC Aplicaciones - Sist. De Ventilacion - Sist. De Ventilacion\GREENHECK\Jobs\PC-GH-2203-358 KukaHome Parque Industrial-R1.gfcj
CAPS 4.38.1089 Generated by: uriel.quiroz@proveedora.mx Page 33 of 106
Printed Date: 06/07/2022
Job: PC-GH-2203-358 KukaHome Parque Industrial-R1
Mark: AWU 01-22
Model: MSX-130-H38

Cooling Specifications
Cooling Performance
Media Required Performance (DB/WB)
Type Cooling Media
Depth (in.) Flow (GPM) EAT (°F) LAT (°F)
Direct Evaporative CELdek 12 1.8 100.7 / 80.1 82.1 / 80.1

Unit Details
Stainless steel sump and media casing Ball valve for flow rate adjustment
Supply line, drain line and supply line drain valves must be field Recirculating pump(s) provided by factory
provided by others
Valve provided for bleed-off rate adjustment

Recirc. Pump Evap Control

Evaporative Cooling Connections

SUPPLY CONNECTION
(FIELD PROVIDED)
LOCATED IN FRONT
OF UNIT

3.252

1.674

19.027

DRAIN
31.027

OVERFLOW
C:\Users\uriel.quiroz\Grupo 4HG\PDC Aplicaciones - Sist. De Ventilacion - Sist. De Ventilacion\GREENHECK\Jobs\PC-GH-2203-358 KukaHome Parque Industrial-R1.gfcj
CAPS 4.38.1089 Generated by: uriel.quiroz@proveedora.mx Page 34 of 106
Printed Date: 06/07/2022
Job: PC-GH-2203-358 KukaHome Parque Industrial-R1
Mark: AWU 01-22
Model: MSX-130-H38

ELEVATION VIEW
170.053

98.504 71.549

63.850

Notes - Elevation View


Standard configuration for unit access is on the right-hand side, when looking into the unit intake in the direction of airflow.
Order of unit sections is from intake of unit to discharge of unit.
Sections included on this unit: Cooling Section, Blower Section

PLAN VIEW
INTAKE SIDE
EVAP COOLING BLOWER
98.504 71.549

ACCESS SIDE
95.528

INTAKE SIDE

ACCESS SIDE -
CONTROL CENTER

Notes - Plan View


Standard configuration for unit access is on the right-hand side, when looking into the unit intake in the direction of airflow.

C:\Users\uriel.quiroz\Grupo 4HG\PDC Aplicaciones - Sist. De Ventilacion - Sist. De Ventilacion\GREENHECK\Jobs\PC-GH-2203-358 KukaHome Parque Industrial-R1.gfcj
CAPS 4.38.1089 Generated by: uriel.quiroz@proveedora.mx Page 35 of 106
Printed Date: 06/07/2022
Job: PC-GH-2203-358 KukaHome Parque Industrial-R1
Mark: AWU 01-22
Model: MSX-130-H38

END VIEW
95.528

40.000
SUPPLY
DUCT

20.600

38.635 40.000

FOOTPRINT VIEW
68.750
CURB LENGTH
RECOMMENDED

92.000
CURB WIDTH
RECOMMENDED

Notes - Footprint View


Minimum Roof Opening: The minimum roof opening size is the illustrated duct diameter plus 0.25 in. on all sides. For example: If the
duct size is 14 x 14 in. square, the minimum roof opening size is 14.5 x 14.5 in. square.
Maximum Roof Opening: There must be a minimum perimeter of 1.75 in. between the roof opening and the roof curb. For example: If
the roof curb is 75 x 30 in. square, the maximum roof opening is 71.5 x 26.5 in. inches square.
The weatherhood and filter sections of the make-up air unit extend beyond the curb. This is by design, to prevent water infiltration.

C:\Users\uriel.quiroz\Grupo 4HG\PDC Aplicaciones - Sist. De Ventilacion - Sist. De Ventilacion\GREENHECK\Jobs\PC-GH-2203-358 KukaHome Parque Industrial-R1.gfcj
CAPS 4.38.1089 Generated by: uriel.quiroz@proveedora.mx Page 36 of 106
Printed Date: 06/07/2022
Job: PC-GH-2203-358 KukaHome Parque Industrial-R1
Mark: AWU 01-22
Model: MSX-130-H38

Electrical Connections
69.500

15.000

ELECTRICAL
CONNECTION

C:\Users\uriel.quiroz\Grupo 4HG\PDC Aplicaciones - Sist. De Ventilacion - Sist. De Ventilacion\GREENHECK\Jobs\PC-GH-2203-358 KukaHome Parque Industrial-R1.gfcj
CAPS 4.38.1089 Generated by: uriel.quiroz@proveedora.mx Page 37 of 106
Printed Date: 06/07/2022
Job: PC-GH-2203-358 KukaHome Parque Industrial-R1
Mark: AWU 01-22
Model: MSX-130-H38

Clearance Specifications
Recommended Minimum Combustible Clearances
Floor (in.) Top (in.) Sides (in.) Ends (in.)
Insulated Units 0 0 0 0
Non-Insulated Units 0 6 6 6

Notes - Combustible Clearances


Clearance to combustibles is defined as the minimum distance required between the heating source and the adjacent combustible
surfaces to ensure the adjacent surface's temperature does not exceed 90 F above the ambient temperature.

Recommended Minimum Service Clearances


Housing 32 and less (in.) Housing 35 and higher (in.)
42 on the controls side of the unit 48 on the controls side of the unit

Notes - Service Clearances


To ensure ample space for component removal (evaporative cooling media, coils, filters, etc.), service clearances should be 6 in. wider
than the width of the module itself.

C:\Users\uriel.quiroz\Grupo 4HG\PDC Aplicaciones - Sist. De Ventilacion - Sist. De Ventilacion\GREENHECK\Jobs\PC-GH-2203-358 KukaHome Parque Industrial-R1.gfcj
CAPS 4.38.1089 Generated by: uriel.quiroz@proveedora.mx Page 38 of 106
Printed Date: 06/07/2022
Job: PC-GH-2203-358 KukaHome Parque Industrial-R1
Mark: AWU 01-22
Model: MSX-130-H38

Wiring Diagram
DS1
L1 T1 ST1 O.L.
MAIN POWER
TO UNIT
460V
L2
L3
T2
T3
L1
L2
T1
T2
M1 GREENHECK
Building Value in Air.
L3 T3 SUPPLY FAN
GROUND MOTOR
Wiring Diagram Code:

111 112 GN00N602A001D20NU15


CAUTION
UNIT SHALL BE GROUNDED IN ACCORDANCE WITH N.E.C.
POWER MUST BE OFF WHILE SERVICING.
NOTES
USE COPPER CONDUCTORS ONLY
(NEUTRAL) 60° C FOR TERMINALS RATED LESS THAN 100 AMPS.
131 75° C FOR TERMINALS RATED 100 AMPS OR MORE.
EVAP PUMP(S) POWER FIELD CONTROL WIRING RESISTANCE SHOULD
(115 VAC BY OTHERS) P1 NOT EXCEED 0.75 OHM.
RC
132 116 FIELD WIRED
(HOT) 11 14 EVAP PUMP(S) FACTORY SUPPLIED AND WIRED
FIELD CONNECTED

WIRE COLOR CODE


BK BLACK BL BLUE BR BROWN
GY GRAY LT BL LIGHT BLUE O ORANGE
PK PINK PR PURPLE R RED
W WHITE Y YELLOW

LEGEND
DS1 MAIN DISCONNECT SWITCH
TR1
FSC FIRE SYSTEM CONTACT
FU# FUSE
24V M# MOTOR
R C OL# MOTOR OVERLOAD
P# EVAP PUMP
RC COOL RELAY
RF SUPPLY FAN RELAY
S2 FAN SWITCH
S4 HEAT AND COOL SWITCH
ST# MOTOR STARTER
TR# TRANSFORMER
TS5 INLET AIR SENSOR - COOL
JUMPER = COOL : DIFFERENTIAL = 2
S2 FSC ST1 O.L.
G 5 RF SUPPLY FAN RELAY
95 96 A2 A1

RF
ST1 SUPPLY FAN
11 14 A2 A1

(OA-SENSOR IS FIELD CONNECTED


OA-SENSOR INTO THE CONTROL CENTER.)
24 VAC SENSOR COM THERMOSTAT CONTROLLER(S)
THERMOSTAT(S) TS5

S4 ST1 TS5
Y1 RC COOLING
13 14 COM NO A2 A1

Template Drawing: U15 DOC NUMBER: ---- REV: ----

Manufacturer reserves the right to change, modify, or improve this product at anytime

C:\Users\uriel.quiroz\Grupo 4HG\PDC Aplicaciones - Sist. De Ventilacion - Sist. De Ventilacion\GREENHECK\Jobs\PC-GH-2203-358 KukaHome Parque Industrial-R1.gfcj
CAPS 4.38.1089 Generated by: uriel.quiroz@proveedora.mx Page 39 of 106
Printed Date: 06/07/2022
Job: PC-GH-2203-358 KukaHome Parque Industrial-R1
Mark: AWU 01-22
Model: MSX-130-H38

Dry Corner Weights


426 lb 435 lb 409 lb 414 lb

426 lb 435 lb 465 lb 471 lb

Wet Corner Weights


683 lb 715 lb 409 lb 414 lb

683 lb 715 lb 465 lb 471 lb

Notes
Estimated corner weights are shown looking down on unit and airflow from left to right. Weights are applied at the base of the unit.
Evaporative cooling section shown separately due to calculation of dry and wet corner weights. Images not drawn to scale.

C:\Users\uriel.quiroz\Grupo 4HG\PDC Aplicaciones - Sist. De Ventilacion - Sist. De Ventilacion\GREENHECK\Jobs\PC-GH-2203-358 KukaHome Parque Industrial-R1.gfcj
CAPS 4.38.1089 Generated by: uriel.quiroz@proveedora.mx Page 40 of 106
Printed Date: 06/07/2022
Job: PC-GH-2203-358 KukaHome Parque Industrial-R1
Mark: AWU 01-22
Model: MSX-130-H38

SEQUENCE OF OPERATIONS

Unit Controls
The unit shall be provided from the factory with:
• 24VAC Transformer
• Terminal Strip
Field Provided Control Requirements
The following field provided control signals must be provided for proper operation of the unit (Reference the unit
wiring diagram for additional information):
• Supply fan enable – Contact closure between R and G (24VAC)
• Cooling enable – Contact closure between R and Y1 (24VAC) *Factory installed jumper allows heating to be
enabled automatically by outside air temperature - remove jumper for field provided control.
Unit Start-Up Sequence
• Supply Fan Enable Is Received
• Supply Fan Is Enabled
Cooling Control
A cooling enable signal must be present and the supply fan must be enabled before the unit will enable cooling.
Cooling Inlet Air Sensor (Cooling Lockout)
The cooling will be locked out when the outside air temperature is below the cooling inlet air sensor set point
(typical 80 F, adj.)
Evaporative Cooling (Recirculating Pump)
When cooling is enabled the pump recirculates water from the sump over the evaporative cooling media and a
float valve maintains the water level in the sump. Supply and drain valves must be field supplied and installed.

C:\Users\uriel.quiroz\Grupo 4HG\PDC Aplicaciones - Sist. De Ventilacion - Sist. De Ventilacion\GREENHECK\Jobs\PC-GH-2203-358 KukaHome Parque Industrial-R1.gfcj
CAPS 4.38.1089 Generated by: uriel.quiroz@proveedora.mx Page 41 of 106
Printed Date: 06/07/2022
Job: PC-GH-2203-358 KukaHome Parque Industrial-R1
Mark: AWU 01-22
Model: MSX-130-H38

Warranty Statement for Make-Up Air


Unit Warranty
Greenheck warrants the equipment to be free from defects in material and workmanship for a period of 1 year (standard) from the
shipment date.

Warranty Notes
Any component which proves defective during the warranty period will be repaired or replaced at Greenheck’s sole option when
returned to our factory, transportation prepaid. All warranties do not include labor costs associated with troubleshooting, removal, or
installation. Greenheck will not be liable for any consequential, punitive, or incidental damages resulting from use, repair, or operation
of any Greenheck product. These warranties are exclusive and are in lieu of all other warranties, whether written, oral, or implied,
including the warranty of merchantability and the warranty of fitness for a particular purpose. No person (including any agent or
salesperson) has authority to expand Seller's obligation beyond the terms of this warranty, or to state that the performance of the
product is other than that published by Seller.

As a result of our commitment to continuous improvement, Greenheck reserves the right to change specifications without notice.

Tempered Air Products (TAP) Statement 2018


C:\Users\uriel.quiroz\Grupo 4HG\PDC Aplicaciones - Sist. De Ventilacion - Sist. De Ventilacion\GREENHECK\Jobs\PC-GH-2203-358 KukaHome Parque Industrial-R1.gfcj
CAPS 4.38.1089 Generated by: uriel.quiroz@proveedora.mx Page 42 of 106
Printed Date: 06/07/2022
Job: PC-GH-2203-358 KukaHome Parque Industrial-R1
Mark: AWU 23-38
Model: MSX-136-H42-II

MSX-136-H42-II
Unit Performance
Design Conditions
Summer
Elevation (ft) Winter (°F) Supply (CFM) Outdoor Air (CFM)
DB (°F) WB (°F)
1,690 100.7 80.1 39.8 42,800 42,800

Unit Specifications
Qty Weight (lb) Cooling Type Heating Type Unit Installation Unit ETL Listing
15 4,545 (+/- 5%) Direct Evaporative None Outdoor/Indoor UL / cUL 1995

Configuration
Unit Orientation Unit Configuration Outdoor Air Intake Return Air Intake Supply Air Discharge
Constant Volume 100%
Horizontal End - End
OA

Cooling Specifications
Media Required Performance (DB/WB)
Type Cooling Media
Depth (in.) Flow (GPM) EAT (°F) LAT (°F)
Direct Evaporative CELdek 12 3 100.7 / 80.1 82.3 / 80.1

Air Performance
Total Fan
External SP Total SP Operating
Type Volume RPM
(in. wg) (in. wg) Power (hp) Qty Type Size (in.) Drive-Type
(CFM)
Supply 42,800 1.4 1.983 502 39.94 1 Forward Curve 36 Belt-Drive

Motor Specifications
Motor Qty Size (HP) Enclosure Efficiency RPM
Supply Fan Motor 1 40 ODP NEMA Premium 1725

Electrical Specifications
Power Supply Rating (V/C/P) MCA (A) MOP (A) SCCR
Unit 460/60/3 65.2 110 5kA

C:\Users\uriel.quiroz\Grupo 4HG\PDC Aplicaciones - Sist. De Ventilacion - Sist. De Ventilacion\GREENHECK\Jobs\PC-GH-2203-358 KukaHome Parque Industrial-R1.gfcj
CAPS 4.38.1089 Generated by: uriel.quiroz@proveedora.mx Page 43 of 106
Printed Date: 06/07/2022
Job: PC-GH-2203-358 KukaHome Parque Industrial-R1
Mark: AWU 23-38
Model: MSX-136-H42-II

CONSTRUCTION FEATURES AND ACCESSORIES


Unit Accessories
Unit Installation - Outdoor Std Factory Installed, Lockable, NEMA 3R Disconnect Std
Unit Construction - Single Wall X Weatherhood - Louvered with aluminum mesh filters X
Wall Insulation Supply Air Filters
Base Insulation - 1in. fiberglass - entire unit base pan Std Outdoor Air Inlet Damper
Paneled Bottom - Sheet metal liner for base insulation Supply Air Outlet Damper
Corrosion Resistant Fasteners Std Return Air Damper
Access and Connections - Right side when facing intake X Diffuser
Service Access - Hinged access doors X Roof Curb
Unit Finish - G90 Galvanized X Combination Curb
Finish Color Electrofin Coil Coating
Supply Fan - Belt-drive, forward-curved X Fan Bearing Extended Lube Lines
Supply Fan and Motor Vibration isolation - Neoprene X Inlet Damper Module
Controls Spare Belts
Unit Controls - Terminal strip X Spare Filters
Remote Panel Motor with Shaft Grounding
BMS Communication Service Outlet
BMS Protocol Service Lights
Temperature Control Evaporative Cooling Accessories
Supply Fan Control Evap Controls - Recirculating Pump X
Unoccupied Mode (Night Setback) Evap Valves (Ship loose)
Control Accessories Louvered intake provided with 2" aluminum mesh filters X
Remote display Warranty Options
Heating Inlet Air Sensor Unit Warranty - 1 Year X
Cooling Inlet Air Sensor X 5 Year Compressor Warranty
Dirty Filter Switch
Fire Stat Type III (Ships loose)
120V/24V Smoke Detector (Ships loose) Standard Option Std
Inlet Damper End Switch Not Included
External Cooling Lockout Relay Included X
Freeze Protection (Supply Air Low Limit)
Auxiliary Supply Starter Contacts
Auxiliary Exhaust Starter Contacts
Heating Coil Freeze Protection
Airflow Proving Monitoring Contact

Notes
Evap cooler pump requires a separate field provided 115V power connection
Evaporative cooler section ships separate and requires field installation.

C:\Users\uriel.quiroz\Grupo 4HG\PDC Aplicaciones - Sist. De Ventilacion - Sist. De Ventilacion\GREENHECK\Jobs\PC-GH-2203-358 KukaHome Parque Industrial-R1.gfcj
CAPS 4.38.1089 Generated by: uriel.quiroz@proveedora.mx Page 44 of 106
Printed Date: 06/07/2022
Job: PC-GH-2203-358 KukaHome Parque Industrial-R1
Mark: AWU 23-38
Model: MSX-136-H42-II

Fan Charts And Performance


Supply Fan Performance
Motor Fan
Total Volume External SP Total SP Operating
RPM Size
(CFM) (in. wg) (in. wg) Power (hp) Qty Qty Type Drive-Type
(HP)
42,800 1.4 1.983 502 39.94 1 40 1 Forward Curve Belt

Pressure Drop (in. wg)


Diffuser Weatherhood Filter Damper Cooling Heating External Total
- - - - 0.583 - 1.4 1.983

Sound Performance in Accordance with AMCA


Sound Power by Octave Band
Lwa dBA Sones
62.5 125 250 500 1000 2000 4000 8000
99 101 101 91 89 90 83 78 97 86 56

Supply Fan

C:\Users\uriel.quiroz\Grupo 4HG\PDC Aplicaciones - Sist. De Ventilacion - Sist. De Ventilacion\GREENHECK\Jobs\PC-GH-2203-358 KukaHome Parque Industrial-R1.gfcj
CAPS 4.38.1089 Generated by: uriel.quiroz@proveedora.mx Page 45 of 106
Printed Date: 06/07/2022
Job: PC-GH-2203-358 KukaHome Parque Industrial-R1
Mark: AWU 23-38
Model: MSX-136-H42-II

Cooling Specifications
Cooling Performance
Media Required Performance (DB/WB)
Type Cooling Media
Depth (in.) Flow (GPM) EAT (°F) LAT (°F)
Direct Evaporative CELdek 12 3 100.7 / 80.1 82.3 / 80.1

Unit Details
Stainless steel sump and media casing Ball valve for flow rate adjustment
Supply line, drain line and supply line drain valves must be field Recirculating pump(s) provided by factory
provided by others
Valve provided for bleed-off rate adjustment

Recirc. Pump Evap Control

Evaporative Cooling Connections

SUPPLY CONNECTION
(FIELD PROVIDED)
LOCATED IN FRONT
OF UNIT

3.252

1.627

19.020

DRAIN
31.020

OVERFLOW
C:\Users\uriel.quiroz\Grupo 4HG\PDC Aplicaciones - Sist. De Ventilacion - Sist. De Ventilacion\GREENHECK\Jobs\PC-GH-2203-358 KukaHome Parque Industrial-R1.gfcj
CAPS 4.38.1089 Generated by: uriel.quiroz@proveedora.mx Page 46 of 106
Printed Date: 06/07/2022
Job: PC-GH-2203-358 KukaHome Parque Industrial-R1
Mark: AWU 23-38
Model: MSX-136-H42-II

ELEVATION VIEW
192.011

116.510 75.501

67.859

Notes - Elevation View


Standard configuration for unit access is on the right-hand side, when looking into the unit intake in the direction of airflow.
Order of unit sections is from intake of unit to discharge of unit.
Sections included on this unit: Cooling Section, Blower Section

PLAN VIEW
INTAKE SIDE
EVAP COOLING BLOWER
116.510 75.501

ACCESS SIDE
100.348

INTAKE SIDE

ACCESS SIDE -
CONTROL CENTER

Notes - Plan View


Standard configuration for unit access is on the right-hand side, when looking into the unit intake in the direction of airflow.

C:\Users\uriel.quiroz\Grupo 4HG\PDC Aplicaciones - Sist. De Ventilacion - Sist. De Ventilacion\GREENHECK\Jobs\PC-GH-2203-358 KukaHome Parque Industrial-R1.gfcj
CAPS 4.38.1089 Generated by: uriel.quiroz@proveedora.mx Page 47 of 106
Printed Date: 06/07/2022
Job: PC-GH-2203-358 KukaHome Parque Industrial-R1
Mark: AWU 23-38
Model: MSX-136-H42-II

END VIEW
100.348

46.000
SUPPLY
DUCT

19.686

35.038 46.000

FOOTPRINT VIEW
72.750
CURB LENGTH
RECOMMENDED

96.750
CURB WIDTH
RECOMMENDED

Notes - Footprint View


Minimum Roof Opening: The minimum roof opening size is the illustrated duct diameter plus 0.25 in. on all sides. For example: If the
duct size is 14 x 14 in. square, the minimum roof opening size is 14.5 x 14.5 in. square.
Maximum Roof Opening: There must be a minimum perimeter of 1.75 in. between the roof opening and the roof curb. For example: If
the roof curb is 75 x 30 in. square, the maximum roof opening is 71.5 x 26.5 in. inches square.
The weatherhood and filter sections of the make-up air unit extend beyond the curb. This is by design, to prevent water infiltration.

C:\Users\uriel.quiroz\Grupo 4HG\PDC Aplicaciones - Sist. De Ventilacion - Sist. De Ventilacion\GREENHECK\Jobs\PC-GH-2203-358 KukaHome Parque Industrial-R1.gfcj
CAPS 4.38.1089 Generated by: uriel.quiroz@proveedora.mx Page 48 of 106
Printed Date: 06/07/2022
Job: PC-GH-2203-358 KukaHome Parque Industrial-R1
Mark: AWU 23-38
Model: MSX-136-H42-II

Electrical Connections
73.000

15.000

ELECTRICAL
CONNECTION

C:\Users\uriel.quiroz\Grupo 4HG\PDC Aplicaciones - Sist. De Ventilacion - Sist. De Ventilacion\GREENHECK\Jobs\PC-GH-2203-358 KukaHome Parque Industrial-R1.gfcj
CAPS 4.38.1089 Generated by: uriel.quiroz@proveedora.mx Page 49 of 106
Printed Date: 06/07/2022
Job: PC-GH-2203-358 KukaHome Parque Industrial-R1
Mark: AWU 23-38
Model: MSX-136-H42-II

Clearance Specifications
Recommended Minimum Combustible Clearances
Floor (in.) Top (in.) Sides (in.) Ends (in.)
Insulated Units 0 0 0 0
Non-Insulated Units 0 6 6 6

Notes - Combustible Clearances


Clearance to combustibles is defined as the minimum distance required between the heating source and the adjacent combustible
surfaces to ensure the adjacent surface's temperature does not exceed 90 F above the ambient temperature.

Recommended Minimum Service Clearances


Housing 32 and less (in.) Housing 35 and higher (in.)
42 on the controls side of the unit 48 on the controls side of the unit

Notes - Service Clearances


To ensure ample space for component removal (evaporative cooling media, coils, filters, etc.), service clearances should be 6 in. wider
than the width of the module itself.

C:\Users\uriel.quiroz\Grupo 4HG\PDC Aplicaciones - Sist. De Ventilacion - Sist. De Ventilacion\GREENHECK\Jobs\PC-GH-2203-358 KukaHome Parque Industrial-R1.gfcj
CAPS 4.38.1089 Generated by: uriel.quiroz@proveedora.mx Page 50 of 106
Printed Date: 06/07/2022
Job: PC-GH-2203-358 KukaHome Parque Industrial-R1
Mark: AWU 23-38
Model: MSX-136-H42-II

Wiring Diagram
DS1
L1 T1 FU1 ST1 O.L.
MAIN POWER
TO UNIT
460V
L2
L3
T2
T3
L1
L2
T1
T2
M1 GREENHECK
Building Value in Air.
FU6 L3 T3 SUPPLY FAN
GROUND 15A,600V MOTOR
CLASS J Wiring Diagram Code:

111 112 GN00N603A001D20NU15


CAUTION
UNIT SHALL BE GROUNDED IN ACCORDANCE WITH N.E.C.
POWER MUST BE OFF WHILE SERVICING.
NOTES
USE COPPER CONDUCTORS ONLY
(NEUTRAL) 60° C FOR TERMINALS RATED LESS THAN 100 AMPS.
131 75° C FOR TERMINALS RATED 100 AMPS OR MORE.
EVAP PUMP(S) POWER FIELD CONTROL WIRING RESISTANCE SHOULD
(115 VAC BY OTHERS) P1 NOT EXCEED 0.75 OHM.
RC
132 116 FIELD WIRED
(HOT) 11 14 EVAP PUMP(S) FACTORY SUPPLIED AND WIRED
FIELD CONNECTED

WIRE COLOR CODE


BK BLACK BL BLUE BR BROWN
GY GRAY LT BL LIGHT BLUE O ORANGE
PK PINK PR PURPLE R RED
W WHITE Y YELLOW

LEGEND
DS1 MAIN DISCONNECT SWITCH
TR1
FSC FIRE SYSTEM CONTACT
FU# FUSE
24V M# MOTOR
R C OL# MOTOR OVERLOAD
P# EVAP PUMP
RC COOL RELAY
RF SUPPLY FAN RELAY
S2 FAN SWITCH
S4 HEAT AND COOL SWITCH
ST# MOTOR STARTER
TR# TRANSFORMER
TS5 INLET AIR SENSOR - COOL
JUMPER = COOL : DIFFERENTIAL = 2
S2 FSC ST1 O.L.
G 5 RF SUPPLY FAN RELAY
95 96 A2 A1

RF
ST1 SUPPLY FAN
11 14 A2 A1

(OA-SENSOR IS FIELD CONNECTED


OA-SENSOR INTO THE CONTROL CENTER.)
24 VAC SENSOR COM THERMOSTAT CONTROLLER(S)
THERMOSTAT(S) TS5

S4 ST1 TS5
Y1 RC COOLING
13 14 COM NO A2 A1

Template Drawing: U15 DOC NUMBER: ---- REV: ----

Manufacturer reserves the right to change, modify, or improve this product at anytime

C:\Users\uriel.quiroz\Grupo 4HG\PDC Aplicaciones - Sist. De Ventilacion - Sist. De Ventilacion\GREENHECK\Jobs\PC-GH-2203-358 KukaHome Parque Industrial-R1.gfcj
CAPS 4.38.1089 Generated by: uriel.quiroz@proveedora.mx Page 51 of 106
Printed Date: 06/07/2022
Job: PC-GH-2203-358 KukaHome Parque Industrial-R1
Mark: AWU 23-38
Model: MSX-136-H42-II

Dry Corner Weights


603 lb 598 lb 498 lb 463 lb

605 lb 599 lb 670 lb 623 lb

Wet Corner Weights


921 lb 902 lb 498 lb 463 lb

923 lb 903 lb 670 lb 623 lb

Notes
Estimated corner weights are shown looking down on unit and airflow from left to right. Weights are applied at the base of the unit.
Evaporative cooling section shown separately due to calculation of dry and wet corner weights. Images not drawn to scale.

C:\Users\uriel.quiroz\Grupo 4HG\PDC Aplicaciones - Sist. De Ventilacion - Sist. De Ventilacion\GREENHECK\Jobs\PC-GH-2203-358 KukaHome Parque Industrial-R1.gfcj
CAPS 4.38.1089 Generated by: uriel.quiroz@proveedora.mx Page 52 of 106
Printed Date: 06/07/2022
Job: PC-GH-2203-358 KukaHome Parque Industrial-R1
Mark: AWU 23-38
Model: MSX-136-H42-II

SEQUENCE OF OPERATIONS

Unit Controls
The unit shall be provided from the factory with:
• 24VAC Transformer
• Terminal Strip
Field Provided Control Requirements
The following field provided control signals must be provided for proper operation of the unit (Reference the unit
wiring diagram for additional information):
• Supply fan enable – Contact closure between R and G (24VAC)
• Cooling enable – Contact closure between R and Y1 (24VAC) *Factory installed jumper allows heating to be
enabled automatically by outside air temperature - remove jumper for field provided control.
Unit Start-Up Sequence
• Supply Fan Enable Is Received
• Supply Fan Is Enabled
Cooling Control
A cooling enable signal must be present and the supply fan must be enabled before the unit will enable cooling.
Cooling Inlet Air Sensor (Cooling Lockout)
The cooling will be locked out when the outside air temperature is below the cooling inlet air sensor set point
(typical 80 F, adj.)
Evaporative Cooling (Recirculating Pump)
When cooling is enabled the pump recirculates water from the sump over the evaporative cooling media and a
float valve maintains the water level in the sump. Supply and drain valves must be field supplied and installed.

C:\Users\uriel.quiroz\Grupo 4HG\PDC Aplicaciones - Sist. De Ventilacion - Sist. De Ventilacion\GREENHECK\Jobs\PC-GH-2203-358 KukaHome Parque Industrial-R1.gfcj
CAPS 4.38.1089 Generated by: uriel.quiroz@proveedora.mx Page 53 of 106
Printed Date: 06/07/2022
Job: PC-GH-2203-358 KukaHome Parque Industrial-R1
Mark: AWU 23-38
Model: MSX-136-H42-II

Warranty Statement for Make-Up Air


Unit Warranty
Greenheck warrants the equipment to be free from defects in material and workmanship for a period of 1 year (standard) from the
shipment date.

Warranty Notes
Any component which proves defective during the warranty period will be repaired or replaced at Greenheck’s sole option when
returned to our factory, transportation prepaid. All warranties do not include labor costs associated with troubleshooting, removal, or
installation. Greenheck will not be liable for any consequential, punitive, or incidental damages resulting from use, repair, or operation
of any Greenheck product. These warranties are exclusive and are in lieu of all other warranties, whether written, oral, or implied,
including the warranty of merchantability and the warranty of fitness for a particular purpose. No person (including any agent or
salesperson) has authority to expand Seller's obligation beyond the terms of this warranty, or to state that the performance of the
product is other than that published by Seller.

As a result of our commitment to continuous improvement, Greenheck reserves the right to change specifications without notice.

Tempered Air Products (TAP) Statement 2018


C:\Users\uriel.quiroz\Grupo 4HG\PDC Aplicaciones - Sist. De Ventilacion - Sist. De Ventilacion\GREENHECK\Jobs\PC-GH-2203-358 KukaHome Parque Industrial-R1.gfcj
CAPS 4.38.1089 Generated by: uriel.quiroz@proveedora.mx Page 54 of 106
Printed Date: 06/07/2022
Job: PC-GH-2203-358 KukaHome Parque Industrial-R1
Mark: LVR
Model: ESD-403

ESD-403 4 in. Frame


APPLICATION & DESIGN
ESD-403 is a weather louver designed to protect air intake and exhaust openings in building exterior walls. Design incorporates a drainable head
member and stationary horizontal blades to channel water to the jambs which guides the water through vertical downspouts for escape at the sill. The
ESD-403 is an extremely efficient louver with AMCA LICENSED PERFORMANCE DATA enabling designers to select and apply with confidence.

PRODUCT DETAILS
Frame:
Frame Type:
4 in. x 0.081 in. Frame Thickness
Channel
Internal View
Blades: 0.081 in. Fixed Blade Thickness
Material: Aluminum
Sizing: 1/4 Inch Under
Shape: Rectangular
Construction: Mechanically Fastened

OPTIONS & ACCESSORIES


Finish: Mill
Bird Screen: 0.75 in. x 0.05 in., Flat Expanded Aluminum, Internal,
Mill Finish
Union Label: No Preference
Warranty: 1 year Standard Product Warranty

SUMMARY

FREE AREA FREE AREA


ID # TAG QTY. W (in.) H (in.) SECT. WIDE SECT. HIGH SHIP SECT.
(ft2) (%)
1-1 135 71 118 31.24 53.7 1 1 135

PERFORMANCE

PRESSURE DROP FREE AREA


ID # TAG APPLICATION VOLUME (CFM) BPWP (ft/min)
(in. wg) VELOCITY (ft/min)
1-1 20,198 0.07 642 1,007
Intake
**Calculated pressure drop does not include the effects of screens, filters or other accessories
Total Louver Qty: 135 Total Weight (lb): 27,023 Louver Area (ft2): 7,854
Total Ship Sect.: 135
**Weight shown is an estimate only based on the default base product configuration without options or accessories.
Larger openings may require field assembly of multiple louver panels to make up the overall opening size. Individual louver panels are designed to withstand windloads up to a maximum of 25
PSF (size and configuration dependent). Design, materials and installation of structural reinforcement required to adequately support large sections or multiple section assemblies within a large
opening are not provided by Greenheck. Options and accessories including, but not limited to, screens, filter racks, louver doors, and blankoff panels are not subject to structural analysis unless
indicated otherwise by Greenheck. Unless specifically indicated, the following are NOT included in the quote provided: structural steel, installation hardware (anchors, angle clips, continuous
angles, shims, fasteners, inserts, backer rod and sealant), field measuring and/or installation, miscellaneous flashing, trim or enclosures, blank off panels, mullion covers or mullion hardware,
hinged frames or removable subframes, custom bird/insect screen, 3-coat, metallic and/or exotic paint finishes, bituminous paints for unlike metals, any applicable taxes, stamped and sealed
structural calculations seismic calculations or job specific engineered submittal drawings.

C:\Users\uriel.quiroz\Grupo 4HG\PDC Aplicaciones - Sist. De Ventilacion - Sist. De Ventilacion\GREENHECK\Jobs\PC-GH-2203-358 KukaHome Parque Industrial-R1.gfcj
CAPS 4.38.1089 Generated by: uriel.quiroz@proveedora.mx Page 55 of 106
Printed Date: 06/07/2022
Job: PC-GH-2203-358 KukaHome Parque Industrial-R1
Mark: LVR
Model: ESD-403

AMCA

Greenheck Fan Corporation certifies that the louver shown herein is licensed to bear the AMCA Seal. The ratings
shown are based on tests and procedures performed in accordance with AMCA Publication 511 and comply with the
requirements of the AMCA Certified Ratings Program. The AMCA Certified Ratings Seal applies to air performance and
water penetration ratings.

C:\Users\uriel.quiroz\Grupo 4HG\PDC Aplicaciones - Sist. De Ventilacion - Sist. De Ventilacion\GREENHECK\Jobs\PC-GH-2203-358 KukaHome Parque Industrial-R1.gfcj
CAPS 4.38.1089 Generated by: uriel.quiroz@proveedora.mx Page 56 of 106
Printed Date: 06/07/2022
Job: PC-GH-2203-358 KukaHome Parque Industrial-R1
Mark: LVRR
Model: ESD-403

ESD-403 4 in. Frame


APPLICATION & DESIGN
ESD-403 is a weather louver designed to protect air intake and exhaust openings in building exterior walls. Design incorporates a drainable head
member and stationary horizontal blades to channel water to the jambs which guides the water through vertical downspouts for escape at the sill. The
ESD-403 is an extremely efficient louver with AMCA LICENSED PERFORMANCE DATA enabling designers to select and apply with confidence.

PRODUCT DETAILS
Frame:
Frame Type:
4 in. x 0.081 in. Frame Thickness
Channel
Internal View
Blades: 0.081 in. Fixed Blade Thickness
Material: Aluminum
Sizing: 1/4 Inch Under
Shape: Rectangular
Construction: Mechanically Fastened

OPTIONS & ACCESSORIES


Finish: Mill
Bird Screen: 0.75 in. x 0.05 in., Flat Expanded Aluminum, Internal,
Mill Finish
Union Label: No Preference
Warranty: 1 year Standard Product Warranty

SUMMARY

FREE AREA FREE AREA


ID # TAG QTY. W (in.) H (in.) SECT. WIDE SECT. HIGH SHIP SECT.
(ft2) (%)
2-1 82 72 48 11.98 49.9 1 1 82

PERFORMANCE

PRESSURE DROP FREE AREA


ID # TAG APPLICATION VOLUME (CFM) BPWP (ft/min)
(in. wg) VELOCITY (ft/min)
2-1 8,186 0.08 675 1,007
Intake
**Calculated pressure drop does not include the effects of screens, filters or other accessories
Total Louver Qty: 82 Total Weight (lb): 6,750 Louver Area (ft2): 1,968
Total Ship Sect.: 82
**Weight shown is an estimate only based on the default base product configuration without options or accessories.
Larger openings may require field assembly of multiple louver panels to make up the overall opening size. Individual louver panels are designed to withstand windloads up to a maximum of 25
PSF (size and configuration dependent). Design, materials and installation of structural reinforcement required to adequately support large sections or multiple section assemblies within a large
opening are not provided by Greenheck. Options and accessories including, but not limited to, screens, filter racks, louver doors, and blankoff panels are not subject to structural analysis unless
indicated otherwise by Greenheck. Unless specifically indicated, the following are NOT included in the quote provided: structural steel, installation hardware (anchors, angle clips, continuous
angles, shims, fasteners, inserts, backer rod and sealant), field measuring and/or installation, miscellaneous flashing, trim or enclosures, blank off panels, mullion covers or mullion hardware,
hinged frames or removable subframes, custom bird/insect screen, 3-coat, metallic and/or exotic paint finishes, bituminous paints for unlike metals, any applicable taxes, stamped and sealed
structural calculations seismic calculations or job specific engineered submittal drawings.

C:\Users\uriel.quiroz\Grupo 4HG\PDC Aplicaciones - Sist. De Ventilacion - Sist. De Ventilacion\GREENHECK\Jobs\PC-GH-2203-358 KukaHome Parque Industrial-R1.gfcj
CAPS 4.38.1089 Generated by: uriel.quiroz@proveedora.mx Page 57 of 106
Printed Date: 06/07/2022
Job: PC-GH-2203-358 KukaHome Parque Industrial-R1
Mark: LVRR
Model: ESD-403

AMCA

Greenheck Fan Corporation certifies that the louver shown herein is licensed to bear the AMCA Seal. The ratings
shown are based on tests and procedures performed in accordance with AMCA Publication 511 and comply with the
requirements of the AMCA Certified Ratings Program. The AMCA Certified Ratings Seal applies to air performance and
water penetration ratings.

C:\Users\uriel.quiroz\Grupo 4HG\PDC Aplicaciones - Sist. De Ventilacion - Sist. De Ventilacion\GREENHECK\Jobs\PC-GH-2203-358 KukaHome Parque Industrial-R1.gfcj
CAPS 4.38.1089 Generated by: uriel.quiroz@proveedora.mx Page 58 of 106
Printed Date: 06/07/2022
Job: PC-GH-2203-358 KukaHome Parque Industrial-R1
Mark: BF 138-161
Model: DS-6-20-170HV

Model: DS-6-20-170HV 42.0


High Volume, Low Speed Ceiling Fan
3.0

Dimensional
Impeller Diameter (ft) 20
Impeller Diameter (in.) 240
Quantity 24
Weight w/o Acc's (lb) 119
Weight w/ Acc's (lb) 235

Installation Clearances
Minimum Fan Spacing (ft) 60
Clearance to Wall (ft) 30
Blade Tip Clearance (ft) 3
Vertical Blade Clearance (ft) 3
Standby Blade Deflection (in.) 1.7

Performance Per Fan


*Tested Direction of Operation Forward
Actual Volume (CFM) 196,200
Coverage Area (ft2) 21,600
Max Coverage Area (ft2) 21,600
Avg. Air Speed (ft/min) 477
Max Avg. Air Speed (ft/min) 477
Fan RPM 78
Max Fan RPM 78
**CFEI at 40% Speed 2.72
**CFEI at 100% Speed 1.44
**Integrated Efficiency
-
(CFM/W)
Total Sound Pressure (dBA) 52

Fan Operation
Direction of Operation
Forward or Reverse
Capability
Communication Protocol Modbus RTU

Motor
Size (W) 1,100 Notes:
All dimensions shown are in units of in. (unless specified
Voltage/Cycle/Phase 460/60/3
otherwise)
Enclosure IP54 Dimensions shown may vary with fan speed. Consult
installation manual for clearance requirements.
Max Motor RPM 78 dBA – A weighted sound pressure level measured 5 ft off
the ground at 20 ft from the center of the fan – dBA levels
***System FLA (Amps) 3.5 are not licensed by AMCA International
*Cataloged performance data tested using forward
**Standby Power (W) 11 direction of operation per 10 CFR Part 430.
**Input Power (W) 1,398 **Based on 208/60/3 testing per 10 CFR 430
***FLA is based on worst case system voltage and phase
combination

C:\Users\uriel.quiroz\Grupo 4HG\PDC Aplicaciones - Sist. De Ventilacion - Sist. De Ventilacion\GREENHECK\Jobs\PC-GH-2203-358 KukaHome Parque Industrial-R1.gfcj
CAPS 4.38.1089 Generated by: uriel.quiroz@proveedora.mx Page 59 of 106
Printed Date: 06/07/2022
Job: PC-GH-2203-358 KukaHome Parque Industrial-R1
Mark: BF 138-161
Model: DS-6-20-170HV
Model: DS-6-20-170HV
High Volume, Low Speed Ceiling Fan
Tags: BF 138 BF 139 BF 140 BF 141 BF 142 BF 143 BF 144 BF 145 BF 146 BF
147 BF 148 BF 149 BF 150 BF 151 BF 152 BF 153 BF 154 BF 155 BF 156 BF
157 BF 158 BF 159 BF 160 BF 161
Standard Construction Features:
Heavy duty frame with protective finish - Extruded aluminum airfoils - High
efficiency direct drive motor designed for either forward or reverse operation -
Factory mounted and wired variable frequency drive - Factory installed plug and
play wiring - Universal ceiling mount - Heavy duty safety restraint cable - Airfoil
and fan hub retaining systems - AMCA certified for Circulating Fan Performance
Selected Options & Accessories:
6 Blade, Extruded Aluminum Airfoil Kit
Mill Finish, No Color
Aluminum Winglet; Hi-Pro Polyester Finish, Flat Black (044) Color
I-Beam Mounting Kit; Hi-Pro Polyester Finish, Flat Black (044) Color
3.5 ft Drop Length; Hi-Pro Polyester Finish, Flat Black (044) Color
Hub Plate and Impeller Hub; Hi-Pro Polyester Finish, Flat Black (044) Color
Hub Plate Decal with Greenheck Logo
Power Wiring Pigtail, Internal, General, 3 ft of Flexible Power Cord from Unit,
Unstripped Wire
Plug-and-Play Network Communication Wiring Pigtail, Internal, Terminated with
Shielded CAT-5e Splitter (RJ45 Ports)
100 ft of Shielded, Twisted Pair (STP) CAT-5e Control Cable
Fire Alarm Wiring Pigtail, Internal, 2.5 ft from Unit, Terminated with Crimp
Connector
Low-Voltage (24VDC/VAC or 115VAC), Normally Closed Electromechanical Fire
Alarm Relay
Braided Galvanized Steel Safety Cable, 16 ft from Unit
Braided Galvanized Steel Guy Wires, 20 ft from Unit
Cable Clamp Hardware for Safety Cable and Guy Wires
Electrical Warranty: 1 Yr (Standard)
Mechanical Warranty: 10 Yrs (Standard)

C:\Users\uriel.quiroz\Grupo 4HG\PDC Aplicaciones - Sist. De Ventilacion - Sist. De Ventilacion\GREENHECK\Jobs\PC-GH-2203-358 KukaHome Parque Industrial-R1.gfcj
CAPS 4.38.1089 Generated by: uriel.quiroz@proveedora.mx Page 60 of 106
Printed Date: 06/07/2022
Job: PC-GH-2203-358 KukaHome Parque Industrial-R1
Mark: BF 138-161
Model: DS-6-20-170HV

Model: DS-6-20-170HV
High Volume, Low Speed Ceiling Fan

Fan Coverage Data

Zone 1 Zone 2 Zone 3 Zone 4


375+ 230+ 105+ <105
Fan Recommended
FPM Air FPM Air FPM Air FPM Air
Speed Coverage Radius
Speed Speed Speed Speed
(RPM) Per Fan (ft)
Radius Radius Radius Radius
(ft) (ft) (ft) (ft)
Selected 78 38 58 75 90 83
Maximum 78 38 58 75 90 83

C:\Users\uriel.quiroz\Grupo 4HG\PDC Aplicaciones - Sist. De Ventilacion - Sist. De Ventilacion\GREENHECK\Jobs\PC-GH-2203-358 KukaHome Parque Industrial-R1.gfcj
CAPS 4.38.1089 Generated by: uriel.quiroz@proveedora.mx Page 61 of 106
Printed Date: 06/07/2022
Job: PC-GH-2203-358 KukaHome Parque Industrial-R1
Mark: BF 138-161
Model: DS-6-20-170HV

Model: DS-6-20-170HV
High Volume, Low Speed Ceiling Fan

Fan Spacing & Clearances

A - Clearance to Wall (ft) B - Fan Spacing (ft) C - Clearance to Floor (ft)


Minimum 30 60 10

Additional Requirements

1. For NFPA 13 compliance in buildings equipped with sprinklers:


-Fan must be centered approximately between four adjacent sprinklers
-Vertical clearance from fan to sprinkler deflector must be a minimum of 3 ft (36 in.)
-Fan must be interlocked to shut down immediately upon a waterflow alarm from the building's fire alarm system
-Interlock with building's fire alarm system shall be in accordance with the requirements of NFPA 72
2. Avoid installing fan directly below a light source to prevent a strobing effect that can be caused by fan rotation

C:\Users\uriel.quiroz\Grupo 4HG\PDC Aplicaciones - Sist. De Ventilacion - Sist. De Ventilacion\GREENHECK\Jobs\PC-GH-2203-358 KukaHome Parque Industrial-R1.gfcj
CAPS 4.38.1089 Generated by: uriel.quiroz@proveedora.mx Page 62 of 106
Printed Date: 06/07/2022
Job: PC-GH-2203-358 KukaHome Parque Industrial-R1
Mark: BF 138-161
Model: DS-6-20-170HV

Perceived Cooling Effect

Feels 12°F
Cooler

Perceived Cooling Effect Based on ASHRAE 55-2017


Perceived
Coverage Area Operative Relative Metabolic Avg. Air Speed
Clothing Level Cooling
Per Fan (ft2) Temp. (F) Humidity (%) Rate (ft/min)
Effect (F)
0.57 Pants, Short
21,600 77 60 1.7 Walking 477 12
Sleeves

C:\Users\uriel.quiroz\Grupo 4HG\PDC Aplicaciones - Sist. De Ventilacion - Sist. De Ventilacion\GREENHECK\Jobs\PC-GH-2203-358 KukaHome Parque Industrial-R1.gfcj
CAPS 4.38.1089 Generated by: uriel.quiroz@proveedora.mx Page 63 of 106
Printed Date: 06/07/2022
Job: PC-GH-2203-358 KukaHome Parque Industrial-R1
Mark: BF 138-161
Model: DS-6-20-170HV

Payback Analysis

Payback Inputs
Electric Cost (USD/ Heating Cost (USD/
Operating Time Heat Source
KwH) therm)
24 hours/day, 7
0.08 Gas 0.80
days/week

Winter Destratification Energy Savings


Estimated Heating Load Annual Energy Cost HVLS Energy Cost Net Energy Cost
Without HVLS With HVLS Savings (USD) (USD) Savings (USD)
0.0 0.0 0 0 0

Summer Cooling Energy Savings


Estimated Cooling Load Annual Energy Cost HVLS Energy Cost Net Energy Cost
Without HVLS With HVLS Savings (USD) (USD) Savings (USD)
0.0 0.0 0 0 0

Equipment Cost
Estimated HVLS Avoided A/C
Equipment First Cost Equipment Cost Net First Cost (USD)
(USD) (USD)
174,720 0 174,720

Payback
Net Operating
Payback Period
Savings Per Year
(Years)
(USD)
0 0.0

C:\Users\uriel.quiroz\Grupo 4HG\PDC Aplicaciones - Sist. De Ventilacion - Sist. De Ventilacion\GREENHECK\Jobs\PC-GH-2203-358 KukaHome Parque Industrial-R1.gfcj
CAPS 4.38.1089 Generated by: uriel.quiroz@proveedora.mx Page 64 of 106
Printed Date: 06/07/2022
Job: PC-GH-2203-358 KukaHome Parque Industrial-R1
Mark: BF 138-161
Model: DS-6-20-170HV

Model: DS-6-20-170HV
Finish Selection

Selected Frame Finish


Finish Type Hi-Pro Polyester
Mount Finish Color Flat Black (044)
Downtube Finish Color Flat Black (044)
Hub/Hub Plate Finish Color Flat Black (044)
Winglet Finish Color Flat Black (044)

Selected Airfoil Finish


Finish Type Mill
Finish Color None

Available Finish Options (Additional Charges May Apply):

C:\Users\uriel.quiroz\Grupo 4HG\PDC Aplicaciones - Sist. De Ventilacion - Sist. De Ventilacion\GREENHECK\Jobs\PC-GH-2203-358 KukaHome Parque Industrial-R1.gfcj
CAPS 4.38.1089 Generated by: uriel.quiroz@proveedora.mx Page 65 of 106
Printed Date: 06/07/2022
Job: PC-GH-2203-358 KukaHome Parque Industrial-R1
Mark: BF 138-161
Model: DS-6-20-170HV

Model: DS-6-20-170HV
High Volume, Low Speed Ceiling Fan

Mechanical Installation Requirements


Selected Mounting Kit: I-Beam

IMPORTANT: HVLS fans must be mounted to building structure as shown in one


of the mounting details on this page. Other mounting methods are not acceptable
unless approved by Structural Engineer of Record (SEOR). For complete installation
instructions, refer to the installation, operation and maintenance manual (IOM).

IMPORTANT: Failure to install the fan's safety retention cable and guy wires
(if provided) will result in voiding of the fan warranty.

Available Mounting Kits (Additional Charges May Apply):

C:\Users\uriel.quiroz\Grupo 4HG\PDC Aplicaciones - Sist. De Ventilacion - Sist. De Ventilacion\GREENHECK\Jobs\PC-GH-2203-358 KukaHome Parque Industrial-R1.gfcj
CAPS 4.38.1089 Generated by: uriel.quiroz@proveedora.mx Page 66 of 106
Printed Date: 06/07/2022
Job: PC-GH-2203-358 KukaHome Parque Industrial-R1
Mark: BF 138-161
Model: DS-6-20-170HV

Model: DS-6-20-170HV
High Volume, Low Speed Ceiling Fan

Electrical Installation Requirements


IMPORTANT: HVLS fans must be installed with the supplied CAT-5e communication cable or
shielded, twisted pair (STP) CAT-5e (by others) that complies with the following specifications. Cable
must be twisted pair, shielded 26 ga. CAT-5e cable with a drain wire and must be compliant with ISO
11801. Cable must use shielded RJ45 connectors with a soldered drain and wiring configuration must
follow EIA/TIA T568B wiring pinout. Individual CAT-5e cable lengths must not exceed 200 ft. in order
to prevent network communication issues.

POWER WIRING
SHIELDED TWISTED PAIR CAT-5e CONNECTION

TO NEXT FAN POWER SOURCE


(IF APPLICABLE) RED
L3
BLACK
TO CONTROL L2
WHITE
L1
GREEN GROUND

FIRE SYSTEM WIRING (IF APPLICABLE)


DIP SWITCH BANK 3
ON

SUPPLIED FIRE RELAY FIRE ALARM


1 2 3 4 5 6 7 8 CONTROL PANEL

BLACK
YELLOW (NC) RED (+) RED
RED
BLUE (COMMON) WHITE (-) WHITE
DIP SWITCH BANK 2
ON

1 2 3

3 HALL CONNECTION
NOTE:
HALL CABLE PLUG HAS
BUILT-IN ALIGNMENT TAB.
MOTOR CABLE CONNECTION DO NOT FORCE THIS PLUG

POWER 1
GROUND 2
POWER 1
GROUND 2

3 HALL CONNECTION

NOTE: If networking multiple HVLS fans to run using a single control source, additional
wiring and network modification may be required. Please refer to the fans's installation,
operation and maintenance manual (IOM)

C:\Users\uriel.quiroz\Grupo 4HG\PDC Aplicaciones - Sist. De Ventilacion - Sist. De Ventilacion\GREENHECK\Jobs\PC-GH-2203-358 KukaHome Parque Industrial-R1.gfcj
CAPS 4.38.1089 Generated by: uriel.quiroz@proveedora.mx Page 67 of 106
Printed Date: 06/07/2022
Job: PC-GH-2203-358 KukaHome Parque Industrial-R1
Mark: BF 138-161
Model: DS-6-20-170HV

Model: DS-6-20-170HV
High Volume, Low Speed Ceiling Fan

HVLS Fan Compliance


Department of Energy (DOE) 10 CFR Part 430 Compliance
DOE Min. CFEI at Calculated CFEI at DOE Min. CFEI at Calculated CFEI at DOE Min. Efficiency Calculated Efficiency
Compliance
40% Speed 40% Speed 100% Speed 100% Speed (CFM/W) (CFM/W)
1.31 2.72 1.00 1.44 - - Yes

ASHRAE 55-2017 Compliance


Perceived Acceptable Calculated
Operative Relative Metabolic Avg. Air Speed Thermal
Clothing Level Cooling Effect Predicted Mean Predicted Mean Compliance
Temp. (F) Humidity (%) Rate (ft/min) Sensation
(F) Vote (PMV) Vote (PMV)
0.57 Pants, -0.5 ≤ PMV ≤
77 60 1.7 Walking 477 12 -0.44 Neutral Yes
Short Sleeves 0.5

C:\Users\uriel.quiroz\Grupo 4HG\PDC Aplicaciones - Sist. De Ventilacion - Sist. De Ventilacion\GREENHECK\Jobs\PC-GH-2203-358 KukaHome Parque Industrial-R1.gfcj
CAPS 4.38.1089 Generated by: uriel.quiroz@proveedora.mx Page 68 of 106
Printed Date: 06/07/2022
Job: PC-GH-2203-358 KukaHome Parque Industrial-R1
Mark: BF 138-161
Model: DS-6-20-170HV
Assembly Drawing
Type: High Volume, Low Speed Ceiling Fan

42.0

3.0

SIDE VIEW

240

BOTTOM VIEW

Notes: All dimensions shown are in units of in..

C:\Users\uriel.quiroz\Grupo 4HG\PDC Aplicaciones - Sist. De Ventilacion - Sist. De Ventilacion\GREENHECK\Jobs\PC-GH-2203-358 KukaHome Parque Industrial-R1.gfcj
CAPS 4.38.1089 Generated by: uriel.quiroz@proveedora.mx Page 69 of 106
Printed Date: 06/07/2022
Job: PC-GH-2203-358 KukaHome Parque Industrial-R1
Mark: BF 138-161
Model: DS-6-20-170HV
Mechanical Warranty
10 Yrs (Standard)

WARRANTY AND LIABILITY: SELLER warrants to Buyer that the mechanical components of HVLS products manufactured are
free from defects in material and workmanship for a period of 10 Yrs (Standard) from the date of shipment. SELLER's
obligations and liabilities under this warranty are limited to furnishing FOB factory or warehouse at SELLER's designated
shipping point, freight allowed to Buyer's city, (or point of export for shipments outside the conterminous United States)
replacement equipment (or at the option of SELLER parts therefore) for all Seller's products not conforming to this warranty and
which have been returned to the manufacturer. No liability whatever shall attach to SELLER until said products have been paid
for and such liability shall be strictly limited to the purchase price of the equipment shown to be defective. SELLER will not be
responsible for any labor, removal, or installation costs. Electrical components are warranted separately as described in the
product's electrical warranty statement. The legal remedies described in this Warranty are the sole exclusive remedy of Buyer.
SELLER MAKES NO OTHER WARRANTY, EITHER EXPRESS OR IMPLIED, REGARDING ITS PRODUCTS, OR ITS
SELECTION AND APPLICATION, INCLUDING, BUT NOT LIMITED TO, COMPLIANCE WITH BUILDING CODES, SAFETY
CODES, LAWS, MERCHANTABILITY OR FITNESS OR A PARTICULAR PURPOSE. This warranty is extended solely to the
Buyer. It is nontransferable and non-assignable, and the Buyer shall not permit or authorize its employees, agents,
representatives or customers to claim, represent or imply that this limited warranty extends or is available to anyone other than
the Buyer. This warranty only applies to the first installation location of the product and terminates if the product is moved or
reinstalled in a new location. ANY MISUSE, NEGLECT, FAILURE TO FOLLOW INSTRUCTIONS OR MANUALS OF
INSTALLATION OF MAINTENANCE REPAIR, SERVICE, RELOCATION OR ALTERATION TO OR OF, OR OTHER
TAMPERING WITH, THE PRODUCTS PERFORMED BY ANY PERSON OR ENTITY OTHER THAN SELLER WITHOUT
SELLER'S PRIOR WRITTEN APPROVAL OR ANY USE OF REPLACEMENT PARTS NOT SUPPLIED BY SELLER, SHALL
IMMEDIATELY VOID AND CANCEL ALL WARRANTIES WITH RESPECT TO THE AFFECTED PRODUCTS. SELLER
RESERVES THE RIGHT TO MAKE FINAL DETERMINATION ON WARRANTY CLAIMS, BASED ON ITS OWN EVALUATION,
AS TO WHETHER THE PROBLEM IN QUESTION IS THE RESULT OF A DEFECT AND NOT A RESULT OF ERROR,
MISUSE, AN ACT OF GOD, OR ABUSE ON THE PART OF THE CUSTOMER WHICH WOULD MAKE THE WARRANTY
VOID. CONDITIONS THAT WOULD MAKE THE WARRANTY VOID INCLUDE BUT ARE NOT LIMITED TO: NOISE HEARD
DURING OPERATION THAT IS WITHIN NORMAL OPERATING LEVELS, IMPROPER APPLICATION, IMPROPER
INSTALLATION, OR ADVERSE SITE CONDITIONS (INCLUDING, BUT NOT LIMITED TO, EXCESSIVE DUST, HEAT,
HUMIDITY, UNSTABLE ELECTRICAL SERVICE, OR ANY OTHER UNKNOWN OR UNFORESEEN CONDITION THAT
AFFECTS THE PROPER OPERATION OF THE PRODUCT). THE WARRANTY AND LIABILITY SET FORTH HEREIN ARE IN
LIEU OF ALL OTHER WARRANTIES AND LIABILITIES WHETHER IN CONTRACT OR IN NEGLIGENCE, EXPRESSED OR
IMPLIED, IN LAW OR IN FACT, INCLUDING IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A
PARTICULAR USE. SELLER PROVIDES NO INDEPENDENT WARRANTY FOR THIRD PARTY PRODUCTS OR
COMPONENTS SOLD TOGETHER OR INCORPORATED WITH SELLER'S PRODUCT(S). THE SELLER HAS THE RIGHT
TO SETTLE ANY AND ALL DISPUTES REGARDING THE WARRANTY.

C:\Users\uriel.quiroz\Grupo 4HG\PDC Aplicaciones - Sist. De Ventilacion - Sist. De Ventilacion\GREENHECK\Jobs\PC-GH-2203-358 KukaHome Parque Industrial-R1.gfcj
CAPS 4.38.1089 Generated by: uriel.quiroz@proveedora.mx Page 70 of 106
Printed Date: 06/07/2022
Job: PC-GH-2203-358 KukaHome Parque Industrial-R1
Mark: BF 138-161
Model: DS-6-20-170HV
Electrical Warranty
1 Yr (Standard)

WARRANTY AND LIABILITY: SELLER warrants to Buyer that the electrical components (including motors, variable frequency
drives, and factory-supplied wiring; excluding UV-C lightbulbs and ballasts) of HVLS products manufactured are free from
defects in material and workmanship for a period of 1 Yr (Standard) from the date of shipment. SELLER's obligations and
liabilities under this warranty are limited to furnishing FOB factory or warehouse at SELLER's designated shipping point, freight
allowed to Buyer's city, (or point of export for shipments outside the conterminous United States) replacement equipment (or at
the option of SELLER parts therefore) for all Seller's products not conforming to this warranty and which have been returned to
the manufacturer. No liability whatever shall attach to SELLER until said products have been paid for and such liability shall be
strictly limited to the purchase price of the equipment shown to be defective. SELLER will not be responsible for any labor,
removal, or installation costs. Mechanical components are warranted separately as described in the product's mechanical
warranty statement. To the extent that SELLER is entitled to pass through a warranty of the original equipment manufacturer of
the electrical goods sold, SELLER will pass through such warranty to Buyer. The legal remedies described in this Warranty are
the sole exclusive remedy of Buyer. SELLER MAKES NO OTHER WARRANTY, EITHER EXPRESS OR IMPLIED,
REGARDING ITS PRODUCTS, OR ITS SELECTION AND APPLICATION, INCLUDING, BUT NOT LIMITED TO,
COMPLIANCE WITH BUILDING CODES, SAFETY CODES, LAWS, MERCHANTABILITY OR FITNESS OR A PARTICULAR
PURPOSE. This warranty is extended solely to the Buyer. It is nontransferable and non-assignable, and the Buyer shall not
permit or authorize its employees, agents, representatives or customers to claim, represent or imply that this limited warranty
extends or is available to anyone other than the Buyer. This warranty only applies to the first installation location of the product
and terminates if the product is moved or reinstalled in a new location. ANY MISUSE, NEGLECT, FAILURE TO FOLLOW
INSTRUCTIONS OR MANUALS OF INSTALLATION OF MAINTENANCE REPAIR, SERVICE, RELOCATION OR ALTERATION
TO OR OF, OR OTHER TAMPERING WITH, THE PRODUCTS PERFORMED BY ANY PERSON OR ENTITY OTHER THAN
SELLER WITHOUT SELLER'S PRIOR WRITTEN APPROVAL OR ANY USE OF REPLACEMENT PARTS NOT SUPPLIED BY
SELLER, SHALL IMMEDIATELY VOID AND CANCEL ALL WARRANTIES WITH RESPECT TO THE AFFECTED PRODUCTS.
SELLER RESERVES THE RIGHT TO MAKE FINAL DETERMINATION ON WARRANTY CLAIMS, BASED ON ITS OWN
EVALUATION, AS TO WHETHER THE PROBLEM IN QUESTION IS THE RESULT OF A DEFECT AND NOT A RESULT OF
ERROR, MISUSE, AN ACT OF GOD, OR ABUSE ON THE PART OF THE CUSTOMER WHICH WOULD MAKE THE
WARRANTY VOID. CONDITIONS THAT WOULD MAKE THE WARRANTY VOID INCLUDE BUT ARE NOT LIMITED TO:
NOISE HEARD DURING OPERATION THAT IS WITHIN NORMAL OPERATING LEVELS, IMPROPER APPLICATION,
IMPROPER INSTALLATION, OR ADVERSE SITE CONDITIONS (INCLUDING, BUT NOT LIMITED TO, EXCESSIVE DUST,
HEAT, HUMIDITY, UNSTABLE ELECTRICAL SERVICE, OR ANY OTHER UNKNOWN OR UNFORESEEN CONDITION THAT
AFFECTS THE PROPER OPERATION OF THE PRODUCT). THE WARRANTY AND LIABILITY SET FORTH HEREIN ARE IN
LIEU OF ALL OTHER WARRANTIES AND LIABILITIES WHETHER IN CONTRACT OR IN NEGLIGENCE, EXPRESSED OR
IMPLIED, IN LAW OR IN FACT, INCLUDING IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A
PARTICULAR USE. SELLER PROVIDES NO INDEPENDENT WARRANTY FOR THIRD PARTY PRODUCTS OR
COMPONENTS SOLD TOGETHER OR INCORPORATED WITH SELLER'S PRODUCT(S). THE SELLER HAS THE RIGHT
TO SETTLE ANY AND ALL DISPUTES REGARDING THE WARRANTY.

C:\Users\uriel.quiroz\Grupo 4HG\PDC Aplicaciones - Sist. De Ventilacion - Sist. De Ventilacion\GREENHECK\Jobs\PC-GH-2203-358 KukaHome Parque Industrial-R1.gfcj
CAPS 4.38.1089 Generated by: uriel.quiroz@proveedora.mx Page 71 of 106
Printed Date: 06/07/2022
Job: PC-GH-2203-358 KukaHome Parque Industrial-R1
Mark: BF 138-161
Model: DS-6-20-170HV

AMCA

Greenheck Fan Corporation certifies that the model shown herein is licensed to bear the AMCA Seal. The ratings
shown are based on tests and procedures performed in accordance with AMCA Publication 211 and comply with the
requirements of the AMCA Certified Ratings Program. The AMCA Certified Ratings Seal applies to air performance
ratings only. The AMCA Certified Ratings Seal applies at free delivery only. Performance ratings do not include the
effects of appurtenances (accessories).

C:\Users\uriel.quiroz\Grupo 4HG\PDC Aplicaciones - Sist. De Ventilacion - Sist. De Ventilacion\GREENHECK\Jobs\PC-GH-2203-358 KukaHome Parque Industrial-R1.gfcj
CAPS 4.38.1089 Generated by: uriel.quiroz@proveedora.mx Page 72 of 106
Printed Date: 06/07/2022
Job: PC-GH-2203-358 KukaHome Parque Industrial-R1
Mark: EF 56-117
Model: SBE-2L42-30
44.00 35.75
Model: SBE-2L42-30
Sidewall Belt Drive Fan
Motor Access From Int. of Bldg.

Dimensional 48.50
Quantity 61
Weight w/o Acc's (lb) 216
Weight w/ Acc's (lb) 516 WEATHERHOOD
GUARD
Max T Motor Frame Size 184
WALL HOUSING INTERIOR EXTERIOR

Optional Damper (in.) 44 x 44 DAMPER


Wall Opening (in.) 51.75 x 51.75 EXHAUST AIRFLOW

Performance
Requested Volume (CFM) 21,900
Actual Volume (CFM) 21,900
Total External SP (in. wg) 0.25
Fan RPM 576
Operating Power (hp) 2.96
Elevation (ft) 1,690
Airstream Temp.(F) 70
Air Density (lb/ft3) 0.070
Drive Loss (%) 4.4
Tip Speed (ft/min) 6,336
Static Eff. (%) 30

Motor
Motor Mounted Yes
Size (hp) 3
Voltage/Cycle/Phase 460/60/3
Enclosure ODP
Motor RPM 1725
Efficiency Rating NEMA Premium
Windings 1
NEC FLA* (Amps) 4.8
Notes:
All dimensions shown are in units of in.
*NEC FLA, MCA and MOP are for reference only – based on
tables 430.248 or 430.25 of National Electric Code 2020. Actual
motor FLA may vary, for sizing thermal overload, consult factory.
MCA and MOP values shown only account for the motor, not
accessories (damper actuator, field supplied VFD, etc).
LwA - A weighted sound power level, based on ANSI S1.4
Sound Power by Octave Band dBA - A weighted sound pressure level, based on 11.5 dB
Sound attenuation per Octave band at 5 ft - dBA levels are not licensed
62.5 125 250 500 1000 2000 4000 8000 LwA dBA Sones by AMCA International
Data Sones - calculated using AMCA 301 at 5 ft
Inlet 92 93 88 87 83 79 75 71 89 77 29

C:\Users\uriel.quiroz\Grupo 4HG\PDC Aplicaciones - Sist. De Ventilacion - Sist. De Ventilacion\GREENHECK\Jobs\PC-GH-2203-358 KukaHome Parque Industrial-R1.gfcj
CAPS 4.38.1089 Generated by: uriel.quiroz@proveedora.mx Page 73 of 106
Printed Date: 06/07/2022
Job: PC-GH-2203-358 KukaHome Parque Industrial-R1
Mark: EF 56-117
Model: SBE-2L42-30
Model: SBE-2L42-30
Sidewall Belt Drive Fan
Standard Construction Features:
- Galvanized steel fan panel - Die formed, galvanized steel drive frame assembly
- Fabricated steel propeller for Levels 1 and 2, welded and painted steel for Level
3 - Adjustable motor pulley - Ball bearing motors - Fan shaft mounted in ball
bearing pillow blocks - Static resistant belts - Corrosion resistant fasteners
Selected Options & Accessories:
NEMA Premium Efficient Motor - meets NEMA Table 12-12
Airflow Direction: Exhaust
Short Wall Hsg, Flush Exterior, w/ OSHA Grd.
Motor Access: From Int. of Bldg.
Weatherhood, Galvanized 45 deg. with Bird Screen
Bearings with Grease Fittings
Unit Warranty: 1 Yr (Standard)
Damper Mounted, WD-320-PB-44X44, Gravity Operated, Not Coated

C:\Users\uriel.quiroz\Grupo 4HG\PDC Aplicaciones - Sist. De Ventilacion - Sist. De Ventilacion\GREENHECK\Jobs\PC-GH-2203-358 KukaHome Parque Industrial-R1.gfcj
CAPS 4.38.1089 Generated by: uriel.quiroz@proveedora.mx Page 74 of 106
Printed Date: 06/07/2022
Job: PC-GH-2203-358 KukaHome Parque Industrial-R1
Mark: EF 56-117
Model: SBE-2L42-30
Assembly Drawing
Type: Sidewall Belt Drive Fan

44.00 35.75

DRAWING VIEWED FROM INTERIOR

50.38 56.38 48.50

WEATHERHOOD
GUARD
50.38
WALL HOUSING INTERIOR EXTERIOR

56.38
DAMPER
EXHAUST AIRFLOW
END VIEW DIMENSIONS ARE FOR HOUSING NOT FAN PANEL
WALL OPENING 51.75 SQ.
MOTOR IS ACCESSIBLE FROM INTERIOR OF BUILDING
THIS IS AN EXHAUST FAN DUE TO MOTOR ORIENTATION

Notes: All dimensions shown are in units of in..

C:\Users\uriel.quiroz\Grupo 4HG\PDC Aplicaciones - Sist. De Ventilacion - Sist. De Ventilacion\GREENHECK\Jobs\PC-GH-2203-358 KukaHome Parque Industrial-R1.gfcj
CAPS 4.38.1089 Generated by: uriel.quiroz@proveedora.mx Page 75 of 106
Printed Date: 06/07/2022
Job: PC-GH-2203-358 KukaHome Parque Industrial-R1
Mark: EF 56-117
Model: SBE-2L42-30
45 Degree Weatherhood

Standard Construction Features:


Galvanized Steel or aluminum construction. 0.5 welded wire birdscreen. Prepunched mounting holes. Field assembled.

35.75 47.13

48.5

SIDE VIEW ELEVATION VIEW

C:\Users\uriel.quiroz\Grupo 4HG\PDC Aplicaciones - Sist. De Ventilacion - Sist. De Ventilacion\GREENHECK\Jobs\PC-GH-2203-358 KukaHome Parque Industrial-R1.gfcj
CAPS 4.38.1089 Generated by: uriel.quiroz@proveedora.mx Page 76 of 106
Printed Date: 06/07/2022
Job: PC-GH-2203-358 KukaHome Parque Industrial-R1
Mark: EF 56-117
Model: SBE-2L42-30
Short Wall Housing
Standard Construction Features:
- Galvanized steel construction - Heavy gauge mounting flanges - Pre-punched mounting holes - Inside
flanges allow damper to be mounted - Overlapping weatherhood flange keeps rain out - OSHA Protective
guard of welded steel wire completely protects the drive side of the wall housing.

44
50.38

50.38

Notes: All dimensions shown are in units of in.

C:\Users\uriel.quiroz\Grupo 4HG\PDC Aplicaciones - Sist. De Ventilacion - Sist. De Ventilacion\GREENHECK\Jobs\PC-GH-2203-358 KukaHome Parque Industrial-R1.gfcj
CAPS 4.38.1089 Generated by: uriel.quiroz@proveedora.mx Page 77 of 106
Printed Date: 06/07/2022
Job: PC-GH-2203-358 KukaHome Parque Industrial-R1
Mark: EF 56-117
Model: SBE-2L42-30

SBE-2L42-30 Min/Max Fan Curve

Performance
Requested Actual
Total External Fan Operating
Volume Volume
SP (in. wg) RPM Power (hp)
(CFM) (CFM)
21,900 21,900 0.25 576 2.96

C:\Users\uriel.quiroz\Grupo 4HG\PDC Aplicaciones - Sist. De Ventilacion - Sist. De Ventilacion\GREENHECK\Jobs\PC-GH-2203-358 KukaHome Parque Industrial-R1.gfcj
CAPS 4.38.1089 Generated by: uriel.quiroz@proveedora.mx Page 78 of 106
Printed Date: 06/07/2022
Job: PC-GH-2203-358 KukaHome Parque Industrial-R1
Mark: EF 56-117
Model: SBE-2L42-30
Warranty
1 Yr (Standard)

WARRANTY AND LIABILITY: SELLER warrants to Buyer that products manufactured are free from defects in material and
workmanship for a period of 1 Yr (Standard) from the date of shipment. SELLER's obligations and liabilities under this warranty
are limited to furnishing FOB factory or warehouse at SELLER's designated shipping point, freight allowed to Buyer's city, (or
point of export for shipments outside the conterminous United States) replacement equipment (or at the option of SELLER parts
therefore) for all Seller's products not conforming to this warranty and which have been returned to the manufacturer. No liability
whatever shall attach to SELLER until said products have been paid for and such liability shall be strictly limited to the purchase
price of the equipment shown to be defective. Motors are warranted by the motor manufacturer for a period of one year. Should
motors furnished by SELLER prove defective during this period, they should be returned to the nearest authorized motor service
station. SELLER will not be responsible for any removal or installation costs. Electrical components, excluding motors, are
warranted only to the extent warranted by the original manufacturer. To the extent that SELLER is entitled to pass through a
warranty of the original equipment manufacturer of the electrical goods sold, SELLER will pass through such warranties to
Buyer. The legal remedies described in this Warranty are the sole exclusive remedy of Buyer. SELLER MAKES NO OTHER
WARRANTY, EITHER EXPRESS OR IMPLIED, REGARDING ITS PRODUCTS, OR ITS SELECTION AND APPLICATION,
INCLUDING, BUT NOT LIMITED TO, COMPLIANCE WITH BUILDING CODES, SAFETY CODES, LAWS,
MERCHANTABILITY OR FITNESS OR A PARTICULAR PURPOSE. This warranty is extended solely to the Buyer. It is
nontransferable and non-assignable, and the Buyer shall not permit or authorize its employees, agents, representatives or
customers to claim, represent or imply that this limited warranty extends or is available to anyone other than the Buyer. ANY
MISUSE, NEGLECT, FAILURE TO FOLLOW INSTRUCTIONS OR MANUALS OF INSTALLATION OF MAINTENANCE
REPAIR, SERVICE, RELOCATION OR ALTERATION TO OR OF, OR OTHER TAMPERING WITH, THE PRODUCTS
PERFORMED BY ANY PERSON OR ENTITY OTHER THAN SELLER WITHOUT SELLER'S PRIOR WRITTEN APPROVAL
OR ANY USE OF REPLACEMENT PARTS NOT SUPPLIED BY SELLER, SHALL IMMEDIATELY VOID AND CANCEL ALL
WARRANTIES WITH RESPECT TO THE AFFECTED PRODUCTS. THE WARRANTY AND LIABILITY SET FORTH HEREIN
ARE IN LIEU OF ALL OTHER WARRANTIES AND LIABILITIES WHETHER IN CONTRACT OR IN NEGLIGENCE,
EXPRESSED OR IMPLIED, IN LAW OR IN FACT, INCLUDING IMPLIED WARRANTIES OF MERCHANTABILITY AND
FITNESS FOR A PARTICULAR USE. SELLER PROVIDES NO INDEPENDENT WARRANTY FOR THIRD PARTY PRODUCTS
OR COMPONENTS SOLD TOGETHER OR INCORPORATED WITH SELLER'S PRODUCT(S). THE SELLER HAS THE
RIGHT TO SETTLE ANY AND ALL DISPUTES REGARDING THE WARRANTY.

C:\Users\uriel.quiroz\Grupo 4HG\PDC Aplicaciones - Sist. De Ventilacion - Sist. De Ventilacion\GREENHECK\Jobs\PC-GH-2203-358 KukaHome Parque Industrial-R1.gfcj
CAPS 4.38.1089 Generated by: uriel.quiroz@proveedora.mx Page 79 of 106
Printed Date: 06/07/2022
Job: PC-GH-2203-358 KukaHome Parque Industrial-R1
Mark: EF 56-117
Model: SBE-2L42-30

AMCA

AMCA Licensed for Sound and Air Performance. Power rating (BHP/kW) includes transmission losses.

Greenheck Fan Corporation certifies that the model shown herein is licensed to bear the AMCA Seal. The ratings
shown are based on tests and procedures performed in accordance with AMCA Publication 211 and AMCA Publication
311 and comply with the requirements of the AMCA Certified Ratings Program. Performance certified is for installation
type A: Free inlet, Free outlet. Power rating (BHP/kW) includes transmission losses. Performance ratings do not include
the effects of appurtenances (accessories). The sound ratings shown are loudness values in fan sones at 5 ft. (1.5 m)
in a hemispherical free field calculated per AMCA Standard 301. Values shown are for installation type A: free inlet
hemispherical sone levels. dBA levels are not licensed by AMCA International. The AMCA Certified Ratings Seal
applies to sone ratings only.

C:\Users\uriel.quiroz\Grupo 4HG\PDC Aplicaciones - Sist. De Ventilacion - Sist. De Ventilacion\GREENHECK\Jobs\PC-GH-2203-358 KukaHome Parque Industrial-R1.gfcj
CAPS 4.38.1089 Generated by: uriel.quiroz@proveedora.mx Page 80 of 106
Printed Date: 06/07/2022
Job: PC-GH-2203-358 KukaHome Parque Industrial-R1
Mark: BF 60-137
Model: DS-6-20-170HV

Model: DS-6-20-170HV 42.0


High Volume, Low Speed Ceiling Fan
3.0

Dimensional
Impeller Diameter (ft) 20
Impeller Diameter (in.) 240
Quantity 78
Weight w/o Acc's (lb) 119
Weight w/ Acc's (lb) 235

Installation Clearances
Minimum Fan Spacing (ft) 60
Clearance to Wall (ft) 30
Blade Tip Clearance (ft) 3
Vertical Blade Clearance (ft) 3
Standby Blade Deflection (in.) 1.7

Performance Per Fan


*Tested Direction of Operation Forward
Actual Volume (CFM) 196,200
Coverage Area (ft2) 21,600
Max Coverage Area (ft2) 21,600
Avg. Air Speed (ft/min) 477
Max Avg. Air Speed (ft/min) 477
Fan RPM 78
Max Fan RPM 78
**CFEI at 40% Speed 2.72
**CFEI at 100% Speed 1.44
**Integrated Efficiency
-
(CFM/W)
Total Sound Pressure (dBA) 52

Fan Operation
Direction of Operation
Forward or Reverse
Capability
Communication Protocol Modbus RTU

Motor
Size (W) 1,100 Notes:
All dimensions shown are in units of in. (unless specified
Voltage/Cycle/Phase 460/60/3
otherwise)
Enclosure IP54 Dimensions shown may vary with fan speed. Consult
installation manual for clearance requirements.
Max Motor RPM 78 dBA – A weighted sound pressure level measured 5 ft off
the ground at 20 ft from the center of the fan – dBA levels
***System FLA (Amps) 3.5 are not licensed by AMCA International
*Cataloged performance data tested using forward
**Standby Power (W) 11 direction of operation per 10 CFR Part 430.
**Input Power (W) 1,398 **Based on 208/60/3 testing per 10 CFR 430
***FLA is based on worst case system voltage and phase
combination

C:\Users\uriel.quiroz\Grupo 4HG\PDC Aplicaciones - Sist. De Ventilacion - Sist. De Ventilacion\GREENHECK\Jobs\PC-GH-2203-358 KukaHome Parque Industrial-R1.gfcj
CAPS 4.38.1089 Generated by: uriel.quiroz@proveedora.mx Page 81 of 106
Printed Date: 06/07/2022
Job: PC-GH-2203-358 KukaHome Parque Industrial-R1
Mark: BF 60-137
Model: DS-6-20-170HV
Model: DS-6-20-170HV
High Volume, Low Speed Ceiling Fan
Tags: BF 60 BF 61 BF 62 BF 63 BF 64 BF 65 BF 66 BF 67 BF 68 BF 69 BF 70
BF 71 BF 72 BF 73 BF 74 BF 75 BF 76 BF 77 BF 78 BF 79 BF 80 BF 81 BF 82
BF 83 BF 84 BF 85 BF 86 BF 87 BF 88 BF 89 BF 90 BF 91 BF 92 BF 93 BF 94
BF 95 BF 96 BF 97 BF 98 BF 99 BF 100 BF 101 BF 102 BF 103 BF 104 BF 105
BF 106 BF 107 BF 108 BF 109 BF 110 BF 111 BF 112 BF 113 BF 114 BF 115 BF
116 BF 117 BF 118 BF 119 BF 120 BF 121 BF 122 BF 123 BF 124 BF 125 BF
126 BF 127 BF 128 BF 129 BF 130 BF 131 BF 132 BF 133 BF 134 BF 135 BF
136 BF 137
Standard Construction Features:
Heavy duty frame with protective finish - Extruded aluminum airfoils - High
efficiency direct drive motor designed for either forward or reverse operation -
Factory mounted and wired variable frequency drive - Factory installed plug and
play wiring - Universal ceiling mount - Heavy duty safety restraint cable - Airfoil
and fan hub retaining systems - AMCA certified for Circulating Fan Performance
Selected Options & Accessories:
6 Blade, Extruded Aluminum Airfoil Kit
Mill Finish, No Color
Aluminum Winglet; Hi-Pro Polyester Finish, Flat Black (044) Color
I-Beam Mounting Kit; Hi-Pro Polyester Finish, Flat Black (044) Color
3.5 ft Drop Length; Hi-Pro Polyester Finish, Flat Black (044) Color
Hub Plate and Impeller Hub; Hi-Pro Polyester Finish, Flat Black (044) Color
Hub Plate Decal with Greenheck Logo
Power Wiring Pigtail, Internal, General, 3 ft of Flexible Power Cord from Unit,
Unstripped Wire
Plug-and-Play Network Communication Wiring Pigtail, Internal, Terminated with
Shielded CAT-5e Splitter (RJ45 Ports)
100 ft of Shielded, Twisted Pair (STP) CAT-5e Control Cable
Fire Alarm Wiring Pigtail, Internal, 2.5 ft from Unit, Terminated with Crimp
Connector
Low-Voltage (24VDC/VAC or 115VAC), Normally Closed Electromechanical Fire
Alarm Relay
Braided Galvanized Steel Safety Cable, 16 ft from Unit
Braided Galvanized Steel Guy Wires, 20 ft from Unit
Cable Clamp Hardware for Safety Cable and Guy Wires
Electrical Warranty: 1 Yr (Standard)
Mechanical Warranty: 10 Yrs (Standard)

C:\Users\uriel.quiroz\Grupo 4HG\PDC Aplicaciones - Sist. De Ventilacion - Sist. De Ventilacion\GREENHECK\Jobs\PC-GH-2203-358 KukaHome Parque Industrial-R1.gfcj
CAPS 4.38.1089 Generated by: uriel.quiroz@proveedora.mx Page 82 of 106
Printed Date: 06/07/2022
Job: PC-GH-2203-358 KukaHome Parque Industrial-R1
Mark: BF 60-137
Model: DS-6-20-170HV

Model: DS-6-20-170HV
High Volume, Low Speed Ceiling Fan

Fan Coverage Data

Zone 1 Zone 2 Zone 3 Zone 4


375+ 230+ 105+ <105
Fan Recommended
FPM Air FPM Air FPM Air FPM Air
Speed Coverage Radius
Speed Speed Speed Speed
(RPM) Per Fan (ft)
Radius Radius Radius Radius
(ft) (ft) (ft) (ft)
Selected 78 38 58 75 90 83
Maximum 78 38 58 75 90 83

C:\Users\uriel.quiroz\Grupo 4HG\PDC Aplicaciones - Sist. De Ventilacion - Sist. De Ventilacion\GREENHECK\Jobs\PC-GH-2203-358 KukaHome Parque Industrial-R1.gfcj
CAPS 4.38.1089 Generated by: uriel.quiroz@proveedora.mx Page 83 of 106
Printed Date: 06/07/2022
Job: PC-GH-2203-358 KukaHome Parque Industrial-R1
Mark: BF 60-137
Model: DS-6-20-170HV

Model: DS-6-20-170HV
High Volume, Low Speed Ceiling Fan

Fan Spacing & Clearances

A - Clearance to Wall (ft) B - Fan Spacing (ft) C - Clearance to Floor (ft)


Minimum 30 60 10

Additional Requirements

1. For NFPA 13 compliance in buildings equipped with sprinklers:


-Fan must be centered approximately between four adjacent sprinklers
-Vertical clearance from fan to sprinkler deflector must be a minimum of 3 ft (36 in.)
-Fan must be interlocked to shut down immediately upon a waterflow alarm from the building's fire alarm system
-Interlock with building's fire alarm system shall be in accordance with the requirements of NFPA 72
2. Avoid installing fan directly below a light source to prevent a strobing effect that can be caused by fan rotation

C:\Users\uriel.quiroz\Grupo 4HG\PDC Aplicaciones - Sist. De Ventilacion - Sist. De Ventilacion\GREENHECK\Jobs\PC-GH-2203-358 KukaHome Parque Industrial-R1.gfcj
CAPS 4.38.1089 Generated by: uriel.quiroz@proveedora.mx Page 84 of 106
Printed Date: 06/07/2022
Job: PC-GH-2203-358 KukaHome Parque Industrial-R1
Mark: BF 60-137
Model: DS-6-20-170HV

Perceived Cooling Effect

Feels 12°F
Cooler

Perceived Cooling Effect Based on ASHRAE 55-2017


Perceived
Coverage Area Operative Relative Metabolic Avg. Air Speed
Clothing Level Cooling
Per Fan (ft2) Temp. (F) Humidity (%) Rate (ft/min)
Effect (F)
0.57 Pants, Short
21,600 77 60 1.7 Walking 477 12
Sleeves

C:\Users\uriel.quiroz\Grupo 4HG\PDC Aplicaciones - Sist. De Ventilacion - Sist. De Ventilacion\GREENHECK\Jobs\PC-GH-2203-358 KukaHome Parque Industrial-R1.gfcj
CAPS 4.38.1089 Generated by: uriel.quiroz@proveedora.mx Page 85 of 106
Printed Date: 06/07/2022
Job: PC-GH-2203-358 KukaHome Parque Industrial-R1
Mark: BF 60-137
Model: DS-6-20-170HV

Payback Analysis

Payback Inputs
Electric Cost (USD/ Heating Cost (USD/
Operating Time Heat Source
KwH) therm)
24 hours/day, 7
0.08 Gas 0.80
days/week

Winter Destratification Energy Savings


Estimated Heating Load Annual Energy Cost HVLS Energy Cost Net Energy Cost
Without HVLS With HVLS Savings (USD) (USD) Savings (USD)
0.0 0.0 0 0 0

Summer Cooling Energy Savings


Estimated Cooling Load Annual Energy Cost HVLS Energy Cost Net Energy Cost
Without HVLS With HVLS Savings (USD) (USD) Savings (USD)
0.0 0.0 0 0 0

Equipment Cost
Estimated HVLS Avoided A/C
Equipment First Cost Equipment Cost Net First Cost (USD)
(USD) (USD)
567,840 0 567,840

Payback
Net Operating
Payback Period
Savings Per Year
(Years)
(USD)
0 0.0

C:\Users\uriel.quiroz\Grupo 4HG\PDC Aplicaciones - Sist. De Ventilacion - Sist. De Ventilacion\GREENHECK\Jobs\PC-GH-2203-358 KukaHome Parque Industrial-R1.gfcj
CAPS 4.38.1089 Generated by: uriel.quiroz@proveedora.mx Page 86 of 106
Printed Date: 06/07/2022
Job: PC-GH-2203-358 KukaHome Parque Industrial-R1
Mark: BF 60-137
Model: DS-6-20-170HV

Model: DS-6-20-170HV
Finish Selection

Selected Frame Finish


Finish Type Hi-Pro Polyester
Mount Finish Color Flat Black (044)
Downtube Finish Color Flat Black (044)
Hub/Hub Plate Finish Color Flat Black (044)
Winglet Finish Color Flat Black (044)

Selected Airfoil Finish


Finish Type Mill
Finish Color None

Available Finish Options (Additional Charges May Apply):

C:\Users\uriel.quiroz\Grupo 4HG\PDC Aplicaciones - Sist. De Ventilacion - Sist. De Ventilacion\GREENHECK\Jobs\PC-GH-2203-358 KukaHome Parque Industrial-R1.gfcj
CAPS 4.38.1089 Generated by: uriel.quiroz@proveedora.mx Page 87 of 106
Printed Date: 06/07/2022
Job: PC-GH-2203-358 KukaHome Parque Industrial-R1
Mark: BF 60-137
Model: DS-6-20-170HV

Model: DS-6-20-170HV
High Volume, Low Speed Ceiling Fan

Mechanical Installation Requirements


Selected Mounting Kit: I-Beam

IMPORTANT: HVLS fans must be mounted to building structure as shown in one


of the mounting details on this page. Other mounting methods are not acceptable
unless approved by Structural Engineer of Record (SEOR). For complete installation
instructions, refer to the installation, operation and maintenance manual (IOM).

IMPORTANT: Failure to install the fan's safety retention cable and guy wires
(if provided) will result in voiding of the fan warranty.

Available Mounting Kits (Additional Charges May Apply):

C:\Users\uriel.quiroz\Grupo 4HG\PDC Aplicaciones - Sist. De Ventilacion - Sist. De Ventilacion\GREENHECK\Jobs\PC-GH-2203-358 KukaHome Parque Industrial-R1.gfcj
CAPS 4.38.1089 Generated by: uriel.quiroz@proveedora.mx Page 88 of 106
Printed Date: 06/07/2022
Job: PC-GH-2203-358 KukaHome Parque Industrial-R1
Mark: BF 60-137
Model: DS-6-20-170HV

Model: DS-6-20-170HV
High Volume, Low Speed Ceiling Fan

Electrical Installation Requirements


IMPORTANT: HVLS fans must be installed with the supplied CAT-5e communication cable or
shielded, twisted pair (STP) CAT-5e (by others) that complies with the following specifications. Cable
must be twisted pair, shielded 26 ga. CAT-5e cable with a drain wire and must be compliant with ISO
11801. Cable must use shielded RJ45 connectors with a soldered drain and wiring configuration must
follow EIA/TIA T568B wiring pinout. Individual CAT-5e cable lengths must not exceed 200 ft. in order
to prevent network communication issues.

POWER WIRING
SHIELDED TWISTED PAIR CAT-5e CONNECTION

TO NEXT FAN POWER SOURCE


(IF APPLICABLE) RED
L3
BLACK
TO CONTROL L2
WHITE
L1
GREEN GROUND

FIRE SYSTEM WIRING (IF APPLICABLE)


DIP SWITCH BANK 3
ON

SUPPLIED FIRE RELAY FIRE ALARM


1 2 3 4 5 6 7 8 CONTROL PANEL

BLACK
YELLOW (NC) RED (+) RED
RED
BLUE (COMMON) WHITE (-) WHITE
DIP SWITCH BANK 2
ON

1 2 3

3 HALL CONNECTION
NOTE:
HALL CABLE PLUG HAS
BUILT-IN ALIGNMENT TAB.
MOTOR CABLE CONNECTION DO NOT FORCE THIS PLUG

POWER 1
GROUND 2
POWER 1
GROUND 2

3 HALL CONNECTION

NOTE: If networking multiple HVLS fans to run using a single control source, additional
wiring and network modification may be required. Please refer to the fans's installation,
operation and maintenance manual (IOM)

C:\Users\uriel.quiroz\Grupo 4HG\PDC Aplicaciones - Sist. De Ventilacion - Sist. De Ventilacion\GREENHECK\Jobs\PC-GH-2203-358 KukaHome Parque Industrial-R1.gfcj
CAPS 4.38.1089 Generated by: uriel.quiroz@proveedora.mx Page 89 of 106
Printed Date: 06/07/2022
Job: PC-GH-2203-358 KukaHome Parque Industrial-R1
Mark: BF 60-137
Model: DS-6-20-170HV

Model: DS-6-20-170HV
High Volume, Low Speed Ceiling Fan

HVLS Fan Compliance


Department of Energy (DOE) 10 CFR Part 430 Compliance
DOE Min. CFEI at Calculated CFEI at DOE Min. CFEI at Calculated CFEI at DOE Min. Efficiency Calculated Efficiency
Compliance
40% Speed 40% Speed 100% Speed 100% Speed (CFM/W) (CFM/W)
1.31 2.72 1.00 1.44 - - Yes

ASHRAE 55-2017 Compliance


Perceived Acceptable Calculated
Operative Relative Metabolic Avg. Air Speed Thermal
Clothing Level Cooling Effect Predicted Mean Predicted Mean Compliance
Temp. (F) Humidity (%) Rate (ft/min) Sensation
(F) Vote (PMV) Vote (PMV)
0.57 Pants, -0.5 ≤ PMV ≤
77 60 1.7 Walking 477 12 -0.44 Neutral Yes
Short Sleeves 0.5

C:\Users\uriel.quiroz\Grupo 4HG\PDC Aplicaciones - Sist. De Ventilacion - Sist. De Ventilacion\GREENHECK\Jobs\PC-GH-2203-358 KukaHome Parque Industrial-R1.gfcj
CAPS 4.38.1089 Generated by: uriel.quiroz@proveedora.mx Page 90 of 106
Printed Date: 06/07/2022
Job: PC-GH-2203-358 KukaHome Parque Industrial-R1
Mark: BF 60-137
Model: DS-6-20-170HV
Assembly Drawing
Type: High Volume, Low Speed Ceiling Fan

42.0

3.0

SIDE VIEW

240

BOTTOM VIEW

Notes: All dimensions shown are in units of in..

C:\Users\uriel.quiroz\Grupo 4HG\PDC Aplicaciones - Sist. De Ventilacion - Sist. De Ventilacion\GREENHECK\Jobs\PC-GH-2203-358 KukaHome Parque Industrial-R1.gfcj
CAPS 4.38.1089 Generated by: uriel.quiroz@proveedora.mx Page 91 of 106
Printed Date: 06/07/2022
Job: PC-GH-2203-358 KukaHome Parque Industrial-R1
Mark: BF 60-137
Model: DS-6-20-170HV
Mechanical Warranty
10 Yrs (Standard)

WARRANTY AND LIABILITY: SELLER warrants to Buyer that the mechanical components of HVLS products manufactured are
free from defects in material and workmanship for a period of 10 Yrs (Standard) from the date of shipment. SELLER's
obligations and liabilities under this warranty are limited to furnishing FOB factory or warehouse at SELLER's designated
shipping point, freight allowed to Buyer's city, (or point of export for shipments outside the conterminous United States)
replacement equipment (or at the option of SELLER parts therefore) for all Seller's products not conforming to this warranty and
which have been returned to the manufacturer. No liability whatever shall attach to SELLER until said products have been paid
for and such liability shall be strictly limited to the purchase price of the equipment shown to be defective. SELLER will not be
responsible for any labor, removal, or installation costs. Electrical components are warranted separately as described in the
product's electrical warranty statement. The legal remedies described in this Warranty are the sole exclusive remedy of Buyer.
SELLER MAKES NO OTHER WARRANTY, EITHER EXPRESS OR IMPLIED, REGARDING ITS PRODUCTS, OR ITS
SELECTION AND APPLICATION, INCLUDING, BUT NOT LIMITED TO, COMPLIANCE WITH BUILDING CODES, SAFETY
CODES, LAWS, MERCHANTABILITY OR FITNESS OR A PARTICULAR PURPOSE. This warranty is extended solely to the
Buyer. It is nontransferable and non-assignable, and the Buyer shall not permit or authorize its employees, agents,
representatives or customers to claim, represent or imply that this limited warranty extends or is available to anyone other than
the Buyer. This warranty only applies to the first installation location of the product and terminates if the product is moved or
reinstalled in a new location. ANY MISUSE, NEGLECT, FAILURE TO FOLLOW INSTRUCTIONS OR MANUALS OF
INSTALLATION OF MAINTENANCE REPAIR, SERVICE, RELOCATION OR ALTERATION TO OR OF, OR OTHER
TAMPERING WITH, THE PRODUCTS PERFORMED BY ANY PERSON OR ENTITY OTHER THAN SELLER WITHOUT
SELLER'S PRIOR WRITTEN APPROVAL OR ANY USE OF REPLACEMENT PARTS NOT SUPPLIED BY SELLER, SHALL
IMMEDIATELY VOID AND CANCEL ALL WARRANTIES WITH RESPECT TO THE AFFECTED PRODUCTS. SELLER
RESERVES THE RIGHT TO MAKE FINAL DETERMINATION ON WARRANTY CLAIMS, BASED ON ITS OWN EVALUATION,
AS TO WHETHER THE PROBLEM IN QUESTION IS THE RESULT OF A DEFECT AND NOT A RESULT OF ERROR,
MISUSE, AN ACT OF GOD, OR ABUSE ON THE PART OF THE CUSTOMER WHICH WOULD MAKE THE WARRANTY
VOID. CONDITIONS THAT WOULD MAKE THE WARRANTY VOID INCLUDE BUT ARE NOT LIMITED TO: NOISE HEARD
DURING OPERATION THAT IS WITHIN NORMAL OPERATING LEVELS, IMPROPER APPLICATION, IMPROPER
INSTALLATION, OR ADVERSE SITE CONDITIONS (INCLUDING, BUT NOT LIMITED TO, EXCESSIVE DUST, HEAT,
HUMIDITY, UNSTABLE ELECTRICAL SERVICE, OR ANY OTHER UNKNOWN OR UNFORESEEN CONDITION THAT
AFFECTS THE PROPER OPERATION OF THE PRODUCT). THE WARRANTY AND LIABILITY SET FORTH HEREIN ARE IN
LIEU OF ALL OTHER WARRANTIES AND LIABILITIES WHETHER IN CONTRACT OR IN NEGLIGENCE, EXPRESSED OR
IMPLIED, IN LAW OR IN FACT, INCLUDING IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A
PARTICULAR USE. SELLER PROVIDES NO INDEPENDENT WARRANTY FOR THIRD PARTY PRODUCTS OR
COMPONENTS SOLD TOGETHER OR INCORPORATED WITH SELLER'S PRODUCT(S). THE SELLER HAS THE RIGHT
TO SETTLE ANY AND ALL DISPUTES REGARDING THE WARRANTY.

C:\Users\uriel.quiroz\Grupo 4HG\PDC Aplicaciones - Sist. De Ventilacion - Sist. De Ventilacion\GREENHECK\Jobs\PC-GH-2203-358 KukaHome Parque Industrial-R1.gfcj
CAPS 4.38.1089 Generated by: uriel.quiroz@proveedora.mx Page 92 of 106
Printed Date: 06/07/2022
Job: PC-GH-2203-358 KukaHome Parque Industrial-R1
Mark: BF 60-137
Model: DS-6-20-170HV
Electrical Warranty
1 Yr (Standard)

WARRANTY AND LIABILITY: SELLER warrants to Buyer that the electrical components (including motors, variable frequency
drives, and factory-supplied wiring; excluding UV-C lightbulbs and ballasts) of HVLS products manufactured are free from
defects in material and workmanship for a period of 1 Yr (Standard) from the date of shipment. SELLER's obligations and
liabilities under this warranty are limited to furnishing FOB factory or warehouse at SELLER's designated shipping point, freight
allowed to Buyer's city, (or point of export for shipments outside the conterminous United States) replacement equipment (or at
the option of SELLER parts therefore) for all Seller's products not conforming to this warranty and which have been returned to
the manufacturer. No liability whatever shall attach to SELLER until said products have been paid for and such liability shall be
strictly limited to the purchase price of the equipment shown to be defective. SELLER will not be responsible for any labor,
removal, or installation costs. Mechanical components are warranted separately as described in the product's mechanical
warranty statement. To the extent that SELLER is entitled to pass through a warranty of the original equipment manufacturer of
the electrical goods sold, SELLER will pass through such warranty to Buyer. The legal remedies described in this Warranty are
the sole exclusive remedy of Buyer. SELLER MAKES NO OTHER WARRANTY, EITHER EXPRESS OR IMPLIED,
REGARDING ITS PRODUCTS, OR ITS SELECTION AND APPLICATION, INCLUDING, BUT NOT LIMITED TO,
COMPLIANCE WITH BUILDING CODES, SAFETY CODES, LAWS, MERCHANTABILITY OR FITNESS OR A PARTICULAR
PURPOSE. This warranty is extended solely to the Buyer. It is nontransferable and non-assignable, and the Buyer shall not
permit or authorize its employees, agents, representatives or customers to claim, represent or imply that this limited warranty
extends or is available to anyone other than the Buyer. This warranty only applies to the first installation location of the product
and terminates if the product is moved or reinstalled in a new location. ANY MISUSE, NEGLECT, FAILURE TO FOLLOW
INSTRUCTIONS OR MANUALS OF INSTALLATION OF MAINTENANCE REPAIR, SERVICE, RELOCATION OR ALTERATION
TO OR OF, OR OTHER TAMPERING WITH, THE PRODUCTS PERFORMED BY ANY PERSON OR ENTITY OTHER THAN
SELLER WITHOUT SELLER'S PRIOR WRITTEN APPROVAL OR ANY USE OF REPLACEMENT PARTS NOT SUPPLIED BY
SELLER, SHALL IMMEDIATELY VOID AND CANCEL ALL WARRANTIES WITH RESPECT TO THE AFFECTED PRODUCTS.
SELLER RESERVES THE RIGHT TO MAKE FINAL DETERMINATION ON WARRANTY CLAIMS, BASED ON ITS OWN
EVALUATION, AS TO WHETHER THE PROBLEM IN QUESTION IS THE RESULT OF A DEFECT AND NOT A RESULT OF
ERROR, MISUSE, AN ACT OF GOD, OR ABUSE ON THE PART OF THE CUSTOMER WHICH WOULD MAKE THE
WARRANTY VOID. CONDITIONS THAT WOULD MAKE THE WARRANTY VOID INCLUDE BUT ARE NOT LIMITED TO:
NOISE HEARD DURING OPERATION THAT IS WITHIN NORMAL OPERATING LEVELS, IMPROPER APPLICATION,
IMPROPER INSTALLATION, OR ADVERSE SITE CONDITIONS (INCLUDING, BUT NOT LIMITED TO, EXCESSIVE DUST,
HEAT, HUMIDITY, UNSTABLE ELECTRICAL SERVICE, OR ANY OTHER UNKNOWN OR UNFORESEEN CONDITION THAT
AFFECTS THE PROPER OPERATION OF THE PRODUCT). THE WARRANTY AND LIABILITY SET FORTH HEREIN ARE IN
LIEU OF ALL OTHER WARRANTIES AND LIABILITIES WHETHER IN CONTRACT OR IN NEGLIGENCE, EXPRESSED OR
IMPLIED, IN LAW OR IN FACT, INCLUDING IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A
PARTICULAR USE. SELLER PROVIDES NO INDEPENDENT WARRANTY FOR THIRD PARTY PRODUCTS OR
COMPONENTS SOLD TOGETHER OR INCORPORATED WITH SELLER'S PRODUCT(S). THE SELLER HAS THE RIGHT
TO SETTLE ANY AND ALL DISPUTES REGARDING THE WARRANTY.

C:\Users\uriel.quiroz\Grupo 4HG\PDC Aplicaciones - Sist. De Ventilacion - Sist. De Ventilacion\GREENHECK\Jobs\PC-GH-2203-358 KukaHome Parque Industrial-R1.gfcj
CAPS 4.38.1089 Generated by: uriel.quiroz@proveedora.mx Page 93 of 106
Printed Date: 06/07/2022
Job: PC-GH-2203-358 KukaHome Parque Industrial-R1
Mark: BF 60-137
Model: DS-6-20-170HV

AMCA

Greenheck Fan Corporation certifies that the model shown herein is licensed to bear the AMCA Seal. The ratings
shown are based on tests and procedures performed in accordance with AMCA Publication 211 and comply with the
requirements of the AMCA Certified Ratings Program. The AMCA Certified Ratings Seal applies to air performance
ratings only. The AMCA Certified Ratings Seal applies at free delivery only. Performance ratings do not include the
effects of appurtenances (accessories).

C:\Users\uriel.quiroz\Grupo 4HG\PDC Aplicaciones - Sist. De Ventilacion - Sist. De Ventilacion\GREENHECK\Jobs\PC-GH-2203-358 KukaHome Parque Industrial-R1.gfcj
CAPS 4.38.1089 Generated by: uriel.quiroz@proveedora.mx Page 94 of 106
Printed Date: 06/07/2022
Job: PC-GH-2203-358 KukaHome Parque Industrial-R1
Mark: AWU 39-59
Model: TSF-230-H50

TSF-230-H50
Unit Performance
Design Conditions
Summer
Elevation (ft) Winter (°F) Supply (CFM) Outdoor Air (CFM)
DB (°F) WB (°F)
1,690 100.7 80.1 39.8 47,374 47,374

Unit Specifications
Qty Weight (lb) Cooling Type Heating Type Unit Installation Unit ETL Listing
20 5,941 (+/- 5%) Direct Evaporative None Outdoor/Indoor UL / cUL 1995

Configuration
Unit Orientation Unit Configuration Outdoor Air Intake Return Air Intake Supply Air Discharge
Constant Volume 100%
Horizontal End - End
OA

Cooling Specifications
Media Required Performance (DB/WB)
Type Cooling Media
Depth (in.) Flow (GPM) EAT (°F) LAT (°F)
Direct Evaporative CELdek 12 0 100.7 / 80.1 82.3 / 80.1

Air Performance
Total Fan
External SP Total SP Operating
Type Volume RPM
(in. wg) (in. wg) Power (hp) Qty Type Size (in.) Drive-Type
(CFM)
Supply 47,374 1.5 1.94 540 31.82 2 Forward Curve 30.2 Belt-Drive

Motor Specifications
Motor Qty Size (HP) Enclosure Efficiency RPM
Supply Fan Motor 1 40 ODP NEMA Premium 1725

Electrical Specifications
Power Supply Rating (V/C/P) MCA (A) MOP (A) SCCR
Unit 460/60/3 65.2 110 5kA

C:\Users\uriel.quiroz\Grupo 4HG\PDC Aplicaciones - Sist. De Ventilacion - Sist. De Ventilacion\GREENHECK\Jobs\PC-GH-2203-358 KukaHome Parque Industrial-R1.gfcj
CAPS 4.38.1089 Generated by: uriel.quiroz@proveedora.mx Page 95 of 106
Printed Date: 06/07/2022
Job: PC-GH-2203-358 KukaHome Parque Industrial-R1
Mark: AWU 39-59
Model: TSF-230-H50

CONSTRUCTION FEATURES AND ACCESSORIES


Unit Accessories
Unit Installation - Outdoor Std Factory Installed, Lockable, NEMA 3R Disconnect Std
Unit Construction - Single Wall X Weatherhood - Louvered with aluminum mesh filters X
Wall Insulation Supply Air Filters
Base Insulation - 1in. fiberglass - entire unit base pan Std Outdoor Air Inlet Damper
Paneled Bottom - Sheet metal liner for base insulation Supply Air Outlet Damper
Corrosion Resistant Fasteners Std Diffuser
Access and Connections - Right side when facing intake X Roof Curb
Service Access - Hinged access doors X Fan Bearing Extended Lube Lines
Unit Finish - G90 Galvanized X Inlet Damper Module
Finish Color Spare Belts
Supply Fan - Belt-drive, forward-curved X Spare Filters
Supply Fan and Motor Vibration isolation - Neoprene X Motor with Shaft Grounding
Controls Service Outlet
Unit Controls - Terminal strip X Service Lights
Remote Panel Evaporative Cooling Accessories
BMS Communication Evap Controls - Recirculating Pump X
BMS Protocol Evap Valves (Ship loose)
Supply Fan VFD Louvered intake provided with 2" aluminum mesh filters X
Supply Fan Control Warranty Options
Melink/Vari-Flow wiring package Unit Warranty - 1 Year X
Control Accessories
Remote display
Heating Inlet Air Sensor Standard Option Std
Cooling Inlet Air Sensor X Not Included
Dirty Filter Switch Included X
Fire Stat Type III (Ships loose)
120V/24V Smoke Detector (Ships loose)
Inlet Damper End Switch
Auxiliary Supply Starter Contacts
Auxiliary Exhaust Starter Contacts
Airflow Proving Monitoring Contact

Notes
Evap cooler pump requires a separate field provided 115V power connection
Evaporative cooler section ships separate and requires field installation.

C:\Users\uriel.quiroz\Grupo 4HG\PDC Aplicaciones - Sist. De Ventilacion - Sist. De Ventilacion\GREENHECK\Jobs\PC-GH-2203-358 KukaHome Parque Industrial-R1.gfcj
CAPS 4.38.1089 Generated by: uriel.quiroz@proveedora.mx Page 96 of 106
Printed Date: 06/07/2022
Job: PC-GH-2203-358 KukaHome Parque Industrial-R1
Mark: AWU 39-59
Model: TSF-230-H50

Fan Charts And Performance


Supply Fan Performance
Motor Fan
Total Volume External SP Total SP Operating
RPM Size
(CFM) (in. wg) (in. wg) Power (hp) Qty Qty Type Drive-Type
(HP)
47,374 1.5 1.94 540 31.82 1 40 2 Forward Curve Belt

Pressure Drop (in. wg)


Diffuser Weatherhood Filter Damper Cooling Heating External Total
- - - - 0.44 - 1.5 1.94

Sound Performance in Accordance with AMCA


Sound Power by Octave Band
Lwa dBA Sones
62.5 125 250 500 1000 2000 4000 8000
97 100 101 91 89 90 84 79 97 86 56

Supply Fan

C:\Users\uriel.quiroz\Grupo 4HG\PDC Aplicaciones - Sist. De Ventilacion - Sist. De Ventilacion\GREENHECK\Jobs\PC-GH-2203-358 KukaHome Parque Industrial-R1.gfcj
CAPS 4.38.1089 Generated by: uriel.quiroz@proveedora.mx Page 97 of 106
Printed Date: 06/07/2022
Job: PC-GH-2203-358 KukaHome Parque Industrial-R1
Mark: AWU 39-59
Model: TSF-230-H50

Cooling Specifications
Cooling Performance
Media Required Performance (DB/WB)
Type Cooling Media
Depth (in.) Flow (GPM) EAT (°F) LAT (°F)
Direct Evaporative CELdek 12 0 100.7 / 80.1 82.3 / 80.1

Unit Details
Stainless steel sump and media casing Ball valve for flow rate adjustment
Supply line, drain line and supply line drain valves must be field Recirculating pump(s) provided by factory
provided by others
Valve provided for bleed-off rate adjustment

C:\Users\uriel.quiroz\Grupo 4HG\PDC Aplicaciones - Sist. De Ventilacion - Sist. De Ventilacion\GREENHECK\Jobs\PC-GH-2203-358 KukaHome Parque Industrial-R1.gfcj
CAPS 4.38.1089 Generated by: uriel.quiroz@proveedora.mx Page 98 of 106
Printed Date: 06/07/2022
Job: PC-GH-2203-358 KukaHome Parque Industrial-R1
Mark: AWU 39-59
Model: TSF-230-H50

ELEVATION VIEW

171.511
100.011 71.500

63.875

Notes - Elevation View


Standard configuration for unit access is on the right-hand side, when looking into the unit intake in the direction of airflow.
Order of unit sections is from intake of unit to discharge of unit.
Sections included on this unit: Cooling Section, Blower Section

PLAN VIEW
100.011 71.500

156.000

Notes - Plan View


Standard configuration for unit access is on the right-hand side, when looking into the unit intake in the direction of airflow.

C:\Users\uriel.quiroz\Grupo 4HG\PDC Aplicaciones - Sist. De Ventilacion - Sist. De Ventilacion\GREENHECK\Jobs\PC-GH-2203-358 KukaHome Parque Industrial-R1.gfcj
CAPS 4.38.1089 Generated by: uriel.quiroz@proveedora.mx Page 99 of 106
Printed Date: 06/07/2022
Job: PC-GH-2203-358 KukaHome Parque Industrial-R1
Mark: AWU 39-59
Model: TSF-230-H50

END VIEW

156.000

SUPPLY
37.000
DUCT

24.172

37.500 103.500

FOOTPRINT VIEW
34.000 34.000 18.000 68.000

152.000

NOTE: Roof openings can be as large


as the curb size - 3.5" or as small
as the duct size + 1/2".

Notes - Footprint View


Minimum Roof Opening: The minimum roof opening size is the illustrated duct diameter plus 0.25 in. on all sides. For example: If the
duct size is 14 x 14 in. square, the minimum roof opening size is 14.5 x 14.5 in. square.
Maximum Roof Opening: There must be a minimum perimeter of 1.75 in. between the roof opening and the roof curb. For example: If
the roof curb is 75 x 30 in. square, the maximum roof opening is 71.5 x 26.5 in. inches square.
The weatherhood and filter sections of the make-up air unit extend beyond the curb. This is by design, to prevent water infiltration.

C:\Users\uriel.quiroz\Grupo 4HG\PDC Aplicaciones - Sist. De Ventilacion - Sist. De Ventilacion\GREENHECK\Jobs\PC-GH-2203-358 KukaHome Parque Industrial-R1.gfcj
CAPS 4.38.1089 Generated by: uriel.quiroz@proveedora.mx Page 100 of 106
Printed Date: 06/07/2022
Job: PC-GH-2203-358 KukaHome Parque Industrial-R1
Mark: AWU 39-59
Model: TSF-230-H50

Clearance Specifications
Recommended Minimum Combustible Clearances
Floor (in.) Top (in.) Sides (in.) Ends (in.)
Insulated Units 0 0 0 0
Non-Insulated Units 0 6 6 6

Notes - Combustible Clearances


Clearance to combustibles is defined as the minimum distance required between the heating source and the adjacent combustible
surfaces to ensure the adjacent surface's temperature does not exceed 90 F above the ambient temperature.

Recommended Minimum Service Clearances


Housing 32 and less (in.) Housing 35 and higher (in.)
42 on the controls side of the unit 48 on the controls side of the unit

Notes - Service Clearances


To ensure ample space for component removal (evaporative cooling media, coils, filters, etc.), service clearances should be 6 in. wider
than the width of the module itself.

C:\Users\uriel.quiroz\Grupo 4HG\PDC Aplicaciones - Sist. De Ventilacion - Sist. De Ventilacion\GREENHECK\Jobs\PC-GH-2203-358 KukaHome Parque Industrial-R1.gfcj
CAPS 4.38.1089 Generated by: uriel.quiroz@proveedora.mx Page 101 of 106
Printed Date: 06/07/2022
Job: PC-GH-2203-358 KukaHome Parque Industrial-R1
Mark: AWU 39-59
Model: TSF-230-H50

Wiring Diagram
DS1
L1 T1 FU1 ST1 O.L.
MAIN POWER
TO UNIT
460V
L2
L3
T2
T3
L1
L2
T1
T2
M1 GREENHECK
Building Value in Air.
FU6 L3 T3 SUPPLY FAN
GROUND 15A,600V MOTOR
CLASS J Wiring Diagram Code:

111 112 GN00N603A001D20NU15


CAUTION
UNIT SHALL BE GROUNDED IN ACCORDANCE WITH N.E.C.
POWER MUST BE OFF WHILE SERVICING.
NOTES
USE COPPER CONDUCTORS ONLY
(NEUTRAL) 60° C FOR TERMINALS RATED LESS THAN 100 AMPS.
131 75° C FOR TERMINALS RATED 100 AMPS OR MORE.
EVAP PUMP(S) POWER FIELD CONTROL WIRING RESISTANCE SHOULD
(115 VAC BY OTHERS) P1 NOT EXCEED 0.75 OHM.
RC
132 116 FIELD WIRED
(HOT) 11 14 EVAP PUMP(S) FACTORY SUPPLIED AND WIRED
FIELD CONNECTED

WIRE COLOR CODE


BK BLACK BL BLUE BR BROWN
GY GRAY LT BL LIGHT BLUE O ORANGE
PK PINK PR PURPLE R RED
W WHITE Y YELLOW

LEGEND
DS1 MAIN DISCONNECT SWITCH
TR1
FSC FIRE SYSTEM CONTACT
FU# FUSE
24V M# MOTOR
R C OL# MOTOR OVERLOAD
P# EVAP PUMP
RC COOL RELAY
RF SUPPLY FAN RELAY
S2 FAN SWITCH
S4 HEAT AND COOL SWITCH
ST# MOTOR STARTER
TR# TRANSFORMER
TS5 INLET AIR SENSOR - COOL
JUMPER = COOL : DIFFERENTIAL = 2
S2 FSC ST1 O.L.
G 5 RF SUPPLY FAN RELAY
95 96 A2 A1

RF
ST1 SUPPLY FAN
11 14 A2 A1

(OA-SENSOR IS FIELD CONNECTED


OA-SENSOR INTO THE CONTROL CENTER.)
24 VAC SENSOR COM THERMOSTAT CONTROLLER(S)
THERMOSTAT(S) TS5

S4 ST1 TS5
Y1 RC COOLING
13 14 COM NO A2 A1

Template Drawing: U15 DOC NUMBER: ---- REV: ----

Manufacturer reserves the right to change, modify, or improve this product at anytime

C:\Users\uriel.quiroz\Grupo 4HG\PDC Aplicaciones - Sist. De Ventilacion - Sist. De Ventilacion\GREENHECK\Jobs\PC-GH-2203-358 KukaHome Parque Industrial-R1.gfcj
CAPS 4.38.1089 Generated by: uriel.quiroz@proveedora.mx Page 102 of 106
Printed Date: 06/07/2022
Job: PC-GH-2203-358 KukaHome Parque Industrial-R1
Mark: AWU 39-59
Model: TSF-230-H50

Dry Corner Weights


784 lb 648 lb 648 lb 753 lb

785 lb 649 lb 838 lb 974 lb

Wet Corner Weights


1,246 lb 987 lb 648 lb 753 lb

1,247 lb 988 lb 838 lb 974 lb

Notes
Estimated corner weights are shown looking down on unit and airflow from left to right. Weights are applied at the base of the unit.
Evaporative cooling section shown separately due to calculation of dry and wet corner weights. Images not drawn to scale.

C:\Users\uriel.quiroz\Grupo 4HG\PDC Aplicaciones - Sist. De Ventilacion - Sist. De Ventilacion\GREENHECK\Jobs\PC-GH-2203-358 KukaHome Parque Industrial-R1.gfcj
CAPS 4.38.1089 Generated by: uriel.quiroz@proveedora.mx Page 103 of 106
Printed Date: 06/07/2022
Job: PC-GH-2203-358 KukaHome Parque Industrial-R1
Mark: AWU 39-59
Model: TSF-230-H50

SEQUENCE OF OPERATIONS

Unit Controls
The unit shall be provided from the factory with:
• 24VAC Transformer
• Terminal Strip
Field Provided Control Requirements
The following field provided control signals must be provided for proper operation of the unit (Reference the unit
wiring diagram for additional information):
• Supply fan enable – Contact closure between R and G (24VAC)
• Cooling enable – Contact closure between R and Y1 (24VAC) *Factory installed jumper allows heating to be
enabled automatically by outside air temperature - remove jumper for field provided control.
Unit Start-Up Sequence
• Supply Fan Enable Is Received
• Supply Fan Is Enabled
Cooling Control
A cooling enable signal must be present and the supply fan must be enabled before the unit will enable cooling.
Cooling Inlet Air Sensor (Cooling Lockout)
The cooling will be locked out when the outside air temperature is below the cooling inlet air sensor set point
(typical 80 F, adj.)
Evaporative Cooling (Recirculating Pump)
When cooling is enabled the pump recirculates water from the sump over the evaporative cooling media and a
float valve maintains the water level in the sump. Supply and drain valves must be field supplied and installed.

C:\Users\uriel.quiroz\Grupo 4HG\PDC Aplicaciones - Sist. De Ventilacion - Sist. De Ventilacion\GREENHECK\Jobs\PC-GH-2203-358 KukaHome Parque Industrial-R1.gfcj
CAPS 4.38.1089 Generated by: uriel.quiroz@proveedora.mx Page 104 of 106
Printed Date: 06/07/2022
Job: PC-GH-2203-358 KukaHome Parque Industrial-R1
Mark: AWU 39-59
Model: TSF-230-H50

Warranty Statement for Make-Up Air


Unit Warranty
Greenheck warrants the equipment to be free from defects in material and workmanship for a period of 1 year (standard) from the
shipment date.

Warranty Notes
Any component which proves defective during the warranty period will be repaired or replaced at Greenheck’s sole option when
returned to our factory, transportation prepaid. All warranties do not include labor costs associated with troubleshooting, removal, or
installation. Greenheck will not be liable for any consequential, punitive, or incidental damages resulting from use, repair, or operation
of any Greenheck product. These warranties are exclusive and are in lieu of all other warranties, whether written, oral, or implied,
including the warranty of merchantability and the warranty of fitness for a particular purpose. No person (including any agent or
salesperson) has authority to expand Seller's obligation beyond the terms of this warranty, or to state that the performance of the
product is other than that published by Seller.

As a result of our commitment to continuous improvement, Greenheck reserves the right to change specifications without notice.

Tempered Air Products (TAP) Statement 2018


C:\Users\uriel.quiroz\Grupo 4HG\PDC Aplicaciones - Sist. De Ventilacion - Sist. De Ventilacion\GREENHECK\Jobs\PC-GH-2203-358 KukaHome Parque Industrial-R1.gfcj
CAPS 4.38.1089 Generated by: uriel.quiroz@proveedora.mx Page 105 of 106
Printed Date: 06/07/2022
Job: PC-GH-2203-358 KukaHome Parque Industrial-R1

Vertical Mount Exhaust Damper Standard Construction Features:


Model: WD-320
- Model WD-320 is a vertical mount exhaust damper
and is constructed of 18 ga galvanized steel with pre-
punched mounting holes and a flanged frame - Damper
blades are 0.025 in. roll formed aluminum with vinyl
seals on the closing edge - Steel axles are 0.188 in.
diameter zinc plated mounted steel in nylon bushings -
Synthetic axle bearings

Damper Configuration:
ID #: Tag: Quantity: W (in.): H (in.): Act Qty: Actuator Model:
10 EF 56-117 61 44 44 0

Notes: All dimensions shown are in units of in.


Width And height furnished approximately 0.125 in. undersize

C:\Users\uriel.quiroz\Grupo 4HG\PDC Aplicaciones - Sist. De Ventilacion - Sist. De Ventilacion\GREENHECK\Jobs\PC-GH-2203-358 KukaHome Parque Industrial-R1.gfcj
CAPS 4.38.1089 Generated by: uriel.quiroz@proveedora.mx Page 106 of 106
Louvers Mill Aluminum Finish
Aluminum in the mill finish state will be commercially smooth and substantially free from blisters, inclusions, voids, slivers and kinks. Slight
discontinuity resulting from flow and die lines inherent in the extrusion process will exist. Occasional discontinuities that can be reasonably removed
making the surface suitable for finishing operations are acceptable. Although aluminum is naturally resistant to corrosion, its appearance changes as
a result of weathering and aging. Aluminum in the mill finish state may also have a non-uniform surface appearance resulting from oil, heat and oxide
discoloration inherent in the manufacturing process.